Installation and Operation Manual
VW FRIEDRICH
Dehumidifier
D25BNP, D50BPA, D70BPA
Models
D25BNP Volts: 115/60Hz Capacity: 25 Pints Moisture Removal: 25 Pint/Day
DSOBPA Volts: 115/60Hz Capacity: 50 Pints Moisture Removal: 50 Pint/Day
D70BPA Volts: 115/60Hz Capacity: 70 Pints Moisture Removal: 70 Pint/Day
97991000_01Congratulations!
“Thank you for your decision to purchase the Friedrich Dehumidifier Please read thoroughly ofthis instalation and Operation Manual
THANK YOU, on behalf of our entire company,
for making such a wise purchase.
Table of Contents
DESCRIPTION OF COMPONENTS
FUNCTION EXPLANATION
INSTALLATION INSTRUCTIONS.
OPERATION INSTRUCTIONS.
OPERATING DO'S AND DONT.
CONTINUOUS DRAINAGE.
MAINTENANCE,
IN CASE OF EMERGENCY.
Do natremove, ible ot
Ne pas suppriner, désactver ou | No lina, dessctivaro
bya th units tecture’ cats uns pasa pr soca pation
SAFETY | ssieysvees. coin | te deponit estes. ke | guna dn uric Slo
FIRST | somey couse. inures | YOU TEOUreE revoRI | tna preduces ge,
ordeah lesen mars
ula mortDESCRIPTION OF COMPONENTS
Figure 1 DERUMIDIFIED
‘owe TERY cee eee ORY AIR VENT
MOIST AIR
INTAKE
oo \
DRAIN BUCKET \ DRAIN PUMP OUTLET continuous
(ONLY ON 50 AND 70 PINT MODELS) DRAINAGE OUTLET
ROLL CASTERS F000
Figure 2
BUCKET FULLLAMP DEFROST LAMP. (CURRENT TEMP / TIMER SET DISPLAY
LAWP LIGHTS WHEN LAMP LIGHTS WHEN UNIT IS WHEN THE UNIT IS RUNNING THE CURRENT TEMP IS DISPLAYED,
DRAIN BUCKETIS._DEFROSTING (SEE PAGE 5). WHEN THE TIMER BUTTON IS PRESSED THIS WINDOW DISPLAYS.
FULL AND NEEDS TO ‘THE TIMER SETTING THEN REVERTS BACK TO THE TEMPERATURE
BE EMPTIED. APTER 10 SECONDS
sO Om ot
sO O- Om CIO
mote bsectmyte — omty
4 4 4
IMERS CURRENT HUMIDITY DISPLAY core SELECTOR
FAN SPEED WHEN THEUNITIS ON PRESS THE DISPLAYS THE CURRENT PRESS THE “CE
HIGHILOW TIMER BUTTON TO DISPLAY THE RELATIVE HUMIDITY (RH) IN SWITCH BUTTONS
POWER OFF TIMER THE ROOM. WHEN THE OR Twit swrTc
POWER SELECTFROM 1-2¢HOURS OF IS PRESSED THE HUMIDITY BETWEEN "CAND ‘F
RUNNING TIME UNTIL THE UNIT SETTING IS DISPLAYED.
SHUTS OFF AUTOMATICALLY. Ser HUMIDITY
WHEN THE UNIT IS OFF PRESS THE [ROJUST THE HUMIDITY % FROM
TIMER SUTTON TO DISPLAY THE 50% TO 90% RH BY PRESSING THE
POWER ON TIER. SELECT FROM @ ox @ BUTTONS. HUMIDITY Is
1-24 HOURS UNTIL THE UNIT WILL
ADJUSTED IN 5% INCREMENTS,
‘TURN ON AUTOMATICALLY.INSTALLATION INSTRUCTIONS
Follow the stops below for unpacking and setup your unit
STEP‘, Remove unit rom carton and inspect.
STEP2. Remove aocessorie rom drain bucket
STEP. Install Roll Casters (D25BNP modal only) per
instalation instructions below,
STEP. Setupunitinpostion with adequate clearance. Installation
of units complete,
Roll Caster Installation (D25BNP Model only)
STEP‘, Locate Rol Castes removed during STEP 2 above
STEP2. Lay uit onits side for ease of instalation.
STEPS, Insert Roll Gastersin los as shown (See Figure 3) until they
cick ito place.
Figure 3
ROLL CASTER
STEP4, Sette unt upright. Roll Caster instalation is complete
STEPS. Allow unto st upright 1 hour before operating
‘Allow 8 inches of space on al sides of the unit
Figure 4
OPERATION INSTRUCTIONS
ZAXWARNING
Electrical Hazards
Do not fold power cord as shown at let
Make sure the plug is placed fully and
firmly into the receptacle,
Do not use multiple sockets as shown at
ret
Make sure the plug is clean
After turing the unit off please take plug
out ofthe receptacle,
Do not have wet hands when connecting
the power plug
Do not pul he power card to avoid a
broken core ifich can lead to danger.Start Operation
STEP‘, Place the unitinan upright positon on afi, steady, stable and
heat resistant surface, Make sure there is nothing flammable
heat sensitive within 39 inches. Operating th product in
any other positon coud cause a hazard.
ZXWARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the
‘same configuration as your dehumidifier’
plug, If ferent, consulta Licensed Electrician
Do not use plug adapters
1 not use an extension cord,
Do not remove ground prong,
‘Abways plug into 9 grounded 3 prong out
Feallure fo follow these instructions can rest in
dea, fie, or electrical shock.
STEP2 nse the pug into stable wall
Socket. The dehumiiarisutablo
feroperatonanancecrtysipply
raving the same votage as that
shown on isang abel
STEP3, Make sure the Drain Buckets correctly placedin the proper
positon See Figure ). (After switching th unit'ON' forthe
fst time, ifthe Bucket Full lamp iluminate, just pul ot
the crain bucket; check io ensue thatthe float levers able
to move freely, then return the drain bucket to the correct
positon)
When Bucket Full Lamp Is On
\When the drain buckets ful, the Bueket Full lamp wililuinate andthe
nit stop operating, The dain bucket should be caefuly removed from
the unit by siding outwards (See Figure 6) and should be epted. Then
place the omy drain bucket back fois proper position, (See Figure 7)
‘he unt wil start operating and run normaly.
Figure 6
PLEASE USE BOTH HANDS
‘TO CAREFULLY EMPTY THE
DRAIN BUCKET.
Defrost
When the unit is operated in low temperatures (less than 54 °F
the surface ofthe evaporator wil accumate a layer of frost which wil
‘reduce the efficiency of tha debumider. Whan this happens the untill go
into perocic defrost mode automaticaly. The Detost Lamp wl iluminale
‘on contol pane, this uit normal (See Figure 7)
‘The dehumicifir wil operate in temperatures downto 41 °F. The ime it
takes to defrost may vary the unit freezes upitshould be tuned off atthe
‘power supply fra few hours and then related. the room temperature
‘emai below 41°F the unt shouldbe suitchedoft itis notrecommended
to use the dehumidifier in tamperatures bolow 41 °F.
Figures
BUCKET FULL LAMP —
Figure 7
DEFROST LAMP —
DRAIN BUCKETOPERATING DO'S AND DON'TS
Do not place anything on lop of the unit o contol panel (See Figure 8
Figure 8
Donot piace anything over he inlet or out points (Soe Figure 9),
Figured ¢
Do not wet the unit or the conto panel (See Figure 1).
Figure 10
Donot use insect clr paint spray around the unit (See Figure 11), tight
‘cause damage tothe plastic parts o stata fre,
Figure 11
o not place the unit on an uneven surface (See Figure 12), to avid
shaking, noise and leakage of water
Figure 12
Do alnayskeep the unt in. away om the wal (See Figue13)to dissipate
the heat propel.
Figure 13
= 800IN.Do not put any foreign objects ino the unt, tis dangerous and will result
in damage tothe unt (See Figure 1).
\When moving or putting unitin storage, donot place the unit ont side or
Upside down and avoid violent shaking (See Figure 16).
Figure 14
Do close all open windows to reach the maximum possible efficiency of
dehumidifier remaving moisture See Figure 15)
Figure 15
Figure 16
‘Do ask professional service technicians to service the uit as required
(Gee Figure 1)
Figure 17CONTINUOUS DRAINAGE
(D25BNP model only)
To save having to periodical empty the drain bucket, this unit can be
canfgued for contnuos drainage You can use th supplied erin hose
to connect to the continuous drainage connector (See Figure 18).
Figure 18
BACK OF UNIT
DRAIN HOSE
DRAIN COVER
Unscrew andremove the drain cover atthe rear ofthe unt (See Figure 1)
Remove the soft rubber stopper. Putitniothe dain bucket for safekeeping
(Gee Figure 19)
Insect the dain hose through the hole ofthe drain cover, Then connect the
ran hase tothe drain port (See Figure 20),
Figure 20
BACK OF UNIT
DRAIN HOSE
DRAIN COVER
% &
Tighten the drain cover in clockwise direction onto the rear of the unit
(Gee Figure 2).
Figure 21
BACK OF UNIT
Figure 19
BACK OF UNIT
‘SOFT RUBBER STOPPER
DRAIN COVER
SS
|= brain cover
r DRAIN HOSE:
Place the bucket in ils original location (See Figure 22),
Figure 22
PUSH THE DRAIN BUCKET
BACK INTO THE UNIT IN THE
DIRECTION THE ARROW IS
PONTING
1 + —=— brain
| BUCKET
DRAIN HoseContinuous Drain Hose Routing
When using the function of continuous drainage, the drain hose must be
paced horizntaly below the drainage hole (See Figue 23),
‘You must avoid uneven ground and folding the hose (See Figure 23),
Figure 23
rE
Continuous Drainage using Built-In Pump
(D50BPA / D70BPA models only)
Installation:
‘STEP 1. — Connect the supplied water hose to the drainage key.
SSTEP2, Connect the drainage key and water hose (1) tothe drain pump
‘let (2) onthe rear panel
SSTEP3, Lead the other end toa sultable locaton for drainage, tke a
tan or sink and insert the plug into the water drain
The maximum distance and he rise may be 15 from the unt. Exceeding
this distance may damage the unit or cause leaks. When the unit's dain
bucket capacity reaches a certain water level, twill rain automatically
(See Figure 2)
Dismantle:
Press the drain release button (3) onthe unit rear panel. The automatic
drainage key wil pul out (See Figure 24,
Figure 24
The rubber drain plug must be inserted in the
continuous drainage outlet (4) for builtin pump
feature to work.
Removing the rubber drain plug will cause the
‘condensation to exit through the continuous
drainage outlet instead of the drain pump outlet.MAINTENANCE
ZAAWARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the
Same configuration as your dehumicifiors
lug if diferent, consulta Licensed Electrician.
Do not use plug adapters.
Do not use an extension cord
Do not remove ground prong,
Always plug into a grounded 3 prong out.
Falure fo Yalow these instructions can result in
‘eat, fire, or electrical sock
For safety reasons, make sure the unit is
unplugged befor servicing or cleaning
Z
Cleaning the shell
STEP, Wpe the seit clean, st cloth
STEP2, {the unitis very diy, use mild detergent then wipe off the
etergent with haf dried cloth,
Z\WARNING
D
2) | Water Hazard
oa Do not wash the unit with a hose
or immerse it in water. This may
cause leakage of electricity or a
shock hazard.
Cleaning the air filter
The purpose ofthe ai iter sto fiter dust and othor materials from the
aic I the filters blocked by dust the electricity usage wil be greater than
normal For eptimal moisture removal and efclency, clean te iter every
two weeks,
10
Cleaning Steps
STEP. Pulltheairfiter out gent (See Figure 25)
Figure 25
ine
_
STEP2. Clean the arfiter wit a vacuum cleaner or washitwith clean
waler and dey with a dy cloth See Figure 28,
‘STEP3. Put the clean air filer back in place and continue to operate
‘he dehumidifier.IN CASE OF EMERGENCY
IFaprobiem occurs, unplug the unit and contact qualified servicing center
immediatly. Do not disassemble the unt youself,
NOTICE
Ifthe power cord on this unit is damaged it must
be replaced by the manufacturer, its service agent
or qualified service technician in order to avoid a
hazard.
NOTICE
This appliance is not intended for use by childern
cr other persons without assistance or supervision
if their physical, sensory or mental capabilities
prevent them from using it safely. Children should
be supervised to ensure that they do not play with
the appliance.2
% FRIEDRICH
Friedrich Air Conditioning Company
"10001 Reunion Place, Suite 500
‘San Antonio, TX 78216
‘00/541 6645
wv eden com
DEHUMIDIFIERS
LIMITED WARRANTY
FIRST YEAR
[ANY PART: 1! any part supplied by FRIEDRICH falls because of a defect in workmanship or material within twelve months from
dato of orginal purchase. FRIEDRICH will repai the product at no charge, provided the product is transported to a Friedrich
‘Authorizes Service Center for repair. ALL transportation charges are the sole responsibly f the owner. Ths remedy is expressly
‘agreed tobe the exclusive remedy within twelve months from the date ofthe orginal purchase
SECOND THROUGH FIFTH YEAR
‘SEALED REFRIGERANT SYSTEM: If the Sealed Retrigeraton System (defined for this purpose as the compressor, condenser
Cell, dehumicifying coll, capillary, fiter drier, and al interconnecting tubing) supplied by FRIEDRICH in your dehuricifier fails
because of a dofect in workmanship or material within sixty months from dato of purchase, FRIEDRICH will pay a labor allowance
‘and parts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the
problem, removal, right charges, and transportation of tha dehumidifer to and from the Service Agency, and the reinstallation
‘charges ssociated with repair ofthe Sealed Refrigeration System. All such cost wll be the sole responsibilty ofthe owner. This
remedy is expressly agreed to be the exclusive remedy within sity months fram the date ofthe orginal purchase
APPLICABILITY AND LIMITATIONS: This warranty is applicable only o units retained within the Fity Sates of the U.S.A. District
‘of Columbia, and Canada, This warranty is not applicable to:
1. Air fiters of fuses,
2. Products on which the model and serial numbers have been removed,
3, Products which have defects or damage which results from improper installation, wiring, electical curent
characteristics, or maintenance; or causes by accident, misuse or abuse, fe, food, alterations andlor misapplication
Of the product andlor units installed in @ corrosive atmosphere, detauit or delay in performance caused by wa,
{government restrictions or restraints, stkes, material shortages beyond the control of FRIEDRICH, or acts of God.
‘OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service
‘Organization in your area. They ae ised in the Yelow Pages. If assistance Is required in obtaining warranty performance, wie to
Room Air Conditioner Service Manager (the Fredich address i at the top ofthis warranty) or email tc@fredrich com,
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the watranty
notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE ANDIOR MERCHANTABILITY
‘SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND.
EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR
IMPLIED WARRANTY.
NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not alow the limitation or exclusion of
‘consequential or incidental damages, s0 the foregoing exclusions and limitations may not apply to you.
OTHER: This warranty gives you specifi legal rights, and you may also have other rights which vary from state to state
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services,
‘All Serica calls for explaining the operation ofthis product wil be the sole responsibilty ofthe consumer.
‘All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to
repairs being made.