——— street se SILICON SEALANT (FACTORY OF FIELD INSTALLED) INSTALL FIRE HYDRANT WITH 41/2 OUTLET TO STREET SIDE HYDRANT FLANGE UBER GASKET ‘SEE HYDRANT BOLT DETAL BREAK OFF RISER FLANGE 6 BREAK OFF RISER, BREAK-AWAY BOLT (SEE NOTE 3) (FACING UP) (CONCRETE PAD IN DEVELOPED AREAS HYDRANT BOLT DETAIL (MATCH SIDEWALK SLOPE) CONCRETE PAD IN OPEN AREAS (SLOPED TO DRAIN) 6 BREAK OFF CHECK VALVE (8 MECHANICAL JOINT BURY 1/290 STAINLESS STEEL ROUND ROD ney MIN. oe LA, | CONCRETE THRUST BLOCK o'MIN. 120 STANLESS STEEL ROUND ROD (6 MECHANICAL JOINT BURY oe) CONCRETE THRUST 8LOCK SECTION AA TES: FIRE HYDRANT SHALL BE CLOW 950 WITH FACTORY APPLIED "BRIGHT WHITE" EPOXY COATING. FIELD APPLIED TOUCH-UP MAY BE REQUIRED AFTER INSTALLATION AND TESTING. ‘ALLEXPOSED METAL SHALL BE PROPERLY PREPARED AND PAINTED WITH "BRIGHT WHITE INDUSTRIAL EPOXY PAINT, FELD APPLIED ‘TOUCH-UP MAY BE REQUIRED AFTER INSTALLATION AND TESTING, BREAK OFF RISER SHALL BE INSTALLED WITH BREAK-AWAY BOLTS AND NUTS ON THE UPPER FLANGE WITH THE BOLTS FACING UP, ‘STANDARD BOLTS AND NUTS SHALL BE USED FOR THE LOWER FLANGE, ALL BELOW GROUND NUTS, BOLTS, AND MISCELLANEOUS STEEL SHALL BE POLYETHYLENE ENCASED AS PER AWWA C-105 OR TAPE WRAPPED AS PER AWWA C.200, 20 NLS MINIMUM IN BOTH CASES, THE CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI. ALL CONCRETE SHALL HAVE A MINIMUM OF § ‘SAOKS TYPE II PORTLAND CEMENT PER CUBIC YARD OF CONCRETE, HYDRANT LATERAL SHALL BE INSTALLED AND BACKFILLED AS PER DETAILW-1, VALVE FOR HYDRANT LATERAL SHALL BE INSTALLED PER DETAIL W-10. ETAL FIRE HYDRANT DETAIL el OR OF ENGINEERING