Innovation Tech Center

VRF 22HP VRF16HP VRF 24HP MATERIAL

Tuberia Fase Neutro


CTO. Fases Hilos F.D. F.P. F.T. F.A. M V In Id e% ΔV z Iter Inc Ipc C/F
COBRE=1

16405.4 11931.2 14000 mm AREA TOTAL ALUMINIO=2 AWG AREA AWG AREA

VRF-01 0 1 3 3 1 0.9 0.91 1 30 220 40.87 40.87 0.95 2.09 0.98 51.09 70 63.7 1 T-35mm 266.90 1 3 - 4 188.40 1 - 4 62.80

VRF-02 1 3 3 1 0.9 0.91 1 7 220 40.87 40.87 0.54 1.18 2.38 51.09 40 36.4 1 T-21mm 128.50 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

VRF-03 1 3 3 1 0.9 0.91 1 12 220 47.89 47.89 1.08 2.37 2.38 59.87 40 36.4 1 T-21mm 128.50 1 3 - 8 84.60 1 - 8 28.20

VRF-04 1 3 3 1 0.9 0.91 1 12 220 34.83 34.83 0.78 1.72 2.38 43.54 40 36.4 1 T-21mm 128.50 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.8 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

VRF-05 1 3 3 1 0.9 0.91 1 17 220 47.89 47.89 1.52 3.35 2.38 59.87 40 36.4 1 T-21mm 128.50 1 3 - 8 84.60 1 - 8 28.20

VRF-06 1 3 3 1 0.9 0.91 1 17 220 40.87 40.87 1.30 2.86 2.38 51.09 40 36.4 1 T-21mm 128.50 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 2.38 0.00 40 36.4 1 T-21mm 121.77 1 3 - 8 84.60 1 - 8 28.20

3 3 1 0.9 0.91 1 18 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 21 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 25 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 14 220 0.00 0.00 0.00 0.00 0.63 0.00 95 86.45 1 T-35mm 352.97 1 3 - 2 258.00 1 - 2 86.00

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 0.63 0.00 95 86.45 1 T-35mm 352.97 1 3 - 2 258.00 1 - 2 86.00

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 0 220 0.00 0.00 0.00 0.00 0.63 0.00 95 86.45 1 T-35mm 352.97 1 3 - 2 258.00 1 - 2 86.00

3 3 1 0.9 0.91 1 20 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 18 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 1.52 0.00 55 50.05 1 T-27mm 196.17 1 3 - 6 140.40 1 - 6 46.80

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 13 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 5.98 0.00 25 22.75 1 T-16mm 55.77 1 3 - 12 35.10 1 - 12 11.70

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 4.77 0.00 40 36.4 2 T-21mm 111.54 2 6 - 13 70.20 2 - 13 23.40

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 0.00 0.00 0 0 3 T-21mm 134.55 3 9 - 14 80.73 3 - 14 26.91

3 3 1 0.9 0.91 1 1 220 0.00 0.00 0.00 0.00 0.00 0.00 0 0 4 T-27mm 179.40 4 12 - 15 107.64 4 - 15 35.88

TOTAL 2 1 3 3 3 0.8 0.9 0.91 1 120 220 253.23 202.59 #N/A #N/A #N/A 253.23 #N/A #N/A 2 #N/A #N/A 1 6 - 4/0 #N/A 2 - 4/0 #N/A

1.52 % Maxima Caida de Tensión en Derivados CARGA INSTALADA


#N/A % Maxima Caida de Tensión en Alimentador FACTOR DE DEMAND
CARGA DEMANDADA
#N/A % Total de Caida de Tensión. FACTOR DE POTENC
CARGA DEMANDADA
35.00 TEMPERATURA AMBIENTE
Innovation Tech Center

Tierra TOTAL FASES


Polos Int. UBICACIÓN

AWG AREA Watts A B C

1 - 10 15.70 14000 4666.667 4666.667 4666.667 3 60 1


1 - 10 15.70 14000 4666.667 4666.667 4666.667 3 60 2
1 - 14 8.97 0 0 0 0 3 15 3
1 - 14 8.97 0 0 0 0 3 15 4
1 - 14 8.97 0 0 0 0 3 15 5
1 - 14 8.97 0 0 0 0 3 15 6
1 - 10 15.70 16405.4 5468.467 5468.467 5468.467 3 60 7
1 - 10 15.70 11931.2 3977.067 3977.067 3977.067 3 50 8
1 - 14 8.97 0 0 0 0 3 15 9
1 - 14 8.97 0 0 0 0 3 15 10
1 - 14 8.97 0 0 0 0 3 15 11
1 - 14 8.97 0 0 0 0 3 15 12
1 - 10 15.70 16405.4 5468.467 5468.467 5468.467 3 60 13
1 - 10 15.70 14000 4666.667 4666.667 4666.667 3 60 14
1 - 14 8.97 0 0 0 0 3 15 15
1 - 14 8.97 0 0 0 0 3 15 16
1 - 14 8.97 0 0 0 0 3 15 17
1 - 14 8.97 0 0 0 0 3 15 18
1 - 14 8.97 0 0 0 0 3 15 19
1 - 14 8.97 0 0 0 0 3 15 20
1 - 14 8.97 0 0 0 0 3 15 21
1 - 14 8.97 0 0 0 0 3 15 22
1 - 14 8.97 0 0 0 0 3 15 23
1 - 14 8.97 0 0 0 0 3 15 24
1 - 14 8.97 0 0 0 0 3 15 25
1 - 14 8.97 0 0 0 0 3 15 26
1 - 14 8.97 0 0 0 0 3 15 27
1 - 14 8.97 0 0 0 0 3 15 28
1 - 14 8.97 0 0 0 0 3 15 29
1 - 14 8.97 0 0 0 0 3 15 30
1 - 14 8.97 0 0 0 0 3 15 31
1 - 14 8.97 0 0 0 0 3 15 32
1 - 14 8.97 0 0 0 0 3 15 33
1 - 14 8.97 0 0 0 0 3 15 34
1 - 14 8.97 0 0 0 0 3 15 35
1 - 14 8.97 0 0 0 0 3 15 36
1 - 14 8.97 0 0 0 0 3 15 37
1 - 14 8.97 0 0 0 0 3 15 38
1 - 14 8.97 0 0 0 0 3 15 39
2 - 14 17.94 0 0 0 0 3 15 40
3 - 14 26.91 0 0 0 0 3 15 41
4 - 14 35.88 0 0 0 0 3 15 42
DESB. 0.00 %

2 - 8 56.40 86742 28914 28914 28914 3 100 MEDIDOR

CARGA INSTALADA = 86742 WATTS


FACTOR DE DEMANDA= 80 %
CARGA DEMANDADA= 69394 WATTS
FACTOR DE POTENCIA= 90 %
CARGA DEMANDADA= 77.104 KVA
MEMORIA DE CALCULO

PROYECTO ELECTRICO INNOVATION TECHCENTER

MEMORIA DE CALCULO DE INNOVATION TECHCENTER

#VALUE!

EL MARQUES, QUERETARO., MEXICO.

CARGA INSTALADA = 86742 WATTS


FACTOR DE DEMANDA= 80 %
CARGA DEMANDADA= 69394 WATTS
FACTOR DE POTENCIA= 90 %
CARGA DEMANDADA= 77.104 KVA

REALIZO: ING.RAUL ASCARY ALVAREZ FONSECA


MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-01
UBICACIÓN 1
CARGA TOTAL 14000 WATTS REFERENCIA NOM-001-2012
LONGITUD 30.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 40.87 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 40.87 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 4 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 70 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 63.7 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 4 AWG - KCM


IMPEDANCIA CALCULADA 0.984 OHMS - KM. TABLA 9 NEC
CANALIZACION T-35mm
CAIDA DE TENSION CALCULADA(%e) 0.95 %
CAIDA DE VOLTAJE(ΔV) 2.09 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 60
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 51.09 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 60 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 4 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 4 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 266.90 mm2
MEMORIA DE CALCULO

DIAMETRO DE TUBERIA CONDUIT = 1 T-35mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-02
UBICACIÓN 2
CARGA TOTAL 14000 WATTS REFERENCIA NOM-001-2012
LONGITUD 7.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 40.87 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 40.87 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) 0.54 %
CAIDA DE VOLTAJE(ΔV) 1.18 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 60
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 51.09 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 60 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
MEMORIA DE CALCULO

CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM


CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 128.50 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 3
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)
MEMORIA DE CALCULO

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 4
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO


MEMORIA DE CALCULO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 5
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94
MEMORIA DE CALCULO

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 6
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


MEMORIA DE CALCULO

POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-03
UBICACIÓN 7
CARGA TOTAL 16405.4 WATTS REFERENCIA NOM-001-2012
LONGITUD 12.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 47.89 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 47.89 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) 1.08 %
MEMORIA DE CALCULO

CAIDA DE VOLTAJE(ΔV) 2.37 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 60
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 59.87 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 60 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 128.50 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-04
UBICACIÓN 8
CARGA TOTAL 11931.2 WATTS REFERENCIA NOM-001-2012
LONGITUD 12.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 34.83 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 34.83 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


MEMORIA DE CALCULO

IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC


CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) 0.78 %
CAIDA DE VOLTAJE(ΔV) 1.72 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 50
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 43.54 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 50 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 128.50 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 9
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.80 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES
MEMORIA DE CALCULO

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 10
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
MEMORIA DE CALCULO

CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 11
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
MEMORIA DE CALCULO

TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS


FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 12
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
MEMORIA DE CALCULO

# CONDUCTORES POR FASE(C/F) 1


CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-05
UBICACIÓN 13
CARGA TOTAL 16405.4 WATTS REFERENCIA NOM-001-2012
LONGITUD 17.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 47.89 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 47.89 AMPERES
MEMORIA DE CALCULO

AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS


COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) 1.52 %
CAIDA DE VOLTAJE(ΔV) 3.35 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 60
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 59.87 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 60 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 128.50 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: VRF-06
UBICACIÓN 14
CARGA TOTAL 14000 WATTS REFERENCIA NOM-001-2012
LONGITUD 17.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
MEMORIA DE CALCULO

CORRIENTE NOMINAL(In) 40.87 AMPERES


FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 40.87 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) 1.30 %
CAIDA DE VOLTAJE(ΔV) 2.86 VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 60
CONDUCTOR PARA PUESTA A TIERRA 10 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 51.09 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 60 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 10 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 128.50 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 15
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
MEMORIA DE CALCULO

VOLTAJE 220 VOLT


MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 16
MEMORIA DE CALCULO

CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012


LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 17
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 18
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 8 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 40 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 36.4 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 8 AWG - KCM


IMPEDANCIA CALCULADA 2.380 OHMS - KM. TABLA 9 NEC
CANALIZACION T-21mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 8 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 8 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 121.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-21mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 19
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 18.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
MEMORIA DE CALCULO

NO. DE COND. ACTIVOS EN CANALIZACION = 3


AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 20
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 21.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)
MEMORIA DE CALCULO

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 21
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 0.90 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO


MEMORIA DE CALCULO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: 0
UBICACIÓN 22
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 4 HILOS
VOLTAJE 440 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2

CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE


CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C

CORRIENTE DEMANDADA(Id) 0.00 AMPERES


AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520000 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 23
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520000 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
MEMORIA DE CALCULO

DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 24
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
MEMORIA DE CALCULO

CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM


CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 25
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 25.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)
MEMORIA DE CALCULO

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 26
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 14.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 2 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 95 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 86.45 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 2 AWG - KCM


IMPEDANCIA CALCULADA 0.625 OHMS - KM. TABLA 9 NEC
CANALIZACION T-35mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO


MEMORIA DE CALCULO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 2 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 2 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 352.97 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-35mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 27
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94
MEMORIA DE CALCULO

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 28
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 2 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 95 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 86.45 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 2 AWG - KCM


IMPEDANCIA CALCULADA 0.625 OHMS - KM. TABLA 9 NEC
CANALIZACION T-35mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


MEMORIA DE CALCULO

POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 2 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 2 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 352.97 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-35mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 29
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
MEMORIA DE CALCULO

CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 30
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 0.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 2 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 95 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 86.45 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 2 AWG - KCM


MEMORIA DE CALCULO

IMPEDANCIA CALCULADA 0.625 OHMS - KM. TABLA 9 NEC


CANALIZACION T-35mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 2 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 2 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 352.97 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-35mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 31
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 20.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES
MEMORIA DE CALCULO

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 32
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 18.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
MEMORIA DE CALCULO

CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 33
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
MEMORIA DE CALCULO

TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS


FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 34
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
MEMORIA DE CALCULO

# CONDUCTORES POR FASE(C/F) 1


CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 35
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
MEMORIA DE CALCULO

AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS


COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 6 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 55 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 50.05 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 6 AWG - KCM


IMPEDANCIA CALCULADA 1.520 OHMS - KM. TABLA 9 NEC
CANALIZACION T-27mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 6 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 6 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 196.17 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-27mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 36
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
MEMORIA DE CALCULO

CORRIENTE NOMINAL(In) 0.00 AMPERES


FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 37
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 13.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
MEMORIA DE CALCULO

VOLTAJE 220 VOLT


MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 38
MEMORIA DE CALCULO

CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012


LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


0 CIRCUITO: 0
UBICACIÓN 39
CARGA TOTAL 0 WATTS REFERENCIA NOM-001-2012
LONGITUD 1.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 0.00 AMPERES
FACTOR DE DEMANDA(F.P) 1.00 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 0.00 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 60 GRADOS CENTIGRADOS
CALIBRE NO. 12 AWG - KCM
# CONDUCTORES POR FASE(C/F) 1
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) 25 AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) 22.75 AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 12 AWG - KCM


IMPEDANCIA CALCULADA 5.980 OHMS - KM. TABLA 9 NEC
CANALIZACION T-16mm
CAIDA DE TENSION CALCULADA(%e) - %
CAIDA DE VOLTAJE(ΔV) - VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 15
CONDUCTOR PARA PUESTA A TIERRA 14 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 0.00 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 15 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 3 12 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 1 12 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 1 14 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 3
AREA OCUPADA POR LOS CONDUCTORES = 55.77 mm2
DIAMETRO DE TUBERIA CONDUIT = 1 T-16mm
MEMORIA DE CALCULO

CALCULO Y SELECCIÓN DE ALIMENTADORES


#VALUE! CIRCUITO: A.P
UBICACIÓN MEDIDOR
CARGA TOTAL 86742 WATTS REFERENCIA NOM-001-2012
LONGITUD 120.000 METROS
SISTEMA UTILIZADO 3 FASES 3 HILOS
VOLTAJE 220 VOLT
MATERIAL DEL CONDUCTOR 1 COBRE=1 ALUMINIO=2
CALCULO DE CONDUCTORES POR CAPACIDAD DE CONDUCCION DE CORRIENTE
CORRIENTE NOMINAL(In) 253.23 AMPERES
FACTOR DE DEMANDA(F.P) 0.80 % ART.220-SECCIONES B O C
CORRIENTE DEMANDADA(Id) 202.59 AMPERES
AISLAMIENTO DEL CONDUCTOR A UTILIZAR THHW-LS
COLUMNA DE LA TABLA 310-15(16) 75 GRADOS CENTIGRADOS
CALIBRE NO. 4/0 AWG - KCM
# CONDUCTORES POR FASE(C/F) 2
CORRIENTE DE NOMINAL DEL CONDUCTOR(Inc) #N/A AMPERES TABLA 310-15(16)
CONDUCTORES ACTIVOS 3
TEMPETATURA AMBIENTE DE 35.00 GRADOS CENTIGRADOS
FACTOR DE CORRECION AGRUPAMIENTO(F.A) 1.00 TABLA 310-15b3a
FACTOR DE CORRECION TEMPERATURA(F.T) 0.91 TABLA 310-15B2a
CORRIENTE PERMISIBLE DEL CONDUCTOR(Ipc) #N/A AMPERES

CALCULO DE CONDUTORES POR CAIDA DE TENSION

CONDUCTOR A UTILIZAR 4/0 AWG - KCM


IMPEDANCIA CALCULADA #N/A OHMS - KM. TABLA 9 NEC
CANALIZACION #N/A
CAIDA DE TENSION CALCULADA(%e) #N/A %
CAIDA DE VOLTAJE(ΔV) #N/A VOLTS

CONDUCTOR MINIMO PARA PUESTA A TIERRA


POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 100
CONDUCTOR PARA PUESTA A TIERRA 8 AWG - KCM TABLA 250-94

PROTECCION CONTRA CORTOCIRCUITO

CORRIENTE TERMICA(Iter) 253.23 AMPERES SECCION 450-3(a)(1)


POLOS CAPACIDAD
INTERRUPTOR A INSTALAR(ITM) 3 100 tabla 450-3(a)(1)

CALCULO DE LA CANALIZACION #HILOS CALIBRE


CALIBRE DEL CONDUCTOR FASES = 6 4/0 AWG - KCM TABLAS CAP. 10 NOM
CALIBRE DEL CONDUCTOR NEUTRO= 2 4/0 AWG - KCM
CALIBRE DEL CONDUCTOR TIERRA FISICA 2 8 AWG - KCM
NO. DE COND. ACTIVOS EN CANALIZACION = 6
AREA OCUPADA POR LOS CONDUCTORES = #N/A mm2
DIAMETRO DE TUBERIA CONDUIT = 2 #N/A
MEMORIA DE CALCULO

FORMULAS UTILIZADAS

Corriente

W
Trifásicos 3F- 3 o 4 Hilos In=
√3×Ef ×F .P .
W
Bifásicos 2F-3 Hilos In=
2×Efn×F . P .
W
Monofásicos 1F-2 Hilos In=
Efn×F .P.

Caída de tensión
173×I× L×Z
Trifásicos 3F- 3 o 4 Hilos e%=
Ef ×1000

Bifásicos 2F-3 Hilos 100×I× L×Z


e%=
Efn×1000
Monofásicos 1F-2 Hilos 200×I ×L×Z
e%=
Efn×1000

Selección de conductores y protecciones

Por Ipc= I permisible del conductor Ipc=Inc×F. A .×F .T


Selección de interruptor por Ipc e In, ambas se deben cumplir

I T ó F≥Ia≥Ipc y I T ó F≤Ipc
El inmediato Superior (Cuando Ipc <= 800 Amp.) 210-22 c), 240-3 b)

I T ó F≥Ia≥Ipc y I T ó F≤Ipc
Calculo de In de motores

MOTOR MONOFASICO C . P . x 746 o Ver Tablas 430-148


In=
EnxF . P . xη
C . P . x 746
MOTOR BIFASICO In= o Ver Tablas 430-149
2×En×F .P . xη
C . P . x746
In=
√3×Ef ×F . P . xη
MEMORIA DE CALCULO

MOTOR TRIFASICO C . P . x746 o Ver Tablas 430-150


In=
√3×Ef ×F . P . xη

Calculo de cargas continuas y cargas no continuas.


In = ∑ In Cargas continuas + ∑ In Cargas no continuas
Ia = (In continuas x 1.25) + In no continuas
Selección de proteccion para motores
Selección de conductores por I y e% y tomar el mayor
Selección de Elemento Térmico (E.T.)

E.T. = In x 1.25 ó 1.15 a 1.70 Art. 430-32, 430-34 y 430-37

Selección de Interruptor de un motor

IT = In x 1.5 a 2.5 ó inmediato Inferior Tabla 430.152 y 430.52


IT = In x 4 ó inmediato Inferior cuando <=100A Art. 430.52 a) c
IT = In x 3 ó inmediato Inferior cuando = > 100A Art. 430.52 a) c
IF = In x 1.5 a 3 ó inmediato Inferior Tabla 430.152 y 430.52
IF = In x 4 ó inmediato Inferior cuando <= 600A Art. 430.52 a) a
IFDE = In x 1.5 a 1.75ó inmediato Inferior Tabla 430.152 y 430.52
IFDE = In x 2.25 ó inmediato Inferior cuando Art. 430.52 a) b

Calculo de alimentador de motores


In= ∑ In de motores.
Ia= ( ∑In de motores x F.D) + (0.25 x In motor mayor)

Calculo de alimentador de cargas continuas y cargas no continuas

Selección de conductor por I.


In = ∑ In Cargas continuas + ∑ In Cargas no continuas

Ia= ((In continuo x 1.25) + In no continuas x F.D.)

Calculo de alimentador de cargas continuas y cargas no continuas


In = ∑ In de Motores + ∑ InCargas continuas + ∑ In Cargas No continuas
Ia =(InMotor Mayor x 0.25) + F.D. ( ∑ InMotores + ∑ InCargas No Continuas) + ∑ InCargas Continuas

Calculo de intrruptor general de cargas continuas,no continuas y motores

IT ó F = IT ó F ó FDE Motor Mayor + ( S In Resto de los Motores x F.D. ) + ( S In Cargas Continuas x 1.25) + ( S In Carga No Continuas. X F.D. )
MEMORIA DE CALCULO

NOMENCLATURAUTILIZADA.

W = Carga (Watts)
In= A= Corriente Nominal (amperes)
V o E = Voltaje
Efn = Voltaje Fase-Neutro (volts) = 256V.
Eff = Voltaje Fase-Fase (volts) = 440V.
F.P. = Factor de Potencia (%)
F.T. = Factor de Temperatura
F.A. = Factor de Agrupamiento
F= Fase
H= Hilos
C/F = No. De conductores por fase
AWG o KCM.= Calibre del conductor
tierra = Cable de tierra física aislada
AREA = Area del conductor (mm2)
n = Eficiencia del motor = 90 %.
M = Distancia (mts.)
e% = Caída de tensión (%) = 5.0% máximo total
INT. = Capacidad del Interruptor
F.D. = Factor de demanda
Z = Impedancia del conductor
Ipc = Corriente Permisible del conductor
Id= Corriente Demandada
It = Corriente del Termo magnético.
Inc = Corriente nominal del conduc
Ia=In = Corriente del nominal
carga continua= es aquella en la que se espera que la corriente electrica circule por mas de tres horas
carga no continua= es aquella en la que se espera que la corriente electrica no circule por mas de tres horas
DIMENSIONES DE TUBERIA CONDUIT Y AREA DISPONIBLE PARA LOS CONDUCTORES
TAMAÑO mas de 2
NOMINAL cond.
mm. Fr=40%
16mm 78
21mm 137
27mm 222
35mm 387
41mm 526
53mm 867
63mm 1236
78mm 1904
91mm 2555
103mm 3282
129mm 5163
155mm 7456

DIMENSIONES DE LOS CONDUCTORES AISLADOS


AREA
TAMAÑO APROX.
NOMINAL mm2.
1 123
2 86
3 73.2
4 62.8
6 46.8
8 28.2
10 15.7
12 11.7
14 8.97
1/0 143
2/0 169
3/0 201
4/0 240
250 297
300 341
350 384
400 427
500 510
600 628
700 710
750 752
800 792
900 875
1000 954

FDECREMENT FDECREMENT
TEMPAMBIENTE AL 60 o C AL 75 o C
25 1.08 1.05
30 1.00 1
35 0.91 0.94
40 0.82 0.88
45 0.81 0.82
50 0.58 0.75
55 0.41 0.67
60 0.58
70 0.47
80

FACTORES DE CORRECCION POR TEMPERATURA


TABLA 310 - 15(B)(2)(A)

CONDUCTORES FACTOR DE
ACTIVOS CORRECCION
1 1
2 1
3 1
4 0.80
5 0.80
6 0.80
7 0.70
8 0.70
9 0.70
10 0.50
11 0.50
12 0.50
13 0.50
14 0.50
15 0.50
16 0.50
17 0.50
18 0.50
19 0.50
20 0.50
21 0.45
22 0.45
23 0.45
24 0.45
25 0.45
26 0.45
27 0.45
28 0.45
29 0.45
30 0.45
31 0.40
32 0.40
33 0.40
34 0.40
35 0.40
36 0.40
37 0.40
38 0.40
39 0.40
40 0.40
41 0.35
42 0.35
FACTORES DE CORRECCION POR AGRUPAMIENTO
TABLA 310 - 15(B)(3)(A)
CEDULA DE CABLEADO
CONDUCTORES CANALIZACION
TAMAÑO
NOMBRE CANTIDAD mm2 AWG CANTIDAD TIPO
COMERCIAL
4 53.48 1/0
T1 1 2" EMT
1 8.36 8
4 13.3 6
T2 1 1" EMT
1 5.26 10
4 13.3 6
T3 1 1" EMT
1 2.08 14
4 5.26 10
T4 1 1/2" EMT
1 2.08 14
4 5.26 10
1 2.08 14
T5 1 12" CHAROLA
4 13.3 6
1 5.26 10
4 5.26 10
1 2.08 14
4 13.3 6
T6 1 12" CHAROLA
1 5.26 10
4 53.48 1/0
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 5.26 10
T7 1 12" CHAROLA
4 53.48 1/0
1 8.36 8
4 5.26 10
1 2.08 14
4 5.26 10
1 2.08 14
4 13.3 6
1 5.26 10
4 53.48 1/0
T8 1 12" CHAROLA
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10
1 2.08 14
8 13.3 6
2 5.26 10
4 53.48 1/0
T9 1 12" CHAROLA
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10

T10 1 12" CHAROLA


1 2.08 14
8 13.3 6
2 5.26 10
8 53.48 1/0
T10 1 12" CHAROLA
2 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10
1 2.08 14
8 13.3 6
2 5.26 10
12 53.48 1/0
T11 1 12" CHAROLA
3 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10
1 2.08 14
12 13.3 6
3 5.26 10
12 53.48 1/0
T12 1 12" CHAROLA
3 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
Lista de material
Cantidad Descripcion modelo
1 Tablero I-line LA400M141B
3 Interruptor Termomagnetico HDA36100
2 Interruptor Termomagnetico HDA36060
1 Interruptor Termomagnetico HDA36050
1 Interruptor Termomagnetico HDA36040
3 Interruptor Termomagnetico HDA36015
500 Cable Calibre 1/0 Negro
130 Cable Calibre 8 Verde
450 Cable Calibre 10 Negro
570 Cable Calibre 6 Negro
75 Cable Calibre 10 Verde
157 Cable Calibre 14 Verde
3 interruptor de seguridad DTU363
5 base aerea IDE-5206 La casa del control
1 Base mural IDE-5326 y gabinete