Professional Documents
Culture Documents
PAPER
Rami Hakam,
P. Eng., Applications Engineer,
Custom Products,
Littelfuse Startco
NGR
How to select the proper neutral-grounding resistor for
a high-resistance grounded electrical system
How to select the proper neutral-grounding resistor for
a high-resistance grounded electrical system
If one of the phases shorts to ground causing a ground Calculating the value of the NGR
fault, the charging current for the other two phases will flow To detect high-impedance faults and provide machine-
through the ground fault. winding protection, the desired ground-fault-current pickup
(b) This makes for a direct way to measure the charging level for the ground-fault relay should be less than 20% of
current: introduce a deliberate ground fault on an the prospective ground-fault current. To put it another way,
ungrounded system and the resulting current through the a good rule of thumb is to multiply the desired ground-fault-
ground fault will be the charging current of the system, as current pickup level by an acceptable tripping ratio (say, 5x),
shown in Fig. 4. The shorting wire should be AWG 8 to and then use the next-largest available standard let-through
minimize its voltage drop. The grounding connection should current rating for the neutral-grounding resistor. For low- to
include a 5 to 10 A current-limiting fuse rated for the full medium-voltage systems, standard NGR current ratings are
system voltage, a variable resistance, and a switch. At its typically 1, 2, 5, 10, 15, and 25 A.
maximum value, the variable resistance should be such as to For example, consider a system with a charging current of
limit the charging current to half of its estimated magnitude. 0.5 A (which is quite common on a 480 V system) and a
Set the resistor to its maximum value, and then close the desired ground-fault pickup level of 1 A. Using a trip ratio
switch. Gradually reduce the resistor setting to zero; this of 5, the value of the NGR should be selected to allow five
will help prevent transient overvoltages during the test. times the desired pickup level current, or 5 A.
Zero sequence ammeter A1 will continue to show zero, and
ammeter A2 will measure the charging current. After taking Another example: in potash mining the trailing cables can
the reading, gradually bring the resistor back to its maximum become quite long, and as such will have correspondingly
value before opening the switch. Repeat the process on large charging currents in the range from 1 to 2 A (or more).
each of the other phases, and choose the one with the The tripping current on each feeder must be above charging
highest current for the rest of the calculations. Please note current to avoid nuisance or sympathetic tripping; a tripping
that the system is isolated from ground during the test. value of 3 A would be reasonable. In this case the NGR
should be selected for a let-through current five times the
desired pickup level, or 15 A.
It is worth noting that the 2009 edition of Canadian Electrical
Code (CEC) rule 10-1102 says that for systems up to 5 kV the
system may continue to operate with NGR currents up to 10
A, but that a visual or audible alarm must be activated.
Fig. 5: If the value of the charging current on a feeder is higher than the trip
point of the ground fault relay, then sympathetic tripping occurs.
Summary
An HRG system can improve safety, aid in compliance with
regulations, and reduce downtime by providing a more stable
distribution system. The critical part to consider is that these
systems must be properly designed and receive proper
maintenance. The use of a dedicated NGR continuity monitor
is one recommended method to ensure a continuously safe
and reliable operation of the system.
Additional technical information and application data for Littelfuse protection relays, generator and engine controls, fuses and other circuit protection
and safety products can be found on www.littelfuse.com. For questions, contact our Technical Support Group (800-832-3873). Specifications,
descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to changes without notice. All data
was compiled from public information available from manufacturers’ manuals and datasheets.
FORM: PFD769
REV: 1-B-030515