You are on page 1of 1

COLUMNA Cº Aº 0.20 x 0.20 MTS. 21.

70

.20 0.20
2.05 .60 3.56 .60 3.54 .60 3.54 .60 3.56 .60 2.05

TUBERIA HDP. 200 MM (8'')


B

0.20
2.4cm
LOSA LOSA LOSA LOSA LOSA

.45
0.60

0.60

0.60

0.60

0.60
SALPICADORA SALPICADORA SALPICADORA SALPICADORA SALPICADORA

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%
BLOQUE DE CONCRETO
DE 9x10x24 CM.
0.60 0.60 0.60 0.60 0.60

2.35
VIENE DEL TANQUE
IMHOFF TUBERIA HDP. 200MM (8'') PERFORADA
A S= 1.00% S= S= 1.00%
A

5.10
3.80
1.00%

ESPECIFICACIONES TECNICAS
CONCRETO:

SOLADO : F'C = 140 Kg/CM2


MUROS : F'C = 175 Kg/CM2
LOSA FONDO : F'C = 175 Kg/CM2
ZAPATAS, COLUMNAS: F'C = 175 Kg/CM2
LOSA TECHO Y VIGAS : F'C = 210 Kg/CM2
AREA NETA LECHO DE SECADO: 156.00 M2
SOPORTE METALICO
TIPO ABRAZADERA
DETALLE "A"
MAXIMA RELACION AGUA/CEMENTO 0.50 PARA MUROS
ALTURA MAXIMA DE VACIADO 1.50 m

DISPOSICION DE LOS LADRILLOS EN LOS


ACERO : Fy = 4200 Kg/CM2
S = 2.5%

S = 2.5%

.80 VER DETALLE


0.60

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%
0.60 0.60 0.60 0.60 RECUBRIMIENTO :
LECHOS DE SECADOS
ZAPATAS : 5.00 CM
MUROS (CARA HUMEDA)
ESC. 3.50 CM
1/10
MUROS (CARA SECA) 2.50 CM
COLUMNAS, LOSAS Y VIGAS : 2.50 CM
.80

.80

.80

.80

.80
TUBERIA HDP. 200 MM (8'') TRASLAPES :

0.45
Ø3/8" : 0.50 m

15.20
Ø1/2" : 0.40 m

.20
NO SE DEBE TRASLAPAR EL Ø VERTICAL DE LOS MUROS

0.45
NO SE DEBERAN CONCENTRAR TRASLAPES EN UNA MISMA SECCION
.80

.80

.80

.80

.80
JUNTAS DE CONSTRUCCION :
S = 2.5%

S = 2.5%

LA SUPERFICIE DE CONCRETO ENDURECIDO DEBERA TENER UN ACABADO

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%
RUGOSO Y DEBERA SER TRATADA ANTES DEL VACIADO DE LA OTRA ETAPA
0.60 0.60 0.60 0.60 0.60 EL TRATAMIENTO SRA UTILIZADO COMO PUENTE DE ADHERENCIA SIKADUR 32
.80 PRIMER O SIMILAR

VER DETALLE
REVESTIMIENTOS :
SOPORTE METALICO
LAS SUPERFICIES INTERIORES EN CONTACTO CON EL AGUA SERAN REVESTIDOS EN DOS CAPAS:
TIPO ABRAZADERA
- PRIMERA CAPA : SERA CON MEZCLA DE CEMENTO-ARENA 1:5 DE 1.50CM DE ESPESOR
ACABADO Y RAYADO
AREA NETA LECHO DE SECADO: 156 M2
- SEGUNDA CAPA : A LAS 24 HORAS CON MEZCLA DE CEMENTO ARENA 1:3 Y 5mm DE ESPESOR
ACABADO FROTACHADO

TERRENO : Q ADM. = 0.80 Kg/cm2


MEJORAR EL TERRENO CON OVER

NIVEL FREATICO ALTO : DRENAR EL AGUA MEDIANTE GALERIAS


FILTRANTES Y/O CANALES DE DRENAJE

VIENE DEL TANQUE

3.80

5.10
IMHOFF S=
A S= 1.00% 1.00% TUBERIA HDP. 200MM (8'') PERFORADA S= 1.00%
A

2.35
S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%

S = 2.5%
0.60 0.60 0.60 0.60 0.60
0.60

0.60

0.60

0.60

0.60
LOSA LOSA LOSA LOSA LOSA

.45
SALPICADORA SALPICADORA SALPICADORA SALPICADORA SALPICADORA

0.20
TUBERIA HDP. 200 MM (8'')

2.05 .60 3.56 .60 3.54 .60 3.54 .60 3.56 .60 2.05

.20 0.20
21.70
01 10/11/2015 ADICIONAL DE OBRA ING. KIKO FELIX ING. JHON TONY
DEPAZ CELI GARCIA LUCERO
B REV- N° FECHA DESCRIPCION PROYECTISTA ENTIDAD
4.10 4.10 .20 4.10 4.10 4.10

.20 .20
PLANTA DE LECHO DE SECADO
.20 .20 .20
MUNICIPALIDAD DISTRITAL DE MANCOS
ESCALA:
1/50

PROYECTO: MEJORAMIENTO Y AMPLIACION DEL SISTEMA DE AGUAY DESAGUE DE LA CIUDAD DE


MANCOS, DISTRITO DE MANCOS, PROVINCIA DE YUNGAY - ANCASH

PLANO:
UBICACION PLANO N°
LECHO DE SECADO
MANCOS
LS-01
LUGAR :
DISTRITO : MANCOS A.D. N° 04:
PROVINCIA : YUNGAY
REGION : ANCASH
PLANTA, CORTES Y
DETALLE
DIBUJO: DISEÑO: APROBADO: FECHA: ESCALA:

J.G. JULIO 2014 INDICADA