Hiroki Orihara
JGC Corporation
2
Contents
1. Background
2. Purpose
3. Step of Simulation
4. Condition
5. Fin-fan Cooler Ventilation Study
6. Pool Fire Condition
7. Pool Fire Simulation Under Fin-fan Cooler Using FLACS Fire
8. Consideration
9. Findings & Further Research
3
1. Background (Module)
• Very high construction cost
in developed countries or
remote locations
Module
• A prefabricated piece of the
plant
• Transported by sea barge
4
2. Purpose
When a pool fire occurs under the fin-fan cooler
To optimize the safety design for the layered equipment layout by fire
simulation using FLACS Fire
• appropriate extent of fireproofing to avoid the escalation of fire
6
3. Step of Simulation
Ventilation study under fin-fan cooler condition
To find the location of pool fire where the fin-fan cooler induced
airflow effect is highly expected
Pool fire simulation to evaluate the effect of fin-fan cooler induced airflow
7
2 m Pool Fire (view from west) 5 m Pool Fire (view from west)
Left: FFC Off Right: FFC On Left: FFC Off Right: FFC On
In both 2 m and 5 m pool fire case, the airflow directs outside the module in “FFC On”
The high temperature portion of pool fire is tilted to outside by the ventilation of fin-fan cooler
13
2 m Pool Fire (ground level plan view) 5 m Pool Fire (ground level plan view)
Left: FFC Off Right: FFC On Left: FFC Off Right: FFC On
The high temperature portion of pool fire is tilted to outside by the ventilation of fin-fan cooler
14
2 m Pool Fire (view from south) 5 m Pool Fire (view from south)
Left: FFC Off Right: FFC On Left: FFC Off Right: FFC On
15
2 m Pool Fire (view from south) 5 m Pool Fire (view from south)
Left: FFC Off Right: FFC On Left: FFC Off Right: FFC On
From the Streamlines, the upward airflow inducing effect by fin-fan cooler
does not have much higher effect than the upward airflow of flame itself
16
10 m Pool Fire (view from south) 10 m Pool Fire (view from west)
Left: FFC Off Right: FFC On Left: FFC Off Right: FFC On
In 10 m Pool
large poolFire
fire,(view from south)
the upward airflow of flameFin-fan Cooler
itself is Ventilation
higher than Study
Left: FFCinduced
Off Right: FFC On
horizontal (View from south)
airflow by fin-fan cooler
The fireproofing design for fin-fan cooler condition to be determined
considering the balance of vertical and horizontal induced airflow
18
Standard dimension
of FSE per API2218
Extended
The contribution of natural
Or wind effect to be considered
Eccentric
19
Appendix
21
North