NOMINAL MOMENT STRENGHT O

GIVEN VALUES
bw (mm) 300 fc' (Mpa) 21 As (mm2) 1570.796
bf (mm) 1500 fy (Mpa) 420 ß1 0.85
hf (mm) 100 Es (Mpa) 200000 ß1 N/A
no. of
d (mm)
540 bars 5
db (mm) 20 εcu 0.003

a(mm) 24.63994

Beam analysis CASE 1

CASE 1 (a ≤ hf) CASE 2 (a > hf)


T (N) 659734.457 Ccf (N) 2142000
C (N) 659734.457 Ccw (N) 131946.891
c (mm) 28.988 T (N) 2273946.89
εS 0.0529 c (mm) 28.988
Confirm εS TRUE
εy 0.0021 >= εy
Confirm εS TRUE
>= εy Φ 0.9
Φ 0.9 Mn (N-mm) 1119205739
Mn (N-mm) 348128697.4 Mn (kN-m) 1119.206
Mn (kN-m) 348.129 ΦMn 1007.285
ΦMn 313.316

NOMINAL MOMENT STRENGHT OF RECTAN

GIVEN VALUES
b (mm) 300 fc' (Mpa) 21 As (mm2) 1570.796
d (mm) 540 fy (Mpa) 420 ß1 0.85
db (mm) 20 E s (Mpa) 200000 ß1 N/A
no. of bars 5 εcu 0.003

CALCULATIONS
a 123.200
T (N) 659734.457
C (N) 659734.457
c (mm) 144.941
εS 0.0082
εy 0.0021
Confirm εS TRUE
>= εy
Φ 0.9
Mn (N-mm) 315617059.4
Mn (kN-m) 315.617
ΦMn 284.055
T STRENGHT OF T-BEAM SECTION

RENGHT OF RECTANGULAR BEAM SECTION