Electronic timers
Table of Contents
Electronic timers
1
Product group picture 1/1
Table of Contents 1/2
Overview 1/3
Approvals and Marks 1/4
CT-D range 1/5
Product group picture 1/5
Table of Contents 1/6
Benefits and advantages 1/7
Ordering details 1/8
Function diagrams 1/9
Connection diagrams 1/12
Technical data 1/13
Technical data, Technical diagrams 1/15
Wiring notes, Dimensional drawings 1/16
CT-E range 1/17
Product group picture 1/17
Table of Contents 1/18
Benefits and advantages 1/19
Ordering details 1/20
Ordering details 1/21
Function diagrams 1/22
Connection diagrams 1/27
Technical data 1/28
Technical diagrams 1/30
Wiring notes, Dimensional drawings 1/31
Notes 1/32
CT-S range 1/33
Product group picture 1/33
Table of Contents 1/34
Benefits and advantages 1/35
Conversion table 1/36
Ordering details 1/37
Ordering details - Accessories 1/40
Function diagrams 1/41
Connection diagrams 1/49
Technical data 1/52
Technical diagrams 1/55
Wiring notes, Dimensional drawings 1/56
1/2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Electronic timers
Overview
A ON-delay CT-MFD CT-ERD CT-MFE, CT- CT-ERE, CT- CT-MVS, CT- CT-ERS
MKE EKE MFS, CT-MBS,
CT-WBS
B OFF-delay CT-MFD CT-AHD CT-MFE CT-AHE, CT- CT-MVS, CT- CT-APS, CT-AHS,
ARE, CT-AKE MFS, CT-MBS CT-ARS, CT-VBS
�E Flasher CT-MVS
starting with ON or OFF
A+ AC BC G CT-MVS, CT-MXS,
further functions CT-MFS, CT-
(depending on device) MBS, CT-WBS
Time ranges 7 (0.05 s - 100 h) Multifunction devices: 8 (0.05 s - 100 10 (0.05 s - 300 h)
CT-SDD, CT-SAD: 4 (0.05 s - 10 min) h) Single-function devices: 5 single CT-ARS, CT-SDS: 7 (0.05 s- 10 min)
ranges (0.05-1 s, 0.1-10 s, 0.3-30 s,
3-300 s, 0.3-300 min)
Control supply voltage Wide and multi ranges Wide ranges Single and dual Wide, multi and single ranges
ranges
Type and number of contacts 1 or 2 c/o contacts 1 c/ o contact 1 or 2 c/o contacts
CT-SDD, CT-SAD: 2 n/o contacts CT-SDE: 1 n/o contact and 1 n/c CT-MVS.21, CT-MFS, CT-MBS: 2nd
contacts c/o contact selectable as inst. contact
CT-MKE, CT-EKE, CT-AKE: 1 thyristor CT-SDS: 2 n/o contacts
Control inputs voltage-related triggering, polarized, voltage-related triggering, polarized voltage-related triggering, non-polarized,
capable of switching a parallel load CT-MFE, CT-AHE, CT-AWE: capable of switching a parallel load
with auxiliary voltage CT-MFS, CT-MBS, CT-AHS:
volt-free triggering
1/3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Electronic timers
Approvals and marks
J existing
j pending
CT-D 1
CT-VWD.12
CT-MFD.12
CT-MFD.21
CT-AHD.12
CT-AHD.22
CT-SDD.22
CT-TGD.12
CT-TGD.22
CT-ERD.12
CT-ERD.22
CT-EBD.12
CT-SAD.22
Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J
D GOST J J J J J J J J J J J J
K CB scheme J J J J J J J J J J J J
E CCC J J J J J J J J J J J J
Marks
a CE J J J J J J J J J J J J
b C-Tick J j J j J j J J J j j j
J existing
j pending
CT-E
CT-AWE
CT-VWE
CT-MKE
CT-MFE
CT-AHE
CT-SDE
CT-ARE
CT-YDE
CT-AKE
CT-ERE
CT-EBE
CT-EKE
CT-IRE
Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J J
C GL J J J J J J J J J J J J J
D GOST J J J J J J J J J J J J J
K CB scheme J J J J J J J J J J
E CCC J J J J J J J J J J
L RMRS J J J J J J J J J J J J J
Marks
a CE J J J J J J J J J J J J J
b C-Tick J J J J J J J J J J J J J
J existing
j pending
CT-S
CT-WBS.22
CT-MBS.22
CT-MVS.12
CT-MXS.22
CT-MFS.21
CT-MVS.2x
CT-AHS.22
CT-ARS.11
CT-ARS.21
CT-ERS.12
CT-APS.12
CT-SDS.2x
CT-ERS.2x
CT-APS.2x
CT-VBS.1x
CT-IRS.1x
CT-IRS.2x
CT-IRS.3x
Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J J J J
C GL J J J J J J J J J J J j j J
D GOST J J J J J J J J J J J J J J J J J J
K CB scheme J J J J J J J J J J J J J J J J J J
E CCC J J J J J J J J J J J J J J J J J J
Marks
a CE J J J J J J J J J J J J J J J J J J
b C-Tick J J J J J J J J J J J J J J J J J J
1/4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Product group picture
1/5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Table of Contents
CT-D Range
1
Product group picture 1/5
Table of Contents 1/6
Benefits and advantages 1/7
Ordering details 1/8
Function diagrams 1/9
Connection diagrams 1/12
Technical data 1/13
Technical data, Technical diagrams 1/15
Wiring notes, Dimensional drawings 1/16
1/6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Benefits and advantages
Characteristics Benefits
1 Diversity:
Direct reading scales 1
2 multifunction timers
10 single-function timers Direct setting of the time delay without any
additional calculation provides accurate time delay adjustment.
Control supply voltages:
Wide range: 12-240 V AC/DC
Multi range: 24-48 V DC, 24-240 V AC LEDs for status indication 2
7 time ranges from 0.05s to 100 h or 4 time ranges from 0.05 s - 10 min All actual operational states are displayed by front-face LEDs, thus sim-
Width of only 17.5 mm plifying commissioning and troubleshooting.
Light-grey housing in RAL 7035
Devices with: Switching currents
1 c/o contact (250 V / 6 A) or 2 c/o contacts (250 V / 5 A) The CT-D range timers allow an output load of up to 6 A on devices with 1
Control input: voltage-related triggering, polarized, c/o contact and up to 5 A on devices with 2 c/o contacts.
capable of switching parallel loads
Approvals / Marks (partly depending)
Connection terminals 3
Width 17,5 mm 4
With their width of 17.5 mm only, the CT-D range timers are ideally suited
for installation in distribution panels.
Operating controls
1 LEDs for status indication
U - green LED:
3 V control supply voltage applied
2 W timing
R, R1, R2 - yellow LED:
V output relay energized
1
2 Time range adjustment
3 3 Fine adjustment of the time delay
2 4 Preselection of the timing function
multifunctional
single-functional
2CDC 253 021 F0004
2CDC 253 066 F0006
2 3 4
1
17.5 mm
1/7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Ordering details
Description
1
The CT-D range in MDRC design with a width of only 17.5 mm fits into all domestic installation
and distribution panels.
The CT-D range represents a link between industry and the installation types. For maximum
flexibility in operation, 10 single-function as well as 2 multifunction devices with 7 timing
functions are available. The devices offer 4 or 7 time ranges from 0.05 seconds up to 100
hours. Their wide input range allows the use in applications worldwide.
2CDC 251 089 F0006
Ordering details
Time Rated Time Control Out- Type Order code Price Weight
function control ranges input put (1 pce)
CT-MFD.12
supply
voltage 1 pce kg (lb)
A
B
CA
24-240 V AC 0.060
CB 7 (0.05 s - 100 h) n 1 c/o CT-MFD.12 1SVR500020R0000
DA 24-48 V DC (0.132)
DB
H
A
B
CA
12-240 V 0.065
CB 7 (0.05 s - 100 h) n 2 c/o CT-MFD.21 1SVR500020R1100
DA AC/DC (0.143)
DB
H
2CDC 251 091 F0006
0.060
A 1 c/o CT-ERD.12 1SVR500100R0000
(0.132)
0.065
A 2 c/o CT-ERD.22 1SVR500100R0100
(0.143)
CT-ERD.22 0.060
B 7 (0.05 s - 100 h) n 1 c/o CT-AHD.12 1SVR500110R0000
(0.132)
0.065
B n 2 c/o CT-AHD.22 1SVR500110R0100
(0.143)
24-240 V AC
CA 24-48 V DC 1 c/o CT-VWD.12 1SVR500130R0000 0.060
A ON-delay DA 1 c/o CT-EBD.12 1SVR500150R0000 (0.132)
B OFF-delay 0.060
CA Impulse-ON ED n 1 c/o CT-TGD.121) 1SVR500160R0000
2 x 7 (0.05 s - (0.132)
CB Impulse-OFF
DA Flasher starting with ON 100 h) 0.065
ED n 1 c/o CT-TGD.221) 1SVR500160R0100
DB Flasher staring with OFF (0.143)
H Pulse former F 4 (0.05 s - 10 2 n/o CT-SDD.222) 1SVR500211R0100 0.065
ED Pulse generator F min) 2 n/o CT-SAD.223) 1SVR500210R0100 (0.143)
F Star-delta change-over 1)
ON and OFF times adjustable independently: 2 x 7 time ranges 0.05 s - 100 h
2)
Transition time 50 ms fixed
3)
Transition time adjustable
Synonyms
1/8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Function diagrams
1 Remarks
Legend Terminal designations on the device and in the diagrams
G Control supply voltage not applied / Output contact open The 1st c/o contact is always designated 15-16/18.
B Control supply voltage applied / Output contact closed The 2nd c/o contact is designated 25-26/28.
A1-Y1/B1 Control input with voltage-related triggering The n/o contacts of the star-delta timers are designated with 17-18 and
17-28.
Control supply voltage is always applied to terminals A1-A2.
A1-A2 A1-A2
2CDC 252 106 F0206
A1-A2 A1-A2
2CDC 252 108 F0206
1/9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Function diagrams
1
�A Flasher, starting with the ON time �B Flasher, starting with the OFF time
(Recycling equal times, ON first) (Recycling equal times, OFF first)
CT-EBD, CT-MFD CT-MFD
Applying control supply voltage starts timing with symmetrical ON & OFF Applying control supply voltage starts timing with symmetrical ON & OFF
times. The cycle starts with an ON time first. The ON & OFF times are times. The cycle starts with an OFF time first. The ON & OFF times are
displayed by the flashing green LED, which flashes twice as fast during displayed by the flashing green LED, which flashes twice as fast during
the OFF time. the OFF time.
If control supply voltage is interrupted, the output relay de-energizes and If control supply voltage is interrupted, the output relay de-energizes and
the time delay is reset. the time delay is reset.
Control input A1-Y1/B1 of the CT-MFD is disabled when this function is Control input A1-Y1/B1 of the CT-MFD is disabled when this function is
selected. selected.
A1-A2 A1-A2
2CDC 252 029 F0206
H Pulse former (Single shot) �E Pulse generator, starting with the ON or OFF time
CT-MFD (Recycling unequal times, ON or OFF first)
This function requires continuous control supply voltage for timing. CT-TGD
Closing control input A1-Y1/B1 energizes the output relay immediately This function requires continuous control supply voltage for timing.
and starts timing. Operating the control contact switch A1-Y1/B1 during Applying control supply voltage, with open control input A1-Y1/B1,
the time delay has no effect. The green LED flashes during timing. When starts timing with an ON time first. Applying control supply voltage, with
the selected ON time is complete, the output relay de-energizes and the closed control input A1-Y1/B1, starts timing with an OFF time first. The
flashing green LED turns steady. After the ON time is complete, it can be ON & OFF times are displayed by the flashing green LED, which flashes
restarted by closing control input A1-Y1/B1. twice as fast during the OFF time.
If control supply voltage is interrupted, the output relay de-energizes and The ON & OFF times are independently adjustable.
the time delay is reset. If control supply voltage is interrupted, the output relay de-energizes and
the time delay is reset.
A1-A2 A1-A2
2CDC 252 110 F0206
A1-Y1/B1 A1-Y1/B1
15-18, 25-28 15-18, 25-28
15-16, 25-26 15-16, 25-26
green LED green LED
t t t1 t2 t2 t1
1/10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Function diagrams
1 F Star-delta change-over
(Star-delta starting)
CT-SDD, CT-SAD
A1-A2
contactor connected to terminals 17-18 and begins the set starting time green LED
t1 t2
t1. The green LED flashes during timing. When the starting time is com-
plete, the first output contact de-energizes the star contactor. t1 = adjusted starting time
t2 = transition time
Now, the transition time t2 starts. When the transition time is complete, CT-SDD: t2 = 50 ms
CT-SAD: t2 adjustable
the second output contact energizes the delta contactor connected to
terminals 17-28. The delta contactor remains energized as long as con-
trol supply voltage is applied to the unit.
2CDC 252 128 F0b06
95 1 3 5
F2 -F1
96 2 4 6
S1 21
0
22
S2 13 53
I K2
14 54 1 3 5 1 3 5 1 3 5
-K2 2 4 6
-K3 2 4 6
-K1 2 4 6
17 17 13 13
K1T K2 K1
18 28 14 14
22 22 1 5 4 97 95
K3 K1 -F2 98 96
21 21
3 2 6
A1 A1 A1 A1
-M1
K1T K1 K3 K2
A2 A2 A2 A2 W1 W2
N V1 M V2
U1 3~ U2
Y N
1/11
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Connection diagrams
CT-MFD.21
2CDC 252 113 F0b06
CT-MFD.12 A CT-ERD.22 A CT-ERD.12 1
A2 16 18 26 28 A2 16 18 A2 16 18 26 28 A2 16 18
18 16 Y1/B1 18 16
18 16 A2 18 16 A2
28 26 A2 28 26 A2
A2 16 18 26 28 A2 16 18 A2 16 18 A2 16 18
18 16 Y1/B1
18 16 A2 18 16 A2 18 16 A2
28 26 A2
A1 15 25 A1 15 Y1/B1 A1 17 A1 17
Y1/ Y1/
B1 A1 15 25 B1 A1 15 A1 17 A1 17
A2 16 18 26 28 A2 16 18 A2 18 28 A2 18 28
18 16 Y1/B1
18 16 A2 28 18 A2 28 18 A2
28 26 A2
1/12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Technical data
1/13
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Technical data
1
CT-D with 1 c/o CT-D with 2 c/o CT-MFD.21
contact contacts
General data
Duty time 100%
17.5 x 70 x 58 mm 17.5 x 80 x 58 mm
Dimensions (W x H x D)
(0.69 x 2.76 x 2.28 in) (0.69 x 3.15 x 2.28 in)
Weight see ordering details
Mounting DIN rail (IEC/EN 60715), snap-mounting without any tool
Mounting position any
Minimum distance to other units horizontal / vertical no / no
Degree of protection housing / terminals IP50 / IP20
Electrical connection
2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
fine-strand with(out) wire end ferrule
1 x 0.5-2.5 mm 2 (1 x 20-14 AWG)
Wire size
2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
rigid
1 x 0.5-4 mm 2 (1 x 20-12 AWG)
Stripping length 7 mm (0,28 in)
Tightening torque 0.5-0.8 Nm
Environmental data
Ambient temperature range operation / storage -20 ... +60 °C / -40 ... +85 °C
Damp heat (cyclic) IEC/EN 60068-2-30 6 x 24 h cycles, 55 °C, 95 % RH
Vibration (sinusoidal) IEC/EN 60068-2-6 40 m/s 2, 20 cycles, 10....150...10 Hz
Shock (half-sine) IEC/EN 60068-2-27 100 m/s 2, 11 ms
Isolation data
Rated impulse withstand voltage Uimp VDE 0110, IEC/EN 60664-1 4 kV; 1.2/50 µs
between all isolated circuits
Pollution category IEC/EN 60664-1, VDE 0110 3
Overvoltage category IEC/EN 60664-1, VDE 0110 III
input circuit / output circuit 300 V
Rated insulation voltage Ui
output circuit 1 / output circuit 2 300 V
Basic insulation (IEC/EN 61140) input circuit / output circuit 300 V
Protective separation (VDE 0106 part 101 and input circuit / output circuit 250 V
part 101/A1; IEC/EN 61140)
Power-frequency withstand voltage test (test between all isolated circuits 2.5 kV, 50 Hz, 1 s
voltage, routine test)
Standards
Product standard IEC 61812-1, EN 61812-1 + A11, DIN VDE 0435 part 2021
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electronic discharge IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV)
radiated, radio-frequency. electromagnetic filed IEC/EN 61000-4-3 Level 3 (10 V / m)
electrical fast transient/burst IEC/EN 61000-4-4 Level 3 (2 kV / 5 kHz)
surge IEC/EN 61000-4-5 Level 4
conducted disturbances, induced by radio-frequency fi elds IEC/EN 61000-4-6 Level 3 (10 V)
Interference emissions IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
1/14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Technical data, Technical diagrams
Technical diagrams
1
Load limit curves
AC load (resistive) DC load (resistive)
1.0
2CDC 252 123 F0206
Switching cycles
2CDC 252 124 F0206
Derating factor F
0.9
0.8
0.7 250 V
resistive load
0.6
0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Switching current [A]
1/15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-D range
Wiring notes, Dimensional drawings
A2
N(-)
58 2.28“ 58 2.28“
0.69“ 0.2“
0.69“ 0.2“
17,5 5 43,4 1.71“
17,5 5 43,4 1.71“
80 3.15“
45 1.77“
70 2.76“
45 1.77“
1/16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Product group picture
1/17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Table of Contents
CT-E Range
1
Product group picture 1/17
Table of Contents 1/18
Benefits and advantages 1/19
Ordering details 1/20
Function diagrams 1/22
Connection diagrams 1/27
Technical data 1/28
Technical diagrams 1/30
Wiring notes, Dimensional drawings 1/31
Notes 1/32
1/18
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Benefits and advantages
Characteristics Benefits
1 Diversity: Direct reading scales 1
2 multifunction timers
Direct setting of the time delay without any additional calculation provides
56 single-function timers accurate time delay adjustment.
4 switching relays
Control supply voltages:
LEDs for status indication 2
Dual range: 24 V AC/DC
All actual operational states are displayed by front-face LEDs, thus sim-
Single range: 110-130 V AC, 220-240 V AC
plifying commissioning and troubleshooting.
Wide range: 24-240 V AC/DC (CT-MFE)
Time ranges
Connection screws in M3 (Pozidrive 1) 3
5 single ranges: 0.05-1 s, 0.1-10 s, 0.3-30 s, 3-300 s, 0.3-30 min
8 time ranges: 0.05 s - 100 h (CT-MFE) Easy and fast tightening and release of the connection screws with po-
zidrive, pan- or crosshead screwdriver.
Devices with 1 c/o (SPDT) contact (250 V / 4 A) or solid-state out-
put for high switching frequencies (thyristor 0.8 A)
Switching relay CT-IRE for added switching contacts with either Solid-state output 4
side-by-side or diagonally positioned connection terminals Devices with solid-state output are the perfect solution for high operation
cycles.
Operating controls
1 LEDs for status indication
U - green LED: V control supply voltage applied
1 R2: red LED: V output relay energized
2 Time range adjustment (only multifunctional devices)
2
3 Fine adjustment of the time delay
4 Preselection of the timing function (only multifunctional devices)
3
1 2 3 4
2CDC 252 166 F0005
A1 AL
A1
AL
1/19
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Ordering details
Description
1
The CT-E range with its excellent price/performance ratio offers an ideal solution for serial
applications. 56 singlefunction devices with 5 different time ranges as well as 2 multifunction
timers with 6 functions and 8 time ranges offer the highest possible flexibility for almost every
application. For high operating cycles, contact-free CT-E timers with solid-state output are
available.
1SVR 550 029 F8100
Ordering details
Time Rated Time Control Output Type Order code Price Weight
function control ranges Input (1 pce)
supply
CT-MFE voltage 1 pce kg (lb)
A
B
CA 24-240 8 0.08
n 1 c/o CT-MFE 1SVR550029R8100
DB V AC/DC (0.05 s - 100 h) (0.18)
DA
H
0.1-10 s 1SVR550107R1100
24 V AC/DC, 0.3-30 s 1SVR550107R4100
220-240 V AC 3-300 s 1SVR550107R2100
0.3-30 min 1SVR550107R5100 0.08
A 1 c/o CT-ERE
0.1-10 s 1SVR550100R1100 (0.18)
110-130 0.3-30 s 1SVR550100R4100
V AC 3-300 s 1SVR550100R2100
0.3-30 min 1SVR550100R5100
0.1-10 s 1SVR550118R1100
1SVR 550 111 F1100
Synonyms
1/20
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Ordering details
Ordering details
1 Time Rated Time Control Output Type Order code Price Weight
function control ranges Input (1 pce)
supply
voltage 1 pce kg (lb)
0.1-10 s 1SVR550148R1100
24 V AC/DC 0.3-30 s 1SVR550148R4100
3-300 s 1SVR550148R2100
2CDC 251 125 F0004
0.1-10 s 1SVR550140R1100
110-130 V AC 0.3-30 s CT-AWE 1SVR550140R4100 0.08
CB n 1 c/o 2)
(0.18)
3-300 s 1SVR550140R2100
CT-AWE 0.1-10 s 1SVR550141R1100
220-240 V AC 0.3-30 s 1SVR550141R4100
3-300 s 1SVR550141R2100
24 V AC/DC,
CT-EBE 1SVR550167R1100 0.08
DB 220-240 V AC 0.1-10 s 1 c/o 7)
(0.18)
110-130 V AC 1SVR550160R1100
0.1-10 s 1SVR550207R1100
24 V AC/DC,
0.3-30 s 1SVR550207R4100
220-240 V AC
3-300 s CT-YDE 1SVR550207R2100 0.08
FA 1 c/o
0.1-10 s
1)
1SVR550200R1100 (0.18)
110-130 V AC 0.3-30 s 1SVR550200R4100
2CDC 251 128 F0004
3-300 s 1SVR550200R2100
24 V AC/DC,
1SVR550217R4100
220-240 V AC
1 n/o + CT-SDE 0.08
CT-IRE FC 0.3-30 s
110-130 V AC 1 n/c 3) 8)
1SVR550210R4100 (0.18)
380-415 V AC 1SVR550212R4100
A
CA 24-240 0.1-10 s, CT-MKE 0.08
1SVR550019R0000
DA V AC/DC 3-300 s 6) 9)
(0.18)
DB
solide-
0.1-10 s 1SVR550509R1000
24-240 state 0.08
A 0.3-30 s CT-EKE 1SVR550509R4000
A ON-delay V AC/DC (0.18)
B OFF-delay 3-300 s 1SVR550509R2000
CA Impulse-ON 0.1-10 s 1SVR550519R1000
CB Impulse-OFF 0.08
Flasher starting with ON B 24-240 V AC 0.3-30 s CT-AKE 1SVR550519R4000
DA (0.18)
DB Flasher staring with OFF 3-300 s 1SVR550519R2000
H Pulse former 24 V AC/DC 1SVR550228R9100
G Switching relay CT-IRE 0.08
G 220-240 V 1 c/o
FA Star-delta change-over 4)
1SVR550221R9100 (0.18)
twice ON-delayed AC/DC
FC Star-delta change-over 24 V AC/DC 1SVR550238R9100
with impulse CT-IRE 0.08
G 220-240 1 c/o
DE Pulse generator starting
5)
1SVR550231R9100 (0.18)
V AC/DC
with ON or OFF
1)
without auxiliary voltage
2)
with control input
3)
with fixed transition time
4)
A1/A2 diagonally
5)
A1/A2 on top
6)
solid-state output, functions and time range selection via external jumpers
7)
symetric ON & OFF times
8)
common contact
9)
Functions: ON-delay (AC/DC), Impuls-ON (AC only), Flasher starting with OFF (AC only)
Notice
CT-...KE are solid-state timers with thyristor output for 2-wire applications. They are connected
directly in series with the control coil of contactors or relays. Voltage should not be applied wit-
hout a load connected, because there is no current limiting in the unit.
1/21
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Function diagrams
Remarks
1
Legend Terminal designations on the device and in the diagrams
G Control supply voltage not applied / Output contact open The c/o contact is always designated 15-16/18.
B Control supply voltage applied / Output contact closed The n/o contacts are designated with 15-16 and 15-18.
A1-Y1/B1 Control input with voltage-related triggering Control supply voltage is always applied to terminals A1-A2/B1.
A1-A2/B1 A1-A2
2CDC 252 130 F0205
15-18 A1-Y1
15-16
15-18
green LED 15-16
red LED green LED
t <t red LED
t
t = adjusted time delay
t = adjusted time delay
Minimum control pulse length: 20 ms
1/22
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Function diagrams
CT-VWE:
A1-A2/B1 A1-A2/B1
2CDC 252 133 F0205
CT-MFE:
A1-A2
A1-A2 A1-A2
2CDC 252 138 F0205
15-18 A1-Y1
15-16
15-18
green LED 15-16
red LED green LED
t red LED
t
t = adjusted pulse time
t = adjusted pulse time
1/23
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Function diagrams
CT-EBE:
A1-A2 A1-A2
2CDC 252 136 F0205
A1-Y1 15-18
15-16
15-18
15-16 green LED
green LED
red LED
t t
1/24
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Function diagrams
FA Star-delta change-over
1
A1-A2/B1
2CDC 252 133 F0206
15-18
15-16
green LED
red LED
Star contactor
Delta contactor
t1 t2
1 3 5
-F1
2 4 6
1 3 5 1 3 5 1 3 5
-K2 2 4 6
-K3 2 4 6
-K1 2 4 6
FC Star-delta change-over 1 5 4 97 95
-F2
CT-SDE 3 2 6
98 96
Applying control supply voltage, energizes the star contactor (K1) and
the line contactor (K2) and begins the set starting time. -M1
When the starting time is complete, contact 15-16 de-energizes the star W1
V1 M
W2
V2
contactor (K1). Now, the fixed transition time starts. U1 3~ U2
When the transition time is complete, contact 15-18 energizes the delta
contactor (K3). Power circuit diagram
1SVC 110 000 F 0392
A1-A2/B1
2CDC 252 134 F0206
15-18
15-16
green LED
red LED
Star contactor
Delta contactor
t1 t2
1/25
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Function diagrams
supply voltage is interrupted, the load de-energizes and the time delay is reset.
Interrupting control supply voltage before the time delay is complete, resets the t = adjusted time delay
time delay. The load does not energize.
A1-A2
and de-energizes with the selected ON & OFF times. The ON & OFF times are
equal. The cycle starts with an ON time first (load energized). If control t = adjusted flashing time
supply voltage is interrupted, the load de-energizes and the time delay is reset.
A1-A2
Notice:
CT-...KE are solid-state timers with thyristor output for 2-wire applications. They are connected directly in series with the control coil of contactors
or relays. Voltage should not be applied without a load connected, because there is no current limiting in the unit.
1/26
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Connection diagrams
A1 15 A1 B1 15 A1 15 A1 B1 15
A2 16 18 A2 16 18 A2 16 18 A2 16 18
16 18 A2 16 18 A2 16 18 A2 16 18 A2
A1 15 A1 15 A1 15 A1 B1 15
A2 B1 16 18 A2 16 18 A2 16 18 A2 16 18
16 18 A2 16 18 A2 16 18 A2 16 18 A2
A1 15 A1 15 A1 15 A1 11
A2 B1 16 18 A2 B1 16 18 A2 16 18 A2 12 14
16 18 A2 16 18 A2 16 18 A2 12 14 A2
A1 A2 A1 X1 X2 A1 AL A1 AL
A1 A1 A1
A1 11 Y2
U
A2 AL AL
A2
A2 12 14
11 12 14 X3 X4 A2 Y2 A2
1/27
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Technical data
Technical data
1
Data at Ta = 25 °C and rated values, unless otherwise indicated
1.) 0.1-10 s
2 time ranges 0.1-300 s (CT-MKE) -
2.) 3-300 s
<50 ms
CT-ARE: <200 ms CT-MKE: <100 ms
Recovery time
CT-AWE, CT-SDE: <400 ms CT-AKE: <300 ms
CT-YDE: <500 ms
Accuracy within the rated control supply voltage tolerance it < 0.5 % / V
it < 0.1 % / °C
Accuracy within the temperature range
CT-MFE: it <0.06 % / °C -
Repeat accuracy (constant parameters) it < 1 %
Star-delta transition time CT-YDE / CT-SDE 50 ms / 30 ms -
Minimum energizing time CT-ARE 200 ms -
Output circuit
15-16/18 Relay, 1 c/o contact -
Kind of output
A1-A2. A1-AL - Thyristor
Contact material AgCdO -
Rated operational voltage Ue VDE 0110, IEC/EN 60947-1 250 V
Maximum switching voltage 250 V AC, 250 V DC
AC12 (resistive) at 230 V 4A -
Rated operational current Ie AC15 (inductive) at 230 V 3A -
(IEC/EN 60947-5-1 ) AC15 (inductive) at 230 V 4A -
DC13 (inductive) at 24 V 2A -
1)
CT-MFE: yes / no
1/28
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Technical data
1/29
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Technical diagrams
Technical diagrams
1
Load limit curves
AC load (resistive) DC load (resistive)
V V
U 200 U 200
100 100
80 80
60 60
50 50
40 40
30 30
20 20
10 10
0,1 0,2 0,5 1 2 4 6 10 0,1 0,2 0,5 1 2 4 6 10
I A I A
1,0
2CDC 252 192 F0205
106
2CDC 252 034 F0208
0,9 9
8
0,8 N
5
F 4
0,7 3
0,6 2
0,5
105
1 2 3 4 5 6 7 8
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
220 V 50 Hz 1 AC I A
cos ϕ
360 cycles/h
1/30
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Wiring notes, Dimensional drawings
Wiring notes
1 for single-function devices with control contact
(CT-AHE, CT-AWE with auxiliary voltage)
A1 Y1
A1 Y1
U I
U
A2
A2
2CDC 252 198 F0b05
A1 Y1 I
I
U U A1 Y1
A2
A2
78,5 3.09“
1/31
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-E range
Notes
1/32
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Product group picture
1/33
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Table of Contents
CT-S Range
1
Product group picture 1/33
Table of Contents 1/34
Benefits and advantages 1/35
Conversion table 1/36
Ordering details 1/37
Ordering details - Accessories 1/40
Function diagrams 1/41
Connection diagrams 1/49
Technical data 1/52
Technical diagrams 1/55
Wiring notes, Dimensional drawings 1/56
1/34
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Benefits and advantages
Characteristics
1
Diversity: Devices with:
8 multifunction timers 1 or 2 c/o contacts
13 single-function timers 2nd c/o contact can be selected as instantaneous contact 1)
8 switching relays Remote potentiometer connection 1)
Control supply voltages: Control input with volt-free or voltage-related triggering
Multi range: 24-48 V DC, 24-240 V AC e.g. to start timing, pause timing
Wide range: 24-240 V AC/DC Extended operating temperature range down to -40 °C 1)
Single range: 380-440 V AC Sealable transparent cover for protection against unauthorized changes
of time values
Innovative connection technology
Integrated marker label
Double-chamber cage connection terminals
Approvals / Marks (partly pending)
Easy Connect Technology
A, C, D, E, K / a, b
Synonyms 1)
selected devices
Benefits
Tool-free wiring and excellent vibration resistance. Push-in terminals provi- All actual operational states are displayed by front-face LED‘s, thus
de connection of wires up to 2 x 0,5 - 1,5 mm² (2 x 20 -16 AWG), rigid or simplifying commissioning and troubleshooting.
fine-strand with or without wire end ferrules.
Double-chamber cage connection terminals 2 Integrated marker label 5
Double-chamber cage connection terminals provide connection of wires Integrated marker labels allow the product to be marked quickly and
up to 2 x 0,5-2,5 mm² (2 x 20-14 AWG) rigid or fine-strand, with or without simply. No additional marker labels are required.
wire end ferrules. Potential distribution does not require additional termi-
nals.
Sealable transparent cover 6
Snap-On housing Protection against unauthorized changes of time and threshold values.
Tool-free DIN rail installation and deinstallation of the Electronic Timer with Available as an accessory.
Snap-On housing.
Time range preselection and fine adjustment 3
2 4 6
1/35
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Conversion table
1SVR 630 010 R0200 CT-MFS.21 1SVR 730 010 R0200 CT-MFS.21S 1SVR 740 010 R0200 CT-MFS.21P
1SVR 630 010 R3200 CT-MBS.22 1SVR 730 010 R3200 CT-MBS.22S 1SVR 740 010 R3200 CT-MBS.22P
1SVR 630 020 R0200 CT-MVS.21 1SVR 730 020 R0200 CT-MVS.21S 1SVR 740 020 R0200 CT-MVS.21P
1SVR 630 020 R3100 CT-MVS.12 1SVR 730 020 R3100 CT-MVS.12S 1SVR 740 020 R3100 CT-MVS.12P
1SVR 630 020 R3300 CT-MVS.22 1SVR 730 020 R3300 CT-MVS.22S 1SVR 740 020 R3300 CT-MVS.22P
1SVR 630 021 R2300 CT-MVS.23 1SVR 730 021 R2300 CT-MVS.23S 1SVR 740 021 R2300 CT-MVS.23P
1SVR 630 030 R3300 CT-MXS.22 1SVR 730 030 R3300 CT-MXS.22S 1SVR 740 030 R3300 CT-MXS.22P
1SVR 630 040 R3300 CT-WBS.22 1SVR 730 040 R3300 CT-WBS.22S 1SVR 740 040 R3300 CT-WBS.22P
1SVR 630 100 R0300 CT-ERS.21 1SVR 730 100 R0300 CT-ERS.21S 1SVR 740 100 R0300 CT-ERS.21P
1SVR 630 100 R3100 CT-ERS.12 1SVR 730 100 R3100 CT-ERS.12S 1SVR 740 100 R3100 CT-ERS.12P
1SVR 630 100 R3300 CT-ERS.22 1SVR 730 100 R3300 CT-ERS.22S 1SVR 740 100 R3300 CT-ERS.22P
1SVR 630 110 R3300 CT-AHS.22 1SVR 730 110 R3300 CT-AHS.22S 1SVR 740 110 R3300 CT-AHS.22P
1SVR 630 120 R3100 CT-ARS.11 1SVR 730 120 R3100 CT-ARS.11S 1SVR 740 120 R3100 CT-ARS.11P
1SVR 630 120 R3300 CT-ARS.21 1SVR 730 120 R3300 CT-ARS.21S 1SVR 740 120 R3300 CT-ARS.21P
1SVR 630 180 R0300 CT-APS.21 1SVR 730 180 R0300 CT-APS.21S 1SVR 740 180 R0300 CT-APS.21P
1SVR 630 180 R3100 CT-APS.12 1SVR 730 180 R3100 CT-APS.12S 1SVR 740 180 R3100 CT-APS.12P
1SVR 630 180 R3300 CT-APS.22 1SVR 730 180 R3300 CT-APS.22S 1SVR 740 180 R3300 CT-APS.22P
1SVR 630 210 R3300 CT-SDS.22 1SVR 730 210 R3300 CT-SDS.22S 1SVR 740 210 R3300 CT-SDS.22P
1SVR 630 211 R2300 CT-SDS.23 1SVR 730 211 R2300 CT-SDS.23S 1SVR 740 211 R2300 CT-SDS.23P
1/36
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Ordering details
Description
1
The highly sophisticated CT-S range in ABB’s new S-range housing offers two different
types of connection terminals and is ideally suited for universal use. Two different connection
technologies are available:
Double-chamber cage connection terminals:
2CDC 251 024 V0011
Accessories:
The CT-S range offers the possibility of using accessories such as a remote potentiometer to
CT-MVS.21P adjust the time delay or a sealable, transparent cover to protect against unauthorized changes.
of time and threshold values.
Ordering details
Time Rated Time Control Out- Type Order code Price Weight
function control ranges input put (1 pce)
supply
voltage 1 pce kg (lb)
0.148
A 24-240 CT-MVS.21S 1SVR730020R0200
(0.326)
2CDC 251 023 V0011
B V AC/DC
0.136
AB
2) 3) 4)
CT-MVS.21P 1SVR740020R0200
(0.300)
CA 0.142
CB CT-MVS.22S 1SVR730020R3300
24-48 V DC, 10 (0.05 s- (0.313)
DE n 2 c/o
CT-MBS.22P
24-240 V AC 300 h) 0.131
FC CT-MVS.22P 1SVR740020R3300
H (0.289)
A+ 0.144
CT-MVS.23S 1SVR730021R2300
G 380-440 (0.317)
V AC 0.133
CT-MVS.23P 1SVR740021R2300
(0.293)
A
B 0.107
AB CT-MVS.12S 1SVR730020R3100
(0.236)
CA
24-48 V DC, 10 (0.05 s-
A(+) ON-delay (accumulative) CB n 1 c/o
24-240 V AC 300 h)
B OFF-delay without aux. DE
voltage H 0.102
CT-MVS.12P 1SVR740020R3100
CA Impulse-ON A+ (0.225)
CB Impulse-OFF G
AB Symmetrical ON-delay and 1)
AB
OFF-delay 0.142
CE CT-MXS.22S 1SVR730030R3300
DA Flasher starting with ON (0.313)
DB Flasher staring with OFF ED 24-48 V DC,
DE Pulse generator starting 2 x 10 (0.05
A+ 24-240 V AC n 2 c/o
FC Star-delta change-over with 5) s- 300 h)
impulse AC 0.131
CT-MXS.22P 1SVR740030R3300
H Pulse former BC (0.289)
G ON/OFF-function G
FA Star-delta change-over twice A 0.145
24-240 CT-MFS.21S 1SVR730010R0200
ON-delayed B 10 (0.05 s- (0.320)
with ON or OFF AB V AC/DC 2 c/o
ED Pulse generator starting with 2) 3) 4) 300 h) 0.133
CA CT-MFS.21P 1SVR740010R0200
ON or OFF (0.293)
CB
EC Single-pulse generator
DA 0.140
CE Impulse-ON/OFF CT-MBS.22S 1SVR730010R3200
DB 24-48 V DC, (0.309)
DA Flasher starting with ON 10 (0.05 s-
FC 24-240 V AC n/ n 2 c/o
DB Flasher starting with OFF H 3) 4) 300 h) 0.129
fixed impulse with adjustable CT-MBS.22P 1SVR740010R3200
AC G (0.284)
time delay
BC Adjustable impulse with fixed
time delay
1)
Asymmetrical ON- and OFF-delay n Control input with voltage-related triggering
2)
Extended temperature range -40 °C n Control input with volt-free triggering
3)
Remote potentiometer connection
4)
2nd c/o contact selectable as instantaneous contact
5)
2 remote potentiometer connections
1/37
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Ordering details
Time Rated Time Control Out- Type Order code Price Weight
function control ranges input put (1 pce) 1
supply
voltage 1 pce kg (lb)
A
0.123
2CDC 251 030 V0011
CA CT-WBS.22S 1SVR730040R3300
(0.271)
DA
24-48 V DC, 10 (0.05 s-
DB 2 c/o
24-240 V AC 300 h)
G 0.115
AC CT-WBS.22P 1SVR740040R3300
(0.254)
CT-ERS.21P BC
0.130
CT-ERS.21S 1SVR730100R0300
24-240 V (0.287)
AC/DC 2) 0.121
CT-ERS.21P 1SVR740100R0300
(0.267)
2 c/o
0.121
CT-ERS.22S 1SVR730100R3300
24-48 V DC, 10 (0.05 s- (0.267)
A
24-240 V AC 300 h) 0.113
CT-ERS.22P 1SVR740100R3300
(0.249)
0.106
CT-ERS.12S 1SVR730100R3100
2CDC 251 033 V0011
0.136
CT-AHS.22S 1SVR730110R3300
24-48 V DC, 10 (0.05 s- (0.300)
n 2 c/o
24-240 V AC 300 h) 0.125
CT-AHS.22P 1SVR740110R3300
(0.276)
0.106
CT-ARS.11S 1SVR730120R3100
CT-SDS.23P (0.234)
1 c/o
0.100
CT-ARS.11P 1SVR740120R3100
24-240 V 7 (0.05 s- 10 (0.220)
B 6)
A(+) ON-delay (accumulative) AC/DC min) 0.124
CT-ARS.21S 1SVR730120R3300
B OFF-delay without aux. (0.273)
2 c/o
voltage 0.115
CT-ARS.21P 1SVR740120R3300
CA Impulse-ON (0.254)
DA Flasher starting with ON 110-127 V
DB Flasher staring with OFF 0.123
AC or CT-VBS.17 1SVR430261R6000
(0.271)
G ON/OFF-function
B 6) 110 V DC 8)
200-240 V 0.118
CE Impulse-ON/OFF CT-VBS.18 1SVR430261R5000
AC/DC 8) (0.260)
DA Flasher starting with ON
DB Flasher starting with OFF 0.114
CT-SDS.22S 1SVR730210R3300
AC fixed impulse with adjustable 24-48 V DC, (0.251)
time delay 24-240 V AC 0.108
Adjustable impulse with fixed CT-SDS.22P 1SVR740210R3300
BC 7 (0.05 s- 10 (0.238)
time delay F7) 2 n/o
min) 0.118
F Star-delta change-over CT-SDS.23S 1SVR730211R2300
380-440 V (0.260)
AC 0.112
CT-SDS.23P 1SVR740211R2300
(0.247)
1)
Asymmetrical ON- and OFF-delay n Control input with voltage-related triggering
2)
Extended temperature range -40 °C n Control input with volt-free triggering
3)
Remote potentiometer connection
4)
2nd c/o contact selectable as instantaneously contact
5)
2 remote potentiometer connections
6)
Without auxiliary voltage
7)
50 ms transition time
8)
For DC contactor coils
1/38
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Ordering details
2CDC 251 073 F0b07
Time Rated Time Control Out- Type Order code Price Weight
1 function control ranges input put (1 pce)
supply
voltage 1 pce kg (lb)
0.121
24 V AC/DC CT-IRS.16 1SVR430220R9100
(0.267)
110-240 V 0.126
CT-IRS.14 1SVR430221R7100
AC (0.278)
2 c/o
2CDC 251 073 F0007
0.135
24 V AC/DC CT-IRS.26 1SVR430220R9300
(0.298)
110-240 V 0.141
CT-IRS.24 1SVR430221R7300
AC (0.311)
G
CT-IRS.35
0.147
24 V AC/DC CT-IRS.26G9) 1SVR430230R9300
(0.324)
2 c/o
110-240 V 0.150
CT-IRS.24G9) 1SVR430231R7300
AC (0.331)
G ON/OFF-function 0.159
24 V AC/DC CT-IRS.36 1SVR430220R9400
(0.351)
3 c/o
220-240 V 0.161
CT-IRS.35 1SVR430221R1400
AC (0.355)
9)
Contacts with gold-plated contacts
1/39
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Ordering details - Accessories
Remote potentiometer
2CDC 252 041 F0009
50 kq ±20 % - 0,2 q, degree of protection IP66 1
Material Diameter Type Order code Price Pack.- Weight
unit 1 piece
in mm 1 piece pieces g / oz
MT-x50B Plastic, black 22.5 MT-150B 1SFA611410R1506 1 0.040
Plastic, chrome 22.5 MT-250B 1SFA611410R2506 1 0.040
Metal, chrome 22.5 MT-350B 1SFA611410R3506 1 0.048
2CDC 252 042 F0009
Z1
Z3
Z2
2CDC 252 043 F0209
pieces g / oz
Plastic, black KA1-8029 1SFA616920R8029 1
Marker label with scale 0-10
48.5 x 44.5 mm Metal, chrome KA1-8030 1SFA616920R8030 1
15
Marker label
12 18
2CDC 252 045 F0209
1/40
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Ordering details - Accessories
1 Accessories
2CDC 252 187 F0005
.453”
11,5
62,5 2.46”
4,5
.886”
pieces g / oz
22,5
10
60 2.36”
Adapter for ADP.01 1SVR430029R0100 1 18.4/0.65
screw mounting1) CT-S
ADP.01 Sealable 22.5 mm COV.01 1SVR430005R0100 1 5.2/0.18
transparent cover
7 .275”
2CDC 252 185 F0005
22,5
.886”
3,5 .138” Sealable CT-S.S/P 22.5 mm COV.11 1SVR730005R0100 1 4 / 0.129
transparent cover1)
68,5 2.70 ”
Marker label
Material for devices Type Order code Price Pack.- Weight
unit 1 piece
front-to-back pieces g / oz
size 107
CT-S without
COV.01 Marker 1)
MAR.01 1SVR366017R0100 10 0.19/0.007
DIP switches
CT-S with DIP
2CDC 252 186 F0005
switches
8
20
.787” CT-S.S/P with
Marker MAR.12 1SVR730006R0000 10 0.152/0.335
DIP switches
MAR.01 1)
also available for CT-S.S/P
8 0.32”
22.5 0.89” 4.8 0.19”
68 2.68”
front to back
110.5 4.31”
COV.11
4T22
0.314“
8
18 0.709“
21 0.827“
MAR.02
1/41
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
Remarks
1
Legend
Terminal designations on the device and in the diagrams:
G Control supply voltage not applied / Output contact open
The 1st c/o contact is always designated 15-16/18.
B Control supply voltage applied / Output contact closed
The 2nd c/o contact is designated 25-26/28, if it responds to the time
delay.
A1-Y1/B1 Control input with voltage-related triggering
If the 2nd c/o contact is selected as an instantaneous contact, the desi-
Y1-Z2 Control input with volt-free triggering gnation 25-26/28 is replaced by 21-22/24.
X1-Z2 Control input with volt-free triggering Control supply voltage is always applied to terminals A1-A2.
A ON-delay A ON-delay
(Delay on make) (Delay on make)
CT-MVS, CT-ERS, CT-WBS CT-MFS, CT-MBS
This function requires continuous control supply voltage for timing. This function requires continuous control supply voltage for timing.
Timing begins when control supply voltage is applied. The green LED If control input Y1-Z2 is open, timing begins when control supply voltage
flashes during timing. When the selected time delay is complete, the is applied. Or, if control supply voltage is already applied, opening con-
output relay energizes and the flashing green LED turns steady. trol input Y1-Z2 also starts timing. The green LED flashes during timing.
If control supply voltage is interrupted, the output relay de-energizes and When the selected time delay is complete, the output relay energizes
the time delay is reset. and the flashing green LED turns steady.
If control input Y1-Z2 closes before the time delay is complete, the time
A1-A2
delay is reset and the output relay remains de-energized.
2CDC 252 017 F0206
15-18, 25-28
15-16, 25-26 Pause timing / Accumulative ON-delay (CT-MFS):
21-24
21-22 Timing can be paused by closing control input X1-Z2. The elapsed time
green LED t1 is stored and continues from this time value when X1-Z2 is re-opened.
t <t
This can be repeated as often as required.
t = adjusted time delay
If control supply voltage is interrupted, the output relay de-energizes and
the time delay is reset.
A1-A2
2CDC 252 018 F0206
Y1-Z2
15-18, 25-28
15-16, 25-26
21-24
21-22
X1-Z2
green LED
t t1 t3 t2
1/42
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
A1-A2 A1-A2
2CDC 252 020 F0206
1/43
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
1)
drop-out voltage and on the wattage of the contactor coil. t1 = OFF-delay (without jumper between terminals 3 and 4 1))
t2 = OFF-delay (with jumper between terminals 3 and 4 1))
1) only for version 200-240 V AC
180 180
Contactor coil drop-out voltage [V]
140 140
80
120 120
100 100 60
80 80
3W 3W
2CDC 252 127 F0205
0 0 0
0 100 200 300 400 0 1 2 0 1 2
t [ms] t [s] t [s]
Time delay guideline values Time delay guideline values Time delay guideline values
200-240 V AC version without jumper 3/4 200-240 V AC version with jumper 3/4 110-127 V AC version
green LED
Y1-Z2
t1 t2 t1 < t2
15-18, 25-28
15-16, 25-26
t1 = adjusted ON-delay
21-24 t2 = adjusted OFF-delay
21-22
t1 = t2
X1-Z2
green LED
t1 t2 t1a t3 t1b t2a t3 t2b
1/44
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
A1-Y1/B1
t = adjusted pulse time
15-18, 25-28
15-16, 25-26
green LED
t1 t2 t1 < t2
t1 = adjusted ON-delay
t2 = adjusted OFF-delay
t1 and t2 independently adjustable
21-24
Y1-Z2 21-22
15-18, 25-28 X1-Z2
15-16, 25-26
green LED
21-24
21-22 t t1 t3 t2
X1-Z2
t = adjusted pulse time t1 + t2 = t
green LED t3 = pause timing
t t1 t3 t2
1/45
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
�A Flasher, starting with the ON time �B Flasher, starting with the OFF time
(Recycling equal times, ON first) (Recycling equal times, OFF first)
CT-WBS CT-WBS
Applying control supply voltage starts timing with symmetrical ON & OFF Applying control supply voltage starts timing with symmetrical ON & OFF
times. The cycle starts with an ON time first. The ON & OFF times are times. The cycle starts with an OFF time first. The ON & OFF times are
displayed by the flashing green LED, which flashes twice as fast during the displayed by the flashing green LED, which flashes twice as fast during
OFF time. the OFF time.
If control supply voltage is interrupted, the output relay de-energizes and If control supply voltage is interrupted, the output relay de-energizes and
the time delay is reset. the time delay is reset.
A1-A2 A1-A2
2CDC 252 029 F0206
�A Flasher with reset, starting with the ON time �B Flasher with reset, starting with the OFF time
(Recycling equal times with reset, ON first) (Recycling equal times with reset, OFF first)
CT-MFS, CT-MBS CT-MFS, CT-MBS
Applying control supply voltage starts timing with symmetrical ON & OFF Applying control supply voltage starts timing with symmetrical ON & OFF
times. The cycle starts with an ON time first. The ON & OFF times are times. The cycle starts with an OFF time first. The ON & OFF times are
displayed by the flashing green LED, which flashes twice as fast during displayed by the flashing green LED, which flashes twice as fast during
the OFF time. the OFF time.
The time delay can be reset by closing control input Y1-Z2. Opening The time delay can be reset by closing control input Y1-Z2. Opening
control input Y1-Z2 starts the timer pulsing again with symmetrical ON control input Y1-Z2 starts the timer pulsing again with symmetrical ON
& OFF times. & OFF times.
If control supply voltage is interrupted, the output relay de-energizes and If control supply voltage is interrupted, the output relay de-energizes and
the time delay is reset. the time delay is reset.
A1-A2 A1-A2
2CDC 252 031 F0206
Y1-Z2 Y1-Z2
15-18, 25-28 15-18, 25-28
15-16, 25-26 15-16, 25-26
21-24 21-24
21-22 21-22
green LED green LED
t t t t t t t t
1/46
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
A1-A2
2CDC 252 035 F0206
A1-A2
1/47
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
EC Single-pulse generator, starting with the OFF time AC Fixed impulse with adjustable time delay
(Delay on make with interval output) (Delayed pulse output) 1
CT-MXS CT-WBS
This function requires continuous control supply voltage for timing. This function requires continuous control supply voltage for timing.
Applying control supply voltage, or, if control supply voltage is already The time delay t1 starts when control supply voltage is applied. The
applied, opening control input A1-Y1/B1 energizes the output relay after green LED flashes during timing. When t1 is complete, the output relay
the OFF time t1 is complete. When the following ON time t2 is complete, energizes for the fixed impulse time t2 of 500 ms and the flashing green
the output relay de-energizes. The ON & OFF times are displayed by the LED turns steady.
flashing green LED, which flashes twice as fast during the OFF time. If control supply voltage is interrupted, the time delay is reset. The output
The ON & OFF times are independently adjustable. relay does not change state.
Closing control input A1-Y1/B1, with control supply voltage applied, de-
A1-A2
A1-Y1/B1
15-18, 25-28
15-16, 25-26
green LED
t1 t2 t1 t2
15-18, 25-28
operation.
15-16, 25-26
green LED
t2 t1 t2 < t1 A1-A2
G Switching relays
CT-IRS
The switching relay may be used to increase the number of available
contacts or to reinforce contacts, or as a coupling/decoupling interface.
Approx. 10 ms after applying control supply voltage to terminals A1-A2,
the output relay energizes.
If control supply voltage is interrupted, the output relay de-energizes.
A1-A2
2CDC 252 055 F0206
n1-n4
n1-n2
n = 1, 2 or 3
1/48
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Function diagrams
t1. The green LED flashes during timing. When the starting time is com- F2
96
plete, the first c/o contact de-energizes the star contactor. S1 21
0
Now, the fixed transition time t2 of 50 ms starts. When the transition 22
time is complete, the second c/o contact energizes the delta contactor S2 13 53
connected to terminals 25-28. The delta contactor remains energized as I K2
14 54
long as control supply voltage is applied to the unit. 15 25 13 13
K1T K2 K1
18 28 14 14
A1-A2 22 22
1 3 5
-F1
2 4 6
1 3 5 1 3 5 1 3 5
-K2 2 4 6
-K3 2 4 6
-K1 2 4 6
F Star-delta change-over 97 95
1 5 4
(Star-delta starting) -F2 98 96
CT-SDS 3 2 6
L1 F3
A1-A2 95
2CDC 252 040 F0206
17-18 F2
96
17-28
S1 21
green LED 0
22
t1 t2
S2 13 53
t1 = adjusted starting time I K2
t2 = transition time (50 ms) 14 54
17 17 13 13
K1T K2 K1
18 28 14 14
22 22
K3 21
K1 21
A1 A1 A1 A1
K1T K1 K3 K2
A2 A2 A2 A2
N
Y N
1/49
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Connection diagrams
A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18
22 24
28 24 26 22 28 26 28 26
18 16 A2 18 16 A2 18 16 A2 18 16 A2
A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28
22 24 22 24
28 26 Y1/B1 28 24 26 22 Y1 28 24 26 22 Y1 28 26
18 16 A2 18 16 A2 18 16 A2 18 16 A2
A1 15 25 A1 15 25 A1 15
A2 16 18 26 28 A2 16 18 26 28 A2 16 18
28 26 28 26
18 16 A2 18 16 A2 18 16 A2
1/50
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Connection diagrams
A2 16 18 26 28 A2 16 18 26 28 A2 16 18 A2 16 18 26 28
28 26 28 26 28 26 Y1
18 16 A2 18 16 A2 18 16 A2 18 16 A2
A1-Y1/B1 Control input A1-Y1/B1 Control input A1-Y1/B1 Control input Y1-Z2 Control input
4
A2 16 18 A2 16 18 26 28 A2 A2
2- 2-
28 26
1+ 2- A2 1+ 2- A2
18 16 A2 18 16 A2
F CT-SDS.22 F CT-SDS.23
A1 17 A1 17
2CDC 252 016 F0b06
A1 17 A1 17
A2 18 28 A2 18 28
18 28 A2 18 28 A2
1/51
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Connection diagrams
A1 11 A1 11 A1 11 21 A1 11 21
A2 12 14 A2 12 14 A2 12 14 22 24 A2 12 14 22 24
24 22 24 22
14 12 A2 14 12 A2 21 A2 21 A2
11-12/14 1. c/o contact 11-12/14 1. c/o contact 11-12/14 1. c/o contact 11-12/14 1. c/o contact
21-22/24 2. c/o contact 21-22/24 2. c/o contact
A1 11 21 A1 11 21 A1 11 21 31 A1 11 21 31
A2 12 14 22 24 A2 12 14 22 24 A2 12 14 22 24 32 34 A2 12 14 22 24 32 34
24 22 24 22 24 22 24 22
14 12 A2 14 12 A2 14 12 A2 14 12 A2
11-12/14 1. c/o contact 11-12/14 1. c/o contact 11-12/14 1. c/o contact 11-12/14 1. c/o contact
21-22/24 2. c/o contact 21-22/24 2. c/o contact 21-22/24 2. c/o contact 21-22/24 2. c/o contact
31-32/34 3. c/o contact 31-32/34 3. c/o contact
1/52
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Technical data
1/53
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Technical data
MTBF on request
Duty time 100%
product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
Dimensions (W x H x D)
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Weight depending on device, see ordering details
Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical / horizontal not necessary / not necessary
Material of housing UL 94 V-0
Degree of protection housing / terminals IP50 / IP20
Electrical connection 2)
2)
Data for all references 1SVR 730 xxx xxx and 1SVR 740 xxx xxx. For devices with 1SVR 430 xxx xxx and 1SVR 630 xxx xxx please refer to the data sheet.
1/54
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Technical data
Environmental data
1 -25...+60 °C / -40...+85 °C,
Ambient temperature ranges operation / storage -40...+60 °C / -40...+85 °C (CT-MVS.21,
CT-MFS.21, CT-ERS.21, CT-APS.21)
Damp heat (cyclic) (IEC/EN 60068-2-30) 6 x 24 h cycle, 55 °C, 95 % RH
functioning 40 m/s 2, 10-58/60-150 Hz
Vibration, sinusoidal (IEC/EN 60068-2-6)
resistance 60 m/s2, 10-58/60-150 Hz, 20 cycles
Vibration, seismic (IEC/EN 60068-3-3) functioning 20 m/s 2
functioning 100 m/s 2, 11 ms, 3 shocks/direction
Shock, half-sine (IEC/EN 60068-2-27)
resistance 300 m/s 2 , 11 ms, 3 shocks/direction
Isolation data
Rated insulation voltage Ui input circuit / output circuit 500 V
Rated impulse withstand voltage Uimp VDE 0110, IEC/EN 60664 4 kV; 1.2/50 μs
between all isolated circuits
Power-frequency withstand voltage test between routine test 2.0 kV, 50 Hz, 1 s
all isolated circuits (test voltage) type test 2.5 kV, 50 Hz, 1 min
Basic insulation (IEC/EN 61140) input circuit / output c ircuit 500 V
Protective separation (IEC/EN 61140; IEC/EN 50178; input circuit / 250 V
VDE 0106 part 101 and part 101/ A1) output circuit
Pollution degree (IEC/EN 60664-1, VDE 0110) 3
Overvoltage category (IEC/EN 60664-1, VDE 110) III
Standards
Product standard IEC 61812-1, EN 61812-1 + A11, DIN VDE 0435 part 2021
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electronic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz) 3 V/m (2 GHz) 1 V/m (2.7 GHz)
electromagnetic field
electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 4, 2 kV A1-A2
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3, 10 V
radio-frequency fields
harmonics and interharmonics IEC/EN 61000-4-13 Level 3
Interference emissions IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
„Approvals and Marks“ see page 1/4.
1/55
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Technical diagrams
Technical diagrams
Load limit curves
1
AC load (resistive) DC load (resistive)
DC voltage [V]
resistive load
resistive load
1.0
0.9
0.8
0.7 250 V
resistive load
0.6
0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Switching current [A]
1/56
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CT-S range
Wiring notes, Dimensional drawings
Wiring notes
1
Control inputs Triggering of the control inputs (volt-free)
(volt-free triggering) with a proximity switch (3 wire)
L(+) L(+) +V
2CDC 252 101 F0b06
A2 Z2 A2 Z2
N(-) N(-) 0V
Control inputs
(voltage-related triggering)
A1 Y1/B1 A1 Y1/B1
A2 A2
The control input Y1/B1 is triggered with electric potential against A2. It is possible to use the
control supply voltage from terminal A1 or any other voltage within the rated control supply vol-
tage range.
Remote potentiometer
L(+)
2CDC 252 104 F0b06
A1 Z3 Z1
A2 Z2
N(-)
100 3.94“
103.7 4.08”
1SVR 430 xxx xxx, 1SVR 630 xxx xxx 1SVR 730 xxx xxx, 1SVR 740 xxx xxx
1/57