You are on page 1of 64

Printed Date: 09/12/2022

Job: SHOPPING LA MOLINA, 240822


Mark: DFD-150
Model: DFD-150

DFD-150 DFD-150: 1 1/2 hour dynamic rated fire damper


APPLICATION & DESIGN
Model DFD-150 is approved for use in walls, floors and partitions with fire resistance ratings less than 3 hours. UL 555 classifies dynamic rated fire
dampers for use in HVAC systems that are operational in the event of fire.
Damper
DAMPER RATINGS
Fire Rating: 1½ hours
Dynamic Closure Rating
Maximum Velocity: 4,000 ft/min vertical mount only,
up to 24 in. x 24 in.;
2,000 ft/min vertical or horizontal mount
on all sizes
MaximumPressure: 4 in. wg Height
PRODUCT DETAILS
Frame: Galvanized Steel
Frame Depth: 3.688
Blade: Galvanized Steel
Closure Device: Fusible Link
Closure Temp: 165 F Width
Velocity: 2,000 ft/min
Sizing: Nominal

OPTIONS & ACCESSORIES • This drawing shows a general damper configuration and is not intended to depict the exact
configuration of all dampers in this submittal.
Transition: A • Damper is furnished approximately 0.250 in. undersize.
Union Label: No Preference • Installation instructions available at www.greenheck.com.

CODES APPROVED
This model meets the requirements for fire dampers established by:
• UL Classfied (U.S. and Canada)
Standard UL 555 (Listing #R13317)
• National Fire Protection Association
NFPA Standard 80,90A & 101
• IBC: International Building Codes
• California State Fire Marshal: CSFM listing # 3225-981:102

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Sections Wide: Sections High: Blade Stack: Mounting:
1-1 1 30.000 in. 14.000 in.
1 1 1.870 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-2 1 10.000 in. 10.000 in.
1 1 1.530 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-3 1 20.000 in. 18.000 in.
1 1 2.550 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-4 1 16.000 in. 16.000 in.
1 1 2.210 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-5 1 20.000 in. 14.000 in.
1 1 1.870 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-6 4 18.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-7 2 12.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-8 6 30.000 in. 30.000 in.
1 1 3.910 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-9 2 17.000 in. 17.000 in.
1 1 2.380 in. Vertical

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 1 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822
Mark: WD-300
Model: WD-300

WD-300 Backdraft Damper


APPLICATION & DESIGN
The WD-300 is a vertical mount backdraft damper for horizontal airflow. The dampers are opened by air pressure differential and closed by gravity.

DAMPER RATINGS
Max. Pressure: Up to 2 in. wg - pressure differential
Max. Velocity: Up to 2,500 ft/min
Temperature: 180 F

PRODUCT DETAILS
Frame: Galvanized Steel
Frame Thickness: 18 ga
Blade: Aluminum
Blade Seal Material: Vinyl
Blade Thickness: 0.025 in. - 0.032 in.
Axle Material: Steel
Axle Bearings: Synthetic
Linkage Material: Galvanized
Actuator Voltage: None
Sizing: Nominal

OPTIONS & ACCESSORIES


Clean Wrap: No
Union Label: No Preference
• This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
• Width and Height furnished approximately 0.125 in. under size.
• Installation instructions available at www.greenheck.com.
• Pressure drop data applies to units with minimum start open pressure. Higher start
open pressure will result in different performance.

SUMMARY
SECTIONS SECTIONS SHIP
ID # TAG QTY W (in.) H (in.)
WIDE HIGH SECTIONS
2-1 8 32.000 32.000 1 1 1
2-2 16 30.000 30.000 1 1 1
2-3 8 37.000 37.000 1 1 1
2-4 4 47.000 47.000 1 1 1

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 2 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-331
Model: FSD-331

FSD-331 Combination Fire Smoke Damper


APPLICATION & DESIGN
Model FSD-331 is a high performance combination fire smoke damper with Class I leakage. High strength airfoil blades ensure the lowest resistance to
airflow in HVAC systems with velocities to 4,000 ft/min and pressures to 8 in. wg. Model FSD-331 may be installed horizontally or vertically (with blades
running horizontally) and is rated for airflow and leakage in either direction.

DAMPER RATINGS
UL 555 Fire Resistance Rating
Fire Rating: 3 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 4,000 ft/min
Pressure: 8 in. wg
Height
UL 555S Leakage Rating
Leakage Class: I
Operational Rating: Actual ratings are size dependent
Velocity: Up to 4,000 ft/min Width

Pressure: Up to 8 in. wg
Temperature: Up to 350 F depending on actuator 5 in.
Damper
Location
"A"
PRODUCT DETAILS
Sleeve
Frame Type: Channel Length
Frame Thickness: 16 ga
Closure Device: RRL • This drawing shows a general damper configuration and is not intended to depict the
Closure Temperature: 350 F exact configuration of all dampers in this submittal.
• Width and height furnished approximately 0.250 in. undersize.
Blade Action: Opposed • Add sleeve thickness for overall sleeved damper dimension.
Blade Seal: Silicone • If the actuator is contained, then it does not extend more than 1.500 in. above or below
Axle/Linkage Material: Plated Steel the damper sleeve.
• Dampers with more than one section wide will be furnished with a single OCI device
Axle Bearings: 316 SS per row when the blade indicator option is selected.
Sizing: Nominal • Installation instructions available at www.greenheck.com.

ACTUATOR INFORMATION CODES APPROVED


Actuator Type: 230 VAC Model FSD-331 meets the requirements for fire
Operating Mode: Two Position dampers, smoke dampers and combination fire smoke
Actuator Operation: Spring Return dampers established by:
Fail Position: Closed National Fire Protection Association:
Time Cycle: Standard NFPA Standards 80, 90A, 92, 101, 105
Operating Temperature: 350 F IBC (International Building Codes)
Velocity: 4,000 ft/min CSFM (California State Fire Marshal)
Pressure: 4 in. wg Fire Damper Listing (3225-0981:103)
NEMA Enclosure: 1 Leakage (Smoke) Damper Listing (3230-0981:104)
Underwriters Laboratories:
OPTIONS & ACCESSORIES UL Classified to U.S. and Canadian safety standards
Sealed Transition/Sleeve: Yes Standard 555 & 555S (Listing # R13317)
Union Label: No Preference

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Drive Arrangement:
Actuator Contained: Actuator Mounting: Actuator Location:
Drive-
Yes External Right Side
MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
Honeywell MS4620F1203 1 Perp Up
3-1 8 32.000 in. 32.000 in.
Sleeve Length: Sleeve Thickness: Damper Location: Mounting:
16.000 in. 20 ga 7.188 in. Vertical
Component
Location Code:
N/A

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 3 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-331
Model: FSD-331
ID # TAG QTY Width Height CONFIGURATION
Drive Arrangement:
Actuator Contained: Actuator Mounting: Actuator Location:
Drive-
Yes External Right Side
MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
Honeywell MS4620F1203 1 Perp Up
3-2 16 30.000 in. 30.000 in.
Sleeve Length: Sleeve Thickness: Damper Location: Mounting:
16.000 in. 20 ga 7.188 in. Vertical
Component
Location Code:
N/A
Drive Arrangement:
Actuator Contained: Actuator Mounting: Actuator Location: Drive-
Yes External Both Sides MLS-21-4FEB-1-
PIGGY
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-3 8 37.000 in. 37.000 in. Honeywell MS4620F1203 4 Perp Up
Sleeve Length: Sleeve Thickness: Damper Location: Mounting:
16.000 in. 20 ga 7.188 in. Vertical
Component
Location Code:
N/A
Drive Arrangement:
Actuator Contained: Actuator Mounting: Actuator Location: Drive-
Yes External Both Sides MLS-21-4FEB-1-
PIGGY
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-4 4 47.000 in. 47.000 in. Honeywell MS4620F1203 4 Perp Up
Sleeve Length: Sleeve Thickness: Damper Location: Mounting:
16.000 in. 20 ga 7.188 in. Vertical
Component
Location Code:
N/A

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 4 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-331
Model: FSD-331

AMCA

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance
ratings only.

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 5 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822
Mark: BR-30
Model: BR-30

BR-30 No Flange Barometric Relief Damper


APPLICATION & DESIGN
The BR-30 is an eccentrically pivoted backdraft damper for low velocity systems. This model is a vertical mounted damper designed to allow horizontal
airflow and prevent reverse airflow.

DAMPER RATINGS
Max. Pressure: 2 in. wg
Max. Velocity: Up to 2,000 ft/min
Temperature: 180 F

PRODUCT DETAILS
Frame: Galvanized
Frame Thickness: 16
Blade: Aluminum
Blade Seal Material: TPE
Blade Thickness: 0.063 in.
Axle Material: Plated Steel
Axle Bearings: Galvanized Ball
Start Open Pressure: 0.05 in. wg
Linkage Material: Galvanized Steel
Jamb Seal Material: None
Operation: Counterbalanced
Sizing: Nominal

OPTIONS & ACCESSORIES


Clean Wrap: No
Union Label: No Preference • This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
• Width and Height furnished approximately 0.25 in. under size.
• Installation instructions available at www.greenheck.com.
• Pressure drop data applies to units with minimum start open pressure. Higher start
open pressure will result in different performance.

SUMMARY
SECTIONS SECTIONS SHIP
ID # TAG QTY W (in.) H (in.)
WIDE HIGH SECTIONS
5-1 14 24.000 24.000 1 1 1

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 6 of 7
Printed Date: 09/12/2022
Job: SHOPPING LA MOLINA, 240822

Damper Drive Arrangements Job Summary -Start-

Drive Arrangement: Drive-MLS-11-1FER-1

Drive Arrangement: Drive-MLS-21-4FEB-1-PIGGY

Damper Drive Arrangements Job Summary -End-

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.982 Generated by: eduhar@primelines-hvac.com Page 7 of 7
Model DFD-150
Dynamic Rated Fire Damper
1 ⁄2 Hour Fire Resistance Rating
1

Application
Model DFD-150 is approved for use in walls, floors, and partitions
with fire resistance ratings less than 3 hours. This model carries a
11⁄2 hour UL fire damper label. UL555 classifies dynamic rated fire
damper for use in HVAC systems that are operational in the event
of fire.

Ratings
UL 555 Fire Resistance
Fire Rating: 11⁄2 hours
Velocity
4000 fpm (20.3 m/s) vertical mount only, up to 24 in. x 24 in.
(610mm x 610mm);
2000 fpm (10.2 m/s) vertical or horizontal mount all sizes
Pressure
Maximum: 4 in. wg (1 kPa)

* W & H dimensions furnished approximately 1⁄4 in. (6mm) undersize.

See complete marking on


Construction product.
Construction Standard Optional UL 555S Classification
R13317
Frame Material Galvanized steel* -
Frame Depth 3 ⁄16 in. (94mm)
11
-
Blade Material Galvanized steel* -
Closure Spring Stainless steel -
Model DFD-150 meets the requirements for fire
212°F or 286°F dampers established by:
Fusible Link 165°F (74°C)
(100°C or 141°C)
• National Fire Protection Association
Mounting Vertical Horizontal
NFPA Standards, 80, 90A, and 101
* in gauges required by UL listing R13317
• International Building Codes (IBC)
• CSFM California State Fire Marshal
Fire Listing (#3225-0981:0102)

W*
W*
Stainless Steel Fusible Link (replaceable)
Closure Spring Stainless Steel Fusible Link (replaceable)
Closure Spring

H*
H*

“K” side
“K” side

Horizontal Mount
Horizontal Mount

3 11/16 in. Vertical Mount


(94mm) 3 11/16 in. Vertical Mount
(94mm)

DFD-150 January 2022


Options and Accessories
• Breakaway connections
• Clean wrap
• Closed indicator switch
• Flanges
• Grille tabs
• Retaining angles
• Security bars
• Sealed transitions and sleeve
• Transitions: B, B2, C, CO, CR, R

Document Links
Installation Instructions Life Safety Damper Catalog

Damper Product Selection Guide Specifications

Damper Warranty

DFD-150 January 2022


Factory Sleeve Option
All fire damper installations require the use of sleeves, angles and methods described in the installation instructions. Sleeves can be
field fabricated or factory furnished as a completed damper/sleeve assembly.
Sleeves are galvanized steel and are available in 20 through 10 ga. (1mm - 3.5mm) thicknesses and lengths up to 36 in. (914mm).
“K” dimension specifies location of damper within the sleeve. Minimum is 4 in. (102mm), maximum is “L” less 4 in. (102mm), which
allows for mounting angle installation, and duct connection at each end of the sleeve. If “K” dimension is not specified, it will be
provided as one half of “L” dimension (damper centered in sleeve).
Note: If using access doors, the door should be installed on the “K” side of the damper.

Sleeve

Damper
H*

K
Damper CL Damper Frame
Location W*
L
Overall Sleeve Length

Sealed Option
When sealed option is selected, B transition will need to be field sealed in the area where duct to sleeve connection is made.

Type B with sleeve

Seal this area.

DFD-150 January 2022


Type A, B, & B2
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Multi-section dampers are factory
assembled ready for installation.

Size Limitations
Inches Type A Type B & B2 P
(mm) Minimum Maximum* Minimum Maximum*
Single H*
H *
4x4 36 x 36 4x3 36 x 31
Section
(102 x102) (914 x 914) (102 x 76) (914 x 787)
Vertical
VERTICAL MOUNT
72 x 48 72 x 45 HORZONTAL MOUNT
(1829 x 1219), (1829 x 1143),
Multi
60 x 60 60 x 56 1 1/2
Varies
1 1/2
Section** NA NA in.

3 in.
W* in.
W *
(1524 x 1524) or (1524 x 1422) or
Vertical
120 x 30 O* 120 x 26
H*
(3048 x 762) (3048 x 660) Type A

16 in.
10 in.
Single
4x4 30 x 30 4x3 30 x 26
Section
(102 x 102) (762 x 762) (102 x 76) (762 x 660)
Horizontal
Multi

3 in.
NA 48 x 36 48 x 33
Section** NA
W* (1219 x 914) (1219 x 838) Damper
Horizontal Location
K Dim.
Sleeve
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult
Length
factory for maximum size for different temperatures and velocities. Varies
** Consult factory for number of sections. Type B2
Multi-Section Limitations - Type A
Maximum Single Section
Dimensions
Maximum damper height is 48 in. (1219mm) when combination width is
Maximum Single Section Dimensions 72 in. (1829mm) or less.

36 in. (914mm) max.


31 in.(787mm)
Max.
48 in. (1219mm)
max.

36 in.
(914mm)
36 in. (914mm) max. max.

Maximum
Type A Single Single
SectionSection
Dimensions 72 in.
(1829mm) max.

Multi Section Limitations - Type B/B2


Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.

31 in.(787mm)
Max.
Multi-Section Limitations
Maximum damper height is 48 in. (1219mm) when combination width is 48 in. (1219mm) or less.

45 in. (1143mm)
36 in. Max.
(914mm)
max.

Type B Single Section

48 in.
72 in.
(1219mm) (1829mm)
max. Max.

Multi Section Limitations - Type B/B2


DFD-150 January 2022
Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.
Type A, B, & B2
Type B & B2 Overall
Damper Dimensions
Vertical Mount

H* O* H* O*
3 (76) 5 (127) 30 (762) 34 (864)
O*
4 (102) 6 (152) 31 (787) 36 (914) H*

5 (127) 7 (178) 32 (813) 37 (940)


6 (152) 8 (203) 33 (838) 37 (940)
7 (178) 9 (229) 34 (864) 37 (940)
8 (203) 10 (254) 35 (889) 38 (965) W*

9 (229) 11 (279) 36 (914) 39 (991) Type B2


Type B
10 (254) 12 (305) 37 (940) 40 (1016)
11 (279) 13 (330) 38 (965) 41 (1041)
Horizontal Mount
12 (305) 14 (356) 39 (991) 42 (1067)
13 (330) 15 (381) 40 (1016) 43 (1092) H* O* H* O*
14 (356) 16 (406) 41 (1041) 44 (1118) 3 (76) 5 (127) 19 (483) 22 (559)
15 (381) 18 (457) 42 (1067) 45 (1143) 4 (102) 6 (152) 20 (508) 23 (584)
16 (406) 19 (483) 43 (1092) 46 (1168) 5 (127) 7 (178) 21 (533) 24 (610)
17 (432) 20 (508) 44 (1118) 47 (1194) 6 (152) 8 (203) 22 (559) 26 (660)
18 (457) 21 (533) 45 (1143) 48 (1219) 7 (178) 9 (229) 23 (584) 27 (686)
19 (483) 22 (559) 46 (1168) 50 (1270) 8 (203) 10 (254) 24 (610) 28 (711)
20 (508) 23 (584) 47 (1194) 51 (1295) 9 (229) 11 (279) 25 (635) 29 (737)
21 (533) 24 (610) 48 (1219) 52 (1321) 10 (254) 12 (305) 26 (660) 30 (762)
22 (559) 26 (660) 49 (1245) 53 (1346) 11 (279) 13 (330) 27 (686) 31 (787)
23 (584) 27 (686) 50 (1270) 54 (1372) 12 (305) 14 (356) 28 (711) 31 (787)
24 (610) 28 (711) 51 (1295) 55 (1397) 13 (330) 15 (381) 29 (737) 32 (813)
25 (635) 29 (737) 52 (1321) 56 (1422) 14 (356) 16 (406) 30 (762) 33 (838)
26 (660) 30 (762) 53 (1346) 57 (1448) 15 (381) 18 (457) 31 (787) 34 (864)
27 (686) 31 (787) 54 (1372) 58 (1473) 16 (406) 19 (483) 32 (813) 35 (889)
28 (711) 32 (813) 55 (1397) 59 (1499) 17 (432) 20 (508) 33 (838) 36 (914)
29 (737) 33 (838) 56 (1422) 60 (1524) 18 (457) 21 (533) -

* Dimension is inches (mm). These dimensions are furnished approximately 1⁄4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart. The top section is a Type B/B2 and the bottom section are Type A.

DFD-150 January 2022


Type C, CO, CR, & R
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Note: All multiple section dampers
with transitions, will include a factory installed sleeve.
Type CR Type CO & C Type R+
Inches (mm)
Minimum Maximum* Minimum Maximum* Minimum Maximum*
Single Section
3 (76) 30 (762) 3 x 3 (76 x 76) 34 x 30 (864 x 762) 3 (76) 34 (864)
Vertical

70 x 44 (1778 x 1118),
Multi Section 55
NA NA 58 x 55 (1473 x 1397) or NA 58 (1473)
Vertical** (1397)
118 x 25 (2997 x 635)

Single Section
3 (76) 25 (635) 3 x 3 (76 x 76) 28 x 25 (711 x 635) 3 (76) 28 (711)
Horizontal
Multi Section
NA 32 (813) NA 46 x 32 (1163 x 787) NA 34 (864)
Horizontal**
+
With 2 in. (51mm) offset. Sizes adjust with an 1 in. (25mm) offset.
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult factory for maximum size for different temperatures and velocities.
** Consult factory for number of sections.

Maximum Single Section Dimensions


Overall Damper Dimensions

Type C Type CO D*+2

Type CR

30in.
30 in. O*
(762mm)
max. (762mm)
max.

34 in. 34 in. D*
(864mm) (864mm)
max. max.
W*+2

Type CO
Type CR Type R O*

H*

W*
W*+2

34 in.
Type C
(889mm)
30 in. max.
(762mm) O*
max. Type R transition is centered on
damper frame. (Dimension are with H*
2 in. (51mm) offset.)

W*
C, CO, CR transitions are positioned 1 in. (25mm)
from bottom of sleeve.

DFD-150 January 2022


Type C, CO, CR & R
DFD-150
Dynamic Fire Damper

Vertical Mount Horizontal Mount

H* or D* O* H* or D* O* H* or D* O* H* or D* O* H* or D* O*
3 (76) 6 (152) 21 (533) 26 (660) 39 (991) 45 (1143) 3 (76) 6 (152) 18 (457) 22 (559)
4 (102) 7 (178) 22 (559) 27 (686) 40 (1016) 46 (1168) 4 (102) 7 (178) 19 (483) 23 (584)
5 (127) 8 (203) 23 (584) 28 (711) 41 (1041) 47 (1194) 5 (127) 8 (203) 20 (508) 24 (610)
6 (152) 9 (229) 24 (610) 29 (737) 42 (1067) 48 (1219) 6 (152) 9 (229) 21 (533) 26 (660)
7 (178) 10 (254) 25 (635) 30 (762) 43 (1092) 49 (1245) 7 (178) 10 (254) 22 (559) 27 (686)
8 (203) 11 (279) 26 (660) 31 (787) 44 (1118) 50 (1270) 8 (203) 11 (279) 23 (584) 28 (711)
9 (229) 12 (305) 27 (686) 32 (813) 45 (1143) 50 (1270) 9 (229) 12 (305) 24 (610) 29 (737)
10 (254) 13 (330) 28 (711) 33 (838) 46 (1168) 51 (1295) 10 (254) 13 (330) 25 (635) 30 (762)
11 (279) 14 (356) 29 (737) 34 (864) 47 (1194) 52 (1321) 11 (279) 14 (356) 26 (660) 31 (787)
12 (305) 15 (381) 30 (762) 36 (914) 48 (1219) 53 (1346) 12 (305) 15 (381) 27 (686) 31 (787)
13 (330) 16 (406) 31 (787) 37 (940) 49 (1245) 54 (1372) 13 (330) 16 (406) 28 (711) 32 (813)
14 (356) 18 (457) 32 (813) 37 (940) 50 (1270) 55 (1397) 14 (356) 18 (457) 29 (737) 33 (838)
15 (381) 19 (483) 33 (838) 39 (991) 51 (1295) 56 (1422) 15 (381) 19 (483) 30 (762) 34 (864)
16 (406) 20 (508) 34 (864) 40 (1016) 52 (1321) 57 (1448) 16 (406) 20 (508) 31 (787) 35 (889)
17 (432) 21 (533) 35 (889) 41 (1041) 53 (1346) 58 (1473) 17 (432) 21 (533) 32 (813) 36 (914)
18 (457) 22 (559) 36 (914) 42 (1067) 54 (1372) 59 (1499)
19 (483) 23 (584) 37 (940 43 (1092) 55 (1397) 60 (1524)
20 (508) 24 (610) 38 (965) 44 (1118) -

* Dimension is inches (mm). These dimensions are furnished approximately 1/4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart.

Copyright © 2022 Greenheck Fan Corporation


DFD-150, R26, January 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice.
Document number 481324
CURTAIN FIRE DAMPERS
DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series
11⁄2 and 3 Hour Curtain Fire Dampers
Vertical and Horizontal Mount

Installation, Operation and Maintenance Manual


Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.

These instructions apply to 11⁄2 and 3 hour rated fire dampers mounted in: 1) masonry, block, or stud walls (blades
must be horizontal) and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must
be installed in accordance with these instructions to meet the requirements of UL 555.
Note: Fire dampers are manufactured and labeled for either vertical or horizontal installation. The dampers must be
installed in accordance with labeling.

Table of Contents
General Information ....................................... 2
Pre-Installation Guidelines ............................ 2
Installation.................................................3-11
• Preparation of Openings ......................... 3
• Clearances Required Between Damper
Sleeves & Wall/Floor Openings .............. 4
• Installing Multiple Section Assemblies.... 4
• Maximum Assembly Tables..................... 5
Receiving and Handling • Sleeve Length Requirements................5-6
Upon receiving dampers, check for both obvious
and hidden damage. If damage is found, record all • Securing the Damper/Sleeve
necessary information on the bill of lading and file Assembly to Wall/Floor Openings .......6-8
a claim with the final carrier. Check to be sure that • Duct to Sleeve Connection.................9-10
all parts of the shipment, including accessories, are
accounted for. • No Connecting Duct or
Transfer Opening................................... 11
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is Commissioning and Periodic Testing........... 11
highly recommended. Do not store at temperatures in
Maintenance ................................................ 11
excess of 100°F (38°C).
Troubleshooting ........................................... 11

Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.

This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.
Curtain Fire Dampers 1
General Information
“UL CLASSIFIED (see complete marking on Pre-Installation Guidelines
product)” The following items will aid in completing the damper
“UL CLASSIFIED to Canadian safety standards installation in a timely and effective manner.
(see complete marking on product)”
1) Check the schedules for proper damper locations
Standard 555 (Listing #R13317)
within the building. Visually inspect the damper for
damage and verify that the fusible link is in place and
has not activated. Never install a fire damper without
Installation Supplements the proper UL approved fusible link in place. Visually
Refer to the appropriate Greenheck installation inspect the link to verify its not damaged. Replace
supplements for special requirements: link as necessary.

• Closed Indicator Switch 2) Lift or handle damper using sleeve or frame. Do not
• Concrete Floor with Steel Deck lift damper using blades.
• Drive Slip Breakaway Connection 3) Dampers have a label indicating the required
• Field Installed Sleeve mounting orientation. When the mounting orientation
• Fire Resistant Ventilated Duct Assembly is horizontal, the 'K side' must be up. Care must
• Firestop Material be taken to ensure that the indicated orientation is
• Fusible Link Replacement adhered to.
• Grille Installation W*

• Metal Stud in Shaftwall Partition Stainless Steel


Closure Spring
Fusible Link (replaceable)

• Non-Concrete Horizontal Mount


• Quick Connect Breakaway Connection H*
• Sealant Supplement “K” side

• Single Side Retaining Angle Horizontal Mount

• Single 3-Sided Retaining Angle Supplement


3 11/16 in.
• Sleeve Extension (94mm) 4) Damper must be installed into duct or opening
Vertical Mount

• Support Mullions square and free of twist or other misalignment.


• ABD Series
5) Damper must be kept clean and protected from
Installation supplements available at www.greenheck. dirt, dust and other foreign materials prior to and
com. after installation. Examples of such foreign materials
include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
6) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper.
7) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining angles.
8) ACCESS: Suitable access (such that the fusible
link may be removed and the damper's blade stack
may be reset, etc.) must be provided for damper
inspection and servicing. Where it is not possible to
achieve sufficient size access, it will be necessary to
install a removable section of duct. (Refer to NFPA
90A).
9) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of final installation
where variations to these instructions are necessary.
2 Curtain Fire Dampers
Preparation of Openings
• Frame wall openings as shown below (see Figure 1, 2, & 2A).
• Gypsum wall board must be fastened 12 in. (305mm) on center (O.C.) to all stud and runner flanges surrounding
opening.
• Prepare opening between studs and sleeve assembly as shown below (see Figure 3 & 4).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes. Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.

24 in. o.c. 24 in. o.c.


Maximum Maximum Ceiling Runner
(metal studs) (metal studs)

12 in.

24 in. o.c.
Maximum

2 in. (51mm)
2 Panhead
Screws
2 in. (51mm)

16 in. o.c. 16 in. o.c.


Maximum Maximum
(wood studs) (wood studs)

Second set of studs are not required on openings


36 in. x 36 in. (914mm x 914mm) or smaller.
Floor Runner Metal stud only
Figure 1 Figure 2

Metal Stud Construction

Gypsum Wallboard

Stud or Runner

Retaining
Angle
1 in. Min.

Damper
In metal stud construction,
Sleeve exposed steel surfaces need
not be covered with gypsum Metal stud only
wallboard.

Figure 2A
Wooden Stud Construction Metal Stud Construction

Gypsum Wallboard
Gypsum Wallboard

Stud or Runner

Stud or Runner

Retaining Retaining
Angle Angle
1 in. Min.
1 in. Min.

Damper
In metal stud construction,
Damper In wood stud construction, Sleeve exposed steel surfaces need
Sleeve gypsum wallboard must cover not be covered with gypsum
all wood stud surfaces. wallboard.

Figure 3 (2 sided angle installation shown) Figure 4 (2 sided angle installation shown)
Curtain Fire Dampers 3
Wooden Stud Construction
Clearances Required Between Damper Sleeves & Wall/Floor Openings
Two-Sided Angle Installation
Two-sided angle installations require clearances for thermal expansion between the damper sleeve and the wall/floor
opening. The minimum required clearances are:
• For galvanized steel dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and 1⁄8 in. per
foot (3mm per .3 m) height with a minimum clearance of 1⁄4 in. (6mm). The total gap may be up to 6 in.
(152mm), 3 in. (76mm) per side, as long as the retaining angles overlap the wall/floor by a minimum of 1 in.
(25mm).
• For stainless steel dampers and stainless steel or galvanized sleeves: 3⁄16 in. per foot (5mm per .3 m) of
damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).

Example:
A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4 in.
(6mm) width and 1/4 in. (6mm) on height
A 48 in. x 12 in. (1219mm x 305mm)
damper will required a minimum
clearance of 1/2 in. (13mm) on width and
1/4 in. (13mm) on height.

These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
Although the minimum requirements are listed above, for ease of installation the following are the recommended
clearances for galvanized dampers:
• Width/Height of 48 in. (1219 mm) or less - ½ in. (13mm) clearance
• Width/Height between 48.01 in. (1220 mm) and 96 in. (2438 mm): 1 in. (25mm) clearance
• Width/Height greater than 96 in. (2438 mm): 1½ in. (38 mm) clearance
Single Side Angle Installation
On vertical mount single side angle installations there are no minimum clearance requirements between the wall
opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the
damper sleeve are recommended.
On horizontal mount single side angle installations a minimum clearance is required between the outside of the
damper sleeve and the floor opening of 1⁄8 in. per foot (3mm per .3m) of damper width and 1⁄8 in. per foot
(3mm per .3m) height with a minimum clearance of 1/4 in. (6mm).

Installing Multiple Section Assemblies


Attachments--Do not
A damper assembly is not restricted to a maximum place attachments
between blade channels
number of sections, but must not exceed the section
sizes and overall sizes shown (see chart below).
The damper sections must be attached together with Blade
Channel
#10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in.
(6mm) diameter nuts and bolts, tack or spot welds, or
3
⁄16 in. (48mm) diameter steel pop rivets. Attachments
must be spaced a maximum of 6 in. (152mm) O.C. and
a maximum of 2 in. (51mm) from corners. Attachments
must be made on front face and back face (air entering
and air exiting side) of damper sections.

Figure 5
4 Curtain Fire Dampers
Maximum Assembly Tables
When multiple sections are shipped unassembled, installer shall fasten dampers together. The table shows
maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory
assembled. Note: All dimensions are shown in inches (W x H). * Sizes listed refer to the damper size, not transition
size.

Maximum Single Maximum Multi-Section


Damper Model Mounting
Section Damper Sizes* Damper Sizes*
FD-100 , FD-300, FD-310, SSFD-350 Vertical 48 X 48 (1219mm x 1219mm) -
96 x 48 (2438mm x 1219mm) or
FD-150 Vertical or Horizontal 48 X 48 (1219mm x 1219mm)
120 x 40 (3048mm x 1016mm)
FD-110 Vertical or Horizontal 48 x 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm)
96 X 48 (2438mm x 1219mm) or
Vertical 48 X 48 (1219mm x 1219mm)
120 X 40 (3048mm x 1016mm)
SSFD-150
Horizontal 36 x 36 (914mm x 914mm) -

Vertical 48 x 48 (1219mm x 1219mm) -


FD-350
Horizontal 40 x 40 (1016mm x 1016mm) 80 x 40 (2032mm x 1016mm)
96 x 48 (2438mm x 1219mm) or
KFD-150 Vertical or Horizontal 36 x 16 (914mm x 406mm)
120 x 40 (3048mm x 1016mm)
KFD-110 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm)
96 X 48 (2438mm x 1219mm) or
SSKFD-150 Vertical 36 x 16 (914mm x 406mm)
120 X 40 (3048mm x 1016mm)
Vertical 36 x 16 (914mm x 406mm) -
KFD-350
Horizontal 36 x 16 (914mm x 406mm) 80 x 40 (2032mm x 1016mm)
SSKFD-350 Vertical 36 x 16 (914mm x 406mm) -
72 x 48 (1828mm x 1219mm) or
Vertical 36 x 36 (914mm x 914mm) 60 x 60 (1524mm x 1524mm) or
DFD-150, DFD-110 120 x 30 (3048mm x 762mm)
24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)
Horizontal
30 x 30 (762mm x 762mm) -
Vertical 36 x 36 (914mm x 914mm) -
DFD-350 24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)
Horizontal
30 x 30 (762mm x 762mm)
Vertical 36 x 36 (914mm x 914mm) -
DFD-310
Horizontal 30 x 30 (762mm x 762mm) -
SSDFD-110, SSDFD-150. SSDFD-350 Vertical 30 x 30 (762mm x 762mm) -
FD-150X Vertical or Horizontal 48 x 48 (1219mm x 1219mm) -
Vertical 36 x 36 (914mm x 914mm) -
DFD-150X
Horizontal 30 x 30 (762mm x 762mm) -

Sleeve Requirements
All fire dampers must be installed in a steel sleeve of the required gauge and length. Note that DFD-150X and
FD-150X series dampers are provided with an integral sleeve. See Table on page 9 for required minimum sleeve
gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside
dimensions.
Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side. When a factory
mounted access door is incorporated as a part of the sleeve, the sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor opening on the access door side.

Curtain Fire Dampers 5


Sleeve Requirements cont....
Fire dampers must be attached to sleeves as shown
in Figure 6. All four sides of the damper frame must Attachments--Do not place attachments between blade channels

be attached to the sleeve with one row of attachments NOTE: Attachments must not enter blade
channel or they may cause interference with
on each side of the blade channel. Attachments must blade closure. Narrow Line and Ultra Thin
be spaced a maximum of 6 in. (152mm) O.C. and a Blade
Channel
dampers do not have flange for attachments
and must be welded to sleeve.
maximum of 2 in. (51mm) from corners. A minimum of
4 attachments (2 on each side of the blade channel) per
side (16 per damper) are required. One of the methods
of attachment shown below must be used: 2 in. Max.

• tack or spot welds 6 in. Max.


Attachments can be
• #10 sheet metal screws staggered or evenly
spaced.
• 1⁄4 in. (6mm) bolts and nuts
• 3⁄16 in. (4.7mm) steel pop rivets

Figure 6: Field attachment of fire dampers to sleeves.

Securing the Damper/Sleeve Assembly to Wall/Floor Openings


The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall or floor.
All fire dampers may utilize the two-sided angle installation method described below. 11⁄2 hour rated fire dampers
may use the single sided angle installation method up to the following maximum sizes:
• Vertical mount: 80 in. W x 50. in. H (2032mm W x 1270mm H), 50 in. W x 80 in. H
(1270mm W x 2032mm H), or 40 in. W x 100 in. H (1016mm W x 2540mm).
• Horizontal mount: 144 in. W x 96 in. H (3658mm W x 2438mm H)
• Retaining Angle Gauge: Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm)
or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a
width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm).
• Retaining Angle Size: The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm).
The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm).
• Retaining Angle Attachment to Sleeve: Retaining angles must be attached to the damper using one or more of
the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
- Tack or spot welds
- #10 (3⁄4 in. [19mm] max.) sheet metal screws
- 1⁄4 in. (6mm) bolts and nuts
- 3⁄16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom, spaced 12 in. (305mm) O.C. maximum are required for
openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in.
high (914mm) require the connections to be no more than 6 in. (152mm) O.C.
The angles must be attached to all 4 sides of the sleeve. Ensure that fasteners do not interfere with the operation of
the damper. The angles need not be attached to each other at the corners.

6 Curtain Fire Dampers


Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont....
• Retaining Angle Attachment to Wall/Floor:
Wall or Floor

Two-Sided Angle Method: For two-sided angle Min. 1 in.

installations the retaining angles shall not be attached to Retaining


Angle
overlay*
Retaining

the wall/floor (see Figure 7).


angle

Sleeve

Single Sided Angle Method: For single side installations Duct

the retaining angles must be attached to the wall/floor (see


2 in.
Max.

Figures 8-11). For metal stud partitions only, the single 6 in. M
ax. Damper

side mounting angle may be directly attached to the metal


stud prior to the installation of the drywall.
6 in. M
ax.

2 in.

• Retaining angles must be attached to the partition


Max.

using one of the methods shown below:


Figure 7: Two-Sided Angle Installation
- Drywall screws of a length such that the
screw engages the steel stud/track by 1/2 in.
(13mm) (steel framing).
- Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood
framing).
- Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm).
• A minimum of two connections per side are required. Additional connections made at a maximum of
12 in. (305mm) O.C. for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater
than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than 6 in.
(152mm) O.C.

Damper
Sleeve Damper
Sleeve

Stud or Runner Stud or Runner


Two layers of 1/2 in. UL
Classified Gypsum Two layers of 1/2 in. UL
Wallboard for 2 hour Classified Gypsum
rated walls. One layer Wallboard for 2 hour
for 1 hour rated walls rated walls. One layer
(see UL Rated Wall for 1 hour rated walls
Design for Additional (see UL Rated Wall
Details). Design for Additional
Details).
Angle Fastener
Angle Fastener

Figure 8: Single Side Angle With Steel Stud Wall - Angle Figure 9: Single Side Angle With Wood Stud Wall
Over Wallboard

Top Side
Damper Angle Fastener
Sleeve
Damper
Sleeve
Two layers of 1/2 in. UL
Classified Gypsum Masonry or
Concrete
Wallboard for 2 hour Masonry or
Wall
rated walls. One layer Concrete
Floor
for 1 hour rated walls
(see UL Rated Wall
Metal Stud Design for Additional
or Runner Details).

Angle Fastener

Damper
Sleeve

Figure 10: Single Side Angle With Steel Stud Wall - Figure 11: S
 ingle Side Angle With Masonry or
Angle Under Wallboard Concrete Wall and Floor
Curtain Fire Dampers 7
Maximum Maximum
6 in. 6 in.

Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......


Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm])
Retaining angles used in conjunction with grille installations must be a minimum of 5⁄8 in. x 1 in. (15mm x 25mm)
16 gauge (1.5mm) steel. Space screws a maximum of 6 in. (152mm) O.C. and a maximum of 2 in. (51mm) from the
corners (minimum of 2 screws per side). See Figure 12 and Figure 13. Duct
Damper
Retaining Angles
Note: Screws used to attach grille are allowed to penetrate reversed angle leg.
Type A
1/4 in. minimum
total clearance
(See Section 1) Wall or Floor

Damper
Sleeve
Damper Sleeve Damper
#10 sheet metal screws
#10 sheet metal screws, 2 2 1/2 in. minimum spaced 6 in. on center
1/2 inches long, spaced 6 Stud or Runner and a maximum of 2 in. Stud or Runner
in. on center and a from the corners Two layers of 1/2 in.
Wall or floor
maximum of 2 in. from the (minimum of 2 screws per UL Classified Gypsum
corners (minimum of 2 Two layers of 1/2 in. UL side). Screw into studs so Wallboard for 2 hour
screws per side). Screw Classified Gypsum as to avoid space Maximum rated walls. One layer
Maximum
into studs so as to avoid Wallboard for 2 hour conflicts with the grille 6 in. for 1 hour rated6 walls
in.
space conflicts with the rated walls. One layer for
Angle Fastener (see UL Rated Wall
grille. 1 hour rated walls (see Design for Additional
Angle Fastener UL Rated Wall Design for
Details).
Additional Details).
Damper

Retaining Angle/Flange
Duct
Retaining Angle Grille (supplied
Grille (supplied by others) by others)
Type B
Figure 12: Wood Stud - Grille 1/4 in. minimum
total clearance
Figure 13: Metal Stud - Grille
(See Section 1)
On types R, CO & CR factory
1/4 in. minimum Duct
furnished duct collar
total clearance Sleeve
qualifies as breakaway
Retaining Angles (See Sleeve Requirements)
connection.
(See Section 4) Wall or Floor

Type A
Retaining Angles
Wall or floor
Wall or floor
Wall or Floor
Max. 6Maximum
in.
Maximum Maximum
Maximum 6 in.
6 in. “K” side 6 in. Wall or
6 in. Retaining angle leg
Floor
shall not exceed 7 in. 1 in. min.
(178mm) overlap
Four sides Sleeve

Mounting Angles
Damper (See Para. 4)
Sleeve
Damper
Max. 6 in. Damper 1/4 in. minimum
total clearance
Duct (See Para. 1) Damper
Duct

Duct
Damper Type C, CO, CR, & R
Retaining Angles Type B
Duct Duct
Type A Sleeve
Retaining Angles (See Sleeve Requirements)
Factory or Field installed
Wall Sleeve
or Floor (See Section 4) Factory Sleeve Factory Sleeve
Type B
Type A
Damper
Damper
Wall or floor
Wall or floor

Damper
On types R & CR factory
Retaining angle leg furnished duct collar
shall not exceed 7 in. qualifies as breakaway
(178mm) connection (See Connecting
Sleeve Ducts to Fire Damper Sleeve)

Damper
Duct Damper

Type B

On types R, CO & CR factory


furnished duct collar Wall or floor
Duct
qualifies as breakaway
Wall or FloorSleeve Type B2 Sleeve
connection. Sleeve
Duct

Wall or floor Type C, CO, CR & R


Type B2 Type B

Factory Sleeve Field Installed Sleeve Field installed Sleeve


Wall or floor
Figure 14: Damper/Sleeves with Transition
8 Curtain Fire Dampers On types R & CR factory
furnished duct collar
qualifies as breakaway
Duct Damper
connection (See Connecting
Duct to Sleeve Connection
Sleeve Gauge and Connection Type Requirements
The size of the damper/duct determines the required
Type of Duct
sleeve gauge and the required duct to sleeve
to Sleeve
connection (see table to the right). The sleeve thickness Sleeve Gauge Duct Dimension
Connection
must also not be less than the gauge of the connecting Permitted
duct. Any duct connection other than the breakaway
14 ga. (0.075 in.)
connections described below are considered rigid. - 10 ga. (0.138 Rigid or
All duct sizes
in.) Breakaway
[2mm - 3.5mm]
36 in. (914mm) max. width
16 ga. (0.060 in.) 24 in. (610mm) max. Rigid or
[1.5mm] height Breakaway
24 in. (610mm) diameter
16 ga. (0.060 in.)
All duct sizes
[1.5mm]
18 ga. (0.048 in.) 85 in. (2159mm) wide and
[1.2mm] over
20 ga. (0.036 in.) 55 in. - 84 in. wide
[0.9mm] (1397mm - 2134mm)
Breakaway only
22 ga. (.030 in.) 31 in. - 54 in. wide
[0.76mm] (787mm - 1372mm)
24 ga. (0.024) 13 in. - 30 in. wide
[0.6mm] (330mm - 762mm)
26 ga. (0.018 in.) 12 in. wide and under
[0.46mm] (305mm)
See Breakaway Connection section for additional information.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.

Approved Breakaway Connections


All breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.

Transverse Joints
The transverse joints shown below are approved as breakaway connections.
• A maximum of two #10 (19mm) sheet metal screws on each side and on the bottom may be used. The
screws should be located in the center of the slip pocket and penetrate both sides of the slip pocket.
• Dampers up to 20 in. (508mm) high may use transverse joints on the top and bottom and Drive Slip joints
(see Figure 16) on the sides.

Plain “S” Slip Hemmed “S” Slip Double “S” Slip


Drive Slip Joint
Figure 16

Inside Slip Joint Standing “S” Standing “S” (Alt.)

Standing “S” (Alt.) Standing “S” Standing “S”


(Bar Reinforced) (Angle Reinforced)

Figure 15 - Transverse Joints

Curtain Fire Dampers 9


Duct Damper
Duct to Sleeve Connection cont....
Type B

Round and Oval Duct Breakaway Connections Wall or Floor


Type R and O
Round or flat oval ducts connected to Type R or O damper factory furnished
collars shall be attached with #10 (19mm) sheet metal screws duct collars qualify
as follows: as breakaway Sleeve
connections.
• Ducts up to 22 in. (558mm) wide (or dia.) and less
shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have
five screws.
Duct Damper
Factory furnished duct collars, type R and O, are also
considered breakaway (see Figure 17).
Type R, O
Figure 17: Type R and O Transition

Manufactured Flanged System Breakaway Connections


Flanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are
approved as breakaway connections when installed as illustrated (see Figure 18).

Fire Damper Sleeve

6 in. long metal cleat or 1/16 in.


max. thickness plastic cleat;
12 in. c-c (min. 1 per side)

Flanged system angles

(Attach per
manufacturer's
instructions)

3/8 in. bolts in


corners are optional

Neoprene or Butyl gasket


between all angles

Duct

Figure 18
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF
addendum to the SMACNA Duct Construction Standards. Standard 6 in. (152mm) metal clip may be used with
spacing as shown in diagram (see Figure 19 & 20). 33⁄8 in. (9.5mm) metal bolts and nuts may be used to fasten
together corner pieces (see Figure
Clip Spacing21). Std. Clip
Length
9 in.
6 in. 6 in. 6 in.
60 in. Duct
4 Req’d. Duct End
7Clip
in. Spacing Std. Clip 7 in. Flange
48 in. Duct
Length
3 Req’d. 9 in.
5 in. 5 in. Corner Piece
6 in. 6 in. 6 in.
Sleeve Duct 60Duct
36 in. in. Duct
3 Req’d.
4 Req’d.
5 in. 5 in.
7 in. 7 in.
24 in. Duct
48 in.
2 Req’d. Duct 3/8 in. bolt
Typical TDC/TDF joint 3 Req’d. (optional)
18 in. Duct & 5 in. 5 in.
Figure 19
Sleeve Duct
Smaller
1 36 in. Duct
Req’d. C
L
3 Req’d. Duct
5 in. 5 in.

24 in. Duct
2 Req’d.
Typical TDC/TDF joint
18 in. Duct &
Smaller
1 Req’d. C
L
Figure 21
Duct
Figure 20
10 Curtain Fire Dampers
No Connecting Duct or Transfer Opening
Openings where duct does not attach on either side will not
require a breakaway connection. Transfer openings are typical of
a non-ducted installation (see Figure 22).
• Sleeve may end flush with the rated wall/floor on both
sides
• Refer to Securing the Damper/Sleeve Assembly to
Wall/Floor Openings for securing retaining angles to
the sleeve.

Figure 22: Transfer opening or no connecting duct

Damper Commissioning and Periodic Testing


The International Fire Code (IFC) requires fire dampers to be maintained in accordance with NFPA standard 80 and
smoke dampers to be maintained in accordance with NFPA standard 105. NFPA 80 and 105 define the frequency
and method for periodically testing life safety dampers.
NFPA 80 & 105 do not require heat to be applied to a damper’s fusible link or thermostat during periodic testing.
Electric or pneumatic actuated dampers are required to be tested by temporarily removing electrical or pneumatic
power from the actuator to ensure the damper fully closes and then fully opens once power is restored. Mechanical
and gravity operated dampers utilizing a fusible link are required to be tested by removing the fusible link and
allowing the damper to fully close and then manually reopening the damper. Re-install the fusible link.
Greenheck’s life safety dampers shall not be tested by applying heat with uncontrollable heat sources (i.e. heat guns,
torches, etc.) as this can permanently damage the thermostat or other parts of the damper.

Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use
mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and
jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.

Symptom Possible Cause Corrective Action


Frame is 'racked' causing blades to bind Adjust frame such that it is square and
on jamb seals plumb
Damper does not fully Screws in damper linkage Damper installed too far into wall. Move
open and/or close out to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see
Damper Maintenance)
Link separated Heat Replace link

Curtain Fire Dampers 11


Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com

12 481324 • DFD DFDX FD FDX, Rev. 9, January 2020 Copyright 2020 © Greenheck Fan Corporation
WD-300 Series
Backdraft Damper
Vertical Mount - Horizontal Airflow

Application
The WD-300 series dampers are designed to prevent reverse
airflow in horizontal exhaust applications. The WD-300 features
a pressure sensitive blade design that opens and remains open
under low velocity conditions. The dampers are opened by air
pressure differential and closed by gravity. Optional motor pack
converts the damper to motorized operation.

Ratings
Pressure
2.0 in. wg (0.5 kPa) - differential pressure
Velocity
2500 fpm (13 m/s)
Temperature
180°F (82°C) *W & H dimensions furnished approximately 1⁄8 in. (3mm) undersize.

Construction Frame Styles


Standard Optional
1 1/2 in. Typical 1 1/2 in. Typical 1 1/2
Frame Material Galvanized steel -
Frame Thickness 18 ga. (1.3mm)
5/8 in. Max. - 5/8 in. Max. 5/8 in. Max.
Typical
Typical Typical
No flange (WD-330) -
Frame Type Flange on intake (WD-300) -
Airflow Airflow Airflow
H* Flange on discharge (WD-320) H* - H* H* H* H* H*
Blade Material Roll formed aluminum -
Blade Thickness 0.025 in. (0.64mm) - 0.032 in.
- 2 3/4 in. M
2 3/4 in. Max.
(0.8mm) for triple panel 2 3/4 in. Max.
Typical Typical Typical

Blade Seals Vinyl -


3 3/8 in. 3 3/8 in. 3 3/8 in.
3/16 in. (4.8mm) dia. zinc plated
Axle steel pin on blade ends
304SS
3 1/2 in. 3 1/2 in. 3 1/2 in. 3 1/2 in.

WD 330 WD 320 WD 330 WD 300 WD 320 WD 330WD 300


Axle Bearings Synthetic
No Flange Frame 304SS
Flange on Discharge No Flange FrameFlange on Intake Flange on Discharge No FlangeFlange
Frameon Intake

Linkage Material Galvanized Steel -

Size Limitations
Minimum Maximum Size
WxH
Size Single Panel Multiple Panels Options
WD-300 & WD-320 • End switch kit (part no. 851038)
Inches 6x6 31 x 74 148 x 148 • Motor packs (24V, 120V, 208-240V, 440V)
mm 152 x 152 787 x 1880 3759 x 3759
WD-330
Inches 6x6 31 x 74 150 x 148
mm 152 x 152 787 x 1880 3810 x 3759

WD-300 Series May 2022


Performance Data

Pressure Drop
Performance data results from testing a 36 in. x 36 in. (914mm x Pressure Drop
914mm) damper in accordance with AMCA Standard 500-D using 36 in. x 36 in. (914mm x 914mm) Damper
Figure 5.5 (unducted). All data has been corrected to represent
standard air at 0.075 lb/ft3 (1.201 kg/m3).
1.2

ΔP Velocity 1.0

Operational Data in. wg fpm

Pressure Drop - in. wg


(kPa) (m/s) 0.8
Non- 0.05 300
Blades start to open
ducted (.012) (1.5)
0.6
Non- 0.15 900
Blades fully open
ducted (.037) (4.5)
0.4

Full Open

0.2 Start Open

0.0
0 500 1000 1500 2000 2500

Velocity - feet per minute (fpm)

Leakage
Leakage testing was conducted in accordance with AMCA
Standard 500-D and is expressed as CFM per sq. ft. of damper Leakage
face area. All data has been corrected to represent standard air 36 in. x 36 in. (914mm x 914mm) Damper
at 0.075 lb/ft3 (1.201 kg/m3).
3

2.5
Static Pressure Difference (in. wg)

1.5

0.5

0
10 20 30 40 50 60 70 80 90

Leakage (cfm/sq. ft)

WD-300 Series May 2022


Motor Packs

Series MP-310 motor pack may be field installed to convert the WD-300 series backdraft damper to motorized operation. Airflow
direction should remain horizontal exhaust when this motorized version is applied. These versatile motor packs feature power opening
with spring return. The springs also provide damper closure in the event of electrical failure.
The MP-310 motor packs are available in voltages of 24, 120, 208, and 440. 575/600 volts may be used with any of the motor packs
by way of a transformer (part no. 380711) and the appropriate 115 volt motor pack (MP-310). MP-310 series motor packs are UL
listed. Please specify voltage when ordering.
There is one motor pack available on the WD-300 series damper to accommodate for larger torque requirements. To determine the
number of motor packs required per WD-300 or WD-320 damper, refer to the table on page 5. To determine the number of motor
packs required per WD-330 damper, refer to the table on page 7. Oversized applications may require several dampers connected
together for one opening.
MP-300 series motor packs are supplied with mounting hardware, assembly instructions and actuator arms for either single, double,
or triple panel installation.

MP-210/220A 110V-120V 208V - 240V 440V


24V (50/60 Hz)
Motor packs (50/60Hz) (50/60Hz) (60Hz)
Stall Amps .66 .15 .07 .041
Spec ID# G24 G110-240 G110-240 G460

Installation Instruction for MP-310

Motor Pack Dimensional Data


WD-300 series dampers are available with an optional motor pack (MP-310). The diagram to the left illustrates the required clearance
needed for proper operation of a mounted motor pack.

Airflow

10 in. Minimum
Space Required

WD-300 series backdraft damper with


optional motorpack

WD-300 Series May 2022


WD-300/320 Selection
Multiple section dampers shown below are supplied as equal size sections. Any damper that has multiple sections, both vertically and
horizontally, will require field assembly and will require additional reinforcement (not supplied by Greenheck) to support the assembly.
These larger dampers must have the additional reinforcement to give them structural stability.
The width dimension is always parallel to the length of the blades.
Note: The type and number of motor packs required can be found on page 5.

WD-300 / WD-320

Width
6 32 50 74 100 148
6 Up 32 Up 50 Up Above 74 100 Up
To 32 To 50 Thru 74 Up To 100 Thru148
6

Single Double Triple Double Double


Panel Panel Panel Panel Panel
One One One Two Three
Thru 74
6 Up

Section Section Section Section Section

74
Height

Single Double Triple Double Double


Panel Panel Panel Panel Panel
Two Two Two Four Six
Abover 74
Thru 148

Section Section Section Section Section

148

*Width and height given in inches.

WD-300 Series May 2022


Motor Pack Selection for WD-300/320
The table below will allow you to determine the type and number of motor packs needed for a given size WD-300/320 backdraft
damper. For further information on a particular motor pack, refer to page 3.

WD-300/320 Motor Pack Selection


Width
6 50 100 148
>=6 and <50 >=50 and <100 >=100 and <=148
6

(1) MP-310 (2) MP-310 (3) MP-310


>=6 and <=74

Motor Pack Motor Packs Motor Packs

74
Height

(2) MP-310 (4) MP-310 (6) MP-310


Motor Packs Motor Packs Motor Packs
> 74 and <=148

148

*Width and height given in inches.

WD-300 Series May 2022


WD-330 Selection

Multiple section dampers shown below are supplied as equal size sections. Any damper that has multiple sections, both vertically and
horizontally, will require field assembly and will require additional reinforcement (not supplied by Greenheck) to support the assembly.
These larger dampers must have the additional reinforcement to give them structural stability.
The width dimension is always parallel to the length of the blades.
Note: The type and number of motor packs required can be found on page 7.

WD-330
Width
6 32 50 64 100 128 150
6 Up 32 Up Above 50 64 Up Above 100 128 Up
To 32 Thru 50 Up To 64 Thru 100 Up To 128 Thru 150
6

Single Double Single Double Single Double


Panel Panel Panel Panel Panel Panel
One One Two Two Four Three
Section Section Section Section Section
Thru 74

Section
6 Up

74
Height

Single Double Single Double Single Double


Panel Panel Panel Panel Panel Panel
Two Two Four Four Eight Six
Section Section Section Section Section Section
Above 74
Thru 148

148

*Width and height given in inches.

WD-300 Series May 2022


Motor Pack Selection for WD-330

The table below will allow you to determine the type and number of motor packs needed for a given size WD-330 backdraft damper.
For further information on a particular motor pack, refer to page 3.

WD-330 Motor Pack Selection


Width
6 50 100 128 150
>=6 and <=50 >50 and <=100 >100 and <128 >=128 and<=150
6

(1) MP-310 (2) MP-310 (4) MP-310 (3) MP-310


Motor Pack Motor Packs Motor Packs Motor Packs
>=6 and <=74

74
Height

(2) MP-310 (4) MP-310 (8) MP-310 (6) MP-310


Motor Packs Motor Packs Motor Packs Motor Packs
>74 and <=148

148

*Width and height given in inches.

WD-300 Series May 2022


WD-300 Series
End Switch Kit Backdraft Damper

End Switch Kit (Optional)


An end switch is a control device used in conjunction with a
motor pack (the end switch is usually wired to a fan and/or to a
light serving as an open/not open indicator). When the damper is
powered open, the blades of the damper hit the spring rod of the
end switch which in turn makes a connection allowing power to Spring Rod
flow to the fan and/or light. This set up would be used when it is
desirable to ensure that the damper is fully open before the fan
starts. Otherwise, with the damper blades are not fully open, the
pressure and air velocity produced by the fan may damage the
blades, making the damper inoperable.

Installation Instruction for End Switch Kit

Horizontally Mounted Damper Vertically Mounted Damper

Document Links

Installation Instructions Backdraft Catalog Damper Product Selection Guide

Specifications Damper Warranty

Copyright ® 2022 Greenheck Fan Corporation


WD-300 Series, R14, May 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice
FSD-331
Combination Fire Smoke Dampers

Application
Model FSD-331 is a combination fire smoke damper with Class I
leakage and 3 hour fire rating. High strength airfoil blades ensure
the lowest resistance to airflow in HVAC systems with velocities
to 4000 fpm (20.3 m/s) and pressures up to 8 in. wg (2kPa). Model
FSD-331 may be installed vertically or horizontally (with blades
running horizontal) and is rated for airflow and leakage in either
direction.
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 3 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 4000 fpm (20.3 m/s)
Pressure: Up to 8 in. wg (2 kPa)
UL 555S Leakage Rating
Leakage Class: I Width and Height dimensions furnished approximately 1⁄4 in. (6mm)
Operational Rating: Actual ratings are size dependent undersize. (Add sleeve thickness for overall sleeved damper dimension).
Right hand drive is shown. Left hand is available upon request.
Velocity: Up to 4000 fpm (20.3 m/s)
Pressure: Up to 8 in. wg (2 kPa) See complete marking on
Temperature: Up to 350°F (177°C) - depending product.
upon the actuator UL 555 and UL 555S
Construction Classification R13317

Standard Optional
Frame Material Galvanized steel - Model FSD-331 meets the requirements for fire dampers,
Frame Material smoke dampers and combination fire smoke dampers
16 ga. (1.5mm) - established by:
Thickness
5 in. x 1 in. National Fire Protection Association
Frame Type (127mm x 25mm) - NFPA Standards 80, 90A, 92, 101, & 105
hat channel IBC International Building Codes
Blade Material Galvanized steel - CSFM California State Fire Marshal

Blade Material Fire Damper Listing (#3225-0981:0103)


14 ga. (2mm)
- Leakage (Smoke) Damper Listing (#3230-0981:0104)
Thickness equivalent
Blade Type Airfoil -
Blade Action Opposed -
Plated steel out of
Linkage airstream, concealed 316SS Maximum Size
in jamb Minimum
WxH Single Multiple
Size
Axle Bearings 316SS - Section Section
Axle Material Plated steel 316SS 32 x 36 (V) or 120 x 96 (V) or
Inches 8x6
30 x 48 (H or V) 120 x 96 (H)
Blade Seals Silicone -
813 x 1270 (V) or 3048 x 2438 (V) or
Jamb Seals Stainless Steel - mm 203 x 152
762 x 1219 (H or V) 3048 x 2438 (H)
RRL/OCI, TOR,
Closure Device RRL
Fusible Link Note: Maximum sizes are dependent on velocities and pressures.
212°F (100°C),
Closure 250°F (121°C),
165°F (74°C)
Temperature 286°F (141°C)*,
*only availabe with fusible link
350°F (177°C)

FSD-331 May 2022


Options and Accessories
• Breakaway connections
• Clean wrap
• Greenheck test switches (GTS)
• Grille tabs
• Momentary switches
• Retaining angles
• RRL/OCI LH
• Security bars
• Sealed transitions and sleeve
• Smoke detectors
• TOR
• Transitions: C, O, R RH

Document Links
Installation Instructions Life Safety Damper Catalog

Damper Product Selection Guide Specifications

Damper Warranty

FSD-331 May 2022


Pressure Drop
AMCA Figure 5.2
5D

D 4 (W) (H)
3.14

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36in. x 36 in. (914mm x 914mm) 12in. X 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop
(fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg)
500 0.03 500 0.01 500 0.01 500 0.01 500 0.02
1000 0.11 1000 0.06 1000 0.05 1000 0.05 1000 0.08
1500 0.24 1500 0.12 1500 0.12 1500 0.12 1500 0.18
2000 0.42 2000 0.22 2000 0.21 2000 0.21 2000 0.33
2500 0.66 2500 0.34 2500 0.32 2500 0.33 2500 0.51
3000 0.95 3000 0.49 3000 0.47 3000 0.48 3000 0.74
3500 1.30 3500 0.67 3500 0.63 3500 0.65 3500 1.00
4000 1.70 4000 0.87 4000 0.83 4000 0.85 4000 1.31

AMCA Figure 5.3

5D 6D

5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36in. x 36 in. (914mm x 914mm) 12in. X 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)

Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
5D
500 0.01 500 0.01 500 0.01 500 0.01 500 0.01
1000 0.06 1000 0.02 1000 0.02 1000 0.03 1000 0.04
1500 0.13
5D 1500 0.06 1500 0.05 1500 0.06 1500 0.10
2000 0.23 2000 0.10 D 2000 4 (W) (H)0.09 2000 0.11 2000 0.18
2500 0.37 2500 0.16 2500 3.14 0.14 2500 0.18 2500 0.29
3000 0.53 3000 0.23 D 4 (W) (H) 3000 0.21 3000 0.25 3000 0.42
3500 0.73 3500 0.32 3.14 3500 0.29 3500 0.34 3500 0.57
4000 0.95 4000 0.42 4000 0.38 4000 0.45 4000 0.74

AMCA Figure 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36in. x 36 in. (914mm x 914mm) 12in. X 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)

Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop Velocity Pressure Drop
(fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg) (fpm) (in. wg)
500 0.04 500 0.03 500 0.03 500 0.03 500 0.03
1000 0.18 1000 0.13 1000 0.12 1000 0.12 1000 0.14
1500 0.42 1500 0.29 1500 0.27 1500 0.27 1500 0.32
2000 0.75 2000 0.52 2000 0.48 2000 0.49 2000 0.57
2500 1.17 2500 0.81 2500 0.75 2500 0.77 2500 0.89
3000 1.68 3000 1.17 3000 1.08 3000 1.11 3000 1.28
3500 2.29 3500 1.60 3500 1.48 3500 1.51 3500 1.75
4000 2.09 4000 2.14 4000 1.93 4000 1.97 4000 2.29

Greenheck Fan Corporation certifies that the model FSD-


331 shown herein is licensed to bear the AMCA seal. The
ratings shown are based on tests and procedures performed
in accordance with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings Programs.
The AMCA Certified Ratings Seal applies to air performance
ratings only.

FSD-331 May 2022


Sleeve Length

Space Envelopes
Externally mounted actuators always require space outside of
T*
the damper sleeve. The “S” dimension illustrates the clearance
S
required for various available actuators.
On damper less than 18 in. (457mm), actuators may also
require clearances above and/or below the sleeve. “B” and “T”
dimensions are worst case clearance requirements for some
dampers less than 18 in. (457mm) high. All dampers 18 in.
(457mm) or more in height, do not require these worst case
clearances. If space availability above or below the damper
sleeve is limited, each damper size should be individually
evaluated.

B*

B* T* S
With With Piggyback
Actuator Type/Model
RRL, RRL/OCI, or RRL, RRL/OCI, or
No Yes
TOR TOR
120 Volt AC
FSLF120 (-S) Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF120 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
FSTF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
MS4104 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4120 Series Honeywell 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
24 Volt AC
FSAF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) NA
FSTF24 (-S) Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
FSLF24-S Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
MS8104 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS8120 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229m)
230 Volt AC
FSLF230-S Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF230-S Belimo 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
FSTF230-S Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
MS4604 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4X09 Series Honeywell ⁄2 in. (13mm)
1
81⁄2 in (216mm) 6 in. (152mm) NA
MS4620 Series Honeywell ⁄2 in. (13mm)
1
913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in.

FSD-331 May 2022


Contained Actuator Option
Dampers can be ordered with a “contained actuator option”. This option will result in the actuator being oriented such that it extends
no more than 11⁄2 inches above or below the sleeve. Note that some damper configurations that are 11 inches high or less will have the
RRL, RRL/OCI, or TOR mounted on the side opposite the actuator when the contained actuator option is selected.

Sleeve Length
Damper
Location

RRL, RRL/OCI, or TOR


opposite actuator

Components contained
within 1½ in. of sleeve
top and bottom

Actuator Parallel

1½ in.

RRL, RRL/OCI, or TOR

Sleeve and Sideplate Dimensional Data


The drawings below and corresponding table show the position of the FSD-331 damper when mounted in a factory sleeve. the
standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of retaining
angles and duct connections.
The standard location of a damper mounted in a factory sleeve (“A” dimension) is shown below. The damper can be positioned at
other locations within a range of 6 in. (152mm) to 16 in. (406mm) for the “A” dimension.

"A" Dimension
1½ in. (38mm) in. (mm)
maximum Sleeve Std Sleeve Max Sideplate
Sleeve All Dampers (RRL) 7 3⁄16 in. (183) 16 (406) 63⁄16 (157)
When Height is 11 in.
(279) or less with RRL, 12 (305) 16 (406) 12 (305)
3¾ in. RRL/OCI, or TOR
(95mm)

NOTE: Entire damper frame is not required to be installed within the wall. The damper
blades, when closed should be contained within the wall.
11/2 in. max.
6 in.
Varies
(152mm) 5 3/8 in.
(137mm)
Sideplate

RH
5 in.
wn A
(127mm)
request
Sleeve Length
3 3/4 in.

6 in.

Varies
5 3/8 in.

T*
5 in.
S A 5 in.
A
Sideplate
Length** Sleeve Length

FSD-331 May 2022


FSD-331
Transitioned Damper Dimensions Combination Fire Smoke Damper

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the FSD-331 can be supplied in a factory sleeve
with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show
overall damper size.

D* + 2 in. (51mm) +T s
W* + 2 in. (51mm)+Ts
W* + 2 in. (51mm)+Ts

D* + 2 in. (51mm)+Ts
H* + 2 in. (51mm)+T s H* + 2 in. (51mm)+Ts
2 1/8 in. H*
2 1/8 in. H* (54mm)
2 1/8 in. (54mm)
(54mm)

W*
W*
16 in. D* 16 in. 16 in.
(406mm) (406mm) (406mm)
Minimum Minimum Minimum

TYPE R TYPE O TYPE C

* These dimension are furnished approximately 1⁄4 in. (6mm) undersize, except round and oval dimensions which are approximately 1⁄8 in. (3mm)
undersize.
TS = (2)(Sleeve Thickness) 48 in.
(1219mm)
48 in. 50 in.
(1219mm) (1270mm)

Multiple Sections Damper


30 in. (762mm)
60 in. (1524mm)
Dampers larger than maximum single section size are30supplied
in. (762mm)as a factory assembly of two or more sections of equal size. The 32 in. (813mm)

following figures show maximum damper section size and assembly configurations for multi-section dampers.

48 in. 96 in.
(2438 mm)
(1219mm)
50 in.
(1270mm)

48 in.
30 in. (762mm) (1219 mm) 96 in. (2435mm)
60 in. (1524mm) 120 in. (3048 mm)
in. (762mm) 32 in. (813mm)

30 in. (762 mm)

Four sections wide


Two Sections
Two sections high

Copyright ® 2022 Greenheck Fan Corporation


FSD-331, R17, May 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice
96 in.
(2438 mm)
Lorem ipsum
Document 481318
Multi-Blade Fire and Combination Fire
® Smoke Damper
DFD-xxx, DFDAF-xxx, FSD-xxx, FSD-xxxV, IMO-xxx, SEDFD-
xxx, SEFSD-xxx, and SSFSD-xxx
11⁄2 and 3 Hour Fire and Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)

Installation, Operation and Maintenance Manual


Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.

These instructions apply to 11⁄2 and 3 hour rated fire and combination fire smoke dampers mounted in: 1) masonry,
block, or stud walls and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must
be installed in accordance with these instructions to meet the requirements of UL 555 and/or UL 555S.
Note: Combination fire smoke and fire dampers are manufactured and labeled for either vertical or horizontal
installation. The dampers must be installed in accordance with labeling.

Table of Contents
General Information .............................................. 2
Pre-Installation Guidelines ................................... 2
Electrical Guidelines.............................................. 2
Installation........................................................3-11
• Preparation of Openings ................................ 3
• Clearances Required Between Damper
Sleeves & Wall/Floor Openings ..................... 4
• Installing Multiple Damper Section
Assemblies .................................................4-5
• Multiple Section Damper Wiring..................... 5
• Maximum Assembly Tables............................ 5
• Inserting Damper into Wall/Floor
Openings........................................................ 6
• Securing the Damper/Sleeve
Assembly to Wall/Floor Openings ..............7-8
• Duct to Sleeve Connection........................9-10
• Actuator & Temperature Response
Device Connections...................................... 11
Commissioning and Periodic Testing.................. 12
Receiving and Handling Maintenance ....................................................... 12
Upon receiving dampers, check for both obvious Troubleshooting .................................................. 12
and hidden damage. If damage is found, record all
necessary information on the bill of lading and file
a claim with the final carrier. Check to be sure that
all parts of the shipment, including accessories, are Safety Warning
accounted for. Improper installation, adjustment, alteration, service
Dampers must be kept dry and clean. Indoor storage or maintenance can cause property damage, injury
and protection from dirt, dust and the weather is or death. Read the installation, operating, and
highly recommended. Do not store at temperatures in maintenance instructions thoroughly before installing
excess of 100°F (38°C). or servicing this equipment.

This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.
Multi-Blade Fire and Combination Fire Smoke Dampers 1
General Information
Pre-Installation Guidelines
“UL CLASSIFIED (see complete marking on
product)” The following items will aid in completing the damper
“UL CLASSIFIED to Canadian safety standards installation in a timely and effective manner.
(see complete marking on product)” 1) Check the drawings for proper damper locations
Standard 555 & 555S (Listing #R13317) within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place and has not activated if provided.
Installation Supplements These electric links have a button for resetting.
Visually inspect the fusible link (if provided) to verify
Refer to the appropriate Greenheck installation
its not missing or broken. Replace link as necessary.
supplements for special requirements:
2) Lift or handle damper using sleeve or frame. Do not
• Concrete Floor with Steel Deck
lift damper using blades or actuators.
• Drive Slip Breakaway Connection
• Field Installed Sleeve 3) Damper has label on outside of sleeve indicating
• Fire Resistant Ventilated Duct Assembly a ‘No Screw’ area. Do not install screws into this
• Firestop Material area as screws may interfere with unexposed blade
• Fusible Link Replacement linkage and prevent damper blades from opening
• Greenheck Test Switch and/or closing.
• Grille Installation 4) Damper has label indicating position of damper
• Metal Stud in Shaftwall Partition and sleeve assembly in the wall. Install accordingly
• Non-Concrete Horizontal Mount to comply with manufacturer’s appropriate UL
• Open or Close Indicator (OCI) Classification file number.
• Quick Connect Breakaway Connection 5) Damper must be installed into duct or opening
• Resettable Link (RRL) square and free of twist or other misalignment. Out
• Resettable Link with Blade Indicator of square, racked, twisted or misaligned installations
(RRL/OCI) can cause excessive leakage and/or torque
• Sealant Supplement requirements to exceed damper/actuator design.
• Single 3-Sided Retaining Angle Supplement 6) Damper and actuator must be kept clean and
• Sleeve Extension protected from dirt, dust and other foreign materials
• Smoke Detector - Various Types prior to and after installation. Examples of such
• Temperature Limited Override (TOR) foreign materials include but are not limited to:
• Tunnel Corridor a) Mortar dust
Installation supplements available at www.greenheck. b) Drywall dust
com. c) Firesafing materials
d) Wall texture
e) Paint overspray
Electrical Guidelines 7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
Electrical Guidelines performed within 5 feet of the damper. Excessive dirt
All wiring shall be done in accordance with the or foreign material deposits on the damper can cause
National Electrical Code ANSI/NFPA-70 latest edition, excessive leakage and/or torque requirements to
any local codes that may apply, and wiring diagrams exceed damper/actuator design.
developed in compliance with the job or project 8) Caulking is not necessary, nor is it allowed, between
design and specifications. the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining angles.
Important! 9) ACCESS: Suitable access (such that RRL’s and
Electrical input may be needed for this equipment. actuators can be maintained, etc.) must be provided
This work should be performed by a qualified for damper inspection and servicing. Where it is not
electrician. Verify power before wiring actuator. possible to achieve sufficient size access, it will be
Greenheck is not responsible for any damage to, or necessary to install a removable section of duct.
failure of the unit caused by incorrect field wiring. To (Refer to NFPA 90A).
avoid causing death or serious bodily harm to building 10) The Code Authority Having Jurisdiction (AHJ) must
occupants, follow all instructions carefully. Dampers evaluate and provide approval of final installation
must close completely to preserve the integrity of the where variations to these instructions are necessary.
fire smoke separation.

2 Multi-Blade Fire and Combination Fire Smoke Dampers


Preparation of Openings
• Frame wall openings as shown below (see Figure 1, 2, and 2A).
• Gypsum wall board must be fastened 12 in. (305mm) on center (O.C.) to all stud and runner flanges surrounding
opening.
• Prepare opening between studs and sleeve assembly as shown below (see Figure 3 & 4).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
Second set of studs are not required on openings
Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller.
36 in. x 36 in. (914mm x 914mm) or smaller.

24 in. o.c. 24 in. o.c.


Ceiling Runner
Maximum Maximum
(metal studs) (metal studs)

12 in.

24 in. o.c.
Maximum

2 in. (51mm)
2 Panhead
Screws
2 in. (51mm)

16 in. o.c. 16 in. o.c.


Maximum Maximum
(wood studs) (wood studs)

Second set of studs are not required on openings


36 in. x 36 in. (914mm x 914mm) or smaller.
Figure 1 Floor Runner
Figure 2
Metal stud only

Metal Stud Construction

Gypsum Wallboard

Stud or Runner

Retaining
Angle
1 in. Min.

Damper
In metal stud construction,
Sleeve exposed steel surfaces need
not be covered with gypsum
wallboard.
Metal stud only
Figure 2A

Wooden Stud Construction Metal Stud Construction

Gypsum Wallboard
Gypsum Wallboard

Stud or Runner

Stud or Runner

Retaining Retaining
Angle Angle
1 in. Min.
1 in. Min.

Damper
In metal stud construction,
Damper In wood stud construction, Sleeve exposed steel surfaces need
Sleeve gypsum wallboard must cover not be covered with gypsum
all wood stud surfaces. wallboard.

Figure 3 (2 sided angle installation shown) Figure 4 (2 sided angle installation shown)
Wooden Stud Construction
Multi-Blade Fire and Combination Fire Smoke Dampers 3
Gypsum Wallboard
Clearances Required Between Damper Sleeves & Wall/Floor Openings
Two-Sided Angle Installation
Two-sided angle installations require clearances for thermal expansion between the damper sleeve and the wall/floor
opening. The minimum required clearances are:
• For galvanized steel dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and 1⁄8 in. per
foot (3mm per .3 m) height with a minimum clearance of 1⁄4 in. (6mm). The total gap may be up to 6 in.
(152mm), 3 in. (76mm) per side, as long as the retaining angles overlap the wall/floor by a minimum of 1 in.
(25mm).
• For stainless steel dampers and stainless steel or galvanized sleeves: 3⁄16 in. per foot (5mm per .3 m) of
damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).
Example:
A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4 in.
(6mm) width and 1/4 in. (6mm) on height
A 48 in. x 12 in. (1219mm x 305mm)
damper will required a minimum
clearance of 1/2 in. (13mm) on width and
1/4 in. (6mm) on height.

These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
Although the minimum requirements are listed above, for ease of installation the following are the recommended
clearances for galvanized dampers:
• Width/Height of 48 in. (1219 mm) or less - ½ in. (13mm) clearance
• Width/Height between 48.01 in. (1220 mm) and 96 in. (2438 mm): 1 in. (25mm) clearance
• Width/Height greater than 96 in. (2438 mm): 1½ in. (38 mm) clearance

Single Side Angle Installation


On vertical mount single side angle installations there are no minimum clearance requirements between the wall
opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the
damper sleeve are recommended.
On horizontal mount single side angle installations a minimum clearance is required between the outside of the
damper sleeve and the floor opening of 1⁄8 in. per foot (3mm per .3m) of damper width and 1⁄8 in. per foot
(3mm per .3m) height with a minimum clearance of 1/4 in. (6mm).

Installing Multiple Section Damper Assemblies


A damper assembly is not restricted to a maximum number of sections, but must not exceed the section sizes and
overall sizes shown (see chart on page 5).
Some multiple section high damper assemblies require additional structural support between the damper frames.
The following multiple section high damper assemblies require the use of either a support mullion between the
damper frames as shown in Figure 5 or individual sleeves around each row of dampers as shown in Figure 6:
• All horizontal mount dampers
• All vertical mount dampers over 72 in. (1829mm) high and greater than 2 sections wide
• All vertical mount dampers rated for more than 4 in. wg (1 kPa)
• All vertical mount dampers that use fusible links as a closure device
The damper sections must be attached together with #10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in. (6mm)
diameter nuts and bolts, tack or spot welds, or 3⁄16 in. (48mm) diameter steel pop rivets. Attachments must be spaced
a maximum of 6 in. (152mm) O.C. and a maximum of 2 in. (51mm) from corners. Attachments must be made on front
face and back face (air entering and air exiting side) of damper sections.
Note: Dampers ordered for individual installation may not be installed together. The full assembly size must be
specified at the time the dampers are ordered.

4 Multi-Blade Fire and Combination Fire Smoke Dampers


Support mullion:
14 ga. 5 in. wide for
vertical mount dampers;
12 ga. 9 in. wide for
horizontal mount dampers

Figure 5: Single sleeve around outside with support Figure 6: Two individually sleeved units with no mullions
mullion
Multiple Section Damper Wiring
Dampers greater than 84 in. (2134mm) high will ship in
two ship sections. Conduit whips from ship section will
need to be wired to junction box on ship section with
the closure device (see Figure 7).
When fire and fire smoke dampers are ordered with an
open/close blade position indicating device (included
with the OCI, RRL/OCI, and TOR accessories) one
device is provided per row of damper sections. For
example, a two section high damper assembly will be
provided with two open/closed indicating devices.
Note that all damper sections on a given row are
operated by a single jackshaft and thus forced to
operate in unison. On two section high dampers,
although the two open/closed indicators are not factory
wired together, it is common industry practice to field
wire the two open switches in series and the two closed
switches in series so that the system monitoring the
damper will detect a fault if either row of dampers fails
to reach the end of stroke condition.
Figure 7: Multiple section damper wiring
Maximum Assembly Tables
Horizontal Mount Vertical Mount
Maximum Maximum
Maximum Single Overall Size for Maximum Single Overall Size for
Damper Model Section Size Multi-Section Damper Model Section Size Multi-section
(inches) Dampers (inches) Dampers
(inches) (inches)
DFD-210 36 x 36 or 32 x 50 128 x 96 DFD-210 36 x 36 or 32 x 50 128 x 100
DFDAF-310 32 x 50 144 x 96 DFDAF-310 32 x 50 128 x 100
FSD-211, 212, 213 36 x 48 or 32 x 50 144 x 96 FSD-211, 212, 213 36 x 48 or 32 x 50 128 x 100
FSD-211M, 212M 30 x 36 144 x 72 FSD-311, 311M,
32 x 50 128 x 100
FSD-231M 36 x 36 72 x 48 312, 312M

FSD-311, 312 32 x 50 144 x 96 FSD-311V 50 X 32 100 x 32

FSD-311M, 312M 32 x 50 128 x 96 FSD-331, DFDAF-330 32 x 36 or 30 x 48 120 x 96

FSD-331, DFDAF-330 30 x 48 144 x 96 32 x 50 NA


IMO-311
IMO-310 32 x 50 NA 32 x 50 NA

IMO-311 32 x 50 NA SEDFD-210,
24 x 30 or 22 x 36 48 x 30
SSDFD-210
SEDFD-210,
24 x 30 48 x 30 SEFSD-211
SEFSD-211 24 x 30 or 22 x 36 88 x 72
SSFSD-211
SSFSD-211 24 x 30 48 x 30

Note: FSD model dampers fitted with a fusible link closure device are limited to single section sizes.

Multi-Blade Fire and Combination Fire Smoke Dampers 5


Inserting Damper into Wall/Floor Openings
Insert the sleeved damper assembly into the prepared opening. Refer to label on outside of sleeve for the
recommended location of the damper in the wall or floor (see Dimension A and Detail 1, Figure 8).
Special attention must be paid to ensure the following:
1) The CL (centerline) of the damper frame remains within the plane of the wall or floor
2) A ttachments made through the retaining angle do not penetrate the ‘No Screw’ area designated on the
damper sleeve.
3) T he sleeve does not extend more than 16 in. (406mm) beyond the wall or floor on the actuator side of the
damper and 6 in. (152mm) on the side opposite the actuator. The sleeve may also extend up to 16 in. (406mm)
beyond the wall or floor if the damper has a factory supplied access door.

Optional blade indicator Clearance for expansion


and/or electric link. (1/4 in. min., 1 1/2 in. max.)
Retaining Angles
(see Section 4)

Airflow
Access door required on
jackshaft side of damper.
Refer to the latest edition
of NFPA 90A. Jackshaft Line of Wall

DO NOT INSTALL SCREWS


BETWEEN THESE LINES
AROUND ENTIRE DAMPER
LINE OF WALL

DO NOT INSTALL SCREW S


BETWEEN THESE LINES
AROUND ENTIRE DAMPER

458549

Actuator
‘A’ Dim.
(Distance from
Damper end of sleeve to
Sleeve face of damper) Detail 1

16 in. max. CL
6 in. max.

Tw

Sleeve Length (L)

Figure 8: P
 roperly Installed Combination fire smoke damper

Most fire and combination fire smoke dampers come with factory supplied sleeves. For field supplied sleeves, see
the Field Supplied Sleeves supplement at www.greenheck.com. The following are recommended sleeve lengths for
various wall thicknesses:

Wall Thickness Recommended


Dimension (TW) Sleeve Length
Dimension (L)
4 - 6 in. 16 in.
(102mm - 152mm) (406mm)
7 - 10 in. 21 in.
(178mm - 254mm) (533mm)
11 - 13 in. 24 in.
(279mm - 330mm) (610mm)

6 Multi-Blade Fire and Combination Fire Smoke Dampers


Securing the Damper/Sleeve Assembly to Wall/Floor Openings
All fire and combination fire smoke dampers may utilize the two sided angle installation method described below.
11⁄2 hour rated fire and combination fire smoke dampers may use the single sided angle installation method up to the
following maximum sizes:
• Vertical mount: 80 in. W x 50. in. H (2032mm W x 1270mm H), 50 in. W x 80 in. H
(1270mm W x 2032mm H), or 40 in. W x 100 in. H (1016mm W x 2540mm).
• Horizontal mount: 144 in. W x 96 in. H (3658mm W x 2438mm H)

• Retaining Angle Gauge: Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm)
or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a
width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm).
• Retaining Angle Size: The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm).
The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm).
• Retaining Angle Attachment to Sleeve: Retaining angles must be attached to the damper using one or more of
the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
- Tack or spot welds
- #10 (3⁄4 in. [19mm] max.) sheet metal screws
- 1⁄4 in. (6mm) bolts and nuts
- 3⁄16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom, spaced 12 in. (305mm) O.C. maximum are required for
openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in.
high (914mm) require the connections to be no more than 6 in. (152mm) O.C..
The angles must be attached to all 4 sides of the sleeve. Ensure that fasteners do not interfere with the operation of
the damper. The angles need not be attached to each other at the corners.

• Retaining Angle Attachment to Wall/Floor:


Two-Sided Angle Method: For two-sided angle installations the
retaining angles shall not be attached to the wall/floor (see
Figure 9). Min. 1 in.
Wall or
Floor

Retaining Overlap*

Single Sided Angle Method: For single side installations the Angle Retaining
Angle
Sleeve
retaining angles must be attached to the wall/floor
(see Figures 10-13). For metal stud partitions only, the single side 2 in
. M
Duct

mounting angle may be directly attached to the metal stud prior to


ax.

6 in
. M Damper
the installation of the drywall.
ax.

• Retaining angles must be attached to the partition using one 6 in


. M
ax.

of the methods shown below: 2 in


. M
ax.

- Drywall screws of a length such that the screw


engages the steel stud/track by 1/2 in. (13mm) (steel *only applicable for damper sizes above 36 in. x 36 in.

framing). Figure 9: Two-sided angle


- Drywall screws of a length such that the screw installation method
engages the wood stud by 13/4 in. (44mm) (wood
framing).
- Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm).
• A minimum of two connections per side are required. Additional connections made at a maximum
of 12 in. (305mm) O.C. for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers
greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than
6 in. (152mm) O.C.

Multi-Blade Fire and Combination Fire Smoke Dampers 7


Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......

Damper
Sleeve Damper
Sleeve

Stud or Runner Stud or Runner


Two layers of 1/2 in. UL
Classified Gypsum Two layers of 1/2 in. UL
Wallboard for 2 hour Classified Gypsum
rated walls. One layer Wallboard for 2 hour
for 1 hour rated walls rated walls. One layer
(see UL Rated Wall for 1 hour rated walls
Design for Additional (see UL Rated Wall
Details). Design for Additional
Details).
Angle Fastener
Angle Fastener

Figure 10: Single Side Angle With Steel Stud Wall - Figure 11: Single Side Angle With Wood Stud Wall
Angle Over Wallboard

Top Side
Damper
Sleeve Angle Fastener
Damper
Sleeve
Two layers of 1/2 in. UL
Classified Gypsum Masonry or
Concrete
Wallboard for 2 hour Masonry or
Wall
rated walls. One layer Concrete
Floor
for 1 hour rated walls
(see UL Rated Wall
Metal Stud Design for Additional
or Runner Details).

Angle Fastener

Damper
Sleeve

Figure 12: Single Side Angle With Steel Stud Wall - Figure 13: Single Side Angle With Masonry or
Angle Under Wallboard Concrete Wall and Floor

Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm])


Retaining angles used in conjunction with grille installations must be a minimum of 5⁄8 in. x 1 in. (15mm x 25mm)
16 gauge (1.5mm) steel. Space screws a maximum of 6 in. (152mm) O.C. and a maximum of 2 in. (51mm) from the
corners (minimum of 2 screws per side). See Figure 14 and Figure 15.
Note: Screws used to attach grille are allowed to penetrate reversed angle leg.

Damper
Sleeve
Damper Sleeve
#10 sheet metal screws
#10 sheet metal screws, 2 2 1/2 in. minimum spaced 6 in. on center
1/2 inches long, spaced 6 Stud or Runner and a maximum of 2 in. Stud or Runner
in. on center and a from the corners Two layers of 1/2 in.
maximum of 2 in. from the (minimum of 2 screws per UL Classified Gypsum
corners (minimum of 2 Two layers of 1/2 in. UL side). Screw into studs so Wallboard for 2 hour
screws per side). Screw Classified Gypsum as to avoid space rated walls. One layer
into studs so as to avoid Wallboard for 2 hour conflicts with the grille for 1 hour rated walls
space conflicts with the rated walls. One layer for
Angle Fastener (see UL Rated Wall
grille. 1 hour rated walls (see Design for Additional
Angle Fastener UL Rated Wall Design for
Details).
Additional Details).

Retaining Angle/Flange
Retaining Angle Grille (supplied
Grille (supplied by others) by others)

Figure 14: Wood Stud - Grille Figure 15: Metal Stud - Grille

8 Multi-Blade Fire and Combination Fire Smoke Dampers


Duct to Sleeve Connection
Sleeve Gauge and Connection Type Requirements
The size of the damper/duct determines the required
sleeve gauge and the required duct to sleeve Type of Duct
connection (see table to the right). The sleeve thickness to Sleeve
Sleeve Gauge Duct Dimension
must also not be less than the gauge of the connecting Connection
Permitted
duct. Any duct connection other than the breakaway
connections described below are considered rigid. 14 ga. (0.075 in.)
- 10 ga. (0.138 Rigid or
All duct sizes
in.) Breakaway
[2mm - 3.5mm]
36 in. (914mm) max. width
16 ga. (0.060 in.) 24 in. (610mm) max. Rigid or
[1.5mm] height Breakaway
24 in. (610mm) diameter
16 ga. (0.060 in.)
All duct sizes
[1.5mm]
18 ga. (0.048 in.) 85 in. (2159mm) wide and
[1.2mm] over
20 ga. (0.036 in.) 55 in. - 84 in. wide
[0.9mm] (1397mm - 2134mm)
Breakaway only
22 ga. (.030 in.) 31 in. - 54 in. wide
[0.76mm] (787mm - 1372mm)
24 ga. (0.024) 13 in. - 30 in. wide
[0.6mm] (330mm - 762mm)
26 ga. (0.018 in.) 12 in. wide and under
[0.46mm] (305mm)
See Breakaway Connection section for additional information.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.

Approved Breakaway Connections


All breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.
Transverse Joints
The transverse joints shown below are approved as breakaway connections.
• A maximum of two #10 (19mm) sheet metal screws on each side and on the bottom may be used. The
screws should be located in the center of the slip pocket and penetrate both sides of the slip pocket.
• Dampers up to 20 inches (508mm) high may use transverse joints on the top and bottom and Drive Slip
joints (see Figure 17) on the sides.

Plain “S” Slip Hemmed “S” Slip Double “S” Slip


Drive Slip Joint
Figure 17

Inside Slip Joint Standing “S” Standing “S” (Alt.)

Standing “S” (Alt.) Standing “S” Standing “S”


(Bar Reinforced) (Angle Reinforced)

Figure 16 - Transverse Joints

Multi-Blade Fire and Combination Fire Smoke Dampers 9


Duct Damper

Approved Breakaway Connections.... Type B

Round and Oval Duct Breakaway Connections


Wall or Floor
Type R and O
Factory furnished duct collars, type R and O, are also factory furnished
considered breakaway (see Figure 18). duct collars qualify
as breakaway Sleeve
Round or flat oval ducts connected to Type R or O damper
connections.
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
• Ducts up to 22 in. (558mm) wide (or dia.) and less
shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up
to and including 36 in. (914mm) wide (or dia.) shall Duct Damper
have five screws.

Type R, O
Figure 18: Type R and O Transition

Manufactured Flanged System Breakaway Connections


Flanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are
approved as breakaway connections when installed as illustrated (see Figure 19).

Fire Damper Sleeve

6 in. long metal cleat or 1/16 in.


max. thickness plastic cleat;
12 in. c-c (min. 1 per side)

Flanged system angles

(Attach per
manufacturer's
instructions)

3/8 in. bolts in


corners are optional

Neoprene or Butyl gasket


between all angles

Duct

Figure 19

Proprietary Flange System Breakaway Connections


(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF
addendum to the SMACNA Duct Construction Standards. Standard 6 in. (152mm) metal clip may be used with
spacing as shown in diagram (see Figure 20 & 21). 33⁄8 in. (9.5mm) metal bolts and nuts may be used to fasten
together corner pieces (see Figure 22).

Clip Spacing Std. Clip


Clip Spacing Std. Clip Length Duct End
Length 9 in. Flange
6 in. 6 9 in.
in. 6 in.
6 in. 6 in. 6 in.
60 in. Duct
60 in. Duct
Corner Piece
4 Req’d. 4Req’d.
7 in. 7 in. 7 in. 7 in.
48 in. Duct
48 in. Duct
3 Req’d.
3 Req’d.
5 in. 5 in.
5 in. 5 in. 3/8 in. bolt
Sleeve Duct 36 in. Duct (optional)
Sleeve Duct 3 Req’d. 36 in. Duct
5 in. 5 in.
3 Req’d.
24 in. Duct 5 in. 5 in.
2 Req’d.
Typical TDC/TDF joint 24 in. Duct
2 Req’d.
18 in. Duct &
Figure 20TDC/TDF joint
Typical Smaller
1 Req’d. C
L
Duct
18 in. Duct &
Smaller
1 Req’d. CL
Duct Figure 22
Figure 21

10 Multi-Blade Fire and Combination Fire Smoke Dampers


Actuator and Temperature Response Device Connections
Actuator Connections Temperature Response Device
Electrical and/or pneumatic connections to damper Connections
actuators should be made in accordance with wiring
RRL:The RRL (resettable link device) incorporates
and piping diagrams developed in compliance with
a single thermostat. When the thermostat
applicable codes, ordinances and regulations (see
temperature is reached the sensor interrupts power
Electrical Guidelines).
to the actuator and the actuator's spring return
mechanism causes the damper to close. Refer to
Figure 23 for wiring of the RRL thermostat.
OCI: The OCI (open or closed indicator) option contains
two single pole single throw switches used to
indicate the damper blade position. The switches
provide a positive open and closed signal and can
be used in conjunction with remote indicator lights.
Refer to
Figure 24 for wiring of the OCI option.
RRL/OCI: The RRL/OCI performs the function of an
RRL and OCI (see description above). Refer
Figure 23: RRL Wiring to Figure 25 for wiring of the RRL/OCI option.
TOR: The TOR (temperature override device) option
incorporates two thermostats with fixed settings
(usually 165°F [74°C] and 350°F [177°C]). The
primary sensor (the sensor with the lower
temperature setting) can be bypassed by an
external contact closure allowing the damper to
reopen until the secondary temperature is reached
(the sensor with the higher temperature setting).
See Figure 26.
 The TOR assembly contains two single pole single
throw switches used to indicate damper blade
position. The switches provide a positive open
Figure 24: OCI and closed signal and can be used in conjunction
with remote indicator lights. See Figure 26 for
wiring of the TOR thermostats and indicator
switches.
If either the TOR or the RRL is ordered with a
pneumatic actuator, an EP switch is required
with an appropriate electric power circuit to allow
the electric thermostat to control the pneumatic
actuator.
Ratings (Figure 23, 24, 25, & 26)
Integral Switch Type: Single Pole, double throw
Electrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac
1/2 Amp, 125 Vdc;
Figure 25: RRL/OCI
1/4 Amp 250 Vdc
5 Amps, 120 Vac “L” (lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165° F (standard primary sensor)
212° F (optional primary sensor)
250° F (secondary sensor )*
350º F (secondary sensor)*
* based on actuator temperature rating

Figure 26: TOR


Multi-Blade Fire and Combination Fire Smoke Dampers 11
Damper Commissioning and Periodic Testing
The International Fire Code (IFC) requires fire dampers to be maintained in accordance with NFPA standard 80 and
smoke dampers to be maintained in accordance with NFPA standard 105. NFPA 80 and 105 define the frequency
and method for periodically testing life safety dampers.
NFPA 80 & 105 do not require heat to be applied to a damper’s fusible link or thermostat during periodic testing.
Electric or pneumatic actuated dampers are required to be tested by temporarily removing electrical or pneumatic
power from the actuator to ensure the damper fully closes and then fully opens once power is restored. Mechanical
and gravity operated dampers utilizing a fusible link are required to be tested by removing the fusible link and
allowing the damper to fully close and then manually reopening the damper. Re-install the fusible link.
Greenheck’s life safety dampers shall not be tested by applying heat with uncontrollable heat sources (i.e. heat guns,
torches, etc.) as this can permanently damage the thermostat or other parts of the damper.

Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use
mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and
jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.

Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.

Symptom Possible Cause Corrective Action


Frame is 'racked' causing blades to bind Adjust frame such that it is square and plumb
on jamb seals
Actuator linkage loose Close damper, disconnect power, adjust and tighten
linkage
Damper does not fully
Defective motor Replace
open and/or close
Screws in damper linkage Damper installed too far into wall. Move out to line as
designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper
Maintenance)
RRL or TOR sensor Heat Push reset button located on backside of RRL or TOR
tripped
Damper does not No power supplied to the actuator Add power supply
operate

Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com

12 481318 • FSD DFD FSD-3xxV, Rev. 8, January 2020 Copyright 2020 © Greenheck Fan Corporation
Drive Arrangement Definition
On multi-blade dampers (except vertical blade and Face & Bypass), they are given a drive arrangement code
that helps describe the construction of the damper. The following breaks down what each number and letter
represents.

22-2FEL- 2
1 2 3 4 5 6 7
1 Number of sections wide

2 Number of sections high


Jackshaft

Damper Height
3 Number of actuators or manual quadrants

4 Who supplies the actuators or manual quadrants


F - Factory
Actuator or
C - Customer Supplied (field mounted) Manual Quadrant
5 Actuator or manual quadrant mounting
E - External
I - Internal
B - Both internal and external

6 Actuator or manual quadrant location


L - Left hand drive
R - Right hand drive
B - Both right and left Damper Width

7 Number of jackshafts

Vertical blade and face & bypass dampers are given a configuration ID number that helps describe the
construction of the damper. See the following examples:

Model Drive Arrangement


Prefix
AMD-23, 33, 42 AMD
AMD-42V VB
DFD-210, 230; DFDAF-310;
MLS
DFDAF-330; SEDFD-210
FBH & FBV FB
FSD, OFSD, CFSD, SMD, SEFSD,
SSFSD, SESMD, SSSMD series MLS
(except vertical blade models)
FSD-311V, SMD-301V VB
GFSD series GFSD
ICD series CC
IMO series MLS
MBD-15 & VCD series (except CC
vertical blade models)
VCD-xxV (vertical blade models) VB
Contained Actuator

Dampers less than 11 inches (279mm) that do not have compact configuration and that have contained actuator as required
will have the RRL, RRL/OCI, or TOR mounted on the side opposite the actuator.

RRL, RRL/OCI, or TOR


RRL, RRL/OCI, or TOR opposite actuator
opposite actuator
Components contained
Components contained within 1 1/2 in. of sleeve
within 1 1/2 in. of sleeve top and bottom
top and bottom

Sleeve Length
Sleeve Length Damper
Damper Location
Location

RRL, RRL/OCI, or TOR


RRL, RRL/OCI, or TOR
Actuator Parallel
Actuator Parallel

©2022 Greenheck Corporation


Contained Actuator Rev. 3 April 2022
BR-30 Series
Barometric Relief Dampers
Vertical Mount - Horizontal Airflow

Application
The BR-30 series is an eccentrically pivoted backdraft damper for
low velocity systems. BR-30 series is a vertical mounted damper
and designed to allow horizontal airflow and prevent reverse
airflow. The blade is formed aluminum which increases sensitivity
and reduces blade mounted counterbalance weights. On-blade
counterweights are provided to fine tune start-to-open and full
open blade operation. Ball bearings minimize friction.
Recommended Applications
• Gravity hood intake and exhaust
• Stairwell pressurization
• Room pressurization
• Ductwork outlets
Poor Applications
• Propeller fan outlets (high velocity)
• Centrifugal fan outlets (high velocity)
• Building pressurization (sensitive to wind)
• Pressure relief exceeding 0.3 in. wg (0.075 kPa) *W & H dimensions furnished approximately 1⁄4 in. (6mm) undersize.

Ratings
1.5 in. 1.5 in.
Back Pressure
2.0 in. wg (0.5 kPa)
Start-to-Open Pressure
0.05 in. wg (.01 kPa)
4 3/8 in.
Velocity MAX

2,000 fpm (10.2 m/s) 1 in.


MAX
Temperature Airflow
180°F (82°C)

Construction
Standard Optional
304SS,
Frame Material Galvanized Steel
Aluminum
5 in.
Frame Thickness 16 ga. (1.5mm) -
No Flange (BR-30) - BR-30 BR-31 BR-32
Frame Type Flange on Discharge (BR-31) - No Flange Flange on Flange on
Flange on Intake (BR-32) - Discharge Intake
Blade Material Aluminum -
Blade Seal TPE None
Size Limitations
Blade Thickness 0.063 in. (1.6mm) -
Maximum Size
Minimum
Axle Plated Steel 316SS WxH
Size Single Section Multiple Sections
Axle Bearings Galvanized Ball Acetal w/SS Ball
Inches 8x6 48 x 74 96 x 148
Linkage Material Galvanized Steel -
mm 203 x 152 1220 x 1880 2438 x 3759
Jamb Seal None EPDM
Blade mounted with -
Counterbalance adjustable weights
Baked Enamel, Feature
Paint Finishes None Hi Pro Polyester, • Selectable start open from .05 to .30 in. wg
Industrial Epoxy (0.012 kPa - 0.075 kPa).

BR-30 Series May 2022


BR-30 Series
Performance Data Barometric Relief Dampers

Performance data results from testing a 12 in. x 12 in. and 36 in. x 36 in. (305mm x 305mm and 914mm x 914mm) in accordance with
AMCA Standard 500-D using Figure 5.3 (fully ducted), 5.2 (ducted exhausting into an open area), and 5.5 (plenum mounted). All data
has been corrected to represent standard air density at 0.075 lb/ft3 (1.201 kg/m3).
Pressure drop data shown is based on minimum start open pressure. Higher start open pressure will result in different pressure drop.

Damper Size Damper Size


12 in. x 12 in. 36 in. x 36 in.
(305mm x 305mm) (914mm x 914mm)
2.0 2.0

5.5 5.5
1.0 1.0
.9 .9
.8 .8
5.2 5.2
.7 .7
.6 .6
.5 .5
5.3 5.3
Pressure Drop (in. wg)

Pressure Drop (in. wg)


.4 .4

.3 .3

.2 .2

.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03
100 200 300 400 500 600 800 1000 2000 3000 100 200 300 400 500 600 800 1000 2000 3000
700 900 700 900

Velocity Velocity
(fpm) (fpm)

Document Links

Installation Instructions Backdraft Catalog Damper Product Selection Guide

Specifications Damper Warranty

Copyright ® 2022 Greenheck Fan Corporation


BR-30 Series, R10, May 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice
Document Number 469420
BR Series Counterweight Adjustments

Installation, Operation and Maintenance Manual


Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.

Table of Contents
General Information ...................................... 1
Pre-Installation Guidelines ............................ 2
Counterweight Adjustment Procedure .......2-5
• Counterbalance Adjustment for
BR-1x Series........................................... 3
• Counterbalance Adjustment for
BR-3x Series........................................... 4
• Counterbalance Adjustment for
BR-4x Series .......................................... 5
Maintenance ................................................. 6

Receiving and Handling Safety Warning


Upon receiving dampers, check for both obvious Improper installation, adjustment, alteration, service
and hidden damage. If damage is found, record all or maintenance can cause property damage, injury
necessary information on the bill of lading and file or death. Read the installation, operating, and
a claim with the final carrier. Check to be sure that maintenance instructions thoroughly before installing
all parts of the shipment, including accessories, are or servicing this equipment.
accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is
highly recommended. Do not store at temperatures in
excess of 100°F (38°C).

This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.

BR Series 1
Pre-Installation Guidelines Counterweight Adjustment
The basic intent of a proper installation is to secure Procedure for BR Models
the damper into the opening in such a manner as to Dampers are shipped from the factory with the frame
prevent distortion and disruption of damper operation. flange location and flow direction as ordered. Location
The following items will aid in completing the damper and size of both counterbalances (blade edge,
installation in a timely and effective manner. adjustable blade weights) are dependent upon the
1) Check the schedules for proper damper locations flow direction and damper size. The damper must be
within the building. Visually inspect the damper for mounted square and plumb and must operate freely
damage. before any weight adjustments are performed. Contact
2) Lift or handle damper using sleeve or frame. Do not Greenheck for required modifications to change the flow
lift damper using blades or linkage. When handling directions.
multiple section assemblies, use sufficient support to The following instructions should be followed when
evenly lift at each section mullion (see Figure 1). Do attempting to adjust counterweights on the BR series
not drag, step on, apply excessive bending, twisting, dampers. Figure 2, 2A, and 2B shows the typical
or racking. location of the adjustable counterweight assembly.
Depending on the size of the damper and specified start
open pressure, the damper may have more than one
counterweight assembly.

Spreader Bar

Adjustable
Attachments
Counterweight
Assembly

Multi section dampers

Figure 1- Supports for lifting a


multi-section damper

Airflow
Figure 2
3) Do not install screws in damper frame that will BR-1x series
interfere with damper blades and prevent them from
opening and/or closing.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper Adjustable
Counterweight
must not be squeezed or stretched into the duct Assembly
opening. Out of square, racked, twisted or misaligned Airflow

installations can cause excessive leakage and/or


prevent free operation.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such
foreign materials include but are not limited to:
a) Mortar dust Figure 2A
b) Drywall dust BR-3x series
c) Firesafing materials
Airflow

d) Wall texture
e) Paint overspray
7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper.

Figure 2B Adjustable
Counterweight
BR-4x series Assembly

2 BR Series
Counterbalance Adjustment for BR-1x Series: Horizontal Mount - Vertical Up
Airflow
Figures 3 & 4 show the components of a typical
adjustable counterweight assembly. BR-1X series
damper with a short height may have a different style
blade and a trimmed mounting bracket. The adjustment
procedure is the same for both styles of blades.
The blade edge counterweight (Figure 4) is factory
set and not intended for field adjustment. For vertical
up airflow, all adjustments should be made in the
adjustable counterweight assembly.
When adjusting the counterbalance weights, you will Figure 3 Adjustable
counterweight
need to adjust the full open pressure and start open assembly
pressure.
Adjusting Full Open Pressure with Closing Force
Adjusting the closing force will also affect the full open
pressure. Figure 4 shows the blade in the full open
position. Additional weights can be added to increase Damper
Blade
the closing force. Removal or trimming of weight will
reduce the closing force. After adjustment, verify blades Counterweight
close under no airflow from the full open position. Adjustment
Bracket
Increase the closing force if the blades fail to close. Counterbalance
Weights
Adjusting Start Open Pressure
When the blades are in the closed position, the
adjustable weights are used for the start open pressure
of the damper. Sliding the weights toward the blade
seal will increase the start open pressure and sliding
Blade Edge
the weights toward the blade edge counterweight will Counterweight
decrease pressure. (Figure 5)
Figure 4 - Adjustable
If sliding the weights to the furthest left position (toward counterweight
the blade seal) does not provide a high enough start assembly detail
open pressure, additional weights can be added. In this
case, the closing force will also increase.
Dampers are factory adjusted to the start open
pressure, based upon your order, for the specified flow
direction. Typically, a minimum of one weight plate
will be used to keep blades closed, although only the
mounting bracket may be sufficient for small damper
sizes. Consult factory for plate quantity and sizing if an
Increases Start Decreases Start
elevated start open pressure is required. Open Pressure Open Pressure
Final Adjustment Check Figure 5: Counterweight adjustment for start open
pressure. Blade is shown in full close position
After adjusting the counterweights, verify that no
interference occurs between the counterweights and
the adjustment blades. If any interference, adjust
counterweights. Also verify that the damper blades
close under no airflow from the full open, 1⁄2 open, and
1
⁄4 open positions. If blades do not close, adjust the
weights as required.

BR Series 3
Counterbalance Adjustment for BR-3x Series:
Vertical Mount - Horizontal Airflow
Figure 6 details the components of a typical adjustable Blade Edge
Counterweight
counterweight assembly. Dampers with a short
height may have a different style blade and a trimmed
mounting bracket. The adjustment procedure is the
same for both styles of blades.
Counterbalance
The blade edge counterweight (Figure 6) is factory set Weights

and not intended for field adjustment. For horizontal


airflow, all adjustments should be made in the Counterweight
Adjustment bracket
Damper Blade
adjustable counterweight assembly.
When adjusting the counterbalance weights, you will
need to adjust the full open pressure and start open
Figure 6 - Adjustable
pressure. Both steps will need to be done. counterweight assembly
Adjusting Start Open Pressure detail

When the blades are in the closed position (Figure


6), the adjustable weight are used for the start open
pressure of the damper. Additional weights can be
added to increase start open pressure and removal or
trimming of weights will reduce start open pressure.
After adjustment, verify blades close under no airflow
form the 1⁄4 open position. If the blades fail to close,
additional weight is required.
Adjusting Full Open Pressure and Closing Force
Adjusting the closing force will also affect the full open
pressure. Figure 7 shows the blade in the full open
position. If blades hang open or more closing force is
desired, slide weights toward the bottom of the bracket.
If the blades close too fast or less closing force is
desired, move weight toward the top of the bracket. Decreases
Closing
Force
Dampers are factory adjusted to the start open Increases
Closing

pressure, based upon your order, for the specified flow Force

direction. Typically, a minimum of one weight plate Bottom of


Bracket
will be used to keep blades closed, although only the
mounting bracket may be sufficient for small damper
Figure 7: Counterweight adjustment in the full open
sizes. Consult factory for plate quantity and sizing if an position
elevated start open pressure is required.
Final Adjustment Check
After adjusting the counterweights, verify that no
interference occurs between the counterweights
and the adjacent blades. If any interference, adjust
counterweights. Also verify that the damper blades
close under no airflow from the full open, 1⁄2 open, and 1⁄4
open positions. If blades do not close, adjust weights as
required.

4 BR Series
Counterbalance Adjustment for BR-4x Series:
Vertical Mount - Horizontal Airflow
Figure 8 details the components of a typical adjustable Blade Edge
counterweight assembly. Dampers with a short Counterweight Counterweight
Adjustment
height may have a different style blade and a trimmed Bracket
mounting bracket. The adjustment procedure is the
same for both styles of blades.
The blade edge counterweight (Figure 8) is factory
set for the specified start open pressure. For vertical
down airflow, minor adjustments can be made in the
adjustable counterweight assembly, then changes to the
blade edge weight would be required. Consult factory Counterbalance
for assistance in adjusting blade edge weight. Weights

When adjusting the counterbalance weights, you will


need to adjust the full open pressure and start open
pressure. Both steps will need to be done.
Figure 7 - Adjustable
Adjusting Full Open Pressure and Closing Force counterweight assembly detail
Adjusting the closing force will also affect the full open
pressure. Figure 8 shows the blade in the full open
position. Additional weights can be added to increase
the closing force. Removal of trimming of weights
will reduce the closing force. After adjustment, verify
the blades close under no airflow from the full open
position. Increase the closing force if the blades fail to
close.
Adjusting Start Open Pressure
When the blades are in the closed position, the
adjustable weights are used for the start open pressure
of the damper. Sliding the weights toward the blade
edge counterweight will increase the start open
pressure and sliding the weights toward the blade seal
will decrease pressure (Figure 9).
If sliding the weights to the furthest left position (toward Increases Decreases
the blade edge counterweight) does not provide a high Open Pressure Open Pressure
enough start open pressure, additional weight to the Figure 8: Counterweight adjustment for start open
blade edge counterweight would be required. pressure. Blade is shown in full close position.
Dampers are factory adjusted to the start open
pressure, based upon your order, for the specified flow
direction. Typically, a minimum of one weight plate
will be used to keep blades closed, although only the
mounting bracket may be sufficient for small damper
sizes. Consult factory if an elevated start open pressure
is required.
Final Adjustment Check
After adjusting the counterweights, verify that no
interference occurs between the counterweights
and the adjacent blades. If any interference, adjust
counterweights. Also verify that the damper blades
close under no airflow from the full open, e, and 1⁄4 open
positions. If blades do not close, adjust weights as
required.

BR Series 5
Damper Maintenance
Greenheck's dampers are designed to be trouble free and hassle free under normal operation. Dampers are to
installed square and straight so as to prevent binding during operation. the following annual damper maintenance
suggestions will help to insure proper damper operation and increase the life expectancy of the damper.
Foreign Matter Over the course of time, dirt and grime may collect on damper surfaces. The damper surfaces
should be cleaned to prevent hindrance to airflow.
Moving Parts Make sure that parts such as linkage, bearings, blades, etc. that are intended to move freely, can do
so. Lubricating these components can prevent possible rusting and unnecessary friction increase.
Use only a moli-spray oil or similar graphite based oil as regular lubricating oil will attract dirt.
Bearings. Synthetic, oil impregnated, and ball bearings (without grease fittings) do not require
lubrication. Ball bearings with grease fittings require only minimal grease.
Closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades
with each other or with the frame.
Operation While operating the damper through its full cycle, check to see that the blades open and close
properly. If there is a problem, check for loose linkage, especially at the actuator. Tighten the linkage
where required.

Notes

6 BR Series
Notes

BR Series 7
Notes

Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts : 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com

GFC 469420 • BR Series, Rev. 6, September 2018 Copyright 2018 © Greenheck Fan Corporation

You might also like