Zero adjustment the air DP-transmitter

The way to get the air measurement back to correct value is to perform a zero
calibration of the DP-transmitter measuring the amount of combustion air.
The transmitter is calibrated with the fan running, and the inlet vanes fully closed.

The zero adjustment is set by:


Step A: Select mode 7 using the "M" button.
Step B: Set zero with the [↑] and [↓] buttons simultaneously.
Step C: Save with "M" button.

Now the value indicated should be very close to 0% and more combustion air will be
supplied to the combustion and the boiler should stop smoking