GST I-9319 Intelligent Addressable Zone Interface Module Datasheet

The I-9319 Addressable Zone Monitor Unit is designed to connect with conventional detectors and occupy one address on the fire alarm control panel loop. It monitors the connection of detectors and transmits fire or fault signals to the control panel. The unit has plug-in terminals to connect to the loop and power supply. It can monitor up to 15 conventional detectors and its address can be programmed with a handheld programmer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
962 views2 pages

GST I-9319 Intelligent Addressable Zone Interface Module Datasheet

The I-9319 Addressable Zone Monitor Unit is designed to connect with conventional detectors and occupy one address on the fire alarm control panel loop. It monitors the connection of detectors and transmits fire or fault signals to the control panel. The unit has plug-in terminals to connect to the loop and power supply. It can monitor up to 15 conventional detectors and its address can be programmed with a handheld programmer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Addressable Zone Monitor Unit Overview

I-9319

Addressable Zone Monitor Unit

Features
 Cable checking.
 Occupying one address. It can be modified through 548m/03
P-9910B programmer or fire alarm control panel
(FACP).
 Monitoring power supply.
0832-CPD-1958
 Two indicators for fire and fault conditions
separately.
If the cable conduit is inside the wall, the base is
 Plug-in structure.
installed onto the back box (Fig. 2). If the cable
 Standard: EN 54-18:2005. conduit is on the surface of the wall, the B-9310
Back Box is available.
Description B-9310
Back Box
Conduit Back Box Conduit
I-9319 Addressable Zone Monitor Unit (the unit) is
the Unit the Unit
designed to connect with conventional detectors,
occupying one address. When any device in the loop
reports fire signal, the unit will transmit the signal to the
FACP which generates fire alarm and displays the
address of the unit.
The end of the unit is connected with P-9907 Active
End of Line Unit, if the output circuit is broken, the unit
will transmit the fault signal to FACP and then the FACP
displays the unit address. When a field device is Fig. 2 Fig. 3
removed, the unit will report fault without affecting Note the upward arrow for mounting direction (Fig. 1).
normal operation of other field devices.
Application
Connection and Cabling
Address can be set in field through P-9910B
Fig. 1 shows terminals of the unit. programmer. The output loop can connect up to 15
65
conventional devices. Detectors, such as C-9102
Photoelectric Smoke Detector, C-9103 Rate of Rise and
o- o+
Fixed Temperature detector can be used together.
8 7 R 2 1 1. When the unit connects with conventional detector
10
5

9 10 15 16 in series, the detector base should connect with an


D1 D2 I-9319 Z1 Z2
1N5819 diode, and P-9907 must be connected to the
output end. P-9907 can also be used as the base of a
Bottom Cover(Remove Top Cover And Terminal Plate)
conventional detector. System connection is shown in
10 Fig. 4.
Fig. 1
Diode
Diode
Z1, Z2: Connecting with loop of FACP, non-polarized.
D1, D2: Connecting with 24VDC power, non-polarized.
Addessable Zone Mornitor Unit

O-, O+: Polarized output. O+


Recommended Cabling
I-9319

2
1.0mm or above fire cable for each terminal, subject to
O-
local codes. The different color cables for O- and O+.
Conventional Detector Conventional Detector P-9907 Active End of Line Unit
Installation
Fig. 4
The unit is simply plugged onto the base after
2. When P-9907 Active End of Line Unit is not used as
corresponding terminals are connected.
detector base, a cover should be added, the system
connection is shown as Fig. 5.

30303457 Issue 4.08


Addressable Zone Monitor Unit
Diode Diode
Specification

O+
Operating Voltage Loop: 24V (16V~28V)
Power:24VDC(20VDC~28VDC)
I-9319

O-
Standby Current Loop≤0.5mA Power≤10mA
Action Current Loop ≤5mA Power≤60mA
Conventional Detector Conventional Detector P-9907 Active End of Line Unit
Programming Electronically addressed. Code
Fig. 5 Method range is within 1~242.
3. If the output end connects with end-of-line resistor, Indicators Alarm LED: illuminates red in
the diode will not be added to the detector base, system fire condition.
connection is shown in Fig. 6. Fault LED: illuminates yellow in
fault condition.
Addressable Zone Monitor Unit

Ingress Protection IP30


O+ Rating

4.7kΩ Resistor
-10℃~+55℃
I-9319

Operating
Temperature
O-
Relative Humidity ≤95%, non condensing
Conventional Detector Conventional Detector Material and Color ABS, white (RAL9016)
Fig. 6 of Enclosure
Dimension 120mm×80mm×43mm
Accessories and Tools (L×W×H) (with base)
Weight About 195g (with base)
Model Name Remark
Limited Warranty
P-9910B Hand Held Order separately
GST warrants that the product will be free of charge for
Programmer
repairing or replacing from defects in design, materials
B-9310 Back Box Order separately and workmanship during the warranty period. This
warranty shall not apply to any product that is found to
have been improperly installed or used in any way not in
WEEE Information
accordance with the instructions supplied with the
2012/19/EU (WEEE directive): Products product. Anybody, including the agents, distributors or
marked with this symbol cannot be employees, is not in the position to amend the contents
disposed of as unsorted municipal waste of this warranty. Please contact your local distributor for
products not covered by this warranty.
in the European Union. For proper
recycling, return this product to your local supplier upon
the purchase of equivalent new equipment, or dispose
of it at designated collection points

This Data Sheet is subject to change without notice. Please contact GST for more information or questions.

Gulf Security Technology Co., Ltd.


No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn
30303457 Issue 4.08

30303457                                                                                    Issue 4.08 
548m/03
30303457                                                                                    Issue 4.08 
O-
O+
Addressable Zon