Professional Documents
Culture Documents
Recent Progress in Liquid Desiccant Dehumidification and Air-Conditioning ... A Review - Chen, Riffat, Et Al
Recent Progress in Liquid Desiccant Dehumidification and Air-Conditioning ... A Review - Chen, Riffat, Et Al
a r t i c l e i n f o a b s t r a c t
Keywords: This paper presents a literature review on the recent research progress in liquid desiccant dehumidification and
Dehumidification air conditioning systems. The physical features of various liquid desiccant materials and their dehumidification
Hybrid system performances have been summarized. With the aim to improve the dehumidification characteristics, mixed sol-
Liquid desiccant
vents desiccants have become research hot topics recently. Various types of dehumidifiers and their integration
Model
with liquid desiccant dehumidification system have been reviewed. The combination of liquid desiccant dehumid-
Review
ification system with solar collector, vapour compression system, heat pump system, CHP system, etc. have been
grouped and compared. It is shown that the majority of the recent research work for liquid desiccant dehumid-
ification systems has concentrated on numerical simulations, a considerable amount of works are still required
for the practical investigations of innovative material (mixed solvents) and hybrid systems.
∗
Corresponding author at: Centre for Renewable Energy Systems Technologies (CREST), Wolfson School of Mechanical, Electrical and Manufacturing Engineering,
Loughborough University, Leicestershire LE11 3TU, United Kingdom.
E-mail addresses: x.j.chen@lboro.ac.uk (X. Chen), saffa.riffat@nottingham.ac.uk (S. Riffat).
https://doi.org/10.1016/j.enbenv.2019.09.001
Received 25 June 2019; Received in revised form 23 August 2019; Accepted 1 September 2019
Available online 15 October 2019
2666-1233/© 2019 Published by Elsevier B.V. on behalf of Southwest Jiaotong University. This is an open access article under the CC BY-NC-ND license.
(http://creativecommons.org/licenses/by-nc-nd/4.0/)
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 1. Schematic diagram of a typical liquid desiccant integrated cooling system [19].
wastage. Desiccant, as an alternative, could dehumidify the air with contaminants in the air during the dehumidification process [11].
the help of its hygroscopic properties. Therefore, the energy required Hence, the absorption process has the potential to remove biological
for a desiccant dehumidification process is about 30% less compared pollutants such as bacteria, fungi and viruses so improving indoor
with conventional vapour compression system. Desiccant materials air quality [12,13]. In addition, liquid desiccant cooling system is
used can be either solid (e.g., silica gel, molecular sieve) or liquid applied extensively in greenhouse to provide controlled temperature
(e.g., lithium chloride (LiCl), calcium chloride (CaCl2 )). Liquid and humidity for food production.
desiccants have a number of merits compared with solid desiccants.
The ability of liquid desiccant to hold moisture is normally greater Previously published review papers are focusing on summarizing the
than that of solid desiccants. Besides, the regeneration temperature advances of liquid desiccants dehumidification in particular respects
of the liquid desiccant is mostly between 40 °C and 70 °C [6], which of modelling method [14], material [15], dehumidifier development
is much lower than that required by the solid desiccant (in the range [16] and the associated contributions for indoor air quality improve-
of 60–115 °C) [7]. Compared with solid desiccant cooling system, ment [11]. Some of the previous published reviews [17,18] are dated
liquid desiccant requires a lower temperature heat for regeneration back to 10 years ago and urgently needs updating. Therefore, this
(50–90 °C) [8]. In contrast, the regeneration process of a solid paper aims to provide a comprehensive update on the research progress
desiccant system often has to be driven by combustion heat of, and development in liquid desiccant cooling system (LDCS) in the last
for example, natural gas [6]. Moreover, the cost of manufacturing decade, with more than 180 research papers summarized and grouped.
a liquid desiccant system is lower than that of a solid desiccant The structure of this review paper is summarized below: The first part
wheel. This makes it possible for the liquid desiccant cooling system focuses on recent development trends in liquid desiccant materials
to be linked with low grade heat sources (solar energy or waste and their characteristics, with unique summary of recent advances in
heat). As the key element in a desiccant cooling system, desiccant mixed and composite desiccant materials. The second part discussed
is a material that has a significant capacity for holding water. The various types of dehumidifier and system configurations, with a brief
moisture transfer between the air and the desiccant is generally summary of mostly cited researches and their working conditions in a
driven by the difference in vapour pressure. When the vapour comprehensive table. The third part of this review plays importances
pressure of the air is greater than that of the desiccant, the moisture on recent experimental and theoretical investigations of desiccant
will be transferred from the air to the desiccant, and vice versa. cooling systems including (i) integrated with vapour compression
Also, due to the relatively lower cost of liquid desiccant material, systems, (ii) evaporative cooling systems, (iii) heat pump systems and
the liquid desiccant system can lead to a shorter payback period. other innovative systems. Linkages and comparisons between different
(2) Environment: The refrigerants such as HFCs, used in vapour com- research cases are presented, and similar study concepts are classified
pression system have relatively high Global Warming Potentials and briefly summarised in Tables, which provide good guidance and
(GWP) [9]. The possible leakage of these refrigerants will con- easy accessibility for future research works.
tribute to global warming. The conventional vapour compression
system is normally driven by electricity with the consumption of 2. Recent progress in liquid desiccant materials
primary energy (fossil fuel, coal, etc.), which poses threats to the
ever-increasing global energy shortage. With the ability to be driven As the key element, liquid desiccant materials play important roles
by low grade energy (such as solar energy, industrial waste heat, in the overall performance of the desiccant cooling system. Therefore,
etc.) in an environmentally friendly way, the desiccant cooling it is crucial to analyse the characteristic of the liquid desiccants in
system has become an important alternative for providing humidity order to select the best candidates for the system. Two types of liquid
control and cooling effect, so it is helpful in reducing greenhouse desiccant materials, including aqueous solution of organic solvent
gas emissions. Carbon reductions of 33.2% with electricity saving such as triethylene glycol, diethylene glycol and ethylene glycol, and
up to 18.9% could be achieved for a hybrid liquid desiccant cooling inorganic aqueous salt solutions such as calcium chloride, lithium
system, according to Sanaye and Taheri [10]. chloride, lithium bromide, and calcium bromide, are widely used
(3) Social: The third advantage of liquid desiccant dehumidification [20]. Triethylene glycol (TEG) solution was utilized in a solar driven
and air-conditioning systems is to remove indoor air pollutants and liquid desiccant cooling system by Oberg and Goswami [21] and
improve the air quality. An additional benefit of the desiccants Abdul-Wahab et al. [22]. Although the experimental results proved
materials is that they are capable of absorbing inorganic and organic TEG to be a good desiccant for the cooling system, due to the fact that
107
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Table 1 and CaCl2 solutions are compared theoretically by Lazzarin et al. [35].
Experimental vapour pressure of aqueous salt solutions [24]. The author concluded that based on the same temperature and crystal
Salt Concn (%) Vapour pressure (kPa) temperature, LiBr showed better heat and mass transfer performance
than that of CaCl2 solution. In order to avoid the crystallization inside
298.15K 303.15K 308.15K 313.15K
a liquid-to-air membrane energy exchanger, Namvar et al. [36] decided
LiCl [25] 30 2.2 2.79 to use magnesium chloride (MgCl2 ) as the desiccant solution. The exper-
40 1.79 2.41
imental results showed that the MgCl2 concentration rate was less than
40 [24] 1.48 1.74 2.13 2.41
44 1.47 2.1 saturation concentration (35.9%) which led to no crystallization risk.
LiBr [25] 31 3.11 3.67 Lithium bromide (LiBr) solution offers similar characteristics during
38 2.9 3.47 dehumidification and regeneration process, but the cost of LiBr is about
40 [24] 2.45 2.82 3.08 3.35 20% higher than LiCl. Liu and Jiang [37] performed experimental tests
44 2.57 3.14
for air mass flow rate between 0.24–0.48 kg/s and inlet air temperature
CaCl2 [26] 35 2.78 3.36
40 2.55 3.13 25.4–38.8 °C, and compared the mass transfer performance of LiBr and
40 [24] 2.1 2.53 2.86 3.14 LiCl. The authors concluded that using the two desiccants, the COPs of
43 2.2 2.8 the liquid desiccant cooling system were quite similar (0.45 for LiBr and
0.47 for LiCl). In order to predict the humidification efficiency [7] of
the system, a mathematical model for an adiabatic counter flow dehu-
TEG has a boiling temperature very close to water, TEG can easily midifier was developed by Kornnaki et al. [38], using three different
evaporate into the processed air. Therefore, the liquid carryover issue desiccant solutions (LiCl, CaCl2 and LiBr). At the inlet air temperature
makes TEG unsuitable for liquid desiccant cooling application. and humidity of 30–42 °C and 13.0 g/kg, the absorption efficiency was
Inorganic salt solutions including calcium chloride, lithium chloride, 0.145, 0.137 and 0.125 respectively for LiCl, LiBr and CaCl2 .
lithium bromide and potassium formate are widely studied and applied Conde [39] reviewed a number of measured data from literature,
in various liquid desiccant dehumidification systems. The performance and proposed a series of interpolating equations for the following
of a desiccant dehumidification process depends greatly on its vapour properties of LiCl and CaCl2 : solubility boundary, vapour pressure,
pressure. The difference in the partial pressure of water in the air and density, surface tension, dynamic viscosity, thermal conductivity,
the vapour pressure of water above the desiccant solution is the major specific thermal capacity and differential enthalpy of dilution. These
driving force for the moisture absorption process in the dehumidifier or equations could be used as the basis for computer-assisted design
the moisture desorption process in the regenerator [23]. The lower the of liquid desiccant cooling system. Due to the fact that some of the
vapour pressure, the drier the outlet air and thus the better a desiccant empirical expressions have limited accuracy, artificial neural network
performs. Table 1 shows the experimentally obtained vapour pressure (ANN) method was applied by Gandhidasan et al. [40] to predict a
under various temperature conditions for LiCl, LiBr and CaCl2 . wide range of vapour pressure of CaCl2 , LiCl and LiBr. The results
validation showed good agreement for LiCl and LiBr compared with
2.1. Halide salt solutions data published in the literature. Other types of halide salts have been
investigated as well. Namvar [36] used magnesium chloride (MgCl2 )
Triethylene glycol was the earliest used halide salt solution. How- as desiccant material for a liquid desiccant system, and found that the
ever its application is limited by high viscosity, which could bring working concentration of MgCl2 is less than saturation concentration
the problem of unstable operation owing to the liquid residence. It (35.9%), which would avoid the problem of crystallization.
was revealed in [27] that glycol is volatile due to its low surface
vapour pressure. As the result, glycol is not suitable for air-conditioning 2.2. Organic acid and ionic liquids
systems as the system cost could be raised dramatically due to glycol
being volatilized into the conditioned space. Furthermore, Rafique et al. The aforementioned three salts have the disadvantages of corrosive
[15] pointed out that the dew point of air reached by using 96% tri- feature, which can cause significant damage to air conditioning system.
ethylene glycol can be achieved by applying 42% LiCl, meaning molar As a less corrosive and more environmentally friendly solution, potas-
concentration of glycol in the air would be 1% that of the water vapour. sium formate (KCOOH) solution has recently been applied in desiccant
As the result the annual loss of triethylene would be significantly high. cooling unit. KCHOOH solution has low toxicity and viscosity, and they
Lithium chloride (LiCl), Calcium chloride (CaCl2 ) and Lithium are neither corrosive nor volatile [41]. Furthermore, at high solution
bromide (LiBr) are three of the most widely used halide salt desiccant concentration potassium formate can outperform conventional liquid
solutions recently. Zuber et al. [28], Sun et al. [29] and Ahmed et al. desiccant by promoting a high degree of vapour pressure depression
[30] measured thermodynamic properties of these desiccants, and they while maintaining a crystallisation temperature of less than 0 °C [42].
found that among these halide sailts, lithium chloride (LiCl) solution is Using KCOOH solution as the desiccant, Elmer et al. [41] reported
the most stable liquid desiccant, which offers the lowest water vapour a novel integrated system in which the regenerator, dehumidifier
pressure and dehydration concentration 30–40%. However the cost of and evaporative cooler were combined into a single heat and mass
LiCl is relatively high. Using LiCl solution as the liquid desiccant, the exchanger. With the inlet air temperature between 30 °C and 35 °C,
dehumidification and regeneration performances of the systems were and relative humidity of 51–70%, the moisture removal rate was in
studied by Zhang et al. [31,32], Fumo and Goswami [20]. Chen et al. the range of 0.15–0.4 g/s, with the average system COP of 0.72. Longo
[33] studied a heat pump driven desiccant cooling system with LiCl and Gasperella [6] experimentally tested the performances of a liquid
solution as the desiccant. With the inlet air temperature and humidity desiccant cooling system using LiBr, LiCl and KCOOH solutions. The
of 25.4–27.8 °C and 13.9–18.2 g/kg, the temperature drop could reach authors summarized that LiCl and LiBr solutions demonstrated better
between 5.2 and 7.4 °C, with average COP of 4.0. dehumidification performance compared with KCOOH solution, which
Calcium chloride (CaCl2 ) solution is the cheapest and most widely performed better in regeneration process. Qiu et al. [43] conducted ex-
available desiccant, but it has the disadvantages of being unstable, perimental investigation of a liquid desiccant cooling system driven by
depending on the air inlet conditions and the solution concentration flue gas waste heat from a biomass boiler. With KCOOH concentration
rate. The numerical investigations on the heat and mass transfer ratio of 47% and the air flow rate of 24000l/min, the average air RH
performance of a cross flow dehumidifier using 40% concentration of decrease was around 12.9–13.3%.
CaCl2 solution in the liquid desiccant systems were experimentally Longo and Gasparella [44] examined the energy saving effect of
studied by Dai and Zhang [34]. The mass transfer performance of LiBr three different liquid desiccants (LiCl, KCOOH and LiBr) in a real flower
108
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
greenhouse application during three years’ time span. The greenhouse solvent solution, the moisture removal rate was 5 times higher than the
equipped with such desiccant based air conditioning system exhibited single CaCl2 solution under the inlet air conditions of 27 °C.
the energy saving of 9.6%, 11.7% and 15.1% respectively for using Due to the fact that the deliquescence property of brine solution
the desiccants of LiCl, KCOOH and LiBr. The authors concluded that such as LiCl and CaCl2 will lead to the reduction of desiccants in the
as a cheap and biodegradable desiccant, KCOOH presented a vapour life cycle, researchers started to analyse composite desiccants [53].
pressure higher than other conventional desiccants. However, KCOOH Composite desiccant usually are formed by confining salts into porous
could not dehumidify air with low moisture content, while LiBr host adsorbents, thereby the limited dehumidification capacity of silica
outperformed KCOOH in this case. gel and the corrosive features of salt solutions could be eliminated [54].
Ionic liquids (ILs) in the form of organic cation and inorganic anion, Chua [55] conducted modelling and experimental investigations on
are generally molten salt at room temperature [45]. The advantageous the heat and mass transfer performance for composite desiccants based
features of non-corrosive, non-combustible and good thermal and dehumidification system. The composite desiccants selected were silica
chemical stability [45] make ILs possible alternatives to other liquid gel-CaCl2 , silica gel-LiCl and silica gel-PVOH. With inlet air temperature
desiccants. However, limited research works have been conducted on around 26–34 °C, and the processed air velocity of 1.33–2.21 m/s, the
experimentally analysing the system performance of ILs integrated moisture removal rate of silica gel- LiCl was 4.5–5.5 g/kg, which was
LDCS, with focuses restricted in [Bmim]BF4 [45], [Dmim]OAc [45], 20% higher than that of single silica gel. The dehumidification effects
[P4441 ][DMPO4 ] [46], [C4 mim][Cl] [46], and [C4 mim][BF4] [46]. with desiccant solution with 32% of LiCl and 10% of CaCl2 were studied
It was concluded that [Dmim]OAc with an inlet mass concentration by Li et al. [56]. The simulation results were compared with the exper-
of 81.7% could reach the same dehumidification efficiency as LiCl of imental data, and it proved that the moisture removal rate could reach
40.9% and LiBr of 45.0% mass concentration [45]. The performance of around 0.8–1.0 g/kg for the incoming air ratio of 8.3 g/kg and incoming
[P4441 ][DMPO4 ] has been tested over 1 year in a LDCS, with the results air temperature of 23–28 °C. Tables 2 and 3 summarizes respectively the
indicating stable system performance with at least 80% electricity dehumidification performances of various desiccant materials from lit-
saving and 20% cost reduction compared with conventional LCDS using erature and the physical properties of various mixed desiccant solvents.
LiCl of 30% mass concentration [46].
3. Recent progress in the configuration of liquid desiccant
2.3. Mixed and composite desiccant dehumidifier/regenerator
Recently there has been increasing research interest in the mixed As the most important component in the dehumidification process,
solvent desiccants. Some of the salts such as LiCl possesses low vapour the flow pattern and various configurations of the dehumidifier have
pressure and are more stable, but the cost is too high compared with aroused researchers’ great interests. In the dehumidifier, the incoming
other salts like CaCl2 . By mixing the salts together, the dehumidifica- humid air gets in contact with the liquid desiccant, which helps to
tion characteristics are expected to be improved, accompanied by a absorb the moisture from air. Based on the way the incoming air gets
considerable reduction in the costs and energy consumption [47]. in contact with liquid desiccant solution, the dehumidifier could be
A number of researches [30,48] have been focused on the working classified as four types, namely: parallel flow, cross flow, counter flow
performance for the different combinations between two solvents. and counter-cross flow. Based on the absence or presence of an internal
In most application the general properties of the mixed solvent after cooling/heating source in the dehumidifier, the liquid desiccant cooling
combination are required as: high elevation of boiling point, high system can be categorized into two types: adiabatic and internally
latent heat of condensation and dilution heat, low vapour pressure, low cooled dehumidifier, as shown in Fig. 2.
crystallization point, easy handling at low temperature, low viscosity,
high density and low cost. Ahmed et al. [30] presented a series of simple 3.1. Parallel flow, cross flow, counter flow and counter-cross flow
mixing rules to predict the vapour pressure, density and viscosity of the dehumidifier/regenerator
desiccant mixture (50% CaCl2 and 50% LiCl). At temperature of 60 °C,
the vapour pressure of CaCl2 and LiCl mixture at 30% concentration Based on the flow pattern, there are generally four types of de-
was about 100 mmHg, which agreed well with the results obtained by humidifiers: parallel flow, counter flow, cross flow and counter-cross
Ertas et al. [23]. In Ertas et al. [23]’s study, the mixture solution was flow. The configurations are shown in Fig. 3.
tested between 26.6 °C to 65.6 °C with concentration from 20wt% to Recent studies have been focused on cross flow dehumidi-
40wt%. The testing results showed that the addition of LiCl into CaCl2 fied/regenerator. Das and Jain [59,60] numerically and experimentally
could reduce the vapour pressure in a nonlinear manner in the whole assessed the performance characteristics of cross flow membrane
temperature range. Chen et al. [49,50] studied the vapour pressures dehumidifier, which is formed by series of alternate solution and air
and densities of the mixed solvent desiccants (glycols+water+salts) in channels in cross flow arrangement. Their results showed that the de-
the temperature range of 30–70 °C. Six ternaries in the combinations humidifier effectiveness improves at lower air channel gap, but the cost
of organic solvents (tetraethylene glycol (T4EG), diethylene glycol increases as the result of higher pressure drop. Liu et al. [61] carried
(DEG) and dipropylene glycol (DPG)) and salts (LiCl and LiBr) were out a theoretical modelling on a cross-flow liquid desiccant dehumid-
selected with salts ratio of 4–25% and glycols ratio of 50–80%. The ifier/regenerator using NTU methods. The experimental results showed
experimental results demonstrated that the selected organic-salts mixed that the moisture effectiveness achieved was in the range of 30%−60%,
system offered lower vapour pressure compared with the commonly which agreed well with the simulation results. By adding the cooling
used desiccant counterpart. water into the dehumidifier to cool the liquid desiccants, six different
Li et al. [51] compared the dehumidification effects of five groups of types of internally cooled dehumidifier were numerically investigated
mixture for LiCl and CaCl2 under the inlet air temperature around 30 °C by the same group of researchers [62]. The simulation results showed
and inlet air humidity in the range of 10 g/kg-12 g/kg. The experimental that the mass transfer driving force for parallel-flow dehumidifier was
results proved that the mixed solvent (31.2% LiCl and 20% CaCl2 ) could less uniform than the counter-flow one, which presented better mass
offer the best moisture removal rate of 4.6 kg/kg under the inlet air hu- transfer performance. Numerical and experimental investigations of a
midity of 12 g/kg. In order to relate the system performance in a more cross-flow dehumidifier packed with honeycomb paper were conducted
cost-effective way, Li et al. [52] defined an equation analysing the ratio by Dai and Zhang [34]. The obtained Nusselt number for the liquid and
between effectiveness and the cost of the liquid desiccant. The mixture gas side were 2.84 and 6.54 respectively, and the Sherwood number
of LiCl and CaCl2 were analysed experimentally with concentration rate was around 5.4. A cross-flow fin-tube dehumidifier was designed by Luo
in the range of 21.5–28.9%. The results indicated that for the mixed et al. [63] using LiCl as the desiccant. The dehumidification efficiency
109
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Table 2
Summary of dehumidification performances from literature.
Reference Solution Air mass flow Inlet air Inlet air humidity / Solution Moisture removal rate (g/s) COP
rate (kg/s) temperature (°C) relative humidity temperature
Chen et al. [33] LiCl 1.75–2.04 25.4–27.8 13.9–18.2 g/kg 15.6–19.2 4.0
Liu and Jiang [37] LiBr 0.33–0.48 25.4–35.4 9.5–18.4 g/kg 19.7–27.2 1.37–2.03 0.45
Liu and Jiang [37] LiCl 0.29–0.50 26.9–35.1 9.8–20.4 g/kg 21.8–29.0 1.53–2.46 0.47
Li et al. [51] 31.2% LiCl and 20% CaCl2 0.07–0.16 30.0 10–12 g/kg – 4.6 –
Koronaki et al. [38] LiCl 0.01–0.10 30–42 12.9–14.9 14–30 – 0.13–0.20
Koronaki et al. [38] CaCl2 0.01–0.10 30–42 12.9–14.9 14–30 – 0.10–0.15
Koronaki et al. [38] LiBr 0.01–0.10 30–42 12.9–14.9 14–30 – 0.12–0.18
Elmer et al. [41] KCOOH 0.074 30.1–34.7 51.4%−70.6% 25.1–25.8 0.15–0.4 0.72
Chua et al. [55] Silica gel + LiCl 26–34 50%−80% 0.0018–0.0042 g/kg (Moisture 1–2.6
removal capacity)
Chua et al. [55] Silica gel + CaCl2 0.042–0.070 26–34 50%−80% – 0.0014–0.0032 g/kg (Moisture 0.4–2.2
removal capacity)
Tu et al. [57] LiCl 1.0 25–45 60% – – 0.3–1.4
Yin et al. [58] LiCl 28.5–34.5 11.8–18.5 g/kg 25–30 0.15–0.30 –
Table 3
Summary of Vapour pressure, density and viscosity for mixed solvents desiccant.
Reference Temperature Mixed Solvents Concentration Vapour pressure (Pa) Density (∗ 10–3 kg/m3) Viscosity (mPa s)
Ahmed et al. [30] 60.0 °C 50% CaCl2 + 50% LiCl 30% wt% 13,330 1.181 1.40
Ertas et al. [23] 60.0 °C 50% CaCl2 + 50% LiCl 30% wt% 17,862 1.160 1.37
Ertas et al. [23] 43.3 °C 50% CaCl2 + 50% LiCl 30% wt% 6265 1.187 1.85
Ertas et al. [23] 60.0 °C 50% CaCl2 + 50% LiCl 40% wt% 11,997 1.286 3.494
Chen et al. [49] 60.0 °C 50%DEG+25%water+25%LiCl 7.863 mol/Kg 3440 – –
Chen et al. [49] 60.0 °C 50%T4EG+25%water+25%LiCl 7.863 mol/Kg 3386 – –
Chen et al. [49] 60.0 °C 50%DPG+25%water+25%LiBr 3.838 mol/Kg 8959 – –
Chen et al. [49] 60.0 °C 50%DEG+25%water+25%LiBr 3.838 mol/Kg 8573 – –
Tsai et al. [50] 60 °C 50%TEG+25%water+25%LiCl 7.863 mol/Kg 2702 1.22 77.97
Tsai et al. [50] 60 °C 50%PG+25%water+25%LiCl 7.863 mol/Kg 2956 1.16 35.77
Tsai et al. [50] 60 °C 50%TEG+25%water+25%LiCl 3.838 mol/Kg 8170 1.29 13.35
Counter Flow
Dehumidifier/
regenerator
Adiabatic
Parallel Plate
Integrated
Cooling
Internally Fin Coil
Packed Tower
with Tubes
[7] achieved was in the range of 50%−60%, under inlet air temperature rate. Lu et al. [66] established a CFD model to analyse the counter-flow
of 27–37 °C, inlet air humidity of 0.017–0.021 g/kg and air flow rate dehumidifier based on VOF (volume of fraction) and RNG (Renormal-
between 0.08 kg/s and 0.2 kg/s. ization group) turbulent model. The modelling results indicated that
Due to the fact that the outlet air stream is located at the entrance of the interfacial pressure and velocity fluctuation should be carefully
the fresh desiccant solution’s inlet, counter flow conditions are generally examined in order to determine the interfacial liquid film wave pattern.
showing better dehumidification ability compared with other two flow According to [67–69], the drawback of cross flow pattern compared
patterns [64]. However, there is very few research or established evalu- with parallel type is that efficiency of cross flow type is 10% approx-
ation indicator which could predict/compare the heat and mass transfer imately lower than that of the parallel flow type. However, parallel
performance of parallel flow, counter flow and cross flow dehumidifier. flow type dehumidifier is not easy for the sealing of liquid desiccants.
In order to address this issue and evaluate the inherent mass transfer Furthermore, the parallel flow exchanger with simple headers located
ability for different flow pattern dehumidifier, Yang et al. [65] defined next to each other is hard for construction in HVAC system. A novel
a novel concept called dehumidification perfectness, which was the heat and mass exchanger that incorporates both parallel and cross flow
ratio between dehumidification effectiveness and the moisture removal exchanger were developed by Vali et al. [69,70] as shown in Fig. 4.
110
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
111
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 6. Schematic diagram of three typical internally-cooled dehumidifiers: (A) parallel plate [58,81]; (B) fin coil [83,84]; and (C) packed tower with cooling tubes
[78].
for the Climatic condition of Hong Kong was proposed by Luo et al. surface area of 790m2 /m3 . The experimental results were validated
[82]. The author concluded that when the LiCl solution concentration is against the simulation data, and the obtained COP was in the range of
smaller than 35%, the dehumidification effect was very limited, and the 4.2–6.5. Considering the corrosion problem, Liu et al. [84] proposed an
optimum concentration rate of the solution should be around 36–39%. internally-cooled fin coil dehumidifier made from thermally conductive
plastic. The heat transfer coefficients between the desiccant solution
3.3. Three typical internally cooled dehumidifiers and the plastic pipe were in the range of 2727–3714 W/m2 K, which
showed comparable heat transfer performance to other internally
The internally cooled dehumidifier can be further categorized cooled dehumidifier made of aluminium or copper.
into three types: parallel plate [58,81], fin coil [83,84] and packed The aforementioned three types of internally-cooled liquid desiccant
tower with tubes [78]. The schematic diagram of these three types of dehumidifiers were quantitatively studied and simulated by Liu et al.
dehumidifier is shown in Fig. 6. [85], Peng and Luo [86]and Zhang et al. [87,88]. The simulation results
For these three types of dehumidifier, the air and the desiccant were compared with the experimental results from other published
solutions are all performed in cross flow direction. The major differ- literature [81,83,84]. The authors defined two parameters, namely,
ences between these three types of dehumidifier are as following: in the heat transfer ability and mass transfer ability to quantitatively analyse
parallel plate dehumidifier (as shown in Fig. 6(A)), the internal cooling the working performance of these three dehumidifiers. It was concluded
water is pumped into water passage located inside the plate. In the that the fin-coil type dehumidifiers offered higher dehumidification per-
fin coil dehumidifier (as shown in Fig. 6(B)), the cooling water flows formance due to higher heat and mass transfer ability, while the packed
inside the coil to cool the liquid desiccant coming down from the top tower with cooling tubes yielded the worst dehumidification effect.
of the dehumidifier. Packed bed dehumidifier (as shown in Fig. 6(C)), Huang et al. [89,90] developed an internally-cooled membrane-
makes use of a non-adiabatic structured packed bed absorber consisting based liquid desiccant dehumidifier (IMLDD) as shown in Fig. 7. In
of rigid media pads with cooling water flowing through tubes, which such design channels are made by membranes and plastic plates being
are embedded in the packing. stacked together, cooling water flows along plastic plates to for the
In order to increase the heat transfer contact area, Yin et al. [58] pro- water falling films in the water channel and sweep air flows over water
posed to add fins to the plates, which led to an internally-cooled fin falling films. Heat released to the solution channel is taken away by
coil dehumidifier. The dehumidification and regeneration performance the falling water through plastic plates, and then extracted by sweep
were measured under different air flow rates, water inlet temperature air through evaporation. They also developed a quasi-counter flow
and solution inlet temperatures. A similar internally-cooled dehumid- parallel-plate membrane channels with cooling tubes (QCPMCC) as
ifier featured with stainless steel fin coil was developed by Zhang shown in Fig. 8 [74]. In their design solution flows into and out of
et al. [83] using LiBr solution as the desiccant. The device consisted of the contractor from side openings, several Z-shaped cooling tubes
eight rows with 22 cooling water channels in each row, with specific with cooling water flowing inside are installed in solution channels to
112
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
113
X. Chen, S. Riffat and H. Bai et al.
Table 4
Summary of dehumidification performance for various types of dehumidifiers according to flow patterns.
Flow pattern Dehumidifier Desiccant Inlet air Inlet air Solution Outlet air Moisture removal Method Reference
solution temperature (°C) humidity (g/kg) temperature (°C) temperature (°C) rate(g/kg)
Parallel-flow Internally-cooled LiCl 35 19.1–21.6 25–30 29.5–36.7 6.1–10.3 Numerical simulation Liu et al. [62]
Counter-flow Internally-cooled LiCl 35 19.1–21.6 25–30 29.5–36.7 6.1–10.3 Numerical simulation Liu et al. [62]
Internally-cooled 23, 27 Saman et al. [77]
Cross-flow Adiabatic LiBr 31.7 13.0 22.9 26.9 3.1 Numerical + Experimental Liu et al. [61]
Internally-cooled LiCl 35 19.1–21.6 25–30 29.5–36.7 6.1–10.3 Numerical Liu et al. [62]
Internally-cooled LiCl 27–37 17.0–21.0 25–30 Dehumidification efficiency: 50%−60% Numerical + Experimental Luo et al. [63]
Internally-cooled CaCl2 29.9–30.1 26.2–26.4 30.4 28.2–29.3 3.4–5.0 Experimental Bansal et al. [78]
Adiabatic CaCl2 29.9–30.1 26.1–26.4 30.4 30.1–30.3 2.9–3.4 Experimental Bansal et al. [78]
Internally-cooled LiCl 22.8–34.3 12.8–17.2 35–38 23–28 4.1–5.8 Experimental Abdel-Salam et al. [79]
Counter-cross-flow Adiabatic MgCl2 25.0–35.2 8.2–20.2 24–28 24.4–28.4 Numerical+Experimental Vali et al. [69,70]
Adiabatic MgCl2 33–37 18–22 29–32 Experimental Mahmud et al. [71]
Adiabatic LiCl and MgCl2 23.9–35 0.31–17.38 24–32.1 24.2–31.4 Experimental Moghaddam et al. [72]
Adiabatic MgCl2 34.0–35.4 24.0–27.6 35.5–38.8 Numerical+Experimental Namvar et al. [73]
Quasi-counter-flow Internally-cooled LiCl 25 Numerical Huang et al. [74]
Adiabatic LiCl 30 19 25 Numerical+Experimental Huang et al. [75,76]
114
Table 5
Summary of dehumidification performance for various types of dehumidifiers according to integrated cooling patterns.
Flow pattern Dehumidifier type Desiccant Inlet air Inlet air Solution Outlet air Moisture Dehumidification Method Reference
solution temperature (°C) humidity (g/kg) temperature (°C) temperature (°C) removal rate efficiency
Parallel-flow Internally-cooled LiCl 35 19.1–21.6 25–30 29.5–36.7 6.1–10.3 g/kg – Numerical Liu et al. [62]
Internally-cooled LiBr – – – ΔT=5–10 Δ𝜔 = 2.2–4.5 – Numerical Jain et al. [91]
Internally-cooled LiCl 23.9–24.8 14.4–14.5 – 25.3–25.6 5.3–8.5 – Experimental Kessling et al. [81]
Counter-flow Internally-cooled LiCl 35 19.1–21.6 25–30 29.5–36.7 6.1–10.3 g/kg – Numerical Liu et al. [62]
Internally-cooled CaCl2 30–38 8.0–13.0 – – 0.5–2.0 kg/h 0.78–0.95 Numerical Saman et al. [77]
Internally-cooled LiCl, LiBr, 35 21.5 30 22.41–31.23 7.5–18.9 0.53–0.76 Numerical Ren et al. [92]
Adiabatic (without fin coil) TEG 15.3–23.7 10.0–16.8 20.5–26.7 18.4–27.7 5.9–10.0 0.45–0.62 Experimental Chung and Wu [93]
Adiabatic (with fin coil) TEG 21.0–26.9 13.6–17.8 22.7–30.3 23.6–30.4 5.8–11.6 0.64–0.80 Experimental Chung and Wu [93]
Cross-flow Adiabatic LiBr 31.7 13.0 22.9 26.9 10 g/kg – Numerical + Experimental Liu et al. [61]
for LiCl dehumidification process in a plate dehumidifier using LiCl authors analysed the variations of vapour pressures under different
as the desiccant. In order to improve the wettability of the solution, a solution temperatures.
multi-porous hydrophilic surface treatment was made as the coating for A mass transfer model based on the kinetic theory of gas was
the grooved plate dehumidifier. The simulation obtained heat transfer promoted by Li et al. [56] for a liquid desiccant cooling system. In this
coefficient of the LiCl solution ranging from 250 to 470 W/m2 K. model, water was considered to be in two-way movements in the form
of molecular. The numerical results proved that the moisture removal
rate could reach around 0.8–1.0 g/kg in the incoming air with a specific
4.2. 𝜀-NTU model
humidity ratio of 8.3 g/kg and temperature if 23–28 °C, which were in
good agreement with the experimental data.
Finite difference model works well for parallel-flow conditions.
Exergy analysis [105] based on the principle of second thermody-
However, when the processed air and liquid desiccant are in counter-
namics law has been applied greatly by researchers as a way to improve
flow configuration, the outlet conditions of the desiccant remain to be
the system performance. Wang et al. [114] conducted exergy analysis
unknown and require iterative calculation, which is time-consuming
for an ideal liquid desiccant system working under three different op-
for the computer simulation. Therefore, many researchers have used
erational conditions. It was demonstrated in the numerical simulation
𝜀-NTU model to predict the heat and mass transfer performance of the
that the operating condition 2 (where the dehumidification tempera-
dehumidification/regeneration. Chen et al. [107] proposed modelling
ture was lower than the ambient temperature) was more efficient than
on a counter-flow and a parallel-flow dehumidifier using 𝜀-NTU model.
other conditions because the exergy of latent heat consumed in the
A 3-D heat and mass transfer analysis on a cross-flow liquid dehumid-
dehumidifier and the regenerator were all coming from exergy supply.
ifier applying 𝜀-NTU model was carried out by Liu et al. [61,108]. The
By lumping the thermodynamic parameters into seven characteristic
effects of various air humidity ratio on the dehumidification efficiency,
parameters, Wang et al. [115,116] proposed a hybrid models which
condensation rate were simulated and compared with the experimental
contains two simple nonlinear equations of the heat and mass transfer
data obtained by Fumo and Goswami [20]. Considering the fact that
coefficients for the dehumidification process. The numerical results
the surface of the packing material may not be entirely wetted during
were validated against the experimental data. With the desiccant
the dehumidification process, a ratio of effective mass transfer area to
flow rate in the range of 2.5–7 kg/min, experimentally obtained heat
the effective heat transfer area was defined in a double film model by
transfer rate was in the range of 0.8–1.3 kW, with 10% difference from
Ren et al. [109] to improve the simulation efficiency. In this model,
the modelling results. With similar aim to avoid iterative computation
the effects of non-unity values of Lewis factor, changes in solution mass
process, Wang et al. [116] proposed two non-linear equations to analyse
flow rate and concentration were also considered. The numerical results
the heat and mass transfer process in the liquid desiccant dehumidifier.
of the outlet air temperature agreed well with the numerical result
The experimental results were obtained to compare with the simulation
presented by the same group of researchers [110], with percentage
predication, and 10% difference was identified. Su et al. [117] carried
difference of 3%. A mathematical model using 𝜀-NTU methods, which
out exergy analysis for a solar-assisted absorption chiller combined with
was suitable for high flow rate desiccant conditions, was applied by
liquid desiccant dehumidification system for cooling and fresh water
Babakhani et al. [111]. The numerical results showed condensation
to assess the system thermal performance. Developed exergy analysis
rate was in the range of 0.35–0.5 g/s, which indicated ±5% deviation
models were solved by calculating the exergy destruction using EES
from the experimental data [20]. Tu et al. [57] developed a simplified
(Engineering Equation Solver) software and they found that the exergy
model based on 𝜀-NTU methods for a liquid desiccant integrated with
efficiency (𝜂 ex ) for the proposed system could reach 25.64%, which is
an evaporative cooling system. The numerical results revealed that
2.97% higher than that of a reference system.Due to the complexity of
with air to dehydrated desiccant mass flow rate ratio in the range of
the dehumidification process, theoretical modelling relies heavily upon
1–7, the cooling capacity was in the range of 50–250KJ and COP would
iterative calculation. A simplified numerical model was developed by
be in the range of 0.41–0.5. However, the numerical result was not ex-
Qi et al. [118] to predict the outlet conditions of an internally cooled
perimentally validated. For membrane-based liquid desiccant heat and
liquid desiccant cooling system. A sets of numerical correlations were
mass contractors, effectiveness correlations were proposed by Zhang
obtained based on the infinite difference model developed by Ren et al.
and Niu [112]. In their research they developed sensible and latent
[92]. Three kinds of effectiveness (enthalpy, moisture and temperature
effectiveness correlations for a flat-plate exchanger with membrane
effectiveness) were defined as the input parameters for this model.
cores. They compared their empirical correlations with experimental
The numerical modelling results were compared with previous exper-
data and found the effectiveness correlations can predict the membrane
imental data [81,91,119], which showed average deviation of around
contractor performance accurately. Zhang [31] extended the work to
20%.
hollow fiber membrane contractors and developed analytical solution
Another way to avoid the complicated iterative process during the
based on solely algebraic correlations. This analytical solution was
simulation is to use response surface methodology (RSM) to obtain a
accurate and convenient for estimating sensible and latent effectiveness
set of calculation correlations. A wide range of experimental data pool
for hollow fiber membrane contractors, but its calculation load was
should be found available in literature in order to carry out such kind of
significantly high since solution outlet temperature and concentration
statistical analysis. Martin and Goswami [120] summarized a deviated
need to be assumed to start calculation. Ge et al. [113] improved
correlation representing the relationship between the dehumidification
Zhang’s model by assuming that desiccant solution mass flow rate and
efficiency and the dimensional parameters of the dehumidifier. Liu
concentration are constant. Their analytical solution was validated
et al. [37] proposed a set of model correlation which linked the solution
by experimental data under different conditions and the discrepancy
regeneration rate with incoming air mass flow rate and humidity,
between analytical and experimental effectiveness was within 10%.
solution temperature and humidity, etc. This set of correlation was later
To sum up, 𝜀-NTU can provide relatively accurate results with less
used to compare with a similar correlation from a simplified model of
iteration than finite difference method. It is time saving and can predict
a packed bed regenerator developed by Kim et al. [121]. The authors
the performance of heat and mass exchangers effectively [14].
[121] compared these two sets of correlations with experimentally ob-
tained results, and demonstrated that the model developed by Liu et al.
4.3. Other models [37] seemed to overestimate the regeneration rate, while the model
proposed by Kim et al. [121] showed deviation difference of ±20%
Ahmed et al. [30] studied the thermodynamic properties of liquid compared with experimental data. Langroudi et al. [122] evaluated a
desiccants (CaCl2 and LiCl) considering a closed system consisting of LDCS using RSM methods combined with 𝜀-NTU model, the maximum
liquid and vapour phase in equilibrium. Using algebraic equations, the dehumidification mass rate was obtained as 0.154 g/s under the air
115
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 9. Schematic diagram of a solar regenerated liquid desiccant system ventilation pre-conditioning system [123].
velocity of 4.1 m/s, desiccant flow rate of 0.035 kg/s, incoming air
humidity of 0.0185 kg/kg.
Using multi-objective Genetic Algorithm method, Sanye and Taheri
[10] simulated a liquid desiccant heat pump system with the opti-
mizations of energy, exergy, economic and environmental aspects. The
simulation results indicated that the proposed system could provide
electricity reduction of 33.2% and carbon reduction of 33.2%, with
payback period of 3.04 years.
116
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
regeneration temperature required for traditional LDCS, the proposed The simulation of yearly system performance of a solar assisted
system could achieve better regeneration effect with lower temperature LDSC for commercial applications in five metropolitan cities (Singa-
heat from solar energy. Using LiCl as the desiccant, the simulation pore, Beijing, Huston, LA and Boulder) were conducted by Qi et al.
results showed that the storage capacity of proposed system could be [129]. The effects of various solar collector areas and monthly solar
improved by 50%, when the regeneration temperature was 60 °C, and radiations, ambient air conditions on the electricity consumption
the inlet air specific humidity was 2.33 kg/kg. saving, sensible heat ratio and monthly average COP were analysed
The liquid desiccant cooling system is also applied extensively in theoretically. Economic analysis was conducted as well. The results
greenhouses to provide controlled temperature and humidity for food indicated that with solar collector up to 600m2 , the annual electricity
production. In the tropical areas where the solar radiation throughout consumption saving could reach to 450 MWh.
the year is abundant, solar assisted liquid desiccant cooling system Li and Zhang [130,131] investigated a solar energy driven hollow
could be an alternative to evaporative cooling system for agricultural fiber membrane-based desalination system as shown in Fig. 12. The
industry [126]. Lychnos and Davies [127] performed experimental and system consists of a membrane-based humidifier, a fin-and-tube type
theoretical simulation for a solar powered liquid desiccant system using dehumidifier and a solar heating unit, which consists of a U-tube
MgCl2 as the refrigerant. The theoretical model was developed and evacuated solar collector and a heat storage tank. The hollow fiber
verified with the experimental results. Compared with conventional membrane-based humidifier is similar to a shell-and-tube heat mass
evaporative cooler, the proposed system could further lower the av- exchanger. Through numerical modelling and experimental tests they
erage daily maximum temperature by 5.5–7.5 °C. As a cross-discipline found that the COP of the system can reach about 0.75 and electric COP
research, this paper also analysed the effect of LDCS on various crops (COPe ) can achieve 36.13, which means electrical energy consumption
growth including lettuce, tomato, cucumber and soya bean. It was con- is much less due to solar energy reclamation Table 6.
cluded that the proposed LDCS could provide year-round cultivation of
all the above crops under the tropical, subtropical climatic conditions. 5.2. Hybrid liquid desiccant and vapour compression systems
Longo and Gasparella [44] conducted a three-years’ experimental
research on a LDCS for a flower greenhouse. The system performance of As the most mature and advanced technology, vapour compression
using three liquid desiccants namely LiCl, KCOOH and LiBr have been (VC) system still dominate the air conditioning market world widely.
analysed and compared. The results indicated an average of 11.7% From thermodynamic point of view, further sub-cooling of the liquid
energy saving by applying the LDCS compared with conventional air refrigerant leaving the condenser can greatly improve the cooling ca-
conditioning system, although LiCl and LiBr offered more effective pacity and COP of VC system. Recent research have been concentrated
dehumidification performance compared with KCOOH. Due to the fact on using ejector [133] or absorption system [134] to act as sub-cooler
that KCOOH is biodegradable and not hazardous to the environment, for VC system. The combination of LDCS with VC system could also
KCOOH was selected by the authors as the most promising desiccant provide sub-cooling effect from the condenser outlet to the compressor
for future use in LDCS. inlet, thus leading to improved system performance.
Implementing a polymer plate heat exchanger into the LDCS, Sha- Yadav [135] conducted a parametric study on the thermal dynamic
hab [128] conducted experimental field tests on a solar driven LDCS. analysis of hybrid VC and liquid desiccant cycle, with the liquid desic-
As shown in Fig. 11, the polymer plate heat exchanger with dimension cant (LiCl) circulating between the condenser and the evaporator. With
of 1.3 × 1.5 × 1.8 m was placed inside the absorber unit with a tilt angle incoming air temperature of 35 °C and RH=40%, solution concentration
of 45°. The system dehumidification performance was tested under ratio of 55–59.5%, the simulation results demonstrated that energy sav-
the summer climatic conditions in Australia using 43% wt LiCl. The ing of 80% could be achieved at 90% of latent load in proposed system.
effects of various air flow rate and desiccant flow rate on the system A thermodynamic analysis of hybrid liquid desiccant and VC
performance were analysed experimentally. The results demonstrated system(as shown in Fig. 13) was performed by She et al. [136]. The
that the proposed system could provide cooling capacity up to 20 kW variations of ambient temperature and RH, the condenser temper-
with dehumidification efficiency up to 72%. ature, and liquid desiccant concentration ratio on the system COP
117
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 12. Schematic of a solar energy driven hollow fiber membrane-based desalination system.
Fig. 13. The schematic diagram of hybrid VC and liquid desiccant system [136].
118
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Dehumidification
Storage capacity:
0.354–3.454kg
Regenerator
years
20%
Moisture removal
0.026–0.037 g/s
0.01–0.03 g/s
0.04–0.2 kg/s
0.2–0.6 g/s
rate
NA
NA
NA
NA
NA
Fig. 14. The schematic diagram of vapour compression system combined with
30%, 35%, 40%, 45%
25.6%−42.7%
32%−36%
33%−37%
Desiccant
43%
37%
NA
NA
NA
proposed system, with maximum COPs about 18.8% higher than that
of conventional VC system.
Liquid desiccant flow
0.003–0.012 kg/s m
0.0021–0.0062 kg/s
0.081–0.12 kg/s
and VC system with total cooling capacity up to 6.2 kW. The variations
of regeneration temperature, condenser and evaporator temperature
0.5–6l/m
on the system COP and specific moisture recovery were analysed under
140 L/h
different liquid desiccant flow rates. The authors concluded that the
rate
NA
NA
NA
NA
similar testing rig, Bassuoni [138] has applied CaCl2 as the desiccant
for the experimental testing. The results showed that about 54% COP
Operating conditions and system performances of various solar driven liquid desiccant dehumidification system.
29.2–31.8
25–28.8
25–35.2
Different from the few applications above, Mohan et al. [139] pro-
NA
NA
NA
25
30
50
posed a hybrid system where the liquid desiccant was used for the
dehumidification of the supply air. As shown in Fig. 14, liquid desiccant
Desiccant
MgCl2
was circulated from the evaporator to the condenser with very low flow
NaCl
LiCl
LiCl
LiCl
LiCl
LiCl
LiCl
LiCl
NA
analysed. The results indicated that higher specific humidity and lower
0.015 kg/kg
Ambient air
67–75%
35–50%
40–82%
55%
65%
using EnergyPlus. With the design cooling capacity of 19 kW, the annual
energy saving and the monthly power consumption for the proposed
system was compared with that of the conventional VC system. The
temperature (°C)
25–28.5
25–30
29.2
31
35
With the aim to reduce the cooling capacity loss of the evaporator,
an auxiliary regenerator was implemented by Li et al. [142] in the
Huston, LA Boulder
(W/m2 K)/Location
South China
Canada
Sydney
Israel
Harrison [125]
Davies [127]
Qi et al. [129]
Gommed and
Shahab [128]
cooler was set with the aim to both capture the liquid droplets from
Lychnos and
[130,131]
Croffot and
Fumo and
[124]
Table 6
119
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Table 7
Operating conditions and system performances of various hybrid VC and liquid desiccant dehumidification system.
Reference Ambient air Ambient air Desiccant Desiccant Evaporator Condenser Specific Conclusions
temperature RH/humidity ratio solution concentration Temperature temperature moisture
(°C) ratio (°C) recovery (kg/kg)
120
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
be achieved compared
simulation results and
of dehumidification
COP: 0.16–0.34
COP: 0.38–0.62
and humidity.
effectiveness.
within 10%.
Conclusions
system
Dehumidification
effectiveness
0.2–1.0
NA
NA
NA
NA
0.004–0.008 kg/kg
film length<0.6m
Moisture removal
Liquid desiccant
rate
NA
NA
NA
LiCl (38% wt)
Desiccant
solution
LiCl
LiCl
LiCl
LiCl
0.007–0.009 kg/kg
RH/humidity ratio
0.00133 kg/kg
were made for the energy saving between the proposed system and
the conventional mechanical compression system. The results indicated
Outlet air
0.0061–
NA
13.7–28.8
Outlet air
system. Double condensers were used in the system (as shown in Fig. 17)
15–23
ing properties. The simulation showed that COP in the range of 0.3–1.3
0.0132–0.0186
zhen, China. With the inlet temperature of 15.8 °C and RH=34.6%, the
27.5–37.5
cooling capacity could reach up to 82.6 kW, and COP of the dehumidifi-
26–35
25–45
30–50
31.6
cation mode was around 4.0–4.2. A similar THIC system which incorpo-
rated two condenser into the heat pump system was proposed by Chen
et al. [154]. The simulation model was validated with experimental re-
Simulation + Experiments
Simulation + Experiments
sults under the climatic condition in Nanjing, China. The results indi-
cated that the COP of the proposed system was 13.6–116.1% more than
Analysis methods
Simulation
Simulation
Pasdarshahri
Tu et al. [150]
[149]
Table 8
5.5 °C, and RH=80%, the results indicated that a COP of 2.6–2.9 could
be achieved, which was 30–40% higher than the heat pump integrated
with electric heater system.
121
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 17. Schematic diagram of hybrid liquid desiccant heat pump system [152].
122
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Table 9
Operating conditions and system performances of various hybrid liquid desiccant and heat pump system.
Reference Analysis methods Ambient air Ambient air Desiccant Special features Conclusions
temperature (°C) RH/humidity ratio solution
Lazzarin and Simulation 22–38 0.008–0.016 kg/kg LiCl Primary + Secondary Energy saving of the proposed
Castellotti [151] condenser system could be up to
26–63% for a typical
summer day compared with
conventional systems
Niu et al. [152] Simulation 25–34 63% LiCl Solution cooled COP: 0.3–1.3
condenser + Air cooled Heat rejected by the air
condenser cooled condenser can be
utilized for heat
regeneration purpose.
Zhao et al. [153] Field trial 23–28 0.0095–0.0135 kg/kg LiCl One condenser cooling capacity could reach
up to 82.6 kW; COP: 4–4.2
Chen et al. [154]. Simulation + Experiment 18–32 0.005–0.0112 kg/kg LiCl Solution cooled COP was 13.6–116.1% more
condenser + Air cooled than that of the
condenser conventional system at
different cooling load
requirement
Zhang et al. Simulation + Experiment –7–5.5 0.0017–0.0041 LiCl One condenser COP of 2.6–2.9 could be
[155,156] achieved, which was 30–40%
higher than the heat pump
integrated with electric
heater system
Chen et al. [33] Simulation + Experiment 24–31 0.0014–0.002 LiCl Low temperature and low COP of 4.0 and sensible
concentration desiccant dehumidification
solution effectiveness between 0.65
and 0.7 could be achieved.
123
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 20. Schematic diagram of the experimental test facility for the cross-flow membrane contactors [60].
Fig. 21. (a) Air and solution flow configuration and (b) a cross-section view of the small-scale single-panel LAMEE [164].
A hybrid CHP system inside which a gas fired internal combustion the dehumidification process reached temperature of 19 °C and RH of
engine (ICE) was coupled with a liquid desiccant system was proposed 90%. The results indicated an electrical power output of 126 kW and
by Badami and Portoraro [160,161]. The energetic and economic thermal power output of 220 kW and the cooling capacity of 168 kW
analyses were conducted to the desiccant unit with dimensions of with payback period between 6.8 and 7.6 years.
2.24×1.42×1.57 m using LiCl as the solution. With the outdoor air Fu et al. [162] conducted experimental research on hybrid CHP
temperature and RH respectively at 28.8 °C and 68%, the air after system with 70 kW natural gas fuelled ICE with a liquid desiccant
124
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
Fig. 22. Schematic view of the novel compressed air drying method based on liquid desiccant [177].
system and a double-effect absorption system. The overall heating, experimental results, with membrane contactors mostly in cross flow
cooling and power generation capacity were reported in this paper. pattern [89,96,169,170]. A free surface model [170–172] was adopted
The results demonstrated that around 113 kW cooling capacity could in order to simulate the desiccant solution flow and the heat mass
be achieved by the liquid desiccant cooling system, and the maximum transfer in the membrane contactor. The authors recently focused on
efficiency of the overall system could be 91% and 85% respectively for the integration of liquid desiccant based membrane contactor with heat
winter and summer conditions. pump systems [173,174], with heat recovery systems [175,176], and
internally cooled dehumidifier [89].
Moghaddam et al. [167] investigated a methodology for scaling up
5.6. Hybrid liquid desiccant with membrane contactor
a small-scale membrane contactor to a full-scale one by applying 𝜀-NUT
method. The sensible and latent effectiveness obtained for small scale
In conventional LDCS, the process air gets direct contact with the
model were respectively 82–88% and 85–90%, which were around 5%
liquid desiccant, which leads to liquid droplets carryover. The corrosive
higher than these obtained from large scale model.
features of these desiccants limit the applications of such system to
industrial sector. In order to overcome this barrier, hydrophobic mem-
brane contactor is utilized in LDCS as the mass exchanger to separate 5.7. Other applications
the air and solution.
Bergero and Chiari [99] presented a simulation of a liquid desiccant Instead of using atmospheric air, compressed air can also be applied
and membrane contractor air conditioning system. The performance in liquid desiccant dehumidification system [177]. With the advantages
of proposed system was compared with a traditional direct expansion of great pressure difference between the desiccant solution and the
AC system. The effects of the air/solution ratio and the membrane processing air, the proposed system could result in lower humidity
regenerator dimension on the compressor performance and the energy ratios. As shown in Fig. 22, the experimental testing rig consisted of
consumption were analysed. The authors concluded that the energy a counter-flow pressurized dehumidifier, a regenerator, a LiCl storage
consumption could be reduced by up to 50% compared with traditional tank and an air compressor. The experimental results indicated that
direct expansion AC system. the moisture removal rate can reach up to 1.4 g/kg with air pressure of
Das and Jain [60,163] conducted experimental analysis on cross- 0.3 MPa and 1.0 g/kg for air pressure of 0.4 MPa, with dehumidification
flow membrane contactors made from various polypropylene (PP) efficiency around 0.9.
with different pore sizes (0. 1 μm and 0.064 μm respectively). The In order to improve the heat and mass transfer of liquid desiccant
experimental setup was shown in Fig. 20. With the vapour flux ranging dehumidification system, Qi et al. [178] proposed to use a titanium
between 726–1295 g/m2h, the dehumidification effectiveness was dioxide super hydrophilic self-cleaning coating materials on the de-
in the range of 23%−45%. Additional resistance created by the PP humidifier surface. Three commonly used materials, SUS304, SUS316
membrane, together with the costs and availability of the desired pore and SUS410 were selected as the coating materials. The experimental
size, PP material seemed to be the technical barrier for the practical results showed that the heat exchange rate and moisture removal rate
application of this membrane contactor system. between the air and the desiccant could be increased by 1.2 and 2 times
A group of researchers [73,164–167] from Canada proposed a small- by applying this technology. This suggested that titanium coating could
scale single-panel liquid to air membrane energy exchanger (LAMEE) significantly improve the mass transfer performance.
as shown in Fig. 21. The experimental testing results were validated Similarly, ultrasonic atomization techniques have been combined
with simulation data using effectiveness-NTU methods, taking into with liquid desiccant dehumidification system to improve the system
account of the variations of heat capacity between incoming air and performance. With the help of ultrasonic atomization technology, the
the desiccant solution, under inlet air temperature between 15–50 °C desiccant solution can be atomized into tiny droplets with diameter
and the humidity ratio in the range of 1–28 g/kg. The experimental about 50 μm. Using LiCl as the solution, Yang et al. [179,180] con-
results showed about 5% discrepancy compared with the simulation ducted experiments when the inlet air temperature and RH are in the
data, with the sensible and latent effectiveness in the range of 75–120% range of 25–38 °C and 26–38% respectively. The moisture removal
and 70–90% respectively. rate of 0.15–0.25 g/s and dehumidification effectiveness of 50% to
Over the past decade, Zhang and his colleagues have carried out 70% were reported from experimental and numerical simulations. The
extensive researches on the membrane-based liquid desiccant air authors also concluded that by applying this technology, the desiccant
dehumidification system [168]. Most of their works have been focused consumption rate was reduced by 73.9% compared with conventional
on the establishment of theoretical models and the validations against dehumidification system.
125
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
[151,114–119,
combined heat
158,173,174]
pump system
[181] experimentally under vacuum condition. The regeneration
Desiccant
temperature of proposed system could be reduced to 20–35 °C with
[157]
the operating vacuum pressure between 1000 Pa and 2000 Pa with
LiBr concentration ratio of 35%. The authors concluded that by using
Desiccant integrated with this system, 40.6% electricity could be saved compared with other
conventional regenerators Table 10.
membrane contactor/
[31,32,60,73,99,113,
163,165,166,167]
energy exchanger
6. Conclusions
[184]
[21]
in the area of liquid desiccant dehumidification and its integration
with other systems. This paper reviews the recent research progress
and development in liquid desiccant dehumidification system. The
combined CHP
merits and drawbacks of the widely used liquid desiccant materials are
[160,161]
Desiccant
[159]
142,141,144,145]
pump system and other innovative systems are grouped and presented.
Summary of recent research progress for liquid desiccant dehumidification system on various aspects according to different types of desiccants.
[138,143]
[141]
[51]
• Single salts including LiCl, LiBr and CaCl2 have been selected as the
desiccants for the dehumidification process. In recent decade, 85%
of the published researches have applied LiCl as the solution for
Desiccant integrated
evaporative cooling
[44,146,147,148,
[20,123,124,19,128,
[89]
flow patterns (parallel flow, counter flow and cross flow) and
Heat and mass
transfer model
[102,105,109,
[69,105,109]
122,182]
[38,77,78]
91,92,94]
[52]
[6]
[39,40]
[39,40]
[23,30]
KCOOH
LiCl
126
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
• The integrations of liquid desiccant dehumidification system with [23] A. Ertas, E.E. Anderson, I. Kiris, Properties of a new liquid desiccant solu-
other systems such as solar collector, vapour compression system, tion—Lithium chloride and calcium chloride mixture, Solar Energy 49 (3) (1992)
205–212.
heat pump system, CHP system have received great attention in [24] T.-W. Chung, C.-M. Luo, Vapor Pressures of the Aqueous Desiccants, J. Chem. Eng.
past decades. The remarkable improvements in the overall system Data 44 (5) (1999) 1024–1027.
performance of the combined liquid desiccant and other types of [25] K.R. Patil, et al., Thermodynamic properties of aqueous electrolyte solutions. 1. Va-
por pressure of aqueous solutions of lithium chloride, lithium bromide, and lithium
systems (VC, heat pump and CHP system) have been reported by iodide, J. Chem. Eng. Data 35 (2) (1990) 166–168.
many research groups. However, most of these investigations are [26] K.R. Patil, et al., Thermodynamic properties of aqueous electrolyte solutions. 2.
limited to theoretical analysis, with few experimental validations Vapor pressure of aqueous solutions of sodium bromide, sodium iodide, potassium
chloride, potassium bromide, potassium iodide, rubidium chloride, cesium chlo-
available. Solar driven liquid desiccant dehumidification system
ride, cesium bromide, cesium iodide, magnesium chloride, calcium chloride, cal-
offers a great opportunity for the dilute desiccant solution to be cium bromide, calcium iodide, strontium chloride, strontium bromide, strontium
regenerated by solar energy. However, the intermittent feature of iodide, barium chloride, and barium bromide, J. Chem. Eng. Data 36 (2) (1991)
225–230.
solar radiation poses potential barrier to its real and sustainable
[27] E. Elsarrag, Dehumidification of Air by Chemical Liquid Desiccant in a Packed
application. It would be necessary to investigate further appropriate Column and Its Heat and Mass Transfer Effectiveness, HVAC&R Res. 12 (1) (2006)
energy storage systems which could be combined with solar driven 3–16.
liquid desiccant system to improve the system stability. [28] A. Zuber, et al., Thermodynamic properties of 1:1 salt aqueous solutions with the
electrolattice equation of state, Oil Gas Sci. Technol. 68 (2) (2013) 255–270.
[29] J. Sun, X.L. Gong, M.H. Shi, Study on vapor pressure of liquid desiccants solution,
J. Refrig. 5 (1) (2004) 87–95.
[30] S.Y. Ahmed, P. Gandhidasan, A.A. Al-Farayedhi, Thermodynamic analysis of liquid
Competing of interest desiccants, Solar Energy 62 (1) (1998) 11–18.
[31] L.-Z. Zhang, An Analytical Solution to Heat and Mass Transfer in Hollow Fiber
The authors declare that they have no known competing financial Membrane Contactors for Liquid Desiccant Air Dehumidification, J. Heat Transf.
133 (9) (2011) 092001 092001-8.
interests or personal relationships that could have appeared to influence [32] L.-Z. Zhang, S.-M. Huang, L.-X. Pei, Conjugate heat and mass transfer in a cross-flow
the work reported in this paper. hollow fiber membrane contactor for liquid desiccant air dehumidification, Int. J.
Heat Mass Transf. 55 (25–26) (2012) 8061–8072.
[33] Y. Chen, X. Zhang, Y. Yin, Experimental and theoretical analysis of liquid desiccant
dehumidification process based on an advanced hybrid air-conditioning system,
References Appl. Therm. Eng. 98 (2016) 387–399.
[34] Y.J. Dai, H.F. Zhang, Numerical simulation and theoretical analysis of heat and
[1] LRg., W., La consommation énergétique de nos bâtiments, un enjeu crucial pour mass transfer in a cross flow liquid desiccant air dehumidifier packed with honey-
l’avenir. https://www.energie.wallonie.be. 2006. comb paper, Energy Conv. Manag. 45 (9–10) (2004) 1343–1356.
[2] J. Adnott, Energy Efficiency of Room Air-conditioners (EERAC) Study, Directorate [35] R.M. Lazzarin, A. Gasparella, G.A. Longo, Chemical dehumidification by liquid des-
General for Energy (DGXVII) of the Commission of the European Communities iccants: theory and experiment, Int. J. Refrigeration 22 (4) (1999) 334–347.
(1999). [36] R. Namvar, et al., +Transient characteristics of a liquid-to-air membrane energy
[3] M. Isaac, D.P. van Vuuren, Modeling global residential sector energy demand for exchanger (LAMEE) experimental data with correlations, Int. J. Heat Mass Transf.
heating and air conditioning in the context of climate change, Energy Policy 37 (2) 55 (23–24) (2012) 6682–6694.
(2009) 507–521. [37] X.H. Liu, X.Q. Yi, Y. Jiang, Mass transfer performance comparison of two commonly
[4] R. Hitchin, C. Pout, P. Riviere, Assessing the market for air conditioning systems used liquid desiccants: LiBr and LiCl aqueous solutions, Energy Conv. Manag. 52
in European buildings, Energy Build. 58 (2013) 355–362. (1) (2011) 180–190.
[5] L. GOG, Cooling with solar energy, Congress on Solar Energy, Tucson, Ariz, 1955, [38] I.P. Koronaki, et al., Thermodynamic analysis of a counter flow adiabatic dehu-
pp. 73–78. midifier with different liquid desiccant materials, Appl. Therm. Eng. 50 (1) (2013)
[6] G.A. Longo, A. Gasparella, Experimental and theoretical analysis of heat and mass 361–373.
transfer in a packed column dehumidifier/regenerator with liquid desiccant, Int. J. [39] M.R. Conde, Properties of aqueous solutions of lithium and calcium chlorides: for-
Heat Mass. Transf. 48 (25–26) (2005) 5240–5254. mulations for use in air conditioning equipment design, Int. J. Therm. Sci. 43 (4)
[7] D. La, et al., Technical development of rotary desiccant dehumidification and air (2004) 367–382.
conditioning: A review, Renew. Sustain. Energy Rev. 14 (1) (2010) 130–147. [40] P. Gandhidasan, M.A. Mohandes, Predictions of vapor pressures of aqueous des-
[8] E. Elsarrag, Evaporation rate of a novel tilted solar liquid desiccant regeneration iccants for cooling applications by using artificial neural networks, Appl. Therm.
system, Solar Energy 82 (7) (2008) 663–668. Eng. 28 (2–3) (2008) 126–135.
[9] R.K. Henderson HI, Model to predict the latent capacity of air conditioners and [41] T. Elmer, et al., An experimental study of a novel integrated desiccant air condi-
heat pumps at part-load conditions with constant fan operation, ASHRAE Trans. tioning system for building applications, Energy Build. 111 (2016) 434–445.
102 (1) (1996) 266–274. [42] S. Atkinson, Vapour absorbent compositions comprising potassium formate, US
[10] S. Sanaye, M. Taheri, Modeling and multi-objective optimization of a modified patent 5846450 (1998).
hybrid liquid desiccant heat pump (LD-HP) system for hot and humid regions, Appl. [43] G. Qiu, H. Liu, S.B. Riffat, Experimental investigation of a liquid desiccant cool-
Therm. Eng. 129 (2018) 212–229. ing system driven by flue gas waste heat of a biomass boiler, Int. J. Low-Carbon
[11] H.-X. Fu, X.-H. Liu, Review of the impact of liquid desiccant dehumidification on Technol. 8 (3) (2013) 165–172.
indoor air quality, Build. Environ. 116 (2017) 158–172. [44] G.A. Longo, A. Gasparella, Three years experimental comparative analysis of a des-
[12] J. Nie, et al., Theoretical study on volatile organic compound removal and energy iccant based air conditioning system for a flower greenhouse: Assessment of differ-
performance of a novel heat pump assisted solid desiccant cooling system, Build. ent desiccants, Appl. Therm. Eng. 78 (2015) 584–590.
Environ. 85 (2015) 233–242. [45] Y. Luo, et al., Investigation on feasibility of ionic liquids used in solar liquid desic-
[13] S.J. Slayzak, et al., Using liquid desiccant as a regenerable filter for capturing and cant air conditioning system, Solar Energy 86 (9) (2012) 2718–2724.
deactivating contaminants. 2007. U.S. Patent No.: 7,306,650, 2007. [46] H. Watanabe, et al., Design of ionic liquids as liquid desiccant for an air condition-
[14] H. Bai, et al., State-of-art in modelling methods of membrane-based liquid desiccant ing system, Green Energy Environ. 4 (2) (2019) 139–145.
heat and mass exchanger: A comprehensive review, Int. J. Heat Mass Transf. 125 [47] J. Lin, et al., Thermodynamic analysis of a hybrid membrane liquid desiccant de-
(2018) 445–470. humidification and dew point evaporative cooling system, Energy Conv. Manag.
[15] M.M. Rafique, P. Gandhidasan, H.M.S. Bahaidarah, Liquid desiccant materials and 156 (2018) 440–458.
dehumidifiers – A review, Renew. Sustain. Energy Rev. 56 (2016) 179–195. [48] A.A. Al-Farayedhi, P. Gandhidasan, M.A. Al-Mutairi, Evaluation of heat and mass
[16] M. Sahlot, S.B. Riffat, Desiccant cooling systems: a review, Int. J. Low-Carbon Tech- transfer coefficients in a gauze-type structured packing air dehumidifier operating
nol. 11 (4) (2016) 489–505. with liquid desiccant, Int. J. Refrigeration 25 (3) (2002) 330–339.
[17] L. Mei, Y.J. Dai, A technical review on use of liquid-desiccant dehumidification for [49] L.-F. Chen, A.N. Soriano, M.-H. Li, Vapour pressures and densities of the mixed–
air-conditioning application, Renew. Sustain. Energy Rev. 12 (3) (2008) 662–689. solvent desiccants (glycols + water + salts), J. Chem. Thermodyn. 41 (6) (2009)
[18] A. Lowenstein, Review of liquid desiccant technology for HVAC applications, 724–730.
Hvac&R Res. 14 (6) (2008) 819–839. [50] C.-Y. Tsai, A.N. Soriano, M.-H. Li, Vapour pressures, densities, and viscosities of
[19] D. Peng, X. Zhang, Y. Yin, Theoretical storage capacity for solar air pretreatment the aqueous solutions containing (triethylene glycol or propylene glycol) and (LiCl
liquid collector/regenerator, Appl. Therm. Eng. 28 (11–12) (2008) 1259–1266. or LiBr), J. Chem. Thermodyn. 41 (5) (2009) 623–631.
[20] N. Fumo, D.Y. Goswami, Study of an aqueous lithium chloride desiccant system: air [51] L. Xiu-Wei, et al., Research on ratio selection of a mixed liquid desiccant: Mixed
dehumidification and desiccant regeneration, Solar Energy 72 (4) (2002) 351–361. LiCl– CaCl2 solution, Solar Energy 82 (12) (2008) 1161–1171.
[21] V. Oberg, D. Goswami, A review of liquid desiccant cooling, Adv. Solar Energy 12 [52] X.-W. Li, et al., Progress in selecting desiccant and dehumidifier for liquid desiccant
(1998) 431–470. cooling system, Energy Build. 49 (2012) 410–418.
[22] S.A. Abdul-Wahab, Y.H. Zurigat, M.K. Abu-Arabi, Predictions of moisture removal [53] L.Z. Li Xin, Wei Lifei, Xiao Jing, Xiao Limin, Review on the Ma-
rate and dehumidification effectiveness for structured liquid desiccant air dehu- terials of Dehumidification, Chem. Ind. Eng. Progress. 8 (2004)
midifier, Energy 29 (1) (2004) 19–34. 811–815.
127
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
[54] S. Techajunta, S. Chirarattananon, R.H.B. Exell, Experiments in a solar simulator [87] L. Zhang, et al., Experimental study and analysis of heat and mass transfer ability of
on solid desiccant regeneration and air dehumidification for air conditioning in a counter-flow packing tower and liquid desiccant dehumidification system, Energy
tropical humid climate, Renew. Energy 17 (4) (1999) 549–568. Build. 158 (2018) 150–161.
[55] K.J. Chua, Heat and mass transfer of composite desiccants for energy efficient [88] L. Zhang, H. Wei, X. Zhang, Theoretical analysis of heat and mass transfer char-
air dehumidification: Modelling and experiment, Appl. Therm. Eng. 89 (2015) acteristics of a counter-flow packing tower and liquid desiccant dehumidification
703–716. systems based on entransy theory, Energy 141 (2017) 661–672.
[56] X.-W. Li, X.-S. Zhang, F. Wang, A kinetic mass transfer model of liquid dehumidi- [89] S.-M. Huang, Z. Zhong, M. Yang, Conjugate heat and mass transfer in an internal-
fication for liquid desiccant cooling system, Energy Build. 61 (2013) 93–99. ly-cooled membrane-based liquid desiccant dehumidifier (IMLDD), J. Memb. Sci.
[57] M. Tu, et al., Simulation and analysis of a novel liquid desic- 508 (2016) 73–83.
cant air-conditioning system, Appl. Therm. Eng. 29 (11–12) (2009) [90] S.-M. Huang, et al., Performance analysis of an internally-cooled plate membrane
2417–2425. liquid desiccant dehumidifier (IMLDD): An analytical solution approach, Int. J.
[58] Y. Yin, et al., Experimental study on a new internally cooled/heated dehumid- Heat Mass Transf. 119 (2018) 577–585.
ifier/regenerator of liquid desiccant systems, Int. J. Refrigeration 31 (5) (2008) [91] S. Jain, P.L. Dhar, S.C. Kaushik, Experimental studies on the dehumidifier and re-
857–866. generator of a liquid desiccant cooling system, Appl. Therm. Eng. 20 (3) (2000)
[59] R.S. Das, S. Jain, Experimental performance of indirect air-liquid membrane con- 253–267.
tactors for liquid desiccant cooling systems, Energy 57 (2013) 319–325. [92] C.Q. Ren, M. Tu, H.H. Wang, An analytical model for heat and mass transfer pro-
[60] R.S. Das, S. Jain, Performance characteristics of cross-flow membrane contactors cesses in internally cooled or heated liquid desiccant–air contact units, Int. J. Heat
for liquid desiccant systems, Appl. Energy 141 (2015) 1–11. Mass Transf. 50 (17–18) (2007) 3545–3555.
[61] X.H. Liu, Y. Jiang, K.Y. Qu, Heat and mass transfer model of cross flow liquid des- [93] T.-W. Chung, H. Wu, Comparison between Spray Towers with and without Fin Coils
iccant air dehumidifier/regenerator, Energy Conv. Manag. 48 (2) (2007) 546–554. for Air Dehumidification Using Triethylene Glycol Solutions and Development of
[62] X.H. Liu, et al., Performance analysis on the internally cooled dehumidifier using the Mass-Transfer Correlations, Ind. Eng. Chem. Res. 39 (6) (2000) 2076–2084.
liquid desiccant, Build. Environ. 44 (2) (2009) 299–308. [94] The European Parliament and the Council of the EU, Directive 2010/31/EU of the
[63] Y. Luo, et al., Experimental and theoretical research of a fin-tube type internally– European parliament and of the council of 19 May 2010 on the energy performance
cooled liquid desiccant dehumidifier, Appl. Energy 133 (2014) 127–134. of buildings (recast), Off. J. Eur. Commun. L153 (2015) 13–35.
[64] X.H. Liu, et al., Experimental study on mass transfer performances of cross flow [95] S. Yamaguchi, et al., Hybrid liquid desiccant air-conditioning system:
dehumidifier using liquid desiccant, Energy Conv. Manag. 47 (15–16) (2006) Experiments and simulations, Appl. Therm. Eng. 31 (17–18) (2011)
2682–2692. 3741–3747.
[65] Z. Yang, et al., Concept of dehumidification perfectness and its potential applica- [96] S.-M. Huang, et al., Fluid flow and heat mass transfer in membrane parallel-plates
tions, Energy 91 (2015) 176–191. channels used for liquid desiccant air dehumidification, Int. J. Heat Mass Transf.
[66] H. Lu, et al., Investigation on the dynamic characteristics of the counter-current 55 (9) (2012) 2571–2580.
flow for liquid desiccant dehumidification, Energy 101 (2016) 229–238. [97] W.Z. Gao, et al., Experimental investigation on the heat and mass transfer between
[67] Zhang, L.Z., Total heat recovery: heat and moisture recovery from ventilation air. air and liquid desiccant in a cross-flow dehumidifier, Renew. Energy 37 (1) (2012)
2008, New York: Nova Science Publishers Inc. 117–123.
[68] Frank P. Incropera, D.P.D., Theodore L. Bergman, S. Adrienne, Lavine Principles of [98] G. Ge, F. Xiao, X. Niu, Control strategies for a liquid desiccant air-conditioning
Heat and Mass Transfer seventh edition ed, Jogn Wiley & Sons, Inc, 2012. system, Energy Build. 43 (6) (2011) 1499–1507.
[69] A. Vali, et al., Numerical model and effectiveness correlations for a run-around [99] S. Bergero, A. Chiari, Performance analysis of a liquid desiccant and membrane
heat recovery system with combined counter and cross flow exchangers, Int. J. contactor hybrid air-conditioning system, Energy Build. 42 (11) (2010) 1976–1986.
Heat Mass Transf. 52 (25) (2009) 5827–5840. [100] A.A. Aly, E.-S.B. Zeidan, A.M. Hamed, Solar-powered open absorption cycle model-
[70] A. Vali, et al., Numerical modeling of fluid flow and coupled heat and mass transfer ing with two desiccant solutions, Energy Conv. Manag. 52 (7) (2011) 2768–2776.
in a counter-cross-flow parallel-plate liquid-to-air membrane energy exchanger, Int. [101] M.S. Park, et al., Numerical and experimental results for coupled heat and mass
J. Heat Mass Transf. 89 (2015) 1258–1276. transfer between a desiccant film and air in cross-flow, Int. J. Heat Mass Transf. 37
[71] K. Mahmud, et al., Performance testing of a counter-cross-flow run-around mem- (1994) 395–402.
brane energy exchanger (RAMEE) system for HVAC applications, Energy Build. 42 [102] M. Raisul Islam, N.E. Wijeysundera, J.C. Ho, Performance study of a falling-film
(7) (2010) 1139–1147. absorber with a film-inverting configuration, Int. J. Refrigeration 26 (8) (2003)
[72] D. Ghadiri Moghaddam, et al., Steady-State Performance of a Small-Scale Liquid– 909–917.
to-Air Membrane Energy Exchanger for Different Heat and Mass Transfer Direc- [103] L.C.S. Mesquita, S.J. Harrison, D. Thomey, Modeling of heat and mass trans-
tions, and Liquid Desiccant Types and Concentrations: Experimental and Numerical fer in parallel plate liquid-desiccant dehumidifiers, Solar Energy 80 (11) (2006)
Data, J. Heat. Transf. 135 (12) (2013) 122002 122002-13. 1475–1482.
[73] R. Namvar, et al., Transient heat and moisture transfer characteristics of a liquid– [104] V. Öberg, D.Y. Goswami, Experimental Study of the Heat and Mass Transfer in a
to-air membrane energy exchanger (LAMEE) model verification and extrapolation, Packed Bed Liquid Desiccant Air Dehumidifier, J. Sol. Energy Eng. 120 (4) (1998)
Int. J. Heat Mass Transf. 66 (2013) 757–771. 289–297.
[74] S.-M. Huang, et al., Laminar flow and heat transfer in a quasi-counter flow par- [105] Z.Q. Xiong, Y.J. Dai, R.Z. Wang, Development of a novel two-stage liquid desiccant
allel-plate membrane channel in the solution side with cooling tubes, Int. J. Heat dehumidification system assisted by CaCl2 solution using exergy analysis method,
Mass Transf. 105 (2017) 769–780. Appl. Energy 87 (5) (2010) 1495–1504.
[75] S.-M. Huang, M. Yang, X. Yang, Performance analysis of a quasi-counter flow paral- [106] J.H. Lee, et al., Combined heat and mass transfer analysis for LiCl dehumidification
lel-plate membrane contactor used for liquid desiccant air dehumidification, Appl. process in a plate type heat exchanger, Appl. Therm. Eng. 96 (2016) 250–257.
Therm. Eng. 63 (1) (2014) 323–332. [107] X.Y. Chen, et al., Analytical solution of adiabatic heat and mass transfer process in
[76] S.-M. Huang, et al., Laminar flow and heat transfer in a quasi-counter flow parallel– packed-type liquid desiccant equipment and its application, Solar Energy 80 (11)
plate membrane channel (QCPMC), Int. J. Heat Mass Transf. 86 (2015) 890–897. (2006) 1509–1516.
[77] W. Saman, S. Alizadeh, An experimental study of a cross-flow type plate [108] X. Liu, et al., Analytical solutions of coupled heat and mass transfer processes in
heat exchanger for dehumidification/cooling, Solar Energy 73 (1) (2002) liquid desiccant air dehumidifier/regenerator, Energy Conv. Manag. 48 (7) (2007)
59–71. 2221–2232.
[78] P. Bansal, S. Jain, C. Moon, Performance comparison of an adiabatic and an inter- [109] C.Q. Ren, Effectiveness–NTU relation for packed bed liquid desiccant–air contact
nally cooled structured packed-bed dehumidifier, Appl. Therm. Eng. 31 (1) (2011) systems with a double film model for heat and mass transfer, Int. J. Heat Mass
14–19. Transf. 51 (7–8) (2008) 1793–1803.
[79] A.H. Abdel-Salam, et al., A Field Study of a Low-Flow Internally Cooled/Heated Liq- [110] R. Chengqin, J. Yi, Z. Yianpin, Simplified analysis of coupled heat and mass transfer
uid Desiccant Air Conditioning System: Quasi-Steady and Transient Performance, processes in packed bed liquid desiccant-air contact system, Solar Energy 80 (1)
J. Sol. Energy Eng. 138 (3) (2016) 031009 031009-14. (2006) 121–131.
[80] W.Z. Gao, et al., Experimental study on partially internally cooled dehumidification [111] D. Babakhani, M. Soleymani, An analytical solution for air dehumidification by
in liquid desiccant air conditioning system, Energy Build. 61 (2013) 202–209. liquid desiccant in a packed column, Int. Commun. Heat Mass Transf. 36 (9) (2009)
[81] W. Kessling, E. Laevemann, C. Kapfhammer, ENERGY STORAGE FOR DESICCANT 969–977.
COOLING SYSTEMS COMPONENT DEVELOPMENT, Solar Energy 64 (4–6) (1998) [112] L.Z. Zhang, J.L. Niu, Effectiveness Correlations for Heat and Moisture Transfer Pro-
209–221. cesses in an Enthalpy Exchanger With Membrane Cores, J. Heat. Transf. 124 (5)
[82] Y. Luo, et al., Experimental study of internally cooled liquid desiccant dehumid- (2002) 922–929.
ification: Application in Hong Kong and intensive analysis of influencing factors, [113] G. Ge, et al., Analytical model based performance evaluation, sizing and coupling
Build. Environ. 93 (Part 2) (2015) 210–220. flow optimization of liquid desiccant run-around membrane energy exchanger sys-
[83] T. Zhang, et al., Experimental analysis of an internally-cooled liquid desiccant de- tems, Energy Build. 62 (2013) 248–257.
humidifier, Build. Environ. 63 (2013) 1–10. [114] L. Wang, N. Li, B. Zhao, Exergy performance and thermodynamic properties of
[84] J. Liu, et al., Experimental analysis of an internally-cooled/heated liquid desiccant the ideal liquid desiccant dehumidification system, Energy Build. 42 (12) (2010)
dehumidifier/regenerator made of thermally conductive plastic, Energy Build. 99 2437–2444.
(2015) 75–86. [115] X. Wang, et al., Heat and Mass Transfer Model for Desiccant Solution Regeneration
[85] J. Liu, X. Liu, T. Zhang, Performance comparison of three typical types of internal- Process in Liquid Desiccant Dehumidification System, Ind. Eng. Chem. Res. 53 (7)
ly-cooled liquid desiccant dehumidifiers, Build. Environ. 103 (2016) 134–145. (2014) 2820–2829.
[86] D. Peng, D. Luo, Modeling and parametrical analysis on internally-heated liq- [116] X. Wang, et al., A hybrid dehumidifier model for real-time performance monitoring,
uid desiccant regenerator in liquid desiccant air conditioning, Energy 141 (2017) control and optimization in liquid desiccant dehumidification system, Appl. Energy
461–471. 111 (2013) 449–455.
128
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
[117] B. Su, W. Han, H. Jin, An innovative solar-powered absorption refrigeration system tem performance in a multi-climate country, Int. J. Refrigeration 34 (5) (2011)
combined with liquid desiccant dehumidification for cooling and water, Energy 1251–1261.
Conv. Manag. 153 (2017) 515–525. [150] M. Tu, et al., Simulation and analysis of a novel liquid desiccant air-conditioning
[118] R. Qi, L. Lu, H. Yang, Development of simplified prediction model for internally system, Appl. Therm. Eng. 29 (11) (2009) 2417–2425.
cooled/heated liquid desiccant dehumidification system, Energy Build. 59 (2013) [151] R.M. Lazzarin, F. Castellotti, A new heat pump desiccant dehumidifier for super-
133–142. market application, Energy Build. 39 (1) (2007) 59–65.
[119] Y. Yin, X. Zhang, Comparative study on internally heated and adiabatic regener- [152] X. Niu, F. Xiao, Z. Ma, Investigation on capacity matching in liquid desiccant and
ators in liquid desiccant air conditioning system, Build. Environ. 45 (8) (2010) heat pump hybrid air-conditioning systems, Int. J. Refrigeration 35 (1) (2012)
1799–1807. 160–170.
[120] V. Martin, D.Y. Goswami, Effectiveness of Heat and Mass Transfer Processes in [153] K. Zhao, et al., Performance of temperature and humidity independent control air–
a Packed Bed Liquid Desiccant Dehumidifier/Regenerator, HVAC&R Res. 6 (1) conditioning system in an office building, Energy Build. 43 (8) (2011) 1895–1903.
(2000) 21–39. [154] Y. Chen, Y. Yin, X. Zhang, Performance analysis of a hybrid air-conditioning system
[121] M.-H. Kim, J.-Y. Park, J.-W. Jeong, Simplified model for packed-bed tower dehumidified by liquid desiccant with low temperature and low concentration,
regenerator in a liquid desiccant system, Appl. Therm. Eng. 89 (2015) Energy Build. 77 (2014) 91–102.
717–726. [155] L. Zhang, E. Hihara, M. Saikawa, Combination of air-source heat pumps with liquid
[122] L.O. Langroudi, H. Pahlavanzadeh, S.M. Mousavi, Statistical evaluation of a liquid desiccant dehumidification of air, Energy Conv. Manag. 57 (2012) 107–116.
desiccant dehumidification system using RSM and theoretical study based on the [156] L. Zhang, C. Dang, E. Hihara, Performance analysis of a no-frost hybrid air condi-
effectiveness NTU model, J. Ind. Eng. Chem. 20 (5) (2014) 2975–2983. tioning system with integrated liquid desiccant dehumidification, Int. J. Refriger-
[123] T. Katejanekarn, S. Kumar, Performance of a solar-regenerated liquid desiccant ation 33 (1) (2010) 116–124.
ventilation pre-conditioning system, Energy Build. 40 (7) (2008) 1252–1267. [157] A. Gasparella, G.A. Longo, R. Marra, Combination of ground source heat pumps
[124] A.K. Mohaisen, Z. Ma, Development and modelling of a solar assisted liquid desic- with chemical dehumidification of air, Appl. Therm. Eng. 25 (2–3) (2005) 295–308.
cant dehumidification air-conditioning system, Build. Simul. 8 (2) (2015) 123–135. [158] S. Shen, et al., Hybrid model for heat recovery heat pipe system in Liquid Desiccant
[125] L. Crofoot, S. Harrison, Performance Evaluation of a Liquid Des- Dehumidification System, Appl. Energy 182 (2016) 383–393.
iccant Solar Air Conditioning System, Energy Procedia 30 (2012) [159] M. Jradi, S. Riffat, Experimental investigation of a biomass-fuelled micro-scale tri–
542–550. generation system with an organic Rankine cycle and liquid desiccant cooling unit,
[126] P.A. Davies, A solar cooling system for greenhouse food production in hot climates, Energy 71 (2014) 80–93.
Solar Energy 79 (6) (2005) 661–668. [160] M. Badami, A. Portoraro, Performance analysis of an innovative small-scale trigen-
[127] G. Lychnos, P.A. Davies, Modelling and experimental verification of a solar-pow- eration plant with liquid desiccant cooling system, Energy Build. 41 (11) (2009)
ered liquid desiccant cooling system for greenhouse food production in hot cli- 1195–1204.
mates, Energy 40 (1) (2012) 116–130. [161] M. Badami, A. Portoraro, G. Ruscica, Analysis of trigeneration plants: engine with
[128] S. Alizadeh, Performance of a solar liquid desiccant air conditioner – An experi- liquid desiccant cooling and micro gas turbine with absorption chiller, Int. J. Energy
mental and theoretical approach, Solar Energy 82 (6) (2008) 563–572. Res. 36 (5) (2012) 579–589.
[129] R. Qi, L. Lu, Y. Huang, Energy performance of solar-assisted liquid desiccant air– [162] L. Fu, et al., Laboratory research on combined cooling, heating and power (CCHP)
conditioning system for commercial building in main climate zones, Energy Conv. systems, Energy Conv. Manag. 50 (4) (2009) 977–982.
Manag. 88 (2014) 749–757. [163] R.S. Das, S. Jain, Experimental performance of indirect air–liquid mem-
[130] G.-P. Li, L.-Z. Zhang, Investigation of a solar energy driven and hollow fiber mem- brane contactors for liquid desiccant cooling systems, Energy 57 (2013)
brane-based humidification–dehumidification desalination system, Appl. Energy 319–325.
177 (2016) 393–408. [164] D.G. Moghaddam, et al., Small-scale single-panel liquid-to-air membrane energy
[131] L.-Z. Zhang, G.-P. Li, Energy and economic analysis of a hollow fiber mem- exchanger (LAMEE) test facility development, commissioning and evaluating the
brane-based desalination system driven by solar energy, Desalination 404 (2017) steady-state performance, Energy Build. 66 (2013) 424–436.
200–214. [165] G. Ge, et al., Comparison of experimental data and a model for heat and mass trans-
[132] K. Gommed, G. Grossman, Investigation of an improved solar-powered open ab- fer performance of a liquid-to-air membrane energy exchanger (LAMEE) when used
sorption system for cooling, dehumidification and air conditioning, Int. J. Refrig- for air dehumidification and salt solution regeneration, Int. J. Heat Mass Transf.
eration 35 (3) (2012) 676–684. 68 (2014) 119–131.
[133] X. Chen, et al., Theoretical studies of a hybrid ejector CO2 compression cooling [166] D. Ghadiri Moghaddam, R.W. Besant, C.J. Simonson, Solution-side effectiveness for
system for vehicles and preliminary experimental investigations of an ejector cycle, a liquid-to-air membrane energy exchanger used as a dehumidifier/regenerator,
Appl. Energy 102 (2013) 931–942. Appl. Energy 113 (2014) 872–882.
[134] A. Elsafty, A.J. Al-Daini, Economical comparison between a solar-powered vapour [167] D. Ghadiri Moghaddam, R.W. Besant, C.J. Simonson, A methodology for scaling a
absorption air-conditioning system and a vapour compression system in the Middle small-scale energy exchanger performance results to a full-scale energy exchanger,
East, Renew. Energy 25 (4) (2002) 569–583. Int. J. Heat Mass Transf. 82 (2015) 555–567.
[135] Y.K. Yadav, Vapour-compression and liquid-desiccant hybrid solar space-condition- [168] S.-M. Huang, L.-Z. Zhang, Researches and trends in membrane-based liquid desic-
ing system for energy conservation, Renew. Energy 6 (7) (1995) 719–723. cant air dehumidification, Renew. Sustain. Energy Rev. 28 (2013) 425–440.
[136] X. She, Y. Yin, X. Zhang, Thermodynamic analysis of a novel energy-efficient re- [169] Zhang, L.-Z., S.-M. Huang, and W.-B. Zhang, Turbulent heat and mass transfer
frigeration system subcooled by liquid desiccant dehumidification and evaporation, across a hollow fiber membrane bundle considering interactions between neigh-
Energy Conv. Manag. 78 (2014) 286–296. boring fibers. Vol. 64. 2013. 162-172.
[137] A. Khalil, An experimental study on multi‐purpose desiccant integrated va- [170] Huang, S.-M., L.-Z. Zhang, and M. Yang, Conjugate heat and mass transfer in mem-
por‐compression air‐conditioning system, Int. J. Energy Res. 36 (4) (2012) brane parallel-plates ducts for liquid desiccant air dehumidification: Effects of the
535–544. developing entrances. Vol. 437. 2013. 82–89.
[138] M.M. Bassuoni, Experimental performance study of a proposed desiccant based air [171] L.-Z. Zhang, et al., Conjugate heat and mass transfer in a hollow fiber membrane
conditioning system, J. Adv. Res. 5 (1) (2014) 87–95. module for liquid desiccant air dehumidification: A free surface model approach,
[139] B.S. Mohan, M.P. Maiya, S. Tiwari, Performance characterisation of liquid desic- Int. J. Heat Mass Transf. 55 (13) (2012) 3789–3799.
cant columns for a hybrid air-conditioner, Appl. Therm. Eng. 28 (11–12) (2008) [172] L.-Z. Zhang, S.-M. Huang, Coupled heat and mass transfer in a counter flow hollow
1342–1355. fiber membrane module for air humidification, Int. J. Heat Mass Transf. 54 (5–6)
[140] Y. Li, L. Lu, H. Yang, Energy and economic performance analysis of an open cycle (2011) 1055–1063.
solar desiccant dehumidification air-conditioning system for application in Hong [173] N. Zhang, S.-Y. Yin, L.-Z. Zhang, Performance study of a heat pump driven and hol-
Kong, Solar Energy 84 (12) (2010) 2085–2095. low fiber membrane-based two-stage liquid desiccant air dehumidification system,
[141] A. Capozzoli, et al., Hybrid HVAC systems with chemical dehumidification for su- Appl. Energy 179 (2016) 727–737.
permarket applications, Appl. Therm. Eng. 26 (8–9) (2006) 795–805. [174] L.-Z. Zhang, N. Zhang, A heat pump driven and hollow fiber membrane-based liq-
[142] L. Yinglin, et al., Performance analysis of a novel liquid desiccant-vapor compres- uid desiccant air dehumidification system: Modeling and experimental validation,
sion hybrid air-conditioning system, Energy 109 (2016) 180–189. Energy 65 (2014) 441–451.
[143] Y.J. Dai, et al., Use of liquid desiccant cooling to improve the performance of vapor [175] X.-R. Zhang, et al., One-step fabrication and analysis of an asymmetric cellulose
compression air conditioning, Appl. Therm. Eng. 21 (12) (2001) 1185–1202. acetate membrane for heat and moisture recovery, J. Memb. Sci. 366 (1) (2011)
[144] D. Pietruschka, et al., Experimental performance analysis and modelling of liquid 158–165.
desiccant cooling systems for air conditioning in residential buildings, Int. J. Re- [176] C.-H. Liang, L.-Z. Zhang, L.-X. Pei, Performance analysis of a direct expansion air
frigeration 29 (1) (2006) 110–124. dehumidification system combined with membrane-based total heat recovery, En-
[145] L. Mucke, et al., Hybrid liquid desiccant air-conditioning systems: A conceptual ergy 35 (9) (2010) 3891–3901.
study with respect to energy saving potentials, Int. J. Refrigeration 69 (2016) [177] Y. Yin, et al., A proposed compressed air drying method using pressurized liquid
64–73. desiccant and experimental verification, Appl. Energy 141 (2015) 80–89.
[146] X. Cui, et al., Theoretical analysis of a liquid desiccant based indirect evaporative [178] R. Qi, et al., A new approach to enhance the heat and mass transfer of liquid desic-
cooling system, Energy 95 (2016) 303–312. cant dehumidification with a titanium dioxide superhydrophilic self-cleaning coat-
[147] J. Woods, E. Kozubal, A desiccant-enhanced evaporative air conditioner: ing, J. Clean Prod. 112 (Part 4) (2016) 3555–3561.
Numerical model and experiments, Energy Conv. Manag. 65 (2013) [179] Z. Yang, et al., Improvement of the ultrasonic atomization liquid desiccant dehu-
208–220. midification system, Energy Build. 85 (2014) 145–154.
[148] M.-H. Kim, et al., Annual operating energy savings of liquid desiccant and evapora- [180] Z. Yang, et al., Experimental study on mass transfer performances of the ultrasonic
tive-cooling-assisted 100% outdoor air system, Energy Build. 76 (2014) 538–550. atomization liquid desiccant dehumidification system, Energy Build. 93 (2015)
[149] G. Heidarinejad, H. Pasdarshahri, Potential of a desiccant-evaporative cooling sys- 126–136.
129
X. Chen, S. Riffat and H. Bai et al. Energy and Built Environment 1 (2020) 106–130
[181] H.R. Yon, et al., Performance investigation on a novel liquid desiccant re- [183] H. Bai, et al., Performance testing of a cross-flow membrane-based liquid desiccant
generation system operating in vacuum condition, Appl. Energy 211 (2018) dehumidification system, Appl. Therm. Eng. 119 (2017) 119–131.
249–258. [184] Z. Chen, J. Zhu, H. Bai, Performance assessment of a membrane liquid desiccant de-
[182] R.S. Das, S. Jain, Simulation of potential standalone liquid desiccant cooling cycles, humidification cooling system based on experimental investigations, Energy Build.
Energy 81 (2015) 652–661. 139 (2017) 665–679.
130