1 Introduction............................................................................................................................. 3
1.1 About the RTU500 Series Function Description........................................................... 3
1.2 Preface........................................................................................................................... 3
1.3 References..................................................................................................................... 4
1KGT151098 V003 1 I
Contents
4 Module comparison..............................................................................................................37
4.1 Overview...................................................................................................................... 37
4.2 Binary input modules................................................................................................... 37
4.3 Binary output modules.................................................................................................37
4.4 Analog input modules.................................................................................................. 38
4.5 Analog output modules................................................................................................38
5 Glossary.................................................................................................................................39
II 1KGT151098 V003 1
Introduction About the RTU500 Series Function Description
1 Introduction
1.2 Preface
This document describes the various hardware modules of the RTU500 series:
• I/O modules
• Communication modules
• Real-time clocks
A more detailed description of these modules can be found in [1], [2], and [3].
Function descriptions part 2 and part 3 contain descriptions of the following hardware modules:
• Racks / housings
• Power supply units
• Communication units, base modules
• Bus connection units, adapter boards
From a mounting point of view, the RTU500 series includes two types of hardware modules:
• Rack-mounted modules
• DIN rail-mounted modules
1KGT151098 V003 1 3
References Introduction
1.3 References
[1] Individual Ident RTU500 series Individual Hardware Data Sheets of all boards,
units and auxiliary equipment
Hardware Data Sheets
[2] Individual Ident RTU500 series Individual Connection and Settings description
of all boards, units and auxiliary equipment
Connection and
Settings documents
[3] 1KGT 150 400 Environmental Data MTBF calculation of all modules
Sheet
[4] 1KGT151104 Interfaces and Transmission protocols
Protocols
4 1KGT151098 V003 1
Rack mounted Modules Racks
2.1 Racks
Following racks are available:
• 560SFR02
• 560MPR01
• 560MPR03
Rack Max. no. of PSUs Max. no. of CMUs Max. no. of I/O Mounting type
560SFR02 2 8 18 /17
1 swing frame
560MPR01 1 2 8 mounting plate
560MPR03 2 8 18 /17
1 mounting plate
Table 2: Technical features: Racks for mounting plate mounting
Rack
19“, 3 U, 20 slots according to DIN 41494; 1 slot
= 20.32 mm
Dimensions 132,8 x 482,6 x 210 mm (H x W x D)
With boards 232 mm (D)
With boards and connector 280 mm (D)
Weight 2.6 kg
Rack
3 U, 9 slots according to DIN 41494; 1 slot =
20.32 mm
Dimensions 132.8 x 192 x 178 mm (H x W x D)
With boards 198 mm (D)
With boards and front connectors 248 mm (D)
Weight 1.4 kg
1KGT151098 V003 1 5
Racks Rack mounted Modules
Rack
19“, 3 U, 21 s according DIN 41494,
1s = 20,32 mm.
Dimensions 132,8 x 482,6 x 190,5 mm (H x W x D)
Mounting depth with boards 212 mm
Mounting depth with boards and front plugs 260 mm
Weight 3,7 kg
The power supply units 560MPR01 and 560MPR03 may be used in the racks 560SFR02 and
560MPR03.
All power supply units occupy 2 slots (8 R), and are able to operate in parallel mode (560SFR02 or
560MPR03 only).
The following table shows the technical features of the power supply units. For more information,
see [1], [2], and [3].
6 1KGT151098 V003 1
Rack mounted Modules Power supply units
1KGT151098 V003 1 7
Communication units of the 560CMU0x type Rack mounted Modules
The following table shows the technical features of the power supply units. For more information,
see [1], [2], and [4].
8 1KGT151098 V003 1
Rack mounted Modules Input/output modules
• 560BCU05
In addition, bus connection units are used to connect the following signals:
• Alarm relay output
• Warning relay output
• Time synchronization input
• Time synchronization output
• Redundant power supply failure
The following table shows the technical features of the bus connection units. For more information,
see [1], [2], and [3].
All input/output modules have a direct connection to the Serial Peripheral Bus (SPB) through the
backplane connector.
The following table shows the technical features of the binary input module 560BIR01:
1KGT151098 V003 1 9
Input/output modules Rack mounted Modules
isolated by opto-couplers
Nominal input voltage 110... 125 V DC (+/- 20%)
Max. input voltage 150 V DC
Input current 1.0... 1.6 mA constant
Logical ‘1’ definitely detected ≥ 85 V DC
Logical ‘0’ definitely detected ≤ 45 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 120 Hz
The module 560BIR01 is able to process the following types of signals or a combination of them:
• 16 single point information with time stamp (SPI)
• 8 double point information with time stamp (DPI)
• 2 digital measured values each with 8 bit (DMI8)
• 1 digital measured value with 16 bit (DMI16)
• 16 integrated totals (max. 120 Hz) (ITI)
• 2 step position information each with 8 bit (STI)
• 2 bitstring input each with 8 bit (BSI8)
• 1 bitstring input with 16 bit (BSI16)
• or combinations of this signal types
The following table shows the technical features of the binary output module 560BOR01:
The module 560BOR01 can be used for the control of 16 binary process signals using relay
contacts. The allocation of an output signal to the processing functions can be done according to
the rules of configuration.
10 1KGT151098 V003 1
Rack mounted Modules Input/output modules
• Single or double commands (SCO or DCO) with 1.5 or 2 pole output with (1 out of n) check
• Regulation step command (RCO), 1 or 2 pole
• Digital setpoints commands, 8 or 16 Bit without strobe (DSO8 or DSO16)
• Digital setpoint commands, 8 or 16 Bit with strobe (DSO8 or DSO16)
• Bitstring output, 1, 2, 8 or 16 Bit (BSO1, BSO2, BSO8 or BSO16)
The command supervision module 23BA23 is used in combination with the binary output module
23BA20 for 1-out-of-n checks.
The following table shows the technical features of the command supervision module 23BA23:
The following table shows the technical features of the analog input module 560AIR01:
50 Ω @ ±10 to ±40 mA
1KGT151098 V003 1 11
Input/output modules Rack mounted Modules
40 mA continuous @ ±2 and ±5 mA
38 V/ 0.5 mA @ ±2 and 20 V DC
Resolution 12 bit + sign
11 bit + sign @ ±2 V DC
AD converter resolution 16 bit
Accuracy at 25 °C ≤ 0.1 %
≤ 0.2 % @ ±2 V DC
Linearity error at 25 °C ≤ 0.1 %
Temperature drift ≤ 100 ppm/K (0... 70 °C)
Max. common mode input voltage ±8 V DC (functional limit)
Max. differential input voltage ± 4 V DC (current input)
± 38 V DC (voltage input)
Common mode rejection > 70 dB @ 25 °C
> 60 dB @ 0… 25 °C
Configurable line frequency fN • 16.7 Hz
• 50 Hz
• 60 Hz
Line frequency interference suppression > 100 dB @ fN ±2 %
> 45 dB @ fN ±10 %
The following table shows the technical features of the analog input module 560AIR02:
12 1KGT151098 V003 1
Rack mounted Modules Input/output modules
±8 V DC (functional limit)
Max. differential input voltage ± 4 V DC (current input)
Common mode rejection > 70 dB @ 25 °C
> 60 dB @ 0… 25 °C
Configurable line frequency fN • 16.7 Hz
• 50 Hz
• 60 Hz
Line frequency interference suppression > 100 dB @ fN ±2 %
> 45 dB @ fN ±10 %
The following table shows the technical features of the binary output module 23AA21.
1KGT151098 V003 1 13
Communication modules Rack mounted Modules
The fiber optical coupler 23OK24 has a direct connection to the Serial Peripheral Bus (SPB)
through the back connector.
The other communication modules do not have a direct connection to the Serial Peripheral Bus
(SPB).
The following table shows the technical features of the fiber optical coupler 23OK24.
Feature Description
No. of channels 2
Fiber type Glass fiber 62.5 / 125 µm
Multi-mode
Wave length 820 nm
Transmission length Max. 2,600 m
Electrical interface RS485
Additional information RS232C to RS485 converter
Table 6: Analog output module 23OK24 – Technical features
14 1KGT151098 V003 1
Rack mounted Modules Communication modules
The following table shows the technical features of the FSK modems of the 23WTxx type.
4-wire transmission
Duplex transmission
Half-duplex transmission
No. of channels 1 1 24
Comments Use only in pairs or
in combination with
500FSD11
Table 7: Technical features: FSK modems of the 23WTxx type
The following table shows the technical features of the unmanaged network switches of the
560NUSxx type.
Optical: 40 km
Table 8: Technical features: Unmanaged network switches of the 560NUSxx type
The following table shows the technical features of the managed network switches of the
560NMSxx type.
1KGT151098 V003 1 15
Real-Time Clock 560RCR01 Type Rack mounted Modules
The real-time clock 560RCR01 can be mounted to any rack of the RTU500 system.
The following table shows the technical features of the real-time clock 560RCR01.
Feature 560RCR01
Input signal GPS
Limitations No
Table 10: Technical features: Real-time clock of type 560RCR01
16 1KGT151098 V003 1
DIN Rail mounted Modules Overview
3.1 Overview
DIN rail-mounted modules are 'standalone' modules that have a serial connection or another type of
connection to other modules in the configuration.
Depending on their mounting type, DIN rail-mounted modules can be mounted to different housing
configurations:
• Base modules
• Base modules with local I/O
• Input modules
• Output modules
• Input/output modules with up to 4 I/O boards
• Additional modules like Power supply units, modems, etc.
The following table shows the technical features of the power supply units. For more information,
see [1], [2], and [3].
(see chapter
"Binary input mod-
ule 23BE40" and
following)
Table 11: Technical features: Power supply units
1KGT151098 V003 1 17
Adapter Modules DIN Rail mounted Modules
• RTU520
° 520CMD01
• RTU530
° 530CID01 (with local I/O)
° 530CID02 (with local I/O)
Base modules have no connection to the RTU500 system bus. They can only be used in
standalone mode.
The following table shows the technical features of the base modules. For more information, see [1],
[2], and [4].
Always mount the adapter modules to the first slot in a rack at the right side.
18 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
Multimeter modules:
• 560CVD03
• 500CVD90
1KGT151098 V003 1 19
Input/Output Modules DIN Rail mounted Modules
The following table shows the technical features of the binary input module 23BE40.
isolated by opto-couplers
Nominal input voltage 110... 125 V DC (+/- 20%)
Max. input voltage 150 V DC
Input current Chopped with 1kHz: average 0.4 mA
Logical ‘1’ definitely detected ≥ 85 V DC
Logical ‘0’ definitely detected ≤ 45 V DC
Oxide film breaking 10 mA for 10 ms
5 ms for changes < 30 sec
Max. number of simultaneous active inputs all inputs
Reverse voltage protection yes
Max. input frequency for integrated totals 25 Hz
isolated by opto-couplers
Nominal input voltage 220... 250 V DC (+/- 20%)
Max. input voltage 300 V DC
Input current Chopped with 1kHz: average 0.4 mA
Logical ‘1’ definitely detected ≥ 168 V DC
Logical ‘0’ definitely detected ≤ 144 V DC
20 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The module 23BE40 is able to process the following types of signals or a combination of them:
• 16 single point information with time stamp (SPI)
• 8 double point information with time stamp (DPI)
• 2 digital measured values each with 8 bit (DMI8)
• 1 digital measured value with 16 bit (DMI16)
• 16 integrated totals (max. 25 Hz) (ITI)
• 2 step position information each with 8 bit (STI)
• 2 bitstring input each with 8 bit (BSI8)
• 1 bitstring input with 16 bit (BSI16)
• or combinations of this signal types
The following table shows the technical features of the binary input module 23BE50.
isolated by opto-couplers
Nominal input voltage 24... 60 V DC (+/- 20%)
Max. input voltage 72 V DC
Input current 1,5 mA constant
Logical ‘1’ definitely detected ≥ 18 V DC
Logical ‘0’ definitely detected ≤ 9 V DC
Max. input frequency for integrated totals 120 Hz
The module 23BE50 is able to process the following types of signals or a combination of them:
• 64 single point information with time stamp (SPI)
• 32 double point information with time stamp (DPI)
• 8 digital measured values each with 8 bit (DMI8)
• 4 digital measured value with 16 bit (DMI16)
• 64 integrated totals (max. 120 Hz) (ITI)
• 8 step position information each with 8 bit (STI)
• 8 bitstring input each with 8 bit (BSI8)
• 4 bitstring input with 16 bit (BSI16)
• or combinations of this signal types
1KGT151098 V003 1 21
Input/Output Modules DIN Rail mounted Modules
The following tables shows the technical features of the binary input module 520BID01:
isolated by opto-couplers
Nominal input voltage 24... 60 V DC (+/- 20%)
Max. input voltage 72 V DC
Input current 1.5... 5 mA
Logical ‘1’ definitely detected ≥ 18 V DC
Logical ‘0’ definitely detected ≤ 9 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 25 Hz
isolated by opto-couplers
Nominal input voltage 110... 125 V DC (+/- 20%)
Max. input voltage 150 V DC
Input current 1.2... 2 mA
Logical ‘1’ definitely detected ≥ 85 V DC
Logical ‘0’ definitely detected ≤ 45 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 25 Hz
The module 520BID01 is able to process the following types of signals or a combination of them:
• 16 single point information with time stamp (SPI)
• 8 double point information with time stamp (DPI)
• 2 digital measured values each with 8 bit (DMI8)
• 1 digital measured value with 16 bit (DMI16)
• 16 integrated totals (max. 25 Hz) (ITI)
• 2 step position information each with 8 bit (STI)
• 2 bitstring input each with 8 bit (BSI8)
• 1 bitstring input with 16 bit (BSI16)
• or combinations of this signal types
22 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The following tables shows the technical features of the binary input module 530BID01:
isolated by opto-couplers
Nominal input voltage 24... 60 V DC (+/- 20%)
Max. input voltage 72 V DC
Input current 1.2... 5 mA
Logical ‘1’ definitely detected ≥ 18 V DC
Logical ‘0’ definitely detected ≤ 9 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 120 Hz
isolated by opto-couplers
Nominal input voltage 110... 125 V DC (+/- 20%)
Max. input voltage 150 V DC
Input current 1.4... 2.1 mA
Logical ‘1’ definitely detected ≥ 85 V DC
Logical ‘0’ definitely detected ≤ 45 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 120 Hz
1KGT151098 V003 1 23
Input/Output Modules DIN Rail mounted Modules
The module 530BID01 is able to process the following types of signals or a combination of them:
• 16 single point information with time stamp (SPI)
• 8 double point information with time stamp (DPI)
• 2 digital measured values each with 8 bit (DMI8)
• 1 digital measured value with 16 bit (DMI16)
• 16 integrated totals (max. 120 Hz) (ITI)
• 2 step position information each with 8 bit (STI)
• 2 bitstring input each with 8 bit (BSI8)
• 1 bitstring input with 16 bit (BSI16)
• or combinations of this signal types
The following tables shows the technical features of the binary input output module 530IOD01:
isolated by opto-couplers
Nominal input voltage 24... 60 V DC (+/- 20%)
Max. input voltage 72 V DC
Input current 1.2... 5 mA
Logical ‘1’ definitely detected ≥ 18 V DC
Logical ‘0’ definitely detected ≤ 9 V DC
Reverse voltage protection yes
Max. input frequency for integrated totals 120 Hz
24 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The following table shows the technical features of the binary output module 23BA40.
1KGT151098 V003 1 25
Input/Output Modules DIN Rail mounted Modules
The following table shows the technical features of the binary output module 520BOD01:
The following table shows the technical features of the binary output module 530BOD01:
26 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The following table shows the technical features of the binary outputs of the 520CSD01 module:
The command supervision module 520CSD01 is used in combination with the binary output module
520BOD01 for 1-out-of-n checks.
1KGT151098 V003 1 27
Input/Output Modules DIN Rail mounted Modules
The following table shows the technical features of the command supervision function of the module
520CSD01:
The following table shows the technical features of the analog input module 520AID01:
R0002:
• ± 1 V DC
• ± 10 V DC
Input impedance 50 ΩR0001
82 kΩ R0002
Max. load 50 mA for 1 min
Resolution 11 bit + sign
≤ 0,5 % @ ±1 V DC
≤ 1% @ ±10 V DC
Linearity error at 25 °C ≤ 0.15 % (positive range)
28 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
10 V DC (voltage inputs)
Common mode rejection > 85 dB @ 25 °C
Configurable line frequency fN • 16.7 Hz
• 50 Hz
• 60 Hz
Line frequency interference suppression > 75 dB @ fN ±5 %
The following table shows the technical features of the PT100 module 520PTD01
Input Channels
Inputs 6 differential inputs PT100,
2/4 wire connection
Measuring range ± 200 °C
A/D converter 12 bit = ± 100%
resolution:
Temp. range -25 ºC … 150 ºC
Overrange -200 ºC … 200 ºC
Accuracy ± 1 ºC (-25 ºC … 125 ºC)
+2 … -0 ºC (125 ºC .. 150 ºC)
Common mode Absolute maximum rating
voltage ± 150 V DC.
Common mode rejection
85 db
Power Supply rejection
75 db at 50 Hz
Line frequency (fN) 16.7, 50 or 60 Hz
The following table shows the technical features of the analog input module 530AID01:
1KGT151098 V003 1 29
Input/Output Modules DIN Rail mounted Modules
> 60 dB @ 0… 25 °C
Configurable line frequency fN • 16.7 Hz
• 50 Hz
• 60 Hz
Line frequency interference suppression > 100 dB @ fN ±2 %
> 45 dB @ fN ±10 %
The following table shows the technical features of the PT100 module 530PTD01
30 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The following table shows the technical features of the analog output module 520AOD01:
– ± 1.25 V DC
– ± 2.5 V DC
– ± 5 V DC
– ± 10 V DC
1KGT151098 V003 1 31
Input/Output Modules DIN Rail mounted Modules
The following table shows the technical features of the analog output module 530AOD01:
32 1KGT151098 V003 1
DIN Rail mounted Modules Input/Output Modules
The following table shows the technical features of the multimeter 560CVD03.
Feature Description
Input voltages 3 pole: 85...400 V AC
Input currents 3 pole: R00x1: 1 A
R00x5: 5 A
Display R002x / R004x: no display
Power factor
Frequency
Calculated energy values Active / apparent energy
Phase rotation
Power supply R002x / R003x: 24...48 V DC
The following table shows the technical features of the multimeter 500CVD90.
Feature Description
Input voltages 4 pole: 10...300 V AC
Input currents 4 pole: R00x1: 1 A, R00x5: 5 A
Table 16: Multimeter 500CVD90 – Technical features
1KGT151098 V003 1 33
Communication modules DIN Rail mounted Modules
Feature Description
Additional values Power (active/reactive/apparent)
Power factor
Frequency
Calculated energy values Energy (active/reactive/inductive/capacitive)
Total harmonic distortion (THD)
Phase rotation
Additional functions Directional fault current detection
Power supply R002x: 20...60 V DC
R004x: 80...260 V AC, 80...330 V DC
Application Direct interface to current and voltage transform-
ers
Directional fault current detection
Overcurrent detection
Table 16: Multimeter 500CVD90 – Technical features
The following table shows the technical features of the FSK modems.
4-wire transmission
Full-duplex transmission
Half-duplex transmission
No. of channels 1 1 24 @ 50 bps
Power supply 24…60 V DC
Table 17: Technical features: FSK modems
34 1KGT151098 V003 1
DIN Rail mounted Modules Communication modules
For EDS500 analog modems portfolio details see EDS500 Brochure 500FSD Analog Modems
(1KGT151032).
Modem data
Frequency bands 2G • GSM 850 MHz
• E-GSM 900 MHz
• DCS 1800 MHz
• PCS 1900 MHz
Frequency bands 3G B1, 2, 5, 8, 19
Network standards GSM/ GPRS/ EDGE/ UMTS/ HSPDA/ HSUPA/
HSPA+
SIM card Mini-SIM: ISO/IEC 7810 ID-000, form factor 2FF
Antenna interfaces 50 Ω SMA-RF connector (female)
Serial interface
Connector DB9 female
Type RS-232C
Bit rate 1200 to 115 200 bps
Signal lines RxD, TxD, RTS, CTS, GND
Interface protocol • AT-commands (Hayes 3GPP 27.007 and
27.005)
• PPP according to RFC 1661 (IETF STD51)
1KGT151098 V003 1 35
Communication modules DIN Rail mounted Modules
The following table shows the technical features of the managed switches.
For EDS500 Ethernet and DSL switch portfolio details see EDS500 Brochure Ethernet and DSL
switches (1KGT151031) and EDS500 Manual - Part 1: Devices (1KGT150966).
36 1KGT151098 V003 1
Module comparison Overview
4 Module comparison
4.1 Overview
Rack mounted modules can be combined with DIN rail mounted modules in a configuration. For
limitations and examples, refer to [4] and [5].
This chapter describes the technical differences between the input/output modules.
ADVICE
Always refer to the relevant Hardware Data Sheet for detailed information.
• R: Rack mounting
• D: DIN Rail mounting
1KGT151098 V003 1 37
Analog input modules Module comparison
11 bit + sign
@ ±2 V DC
Table 21: Feature comparison: Analog input modules
38 1KGT151098 V003 1
Glossary
5 Glossary
AC Alternating Current
AD Active Directory
dB Decibel
DC Direct Current
GND Ground
Max Maximum
ms Millisecond
1KGT151098 V003 1 39
Glossary
SPB Serial Peripherial Bus is the RTU I/O bus used with RS485 or fibre
optical media
40 1KGT151098 V003 1
1KGT151098 V003 1 41
Note:
The specifications, data, design or other information contained in this document (the “Brochure”)
- together: the “Information” - shall only be for information purposes and shall in no respect be
binding. The Brochure does not claim to be exhaustive. Technical data in the Information are only
approximate figures. We reserve the right at any time to make technical changes or modify the
contents of this document without prior notice. The user shall be solely responsible for the use of
any application example or information described within this document. The described examples
and solutions are examples only and do not represent any comprehensive or complete solution.
The user shall determine at its sole discretion, or as the case may be, customize, program or add
value to the Hitachi ABB Power Grids products including software by creating solutions for the
end customer and to assess whether and to what extent the products are suitable and need to be
adjusted or customized.
This product is designed to be connected to and to communicate information and data via a network
interface. It is the users sole responsibility to provide and continuously ensure a secure connection
between the product and users or end customers network or any other network (as the case may
be). The user shall establish and maintain any appropriate measures (such as but not limited to the
installation of firewalls, application of authentication measures, encryption of data, installation of
anti-virus programs, etc) to protect the product, the network, its system and the interface against
any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of
data or information. Hitachi ABB Power Grids is not liable for any damages and/or losses related
to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of
data or information.
Hitachi ABB Power Grids shall be under no warranty whatsoever whether express or implied and
assumes no responsibility for the information contained in this document or for any errors that
may appear in this document. Hitachi ABB Power Grids's liability under or in connection with this
Brochure or the files included within the Brochure, irrespective of the legal ground towards any
person or entity, to which the Brochure has been made available, in view of any damages including
costs or losses shall be excluded. In particular Hitachi ABB Power Grids shall in no event be liable
for any indirect, consequential or special damages, such as – but not limited to – loss of profit,
loss of production, loss of revenue, loss of data, loss of use, loss of earnings, cost of capital or
cost connected with an interruption of business or operation, third party claims. The exclusion of
liability shall not apply in the case of intention or gross negligence. The present declaration shall
be governed by and construed in accordance with the laws of Switzerland under exclusion of its
conflict of laws rules and of the Vienna Convention on the International Sale of Goods (CISG).
Hitachi ABB Power Grids reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in part -
is not permitted without the prior written consent of Hitachi ABB Power Grids.
42 1KGT151098 V003 1