F and G:

- Resumed working on some pending punch list.

Observations:

- Threshold values for GD and H2S detectors are lower compared to our existing P/F. For gas detector
(HA: 20 PPM, HHA: 40 PPM) and H2S detector (HA: 5% , HHA: 10%).
- IF one GD activated ( HA or HHA) in one fire zone alarm will received only on HMI, no audible alarm.
- IF one GD activated (HHA) and 2 or more detectors are surpress or inhibited in one fire zone, will
initiate ESD-1 on JA P/F, audible alarm.
- IF 3 or more GD detectors in one fire zone gets faulty will initiate ESD-1 on JA P/F, audible alarm.
- For any Manual call points activation there will be no audible alarm and alarm will received on HMI.
- For single low H2S detection (High alarm) within JA P/F including inside WHCP will initiate audible
alarm, activate crane alarm lamp, activate strobe light and warning lights.
- For single high H2S detection (high high alarm) within JA P/F including inside the WHCP will initiate
audible alarm, activate strobe light and warning lights.

For confirmed gas detection (2OON) with any outdoor fire area, following actions initiated:
- Activate PA/GA fire and gas detection alarm.
- Initiate ESD-1 on JA P/F.
- Initiate electrical isolation of Non-zone 1 equipment on JA platfom.
- Activate all JA P/F strove lights and warning lights.
- Reduce radio power transmission.

HVAC shall tripped and all fire dampers will close by FGS in case of below causes:
- Confirmed fire on battery room, instrument and electrical room (2OON).
- Confirmed HC gas within any indoor area (2OON).
- Confirmed H2S gas detection at air intake A, B and air locks (2OO3). No ESD-1 activation.
- Confirmed smoke detection at both air intakes (A and B) (2OON).

HVAC Gas tight dampers will closed in case of below causes:


- Confirmed HC gas within any indoor area (2OON).
- Confirmed H2S gas detection at air intake A, B and air locks (2OO3).
- Confirmed smoke detection at both air intakes (A and B) (2OON).