You are on page 1of 36

ZXDU58 B121

DC Power System
Product Description

Version: V4.5R99M05

ZTE CORPORATION
NO. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://ensupport.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright © 2012 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit ZTE technical support website http://ensupport.zte.com.cn to inquire related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.0 2011-08-22 First edition

Serial Number: SJ-20110729161742-002

Publishing Date: 2011-08-22 (R1.0)

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Contents
About This Manual ......................................................................................... I
Chapter 1 System Overview ...................................................................... 1-1
1.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-1
1.3 Implementation Example .................................................................................... 1-2

Chapter 2 System Structure ...................................................................... 2-1


2.1 Overall System Structure .................................................................................... 2-1
2.2 Power Distribution Unit ....................................................................................... 2-2
2.3 Grounding Design .............................................................................................. 2-3
2.4 Slot Configuration............................................................................................... 2-3

Chapter 3 System Modules........................................................................ 3-1


3.1 ZXD030 S480 Rectifier ....................................................................................... 3-1
3.1.1 Rectifier Parts .......................................................................................... 3-1
3.1.2 Rectifier Indicators.................................................................................... 3-1
3.1.3 Rectifier Electrical Specifications ............................................................... 3-2
3.1.4 Output Power Control ............................................................................... 3-3
3.2 Monitoring Unit................................................................................................... 3-4
3.2.1 CSU Parts ............................................................................................... 3-4
3.2.2 CSU Indicators......................................................................................... 3-4
3.2.3 CSU Software .......................................................................................... 3-5

Chapter 4 System Specifications.............................................................. 4-1


4.1 System Configuration ......................................................................................... 4-1
4.2 Technical Specifications...................................................................................... 4-2
4.3 Compliance Standards ....................................................................................... 4-4

Appendix A Signal Interfaces on the UIB................................................ A-1


Chapter 5 Dimensions................................................................................ 5-1
Appendix B Electrical Connection Diagram ........................................... B-1
Appendix C Documentation Guide .......................................................... C-1
Glossary .......................................................................................................... I

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


II

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


About This Manual
Purpose
This manual applies to the ZXDU58 B121 (V4.5R99M05) DC Power System. The
ZXDU58 B121 system is designed to be installed in a cabinet and provides power for -48
V communication equipment. This manual describes the system structure, characteristics
and application.

Intended Audience
This manual is intended for:
l Planning engineers
l Maintenance engineers

What Is in This Manual


This manual contains the following chapters/appendixes:

Chapter/Appendix Summary

Chapter 1, System Overview Introduces the system, typical operating configurations and
describes the system features.

Chapter 2, System Structure Describes the external system structure, internal system
structure and signal interfaces.

Chapter 3, System Modules l Describes the parts, indicators, and specifications of


the rectifier.
l Describes the appearance, indicators, functions,
operations and specifications of the monitoring unit.

Chapter 4, System Specifications Provides the technical specifications and compliant standards
of the system.

Appendix A, Signal Interfaces on the Describes the interfaces on the User Interface Board (UIB).
UIB

Appendix B, Dimensions Provides the dimensions of the chassis.

Appendix C, Electrical Connection Provides the electrical connection diagram of the system.
Diagram

Appendix D, Documentation Guide Lists the manual suite of the system.

Conventions
This document uses the following typographical conventions.

Typeface Meaning

Italics Refers to other related manuals and documents.


I

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Typeface Meaning

Bold Menus, menu options, function names, input fields, option button names, check
boxes, drop-down lists, dialog box names, window names, parameters and
commands.

CAPS Keys on the keyboard, buttons on screens and company name.

Danger: Indicates an imminently hazardous situation, which if not avoided,


will result in death or serious injury.

Warning: Indicates a hazard that, if not avoided, could result in serious injuries,
equipment damages or interruptions of major services.

Caution: Indicates a potential hazard that, if not avoided, could result in


moderate injuries, equipment damages or partial service interruption.

Note: Provides additional information about a certain topic.

II

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 1
System Overview
Table of Contents
System Introduction....................................................................................................1-1
System Features ........................................................................................................1-1
Implementation Example ............................................................................................1-2

1.1 System Introduction


The ZXDU58 B121 system is designed to be installed in a cabinet. The system can
provide -48 V power for mobile base stations, access network equipment, remote switch
offices, transmission equipment, ground satellite transceiver stations, and microwave
communication devices.
When fully configured, the ZXDU58 B121 system is equipped with three ZXD030 S480
(V1.10) rectifiers, which form a power system with rated output current of 90 A.
Figure 1-1 shows the ZXDU58 B121 appearance.

Figure 1-1 ZXDU58 B121 Appearance

1.2 System Features


The ZXDU58 B121 system has the following features:
l A wide range of input phase voltage (90V AC - 264V AC) makes the system suitable
for areas with unstable voltage.
l The ZXDU58 B121 chassis contains the power distribution unit, rectifiers, and
monitoring unit.

1-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

l The ZXDU58 B121 system supports multiple networking modes, such as RS232,
RS485.
l Hot-pluggable rectifiers.
l Intelligent monitoring unit.
l High reliability with Mean Time Between Failures (MTBF) ≥ 2.2 × 105 h.
l Compact structure design. The ZXDU58 B121 chassis is 5 U in height and 19 inches
in width. It is designed to be installed into a main equipment.
l Cable connections are performed in front of the equipment.

1.3 Implementation Example


The ZXDU58 B121 system is designed to be installed in a cabinet.
For the implementation example of the system, see Figure 1-2.

Figure 1-2 Implementation Example of the System

• AC input mode:
three-phase, five-wire
(L1/L2/L3/N/PE)

1-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 2
System Structure
Table of Contents
Overall System Structure............................................................................................2-1
Power Distribution Unit ...............................................................................................2-2
Grounding Design ......................................................................................................2-3
Slot Configuration.......................................................................................................2-3

2.1 Overall System Structure


The ZXDU58 B121 system consists of the ZXD030 S480 rectifiers, monitoring unit, and
power distribution unit. Figure 2-1 shows the appearance and its components.

Figure 2-1 System Structure

2-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

2.2 Power Distribution Unit


The AC distribution part of the ZXDU58 B121 system consists of the AC input/output circuit
breakers and AC Surge Protection Device (SPD). The DC distribution part of the system
consists of the DC output circuit breakers and battery circuit breakers.
Figure 2-2 shows the power distribution unit of the system.

Figure 2-2 Power Distribution Unit

• This image is for reference


only. The actual product
may differ.

The following describes the components of the DC distribution part:


l Battery circuit breakers: Two battery packs are configured in the ZXDU58 B121
system.
l DC output circuit breakers: The number and capacity of breakers vary with specific
contracts.
DC output is comprised of LLVD1 and LLVD2. Primary loads are connected to LLVD2
and secondary loads to LLVD1.

The detection cables marked with F1** and F10E* (optional) belong to LLVD1. The
detection cables marked with F2** belong to LLVD2.
Figure 2-3 shows the terminals.

2-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 2 System Structure

Figure 2-3 Electrical Connection Terminals

• This image is for reference


only. The actual product
may differ.

2.3 Grounding Design


On the installation site, the PE bolt of the ZXDU58 B121 system should be connected to
the PE busbar of the site to protect the equipment against damage and avoid personal
injury.
Figure 2-4 shows the grounding design of the system.

Figure 2-4 Grounding Design of the System

2.4 Slot Configuration


Figure 2-5 shows the slot configuration.

2-3

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Figure 2-5 Slot Configuration

• SMR = Switching Mode


Rectifier

2-4

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 3
System Modules
Table of Contents
ZXD030 S480 Rectifier...............................................................................................3-1
Monitoring Unit ...........................................................................................................3-4

3.1 ZXD030 S480 Rectifier


3.1.1 Rectifier Parts
In the ZXDU58 B121 system, the rectifiers convert AC to DC.

For the appearance and structure of the ZXD030 S480 rectifier, see Figure 3-1.

Figure 3-1 ZXD030 S480 Rectifier

3.1.2 Rectifier Indicators


For the indicators of the rectifier, see Figure 3-2. For a description of the working status of
the indicators, refer to Table 3-1.
l Normally, only the power indicator is lit.
l In case that output current limit occurs, the power indicator flashes.
l In case that a system fault occurs, the alarm indicator is lit. For example, in case of
under-voltage protection, the power indicator is not lit and the alarm indicator is lit.
l In case a rectifier fault occurs, the fault indicator is lit.
l When the power and alarm indicators flash at the same time, a program is being
downloaded.

3-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Figure 3-2 Rectifier Indicators

Table 3-1 Status Indication

Indicator Normal Sta- Abnormal Indication


tus Status

Power Lit Not lit No AC input or the AC input voltage is lower


(green) than 75 V.

Flashing Output current limit

Alarm Not lit Lit l AC input over/under-voltage


(yellow) l PFC output over/under-voltage
l Over-temperature

Flashing l Fast flashing: The communication


between the rectifier and the Centralized
Supervision Unit (CSU) is interrupted.
l Slow flashing: The rectifier is in the sleep
mode.

Fault Not lit Lit l DC output over-voltage/current


(red) l Output fuse blows
l Fan fault
l Other fault

3.1.3 Rectifier Electrical Specifications


For a description of the specifications of ZXD030 S480 rectifier, refer to Table 3-2.

Table 3-2 Electrical Specifications of the ZXD030 S480 Rectifier

Item Specifications

AC input mode Single-phase three-wire (L/N/PE)

AC input voltage Rated input voltage: 100 V - 240 V, range: 85 V to 295 V

DC output voltage Rated output voltage: 53.5 V, range: 42 V - 58 V

Output current limit 3 A - 35 A (adjustable)


After current limited occurred, flyback proceeds when the output voltage
falls below 40 VDC.

Output power Rated output power: 1605 W; maximum output power: 1740 W

3-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Modules

3.1.4 Output Power Control


To ensure reliable operation, the output power of the ZXD030 S480 rectifier varies with the
AC input voltage and DC output voltage.

Power Control by AC Input


For the relation between the output power and the AC input voltage, see Figure 3-3.
l When the AC input voltage falls in the range of 165 VAC ~ 295 VAC, the maximum
output power of the rectifier is 1740 W.
l When the AC input voltage falls in the range of 85 VAC ~ 165 VAC, the maximum
output power of the rectifier varies linearly with the AC input voltage.

Figure 3-3 Output Power Versus AC Input Voltage

Power Control by DC Output


In the case of the AC input voltage falls in the range 165 VAC ~ 295 VAC with the
maximum output power 1740 W provided, if the load keeps increasing, the output voltage
will decrease. And the maximum output power decreases consequently. For a detailed
curve, see Figure 3-4.
l When the output voltage falls in the range of 50 VDC ~ 58 VDC, the output power is
1740 W. For example, when the DC output voltage is 58 VDC, the output current is
30 A; when the DC output voltage is 58 VDC, the output current is 34.8 A.
l When the output voltage falls in the range of 40 VDC ~ 50 VDC, the rectifier provides
a constant output current 34.5 A. And the maximum output power falls linearly with
the output voltage.
l When the output voltage falls down 40 VDC, the output voltage and current start
flyback process.

3-3

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Figure 3-4 Output Power Versus DC Output Voltage

3.2 Monitoring Unit


3.2.1 CSU Parts
The CSU manages the power distribution unit, rectifiers and batteries of the ZXDU58 B121
system.
Figure 3-5 shows the appearance and structure of the CSU.

Figure 3-5 Centralized Supervision Unit

• PWR: Power indicator • RUN: Running indicator • ALM: Alarm indicator

3.2.2 CSU Indicators


Figure 3-6 shows the indicators of the CSU. Table 3-3 describes the indicators.

Figure 3-6 CSU Indicators

3-4

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Modules

Table 3-3 CSU Indicators

Designation Name Description

PWR Power indicator Lit (green): The CSU is powered.

RUN Run indicator Flashing (green): The CSU is running normally.

Lit (red): A fault occurs to the system. For example,


ALM Alarm indicator
the AC input fails, or some rectifier is faulty.

3.2.3 CSU Software


CSU software version: V1.20F.

Users can perform the following operations through the CSU:


l Setting parameters
l Querying system operation data, alarms and records
l Setting the operational mode (work mode)
l Managing alarms, batteries and rectifiers
l Starting Manual Detect

Note:
For details of these operations, refer to the ZXDU58 B121 (V4.5R99) DC Power System
Operation and Maintenance Manual.

3-5

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

This page intentionally left blank.

3-6

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 4
System Specifications
Table of Contents
System Configuration .................................................................................................4-1
Technical Specifications .............................................................................................4-2
Compliance Standards ...............................................................................................4-4

4.1 System Configuration


Table 4-1 describes the ZXDU58 B121 system configuration.

Table 4-1 System Configuration

Item Configuration

AC Power AC input l Three-phase five-wire (L1/L2/L3/N/PE)


Distribution l AC input Miniature Circuit Breaker (MCB)
20A/4P

AC output MCB 1*6 A

AC Surge Protection Class C SPD


Device (SPD)

DC Power Battery input MCBs 2*100 A


Distribution
DC output l Rated DC output current: 90 A
l DC output MCBs:

à Load Low Voltage Disconnect (LLVD) 1 :


1*100 A + 1*63 A MCBs

à LLVD2 : 1*32 A + 1*10 A MCBs

Emergency light None

DC SPD None

Chassis One chassis, which is designed to be installed in a


cabinet

Rectifier ZXD030 S480 (V1.10) rectifiers; three sets


(maximum)

Monitoring unit One set

Other components l LLVD1 contactor and LLVD2 contactor


l Two battery temperature sensors and cables

• This table is for reference only. The actual product may differ.

4-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

4.2 Technical Specifications


Table 4-2 describes the technical specifications of the ZXDU58 B121 system.

Table 4-2 Technical Specifications

Item Specification

Working Environment

Operating temperature -20 ℃ to +55 ℃

Storage temperature -40℃ to +70℃

Relative humidity 10% to 90% (non-condensing); 40% to 60%


recommended

Air pressure 70 kPa to 106 kPa

Other requirements No conductive dusts or corrosive gases

No explosion hazard, no shake or jolt

Ground slope is no more than 5°

AC Power Distribution

AC input mode Three-phase five-wire (L1/L2/L3/N/PE)

AC input voltage l Range: 90 V - 264 V


l Output current limit of each rectifier is 3 A ~ 35 A
(adjustable). In case of current limit , flyback occurs
when the output voltage falls to 40 V.

AC input frequency 50/60 Hz

Maximum AC input current 15 A

AC input power factor ≥ 0.99 (with full load)

AC Surge Protection Device (SPD) Class C SPD, with discharging current ≤ 40 kA

DC Power Distribution

DC output voltage l Rated output voltage: -53.5 V


l Range: -42 V to -58 V

Rated DC output current 90 A (in full configuration with three ZXD030 S480
rectifiers)

Maximum output power 5 kW

Source effect ≤ 0.1%

Load effect ≤ 0.5%

Regulated voltage precision ≤ 0.6%

Weighted noise voltage < 1 mV

Peak-peak noise voltage ≤ 100 mV

4-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 4 System Specifications

Item Specification

Broad frequency noise voltage ≤ 30 mV (3.4 kHz~150 kHz)


≤ 20 mV (0.15 MHz~30 MHz)

Discrete frequency noise voltage ≤ 5 mV (3.4 kHz~150 kHz)


≤ 3 mV (150 kHz~200 kHz)
≤ 2 mV (200 kHz~500 kHz)
≤ 1 mV (0.5 MHz~30 MHz)

DC voltage drop < 500 mV

Rated output power of the rectifier 1605 W

Maximum output power of the rectifier 1740 W

Rectifier efficiency ≥ 91% (50% - 100% output power)

Load sharing quality of the rectifiers The difference between the maximum current and
minimum current is less than 1.5 A (with 10% of rated
load or above)

Alarm Threshold and Precision of the Monitoring Unit

AC Vol. Max. Default: (286 ± 5) V

Threshold of recovery from AC Default: (276 ± 5) V


over-voltage alarm

AC Vol.Min. Default: (154 ± 5) V

Threshold of recovery from AC Default: (164 ± 5) V


under-voltage alarm

DC Vol.Max. Default: (58 ± 0.2) V

Threshold of recovery from DC Default: (57.5 ± 0.2) V


over-voltage alarm

DC Vol.Min. Default: (48.0 ± 0.2) V

Threshold of recovery from DC Default: (48.5 ± 0.2) V


under-voltage alarm

BatVol Min. Default: (47.0 ± 0.2) V

Precision of AC voltage ±1%

Precision of the battery current and the out- ±1%


put current of the system

Precision of the battery voltage and the ±0.5%


output voltage of the system

Temperature precision ±3 ℃

Humidity precision ±5%

Dimensions and Weight

4-3

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Item Specification

Chassis dimensions 220 mm × 483 mm × 362 mm (H × W × D)

Chassis weight Approximately 20 kg (excluding the rectifiers and the


monitoring unit)

Rectifier weight 1.6 kg/set, three sets (maximum)

Monitoring unit weight 1.8 kg

Battery weight Refer to the user manual from the battery provider

Others

Noise ≤ 55 dB(A)

Mean Time Between Failures (MTBF) ≥ 2.2 × 105 h

Safety standard IEC 60950

EMC standard EN55022; IEC61000

Conductive disturbance and radioactive EN55022 level A


disturbance

• The rectifier in this table is the ZXD030 S480 (V1.10) rectifier.

4.3 Compliance Standards


EMC Standards
This system is in compliance with the following Electromagnetic Compatibility (EMC)
standards:

l DIN/EN 55022
l IEC61000

Safety Standards
This system is in compliance with the UL/IEC/EN 60950 standards.

Other Standards
This system is also in compliance with the following standards:

l CE
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of the
European Union.
l This device complies with Part 15 of the FCC Rules and is subject to the following
two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause
undesired operations.

4-4

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 4 System Specifications

Note:
ZTE CORPORATION reserves the right to upgrade or make changes to the compliance
standards without further notice. For the related information, visit ZTE technical support
website http://ensupport.zte.com.cn.

4-5

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

This page intentionally left blank.

4-6

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Appendix A
Signal Interfaces on the UIB
The User Interface Board (UIB) provides communication interfaces and signal interfaces.
Figure A-1 shows the layout of the signal interfaces on the UIB. Figure A-2 shows the pin
configuration of the interfaces. Table A-1 describes the interfaces.

Figure A-1 Layout of the Signal Interfaces on the UIB

A-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Figure A-2 Pin Configuration of the Signal Interfaces on the UIB

• NC: Normally Closed • NO: Normally Open • GND: Ground

Table A-1 Signal Interfaces

Interface Name

X1 Battery 1 temperature

X2 Battery 2 temperature

X3 Ambient temperature

X4 Smoke Alarm

X5 Door alarm

X6 RS485/RS422
(RS485 and RS422 cannot be used at the same time)

X7 In-relay 1-4

X8 Out-relay 1 and 2. Software code: A1, A2.

X9 Out-relay 3 and 4. Software code: A3, A4.

X10 Out-relay 5 and 6. Software code: A5, A6.

A-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Appendix A Signal Interfaces on the UIB

Interface Name

X11 Water alarm

X12 RS232

A-3

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

This page intentionally left blank.

A-4

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Chapter 5
Dimensions
The dimensions of the ZXDU58 B121 chassis are 220 mm × 483 mm × 362 mm (H × W
× D).
Figure 5-1 shows the dimensions of the ZXDU58 B121 chassis.

Figure 5-1 ZXDU58 B121 Cabinet Dimensions

5-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

This page intentionally left blank.

5-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Appendix B
Electrical Connection
Diagram
Figure B-1 for the electrical connection diagram of the ZXDU58 B121 (V4.5R99M05)
system.

Figure B-1 ZXDU58 B121 (V4.5R99M05) Electrical Connection Diagram

B-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

This page intentionally left blank.

B-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Appendix C
Documentation Guide
Applicable Product
This guide and related documents apply to the ZXDU58 B121 (V4.5R99M05) DC power
system.

Manual Suite
Refer to the table below for the manual suite of the ZXDU58 B121 system.

Document Description and Intended Audience

DC Power System Safety Information This manual describes the personal health & safety
information and the system security information that you
should learn when working with the ZTE system products.
Intended Audience: This manual is intended for device
installation engineers, commissioning engineers and
maintenance engineers.

ZXDU58 B121 (V4.5R99M05) DC In this manual, you will learn about:


Power System Product Description l System structure and components
l System application
l System features and technical specifications
l Electrical connection diagram
Intended Audience: This manual is intended for planning
engineers and maintenance engineers.

ZXDU58 B121 (V4.5R99M05) DC In this manual, you will learn about:


Power System Installation Guide l Equipment installation
l Cable connection
l System commissioning
Intended Audience: This manual is intended for device
installation engineers and commissioning engineers.

ZXDU58 B121 (V4.5R99) Monitoring This manual describes the alarms and provides the default
Unit Alarm List level and output relay of the alarms.
Intended Audience: This manual is intended for
commissioning engineers and maintenance engineers.

C-1

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

Document Description and Intended Audience

ZXDU58 B121 (V4.5R99) DC Power In this manual, you will learn about:
System Operation and Maintenance l Monitoring software operation
Manual
à Querying real-time running status

à Querying real-time alarms

à Querying history alarms

à Energy-saving management

à Battery management

à System management, including parameter setting,


rectifier power-on and power-off by the software

l Routine maintenance
l Alarm handling
l System startup and shutdown
l Indicators description
l Components replacement
Intended Audience: This manual is intended for
commissioning engineers and maintenance engineers.

How to Get in Touch


ZTE welcomes your comments and suggestions on the quality and usefulness of this
document.
The following sections provide information on how to obtain support for the documentation.
If you have problems, questions, comments, or suggestions regarding your product,
contact us by e-mail at 800@zte.com.cn. You can also call our customer support center
at (86) 755 26771900.

For further questions, comments, or suggestions on the documentation, you can fax your
comments and suggestions to (86) 755 26770801. You can also browse our website at htt
p://ensupport.zte.com.cn, which contains various interesting subjects like documentation,
knowledge base, forum and service request.

C-2

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


Glossary
AC
- Alternating Current
- 交流电,交流
DC
- Direct Current
- 直流电
EMC
- Electro Magnetic Compatibility
- 电磁兼容能力
GND
- Ground
- 地线
LLVD
- Load Low Voltage Disconnect
- 低压负载下电

MCB
- Miniature Circuit Breaker
- 小型断路器
MTBF
- Mean Time Between Failures
- 平均故障间隔时间
NC
- Normally Closed
- 常闭

NO
- Normally Open
- 常开
PC
- Personal Computer
- 个人电脑
PE
- Protective Earth
- 保护地
RoHS
- Restriction of Hazardous Substances
- 有害物质限制
I

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential


ZXDU58 B121 Product Description

SMR
- Switching Mode Rectifier
- 开关整流器
SPD
- Surge Protection Device
- 电涌保护装置

II

SJ-20110729161742-002|2011-08-22 (R1.0) ZTE Proprietary and Confidential