Wiring Instructions for adding the

P4 LMHF I/O Panel with S2A-343-0101


Card to existing LMHF Systems
J9
with modular LMHF controller.

Cables supplied with the I/O Kit

Existing Wiring Harness in the System


*

J9
J9A P4

P4A

* P4A connection is not used


an all LMHF systems.

1. Power Down the system


2. Mount the LMHF I/O Panel in the System Rack
3. Disconnect the J9 and P4 (if used) Connector from the
LMHF Controller and connect it to the J9A and P4A
Connector on the S2A-343-0101 Card.
4. Connect the J9 and P4 connectors on LMHF
Controller and the I/O board using the supplied cables.
5. Restore power to the system.

CPN123614 ECN/DATE

ISSUE DATE: ECN19311-11/11


INSTRUCTION DRAWING NUMBER:
P25-LLMHF-IO-PNL-1

Page 1 of 2
Signal Connections to the S2A-343 Card.

TS1 CONNECTOR - FACTORY CONNECTIONS

SIGNAL NAME PIN # POLARITY DESCRIPTION - Function Assigned RATING

V1 1, 2 Pos ( + ), Neg ( - ) Voltage Input 1 - Load Voltage 0 - 100VDC

I1 3, 4 Pos ( + ), Neg ( - ) Current Input 1 - Load Current +/- 50 mV

I2 5, 6 Pos ( + ), Neg ( - ) Current Input 2 +/- 50 mV

K1 LVLD1 7, 8, 9 NC, C, NO K1 Alarm Relay - LVLD 1 60Vdc / 1A

E1 10, 11 NEG ( - ) Battery ( Hot ) - 48V 20 - 60 Vdc

K2 LVLD2 12, 13, 14 NC, C, NO K2 Alarm Relay - LVLD 2 60Vdc / 1A

K3 LVLD3 15, 16, 17 NC, C, NO K3 Alarm Relay - LVLD 3 60Vdc / 1A

SYSTEM 18, 19 Neg ( - ), Pos ( + ) Input Power 60 Vdc

TS2 - Digital Inputs

SIGNAL NAME PIN # POLARITY DESCRIPTION - Function Assigned RATING

D1 1, 2 Pos ( + ), Neg ( - ) Digital Input 1 - Distribution Breaker Alarm 0 - 60 Vdc

D2 3, 4 Pos ( + ), Neg ( - ) Digital Input 2 - Battery Breaker Alarm 0 - 60 Vdc

D3 5, 6 Pos ( + ), Neg ( - ) Digital Input 3 - LVLD Manual In Alarm 0 - 60 Vdc

D4 7, 8 Pos ( + ), Neg ( - ) Digital Input 4 - LVLD Manual Out Alarm 0 - 60 Vdc

TS3 - Temperature Probe Inputs

SIGNAL NAME PIN # POLARITY DESCRIPTION RATING

T1 1, 2 Pos ( + ), Neg ( - ) Temperature Probe 1 0 - 20 Vdc with Power Source

T2 3, 4 Pos ( + ), Neg ( - ) Temperature Probe 2 0 - 20 Vdc with Power Source

T3 5, 6 Pos ( + ), Neg ( - ) Temperature Probe 3 0 - 20 Vdc with Power Source

T4 7, 8 Pos ( + ), Neg ( - ) Temperature Probe 4 0 - 20 Vdc with Power Source


TS4 – Alarm Connections

SIGNAL NAME PIN # POLARITY DESCRIPTION - Function Assigned RATING

K4 1, 2, 3 NC, C, NO K4 Alarm Relay - System Minor Alarm 60Vdc / 1A

K5 4, 5, 6 NC, C, NO K5 Alarm Relay - System Major Alarm 60Vdc / 1A

K6 7, 8, 9 NC, C, NO K6 Alarm Relay - AC Mains Alarm 60Vdc / 1A

K7 10, 11, 12 NC, C, NO K7 Alarm Relay - Not Assigned 60Vdc / 1A

K8 13, 14, 15 NC, C, NO K8 Alarm Relay - Not Assigned 60Vdc / 1A

K0 16, 17, 18 NC, C, NO K0 Alarm Relay - * System Fail Output 60Vdc / 1A

* - System Fail Output Relay (K0) is a fail safe and will de-energize during an alarm condition. This relay can not be assigned to any other alarm.

TS5 - LVLD Switch Bypass Connection and Alarm Signal

SIGNAL NAME PIN # POLARITY DESCRIPTION RATING

K1 - SW1 1, 2 LVLD 1 Switch Bypass Connection

K2 - SW2 3, 4 LVLD 2 Switch Bypass Connection

K3 - SW3 5, 6 LVLD 3 Switch Bypass Connection

LVLD Alarm 7, 8 Pos ( + ), Neg ( - ) LVLD IN Bypass Mode Alarm Output 60Vdc

LVLD Switch Bypass Connection allows the user to connect an external LVLD Control Override Switch. Also, the pins can be shorted with a jumper wire to
permanently override the LVLD control (If used the LVLD will stay in bypass mode, however the LEDs on the card will not change from auto mode).