HEAT LOAD SPREAD SHEET

CLIENT : Kalyani Steel Limited | Sheet No :1 Date : 12.09.2022


Site : |------ -------------- --------------------------- -------------- -----------
Desc. : | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs/By MSK | ODC 103 92 65 211
Area : TG Building Control Room | IDC 72 55 65
| Diff 32 146
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 12.0 1484 17808 3.0 10 810
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
A B C D
SOLAR GAIN FROM GLASS BTU/HR | GSHR 0.72
NORTH 60 39 0.56 1310 | RSHR 0.99
SOUTH 0 11 0.56 0 | ERSHR 0.94
EAST 0 0 0.56 0 | ADP 56.00
WEST 0 158 0.56 0 | CFM 12534
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 804 14 0.40 4502 |
SOUTH 900 26 0.40 9360 | LOAD 24.80 TR
EAST 0 12 0.40 0 | AIR 12534 cfm
WEST 0 26 0.40 0 | ADP 56.00 F
ROOF 1484 58 0.35 15063 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 60 32 1.13 2136 |
PARTITION 456 27 0.40 4834 | AREA/TR 60
PART GLASS 0 27 0.40 0 | CFM/TR 505
CEILING 0 27 0.60 0 | CFM/SFT 8.45
FLOOR 0 27 0.40 0 TR based 400CFM 31.33
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
PEOPLE 10 245 2450 |
LIGHTS 2.00 1484 1 3.4 10091 |
APPLIANCE 35.00 1.00 3411 119385 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL ROOM SENSIBLE HEAT (RSH) 169131 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
INFILTRATION |
OUTSIDE AIR 810 32 0.10 1.08 2728 |
SAFETY 10% 17186 |
FAN 0 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 189045 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
PEOPLE 10 205 2050 |
INFILTRATION |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL ROOM LATENT HEAT (RLH) 2050 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
OUTSIDE AIR 810 146 0.10 0.68 7983 |
SAFETY 10% 1003 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM LATENT HEAT (ERLH) 11036 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM TOTAL HEAT (ERTH) 200081 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
OA Sensible 810 32 0.90 1.08 24828 |
OA Latent 810 146 0.90 0.68 72654 |
RA GAIN |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
GRAND TOTAL HEAT 24.80 TR 297563 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
HEAT LOAD SPREAD SHEET

CLIENT : Kalyani Steel Limited | Sheet No :1 Date : 12.09.2022


Site : |------ -------------- --------------------------- -------------- -----------
Desc. : | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs/By MSK | ODC 103 92 65 211
Area : SWAS Wet Panel Room | IDC 72 55 65
| Diff 32 146
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 11.0 130 1430 3.0 2 72
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
A B C D
SOLAR GAIN FROM GLASS BTU/HR | GSHR 0.61
NORTH 0 39 0.56 0 | RSHR 0.95
SOUTH 0 11 0.56 0 | ERSHR 0.89
EAST 0 0 0.56 0 | ADP 56.00
WEST 0 158 0.56 0 | CFM 641
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 165 14 0.40 924 |
SOUTH 165 26 0.40 1716 | LOAD 1.63 TR
EAST 99 12 0.40 475 | AIR 641 cfm
WEST 99 26 0.40 1030 | ADP 56.00 F
ROOF 130 58 0.35 1320 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION 0 27 0.40 0 | AREA/TR 80
PART GLASS 0 27 0.40 0 | CFM/TR 393
CEILING 0 27 0.60 0 | CFM/SFT 4.93
FLOOR 0 27 0.40 0 TR based 400CFM 1.60
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------
PEOPLE 2 245 490 |
LIGHTS 2.00 130 1 3.4 884 |
APPLIANCE 0.50 1.00 3411 1706 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL ROOM SENSIBLE HEAT (RSH) 8544 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
INFILTRATION |
OUTSIDE AIR 72 32 0.10 1.08 242 |
SAFETY 10% 879 |
FAN 0 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9665 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
PEOPLE 2 205 410 |
INFILTRATION |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL ROOM LATENT HEAT (RLH) 410 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
OUTSIDE AIR 72 146 0.10 0.68 710 |
SAFETY 10% 112 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM LATENT HEAT (ERLH) 1232 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
SUB TOTAL EFFECTIVE ROOM TOTAL HEAT (ERTH) 10896 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
OA Sensible 72 32 0.90 1.08 2207 |
OA Latent 72 146 0.90 0.68 6458 |
RA GAIN |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- |
GRAND TOTAL HEAT 1.63 TR 19562 |
------------------------- ---------------------- ---------------------- ------------------- -------------- -------------- --------------------------- -------------- -----------