Expert Workshop

Connect your line


differential application
in Process Bus
with a conventional one

Unrestricted | © Siemens 2022 | SI EA |


Markus Kraft
Promoter for SIPROTEC5 Digital Substation portfolio:
▪ Merging Unit 6MU85
▪ Fault Recorder 7KE85
▪ Power-Quality Basic in Protection

Smart Infrastructure
SI EA PLM PROT HV

Humboldtstr. 59
90459 Nuernberg, Germany
Mobile: +49 162 25 82 134
mailto: markus.kraft@siemens.com

Unrestricted | © Siemens 2022 | SI EA |


José Malagón
Promoter for System Stability and Digital Substation
▪ Merging Unit 6MU85
▪ Wide Area Monitoring and PMU

Smart Infrastructure
SI EA PLM PROT HV

Humboldtstr. 59
90459 Nuernberg, Germany
Mobile: +49 172 1534595
mailto: jose.malagon@siemens.com

Unrestricted | © Siemens 2022 | SI EA |


Yelitza Rojas
Product Portfolio Consultant
Smart Infrastructure Electrification and Automation

Smart Infrastructure
SI EA PLM PROT MV

Humboldtstr. 59
90459 Nuernberg, Germany
Mobil +49 15221847859
E-Mail yelitza.rojas@siemens.com
Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Test with SIPROTEC DigitalTwin

Unrestricted | © Siemens 2022 | SI EA |


Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Test with SIPROTEC DigitalTwin

Unrestricted | © Siemens 2022 | SI EA |


Sample and time synchronization
Why to differentiate between different types of synchronization

Application SMV PMU Fault Records / Logs Date and Time


Required accuracy 4 µs 1 µs 1 ms 1 ms
Relative reference time
is sufficient and used to
Accuracy type align or synchronize Absolute time stamp which contains exact date and time.
several signals among
each other.
Applicable IEEE 1588v2/PTP IEEE 1588v2/PTP IEEE 1588v2/PTP
IEEE 1588v2/PTP
synchronization IRIG-B IRIG-B IRIG-B
IRIG-B
methods PPS NTP NTP

Unrestricted | © Siemens 2022 | SI EA |


Central protection for small substations
SIPROTEC 7SJ85 and SIPROTEC 7SS85

Highlights 7SJ85
Sample synchronization IEEE 1588v2 PTP GMC 12 feeder protection including
via build in GMC clock (sample synchronization)
✓ 50/51, 67/67N protection
New in V9.20 7SJ85 ✓ 81 Frequency protection
7SS85 ✓ …
Highlights 7SS85
Process Bus (PRP) 10 feeder protection including
Process Bus (HSR) ✓ 87B differential protection
✓ 21 Impedance protection
✓ 50/51protection
✓ 81 protection
✓ …
NEW in 9.20
Build in IEEE 1588v2/PTP master
6MU85 6MU85 6MU85
clock* to synchronize sampled
values of the Merging Units.
* One instance of master clock per physical network is
allowed

Unrestricted | © Siemens 2022 | SI EA |


IEC 61850
Full digital Energy Automation System

Control Center PDI PDI PDI PDI Control Center

SICAM PAS 7SL86 7SL86 7UT85 7UT85 7SL86 7SL86 7UT85 7UT85 SICAM PAS
SICAM SCC IEEE 1588 Main 1 Main 2 6MD85 Main 1 Main 2 6MD85 Main 1 Main 2 6MD85 Main 1 Main 2 6MD85 7KE85 7SS85 IEEE 1588 SICAM SCC
Main 1 GMC SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS
GMC Main 2

Station
Station BusBus PRP
RSTP/HSR/PRP

Process Bus PRP

6MU85 6MU85 6MU85 6MU85


Main 2 Main 2 Main 2 Main 2

6MU85 6MU85 6MU85 6MU85


Main 1 Main 1 Main 1 Main 1

6MU85 6MU85

Unrestricted | © Siemens 2022 | SI EA |


Sample synchronization
New in V9.20
IEEE 1588v2/PTP Grand Master Clock functionality for distributed Busbar Protection

7SS85
Benefits
Individual GMC clock
for each HSR ring The SIPROTEC 7SS85 central unit
acts as IEEE 1588v2/PTP grand
master clock (GMC) to synchronize
the Merging/Bay Units
✓ Self synchronization of the
distributed Buspar Protection
system
HSR Ring #1 HSR Ring #2 HSR Ring #3 ✓ Up to 45 bays
max. 15 MU max. 15 MU max. 15 MU
✓ Cost effective HSR network,
avoiding network switches
✓ Synchronize sampled values
without additional
synchronization equipment
6MU85 6MU85 6MU85 6MU85 6MU85 6MU85

Unrestricted | © Siemens 2022 | SI EA |


Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Test with SIPROTEC DigitalTwin

Unrestricted | © Siemens 2022 | SI EA |


Digital Substation design changes and benefits
Process Bus Overview

Apps and Data


Analytics

IoT
Interface
Station Bus

Process Bus

*for simplification, the required IEEE 1588v2/PTP master clock is not shown
Unrestricted | © Siemens 2022 | SI EA |
Process Bus based on SIPROTEC 5 merging unit
SIPROTEC 6MU85

The Merging Unit is the interoperable interface,


between primary and secondary equipment for process bus
solutions, conforming to IEC 61869 and IEC 61850-9-2.

Measured values of conventional and low power instrument


transformers are converted into standardized, Ethernet-based
telegrams (SMV).

Unrestricted | © Siemens 2022 | SI EA |


Merging Unit – SIPROTEC 6MU85
Digitalization of all primary data close to the process

Field/Bay
Automatic voltage
Interlocking
regulator
Logic for transformer
cooling group control Inductive
Other user
defined logic Current
measurement core Transformer Inductive
Circuit Breaker protection core 1A, 5A Voltage
Trip, Control and Position Transformer
Trip Circuit Supervision
Point on Wave Switching
Disconnector Flow sensor
Control and Position 4..20 mA

Tap Changer Temperature Sensor


Position and Control 4..20 mA
digital or 4..20mA
110001 11000 100011 00001110 1111 110001 11000 100011 01110

Buchholz Relay IEC 61850-9-2 and IEC 61850-8-1 GOOSE


Trip and Alarm

Pressure sensor
Pressure relief devices Temperature Sensor for SF6, …
up to 12x PT100
TR1200 IP
Unrestricted | © Siemens 2022 | SI EA |
Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Test with SIPROTEC DigitalTwin

Unrestricted | © Siemens 2022 | SI EA |


Line differential protection
Concentration of Line Differential Protection on one line terminal end

Benefits
PTP
Substation A

GMC ✓ Concentration of Line Differential


7SL8x Line Protection Protection on one side of the line
Current MP 1 ✓ ~250 km maximum length of the
7SD8x (subscribed SMV) fiber optic cable between
FG Line
Merging Unit and protection
87 devices 1)
Process Bus STUB
Synchronization
optical PPS

Ethernet network
Current MP 2 Show
(subscribed SMV) via IEEE 1588v2/PTP
Substation B

Simplified representation
✓ Perfect for stations with available
IEEE 1588v2/PTP
Synchronization Show
via optical PPS 2)
6MU85
✓ Cost effective synchronization
1) Theoretical maximum length based on the latency introduced by the distance. Single-Mode SFP at the Ethernet switches and Perfect for stations without
Single-Mode fiber optic cables will be required to bridge the distance.
2) Fiber-Optic repeater (7XV5461-0Bx00) for PPS signal required to bridge the distance. available IEEE 1588v2/PTP

Unrestricted | © Siemens 2022 | SI EA |


Line differential protection and teleprotection
Cost-effective integration into the existing power grid

Process bus (PRP) Highlights using 87L


Classical connected line terminals do
Substation A

not require high-precision time


synchronization

PTP GMC Protection Interface (PI) connects


PI PI
✓ SIPROTEC 5
process bus process bus ✓ SIPROTEC 4
FO FO
on both line on one line ✓ C37.94 New in V9.20
terminals terminal
PI PI
Substation B

PTP GMC No high-precise synchronization


for classical connected terminals

SIPROTEC 4 or SIPROTEC 5
Line differential protection device

Process bus (PRP)

Unrestricted | © Siemens 2022 | SI EA |


SIPROTEC 5 Process Bus Client
Engineering Guidelines for 87L – Overview

Protection Interface Constellation Protection Interface Constellation


Line Topology 87L 87L Ring Topology

Two Terminal

Three Terminal

Unrestricted | © Siemens 2022 | SI EA |


SIPROTEC 5 Process Bus Client
Engineering Guidelines for 87L – Two terminal constellation
Protection Interface Link
Process Bus Network

Ring Topology Line Topology

PI - Ring Configuration P PI - Line Configuration P

PI - Ring Configuration P PI - Line Configuration


P

Unrestricted | © Siemens 2022 | SI EA |


SIPROTEC 5 Process Bus Client
Protection Interface Link
Engineering Guidelines for 87L – Three terminal constellation
Process Bus Network

Ring Topology Line Topology

P P

P P
87L must be blocked via CFC logic if a

P
merging unit is positioned in the middle of
the line topology.

Unrestricted | © Siemens 2022 | SI EA |


SIPROTEC 6MU85 Merging Unit
Base Variants

Key functions
SIPROTEC ✓ Digitalization of all primary
6MU85 data close to the process
1) 2)
6MU85 CIT LPIT ✓ Adapts to all sensors
Variant equipped BI BO3) Example Application
with CT VT CT VT
✓ Direct tripping of CB
AJ1 4) IO201 4 11 9 Merging Unit for distributed BBP ✓ Trip circuit supervision

AJ2 IO202 4 4 11 9
“Standard” Merging Unit ✓ Backup protection functions
for process bus
✓ CB wear monitoring
4) Transformer protection (one MU for
AJ3 IO203 8 7 7
primary and secondary side)
✓ Adapts to your requirements
Siemens Energy GIS LPIT with
AJ4 IO240 4 5) 4 6) 3 3
Rogowski Coil and Capacitive Sensor

1) CIT = Conventional Instrument Transformer 4) IEC 61850-9-2 LE streams require an expansion module with voltage inputs
2) LPIT = Low Power Instrument Transformer 5) Siemens Energy GIS - Rogowski Coil
3) Includes Live-Contact 6) Siemens Energy GIS - Capacitive Voltage Sensor

Unrestricted | © Siemens 2022 | SI EA |


Merging Unit – SIPROTEC 6MU85
Supports customized CIT and LPIT core assignments

One MU per CIT core Redundant MU for all CIT Redundant MU and LPIT cores
cores

87L/21-1 87L/21-1
87L/21-2 87L/21-2 87L/21-1
87L/21-2

Unrestricted | © Siemens 2022 | SI EA |


Line differential protection and tele protection
Mix LPIT (Low Power Instrument Transformers) with Conventional Instrument Transformers

Process bus (PRP)


Substation A

End 1-87L

PTP GMC
PI

Communication
network

End 2-87L PI
Substation B

PTP GMC

Process bus (PRP)

Unrestricted | © Siemens 2022 | SI EA |


Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Configuration in DIGSI 5

Unrestricted | © Siemens 2022 | SI EA |


Mix LPIT with Conventional Instrument Transformers for Line Differential Protection
How to configure in DIGSI?
Communication
network

End 2-87L PI
Substation B

PTP GMC

Process bus (PRP)

Unrestricted | © Siemens 2022 | SI EA |


Mix LPIT with Conventional Instrument Transformers for Line Differential Protection
How to configure in DIGSI?

Unrestricted | © Siemens 2022 | SI EA |


Mix LPIT with Conventional Instrument Transformers for Line Differential Protection
How to configure in DIGSI?

Unrestricted | © Siemens 2022 | SI EA |


Mix LPIT with Conventional Instrument Transformers for Line Differential Protection
How to configure in DIGSI?

Unrestricted | © Siemens 2022 | SI EA |


Table of contents
1. Main Q&A topic of last Webinar:
Time synchronization mechanism

2. Merging Unit 6MU85

3. Application
Line differential Protection

4. Test with SIPROTEC DigitalTwin

Unrestricted | © Siemens 2022 | SI EA |


Benefits of Process Bus Application with SIPROTEC 5

• Concentration of Line Differential Protection on one side of the line,


measurement acquisition based on IEC 61850-9-2

• Line differential protection with mix of measurement acquisition, for


example direct analog inputs from CIT, sample values from CIT, and
sample values from LPIT

• Interoperability between SIPROTEC 4 connected to directly to the


analog inputs, and SIPROTEC 5 based on SMV IEC 61850-9-2

Unrestricted | © Siemens 2022 | SI EA |


Contact
Published by Siemens 2022
Smart Infrastructure
Electrification & Automation
Humboldtstr. 59
90459 Nuremberg
Germany
For the U.S. published by
Siemens Industry Inc.
100 Technology Drive
Alpharetta, GA 30005
United States
www.energy automation and smart grid
© Siemens 2022
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or performance
features which may not always specifically reflect those described, or which
may undergo modification in the course of further development of the
products. The requested performance features are binding only when they
are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens, its
affiliated companies or other companies whose use by third parties for their
own purposes could violate the rights of the respective owner.

You might also like