You are on page 1of 6

the leading electrical & electronics monthly

eema 1OUrna
VOL 13 ISSUE NO.9 MAY 2022 PGS. 108 ISSN 0970-2946 Rs. 100/

The Countdown Begins...


25-27 May 2022, BIEC, Bangalore

distribulec buildlec
India's only exhibition on Hi-Tech Power Distribution A Unique Exposition on Building Electrical Systems

intelect
Conference on Intelligent Electricity

UMANGUSAV

O
24 30 58
Special Feature: ELECRAMA 2023 space booking announcement
Policy Updates: Extension ofIGST...and more updates
Guest Article Electric Vehicles and Ernvironment
Evaluation: Power Consumption and Distribution Systems
Tutorials

Prevention of intrusion
of Zero Sequence Current
(10) from the
Differential Relay
protection circuit of the
Transformers with
grounded neutral
(Part 1)

1.0 Synopsis/Preamble;
the
As name signifies, the Differential
protection is based on the current
differential of the primary (input)and the
secondary(output) currents of a transformer.
This is the most vital protection of a
transformer categorized as Unit protection
covering a specific zone of operation
of a transformer from HV CTs to LV CTs.
This protection is implemented through
the differential relay which identifies the
Current differential in the secondary circuit
through the replica of the primary currents.
The main constraint in this protection is to
have CTs of similar characteristics (knee
point voltage) and their connections should
be such that the currents in each phase
are equal in magnitude in normal running
conditionsas well as in the through-fault
conditions and also elimination of the Zero
sequence current (lo) from the Differential
protectionSecondarycircuitry.
This Article covers concept of Transformer
Differential-Protection, secondary
connections vis avis eliminating phase
shift due to vector groupdifference feeding
equivalent secondary currents from HV& LV
using Auxiliary CTs and avoiding intrusion
of Zero sequence currents (lo) in case of
external Earth-Faults in star-connected
neutral- earthed Transformers.
Tutorials

Key words: Equipment no 87, Auxiliary CTs, (iv) In case there is a fault with Power source on
LV side as well: In such cases the fault will
lo-Zero sequence current be fed either ends ie the
from direction of
shal in the LV side
3.0 Concept of Transformer Differential Protection: This current
Differential
reverse
CTs and the
relay operating element/ coil shall
is the mOst critical and vital protection of the Power
Transformer. It compares the Secondary Currents of HV get the added operating current ie it shall get
and LV side of the transformer in magnitude and phase. 11+12 and operate.
The direction of HV and LV secondary currents in the (V) In case of fault in HV side in differential Zone
Coil is in
Operating such that they oppose eachother similar shall take place and the
condition to (iv)
the
normal operating condition. The HV and LV Currents
are made available to this relay through the main CTs.
Differential relay shall operate.
1.2 The effect of variation in LV-HV voltages
and variation
2 currents due to OLTC operations
characteristics of the CTs:
The variation in LV-HV
effect of voltages-currents
due to OLTC operations and also difference in CTs
izia
Lannn characteristics as far as ratio erors and the limit
for saturation are concerned, these are also taken
care of by the restraining elements/coils (in T
formation)on either side of the operating element/
coil through Bias settings. The characteristic of
Differential relay is such that the lower portion
of the characteristic depicts non-operating zone
Basic schematic diagram of while the upper portion over the characteristic
Transformer Diff. Protection curve shows the operating-Zone. (Refer figure:1B).
Figure 1A.Basic schematic of transformer Diferential protection 1.3 Characteristic of Modern Numerical Differential
relay;
Num. Trasformer diff.Relay
Biasd Characteristic
ldiruinom

Restrainig region

Operating region

estraint rogion

(i+ia)/2 ****************7*******
Operating region
C and
CT errors
Figure 1 B; Transformer Differential Protection & Characteristic
showing operating and restraining zones.
Figure 1A & B Basic theory of Transformer Differential bis/inom
Protection & Characteristic showing operating and restraining
zones. Figure 1C: Biased characteristic of modern Num.Diff relay.
1.1 Analysis of the characteristic: (Refer figure 1 A Brief description of the slopes as depicted in the
5) figure1C;
) I n case of feeding a load, the I1 and l2 are
equal thus the relay restrains. Slope 1; It is flat and depends on IS setting.

(i) In case of fault beyond differential Zone; In this Slope 2; Denoted by K1and it is settable.It shall take
case also the differential relay shall restrain as care of internal faults up to full-load current
11 =12 are equal and cancel each other in the and also segregate the restraining area for
secondary current loops. taking care against Tap changer operation
(ii) In case there is a fault in differential Zone in LV and the CT error. It is generally set at 30%.
side with Radial feed: the Differential Relay's
Slope 3; Denoted by K2 and it is settable. It is used
operating element shall receive secondary
Current from HV side CT only. There will not to ensure stability under heavy through fault
conditions,which may possibly saturate any
be any Fault current from LV side and the
of the CTs. It generally set at 80%.
differential relay shall operate.

52 May 2022 ieema journal


Tutorials
Note: The above brief description of the Biased I Figure3;
characteristic of the Numerical Differential Relay has a) Basic scheme of differential protection offor 2
been given only to apprise the readers. Further, details winding Dyn1 transformer
etc. shall be described in the Part-2 of this article.
b) the conventional differential connections

2.0 Magnetizing inrush current; are made such that the secondary CirCuit
of CTs on the Delta side of the Transformer
Winding are connected in star formation and
the CT's secondary in the star side of the
Inrush current transformers connected in delta
are
formation
but just opposite to the vector group of the
the Cis circuit
Applied voltage Transtormer ie secondary
delta in the instance case. The vector grOup
of the 2-winding transformer is Dyn1(-30)

AAAAAA
V VV V VV c)
then the CTs secondarieson Star sideof the
transformers would be in (+30).
This is done to match the correct phase in the
differential protection relay.
d) It may be mentioned here that on either side of
Figure 2: Graphical depiction of 2nd harmonic Inrush current. the transformers, the full load current would be
differe
The phenomenon of inrush-current is seen as a fault e) For example, in 20 MVA 132kV /33 kV
by the Differential relay when energizing the transformer Dyn1,Transformer the full load currents thereof
from HV side keeping the LV side open(unloaded). 2nd are, on the Hy Side 87.5 A and on the Ly Side
harmonic Current to the tune of 63% of the fundamental 350 A. On HV side required CTs would be of
is predominately contained in the inrush-current. Thus, 87.5/1 Aand on LV side the Cis needed would
be 350/0.577A.
the Differential relays must have 2nd harmonic restraints
to combat such situations. O n LV side why this odd ratio? Answer is to
have equal current in the leads to be connected
to the differential relay ie the current in the
3.0 Condition of Over Excitation (Over external wires would be 3x 0.5771 A.
fluxing): 9) The CIs mentioned in sr. t) are to be tailor-made
The condition of over excitation can be experienced (got manufactured exclusively for the instance
by the Generators Transformer when unit connected case). Theretore, or each Iranstormer of
diferent MVA, voltage ratio and full load
generator is separated while exporting VARs,
Currents, the CTs have to be tailor-made.
experiences over excitation due to sudden increase
of HV votage resulting into saturation due to Over h) Standard rating CTS are available in the market
ie for the instant case the CTs have to be; for
excitation condition. This condition is seen as a fault by
HV side -100/1 A and for LV side-400/1 A.
the differential relay. The 5th Harmonic component is
substantially present in the magnetizing current of an F o r such main CTs , Auxiliary CTs ( Interposing
Over excited Transformer. To curb this phenomenon CTs) are required which would not only
transform secondary of the CTS to required
the relay should possess 5th harmonic restraint
ratios but also would connect the CT external
characteristics.
leads to correct Phases.
I. Figure 4;
4.0 Basic schematic of Transformer
Basic scheme of differential protection of an Auto-
differential Protection; transformer, YNaod11

w n

Operating colh eerating.cols


RO-Restraing cOil RC-Restraining col
Figure 4: Basic schematic diagram of differential
It can be seen from the Schematic diagrams protection of an aut0-transformer YNaod11.

54 May 2022 ieema journal


Tutorials
The above criteria hold good for the windings are in star
Since the voltage ratio Is
formation being an auto-Transformer with a common v=4
Neutral. In this case Delta-tertiary is also there as a Therefore, the LVcurrent has to be
stabilizing winding.
Note: 87.5x4=350A.
a) The whole exercise is done to prevent the replica Note: Since, the primary CTs 87.5/1 A on HV side
Zero Sequence toto enter into the and 350/1 A on LV side have to be tailor-made as
ofdifferential current
protection Circuit and mal-operate the such odd ratio CTs are not in the manufacturing
Differential Relay for external earth faults. range of the vendors, therefore, the main primary
b) It may be kept in mind that the secondary CTs used are HV side 100/1-1-1 A and LV side
returnneutral wire of star connected Auxiliary CT or 400/1-1-1 A.
the
Star pointof
modules shouldall
notthebe3 grounded.
operating current coils
As they wouldor I n e Ditferential relay must get 1 Amp current while
form a parallel path to the main Cis grounded the Transformer is in service to its full capacity ie at
neutral. 20 MVA, (with full load currents).

4.1 Practical Differential protection circuits with i Now, to get 1 amp at the terminals of the Differential
Auxiliary CTs(Interposing CTs): relay, the Interposing CTs are used.
1
Practical sample Connection diagram of
CTS ofa 20
At full load, the main Transformer CTs shall carry
Differential protection with auxiliary
MVA, 132KV/33kV, Dyn11, Transformer:
and transform them into secondarycurrents as
follows
The Connection diagram for Differential protection
of 20 MVA, 132kV/33kV, Dy11, Transformer. (with HV side
87.5
= 0.875Amp. LV side: 0.875Amp.
100 400
Full load Currents HV-87.5A & LV. 350A).Ratios
of CTs installed on HV side-100/1A and LV side- iv. It may be borne in mind that main CTs are available
400/1A respectively is shown in
figure. with 1 Amp secondary or 5 Amp. Secondary
currents only. The CTs with 1 amp. secondaryis
20MVA 132/33KV Dy11 TRANSFORMER used in EHV sub stations where the lead lengths of
the control cables are very long, whereas 5 amp.
secondarycurrents are generally used in the Sub-
transmission sub-stations.
v.Now, as per the prime requirement of the Differential
APTA Protection, the Zero sequence currents should
be prevented to enter into the Differential relay's
circuit. This may trip the Differential relay spuriously
whenever any Phase to ground faults ocCur outside
the differential zone
Figure-5: Differential connection diagram using
Interposing CTs on 20 MVA, 132/33KV Dyn11 Transformer. T o avoid such spurious trippings, the auxiliary
Note: CTs on the star side be connected in Delta and
0 '0'stands for operating element, the Delta side be connected in star formation
such connections are formed in the Secondary
i) R stands for restraining element.
windings of the auxiliary CIS so as to get 1
amp at the differential relay terminals.
5.0Why Use Interposing Cts (Auxiliary
We have to accordingly form the delta in the
Cts)? side where star formation of the Transformer
Explanation: winding is there. In the instant case pleases refer
The Full load currents are HV-87.5 A and L-350 to the figure the auxiliary CTs on the HV side
Amp. are connected in Star formation with a Ratio of
How do you arrive at this?
A and on LV side the ratio should De
0.577
HV Full load current The reason is when the current on
MVA..1000 1000 20000
Why577A?
0.577

3kV 3x132 1.732 x 132 87.479 As87.5A the external leads from delat formed Auxiliary
CTs wOuld be v3 x 0.577 = 0.999 A 1A.

May 2022 ieema journal


Tutorials

vi. General practice followed while cabling/ wiring the Note: Such EHV transformers are used in the Grid sub-
CTs in the switch yard, ll the 3 secondaries (of R, Y stations.
B Phases) of the CTs are wired up in star formation The Primary Terminals(P1& P2)of main 132kV
resulting into R:Y-B-N leads, which are brought to and 33kv CIs should be connected in such a way
the control-room through control cables and are that P1 of CTs of HV side and that of LV side must
terminated on the terminal block of the Control &
face towards the Transformer.
Relay panel of the Transformer.
The star points of the secondary winding on both
vii. The Star point (Neutral point) of the secondaries of 132kV and 33kV side are formed towards the
main CTsshould be towards the Transformer side Transtormer
or it may be away from the Transformer on both Hv
In the instant case since P1 of HV and LV
and LV the sides. The position of P1 and P2 (the
side CIs are facing towards the Transformer
primary terminals) decide this.
therefore all the 1S1 are shorted together s0
In instant case P1s of the CT primary terminal are as to form the star pointie Neutral, which in-
towards transformer side on HV as well as on LV turn becomes the secondary neutral lead. This
side. secondary is then Earthed.
The Auxiliary Current transformers are required as
Thus to form neutral of secondary CT circuit, all (")
the CTs available in the market are either having9
S1 are to be looped together.
1.0 Amp or 5.0Amp secondary current.
Note about the CTs with reference to IS:2705; The reason for selection of ratio for the Auxiliary
() this is the prefix for the core terminals to indicate the Current Transformers;
number of the core.
HV side CT ratio is 100/1A so for full load
Each secondary core (winding) has 2 terminals. S1 and current (87.5A) flow the secondary current of
$2. main HV side CTs would be 0.875A.
Say there are 3 cores in a CT then they will be numbered o LV side CT ratio is 400/1A so for full load
as 1S1-1S2, 2S1-2$2 and 3S1-3$2. current of 350 A, the main CTs secondary
The CIs generally have 3 cores. Current would be 350/400 A=0.875A

Metering Core. Why the ratio of Aux. CTs is selected as


5P10, 20-Protection core. 0.875/0.577A?
o The answer is as line currents in delta
PS core (Special protection core).: This is used for
Differential protection( as per IEC:60044-1revised to connection would bev3x0.577 1Amp.
IEC 61869-1:2007 it is Px core) the Auxiliary CTs are used in delta formation
for eliminating Zero sequence current in the
6.0 In case of YNyn0 Transformer: Diferential circuit.
Figure 6 depicts the schematic diagram for Differential 87 is the device number allocated for the
potection for a 132/33kV, 20 MVA YNyn0 Transformer;
differential relay.
132/33KV 20MVA TRANSEORMER Note: Part-2 of this Tutorial contains;
the relevant details about prevention methodology
of Zero sequence current (10)in the modern
Numerical differential relay
o C
Salient points regarding Setting etc including
inrush current restraint function.

Author

ndex.Difereial Rolay, Oneperating col & Re Restaning eo K.K.Murty,


B.E.(Hons).FIE, CE, Member CIGRE.
Figure 6: Diferential Protection connection diagram of 20
YNyn0, Transformer with Interposing CTs Retd, Chief Engineer (Testing &Commun.) M.P Power
MVA, 132kV/33kv,
(Aux. CTs). Transmission Co. Ltd.

ieema joUrnal May 202 57

You might also like