You are on page 1of 15

Building and Environment 121 (2017) 200e214

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Correlating variability of the leakage characteristics with the hydraulic


performance of an auxiliary ventilation system
Saad Akhtar, Mustafa Kumral, Agus P. Sasmito*
Department of Mining and Materials Engineering, McGill University, 3450 University Street, Montreal QC H3A0E8, Canada

a r t i c l e i n f o a b s t r a c t

Article history: Ventilation is one of the key factors in controlling underground working environment by providing
Received 24 February 2017 sufficient amount of fresh air for breathing, dispersing harmful gasses and dust and to some extent for
Received in revised form heating/cooling. Insufficient airflow is dangerous for the working face and can lead to fatalities. Duct
16 May 2017
leakage is the most common reason for the insufficient fresh air in underground working and has been
Accepted 19 May 2017
the subject of many studies in the literature. However, the main focus has been on ascertaining its impact
Available online 20 May 2017
on the ventilation requirements of the underground environment. This study aims to identify key var-
iables associated with duct leakage that significantly impacts the power consumption levels of auxiliary
Keywords:
Auxiliary ventilation
fans which form an integral part of the underground ventilation system. A three-dimensional Compu-
CFD tational Fluid Dynamics (CFD) modeling approach is undertaken in conjunction with Monte Carlo sim-
Duct leakage ulations and multiple regression analysis to quantify the effect of duct leakage on the fan operating point
Fan operating point and discharge flow rate towards the working face. Various cases involving the positioning, orientation,
Flow resistance and size of the rupture in the ventilation duct are simulated, and their respective effects on fan operating
point and power levels are determined. Results indicate that the operating point of a fan for ventilation
ducts is strongly correlated with the position and size of the rupture, resulting in reduced delivery of
ventilation air towards the working face for different levels of fan power consumption.
© 2017 Elsevier Ltd. All rights reserved.

1. Introduction delivered, is dependent upon the level of air leakage from ducts
which in turn is influenced by different factors such as the type of
Sufficient fresh airflow is the key to maintaining the good un- duct material, rupture in ducts, duct joints etc. [9e11]. Hence in
derground working environment as it is used for breathing, order to accomplish a safe and efficient ventilation system, it is
dispersing harmful gasses and dust, and thermal comfort. Insuffi- pertinent to examine the mechanics of flow leakage in detail [12].
cient fresh air can lead fatalities due to oxygen deficiency, explosion The quantification of air leakage and its effect on the overall
due to flammable gas (such as methane in a coal mine), health energy consumption has been a subject of several experimental and
problems due to dust and diesel emission. Duct leakage has been numerical studies. Kalamees et al. [13] and Belleudy et al. [14]
the most common reason for the insufficient fresh air. Accurately conducted experimental and numerical studies, exploring a
incorporating the effect of duct leakage in the design process of the related issue, where they quantified the average leakage rates from
auxiliary ventilation system has been the Achilles heel for venti- the structures. In another study by Jokisalo et al. [15] the effect of
lation engineers [1e4]. Meticulous consideration of the impact of infiltration on the energy consumption of a building under cold
flow leakage from auxiliary ventilation duct is very important in environment is evaluated. The study found out that infiltration can
ensuring the optimum levels of fresh air delivered while main- cause a spike of up to 30% in the overall energy consumption by
taining acceptable levels of contaminants in the underground space heating equipment.
environment [5e8]. One direct corollary of this consideration is a There are numerous studies in the literature which have
selection of appropriate fan for the job. Fan's operating point, which attempted to incorporate the effect of leakage while analyzing the
is defined by its operating pressure and corresponding flow rate performance of auxiliary ventilation systems. Lee et al. [16] inves-
tigated the impact of leakage through airways to analyze ventila-
tion efficiency of coal mines. They presented a mathematical
* Corresponding author. formulation to determine the pressure drop and air flow rate while
E-mail address: agus.sasmito@mcgill.ca (A.P. Sasmito).

http://dx.doi.org/10.1016/j.buildenv.2017.05.029
0360-1323/© 2017 Elsevier Ltd. All rights reserved.
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 201

incorporating air leakage in ducts. Wolski et al. [17] presented a however, none has attempted to quantify the effect of these pa-
numerical study to determine leakage factors in ducts in order to rameters from mechanistic and continuum point of view. There-
estimate system performance for different fan configurations. The fore, for first approximation, the scope of present study is limited to
study came up with an optimized system of series of fans in an three leakage factors, i.e. rapture location, rapture size and rapture
auxiliary ventilation system. These early studies though valuable orientation. The effect of other parameters, such as duct material,
needed further model refinement in order to effectively incorpo- duct joint, duct diameter, duct length and so forth will be evaluated
rate the effect of duct leakage on overall ventilation efficiency. in our future study.
Auld [9] studied the difference between auxiliary ventilation The geometrical parameters associated with the rupture are
characteristics for leak-free and leaky ducts. The study introduced assumed to be stochastic in nature. Consequently, their impact on
the concept of duct efficiency which takes into the account the the output variables is also studied probabilistically. Monte Carlo
variability in duct leakage with the increasing fan operating pres- statistical simulations have been carried out in conjunction with
sure. It uses the spreadsheet method to compute the fan operating regression analysis to determine the dependency of rupture char-
points in a leaking duct. The study concluded that it would be faulty acteristics on response variables. Based on the analysis of the dis-
to select fan based on a leak-free system characteristic curve. tribution of the output variables, recommendations are drawn for
Furthermore, it posited that the leakage condition of the duct estimating the likelihood of instances which are critical to the fan
become increasingly important as the duct length increases. In performance and ventilation requirements. Resistance analogy for
another study, Onder et al. [18] attempted to optimize the opera- the duct leakage is also developed stochastically to create an easy to
tional factors affecting the volumetric flow rate of air reaching the follow the method in the context of ventilation professionals.
working face. Factors considered in the study include duct diam-
eter, friction factor, air flow rate at the duct inlet, duct length and 2. Methodology
resistance coefficient of a leakage path. The study developed a
computer program to solve for the fan operating point and air flow This section provides a description of various steps involved in
rate at working face while incorporating Kirchoff resistance anal- the computational fluid dynamics (CFD) analysis coupled with
ogy to model duct leakage. It was found that duct diameter and fan statistical methods. The flowchart showed in Fig. 1 elucidates the
flow rate significantly affect the ventilation output. The volume interaction between CFD calculations and statistical methods for
flow rate to the working face was less sensitive to duct length, this study. The rupture characteristics (size, location, and orienta-
friction factor and resistance coefficient for duct leakage. tion) are taken to be random variables and are treated as such.
In another study, Onder et al. [19] presented statistical model of Monte Carlo Simulation (MCS) is used to generate a case list of
the volume flow rate reaching the working face using the field data random samples for both independent and combined analysis of
from an underground mine. Multiple regression analyses were the impact of input parameters on output variables. These random
carried out to study the effect of variables such as duct diameter, samples are fed into the CFD simulation package which then yields
length, friction factor, resistance coefficient of leakage path, fan the case specific values of output variables such as fan power, fan
operating pressure and flow output etc. on the volumetric flow rate flow rate, leakage through rupture, flow rate towards the working
at working face. Statistically, significant correlations were devel- face and operating pressure of the fan. These results are then
oped with acceptable accuracy to carry out optimization studies for analyzed by developing probability distributions for various
ventilation design. response variables which give important insights on ventilation
All of the afore-mentioned studies lay their prime focus on system design.
ascertaining the overall impact of leakage on the ventilation system The preceding sub-section discusses the methodology for the
characteristics. However, a component-level approach of tackling CFD study which includes flow model and boundary conditions
the leakage issue lacks in the literature. Variables such as rupture followed by a description of numerics. The last sub-section ex-
positioning, leak orientation, and rupture size are some of the key pounds the statistical method as tersely outlined afore.
considerations that must be taken into account while designing
such systems. These factors are of paramount importance, espe- 2.1. Computational fluid dynamics (CFD) study
cially in the underground mining industry, as in some countries, the
flow rate in working space is regulated by law, e.g. in typical Ca- The schematic of the portion of the underground working face
nadian mines in Ontario province requires 0.063 m3/s of fresh air modeled along with the rupture in the auxiliary duct is shown in
per kW power of diesel machine. Thus, if the airflow rate at the Fig. 2. The schematic shown in the figure comprises of the main
working face is below the minimum requirement due to leakage, drift with a branching tunnel towards working face. It also contains
the mine operation can be shut down by law. Also, it is not un- an auxiliary ventilation system as highlighted by the smaller curved
common in underground operations to have tears and ruptures in duct inside the outer drift structure. The auxiliary duct is taken to
the auxiliary ventilation ducts due to the movement of heavy ma- be 68.58 m (225 ft) long with a 90 bend. The end of the duct is kept
chinery below the ducts. This leads to air leakage and inefficiency of at 15.24 m from the working face. The topology of the rupture and
the ventilation system. On top of that, insufficient airflow at the the dimensions of the working face are also shown in Fig. 2.
working face can lead to fatalities, especially in the underground
coal mines that emit flammable gasses such as methane. This study 2.1.1. Mathematical model
aims to fill that gap by studying the effect of these parameters on The objective of the CFD study is to solve for the flow field for
fan power requirement and system volumetric flow rate at the three-dimensional fluid flow taking into account ruptures and
working face through well-established computational fluid dy- bends in the auxiliary duct. To enhance the accuracy of the analysis,
namics (CFD) approach coupled with Monte-Carlo and regression surface roughness has also been incorporated into the model. For
models. Furthermore, as pointed in the literature [20], the resis- the full-scale three-dimensional structure, the resolution of the
tance to air flow in a ventilation system is critical to the overall turbulent flow field requires solving continuity and momentum
performance of the system. Thus, quantification of the impact of conservation equations. The mathematical equations are presented
leakage on system's efficiency is crucial. Note that the leakage here in tensor notation for the Cartesian coordinate system. Equa-
phenomenon is complex in nature, highly non-linear and is tion (1) is the mathematical representation of the principle of
affected by many factors that interacts to each other. Thus far, conservation of mass and is most commonly referred to as
202 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

Fig. 1. Flow chart showing the interaction between statistical and Computational Fluid Dynamics portions of the study.

continuity. Equation (2) models the rate of conservation of mo- and is assumed to as Newtonian and viscous. Normal and shear
mentum principle for this problem. Air is taken as the working fluid stresses in Equation (2) are modeled by invoking stokes assumption
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 203

Fig. 2. Geometric details of the underground drift and rupture morphology (Schematic not to scale). The Roman numerals are represented as follows: I- Drift inlet, II- Drift outlet,
III-Working face, IV- Fan/auxiliary duct inlet, V-Rupture, and VI-Auxiliary duct outlet. Fixed properties: Flow rate through I and surface roughness of the walls. Variables: Flow rate
and pressure drop through IV, V and VI.

[21]. Stokes assumption takes the coefficient of bulk viscosity to be delivered at drift inlet.
zero which significantly simplifies the momentum equations. The Using the predefined value of roughness constant, roughness
assumption holds true for the majority of the ideal gasses. The height was varied in the model such that the required pressure
constitutive relation for deviatoric stress tensor is given by equa- drop was achieved in the simulation. This ‘tuned’ value of rough-
tion (3). The major unknown parameters in equations (1)e(3) are ness height comes out to be 0.2 m for the underground walls.
velocity field ‘u’ and pressure ‘p’. For the detailed description of
other variables used, the reader is referred to nomenclature section.
2.1.2. Boundary conditions
vðrui Þ Boundary labels are shown in Fig. 2 whereas corresponding
¼0 (1) values of flow rates, turbulence characteristics and surface rough-
vxi
ness for the ventilation system are provided in Table 1. Inlet flow-
  rate for the underground tunnel is taken to be 11.8 m3/s (25000
v rui uj vðpÞ v  
¼ þ s (2) CFM) which is the standard value for an average Canadian mine
vxi vxj vxi ij with 187 kW (250 hp) of diesel machinery operating inside the
tunnel. This is assuming that the air flow requirement is 0.063 m3/s
!
2 vu vui vuj per kW (100 CFM/hp). Since only a single main drift is modeled, the
sij ¼  ðm þ mturb Þ k dij þ ðm þ mturb Þ þ (3) exit of the drift is taken to be at atmospheric pressure.
3 vxk vxj vxi
Inputs to the fan boundary condition type are the pressure-flow
The current study uses Reynolds Averaging approach to model rate polynomial equation where pressure is modeled as:
the turbulence stresses in the rate of momentum conservation
equation. Reynolds averaging has proved to be cost effective while
X
N
Dp ¼ Cn Q i1 (5)
providing acceptable levels of accuracy for underground ventilation i¼1
simulations [22,23] amongst other wide range of engineering ap-
plications [24]. The turbulence model used in this study is the The range of flow rate and corresponding total pressure drop
standard k-epsilon with non-equilibrium near wall formulation. across the fan depends on the type of fan selected. A plot of flow
According to several previous studies [25e28], k-epsilon provides rate versus pressure drop based on the correlation given in equa-
better local velocity results for the underground ventilation system. tion (5) is known as fan curve. For this study, quadratic polynomial
(i ¼ 3) is used to model the fan curve. The prime consideration for
2.1.1.1. Calibration of the surface roughness of the walls. In order to appropriate fan selection is efficiency which is a strong function of
accurately incorporate the effect of surface roughness, the CFD its operating point. The operating point, and thus efficiency, of a fan
model requires inputs in the form of roughness height and is determined by the intersecting point of fan curve and system
roughness constant. The roughness height takes into account the characteristic curve on flow rate versus pressure drop plot. For the
extent of the roughness of the wall whereas roughness constant graphical description of the concepts above, the reader is referred
represents the distribution of roughness over the whole wall. The to the work of Munson, Young, and Okiishi [29].
afore-mentioned wall roughness parameters are not reported in The system characteristic curve geometrically represents the
the literature.
For roughness constant, a value of 0.5 was assumed which sig- Table 1
nifies an even distribution of the roughness over the whole wall. Values of different system and flow parameters.
The roughness height was calculated through a verification
Parameter Units Values
method. Using the friction factor value of 0.019 for a moderately
Velocity at inlet m/s 0.54
rough surface [4] in equation (4) along with base case values for all
Velocity at duct inlet (for system characteristic curve) m/s 1.6e11.2
other parameters, the pressure drop was calculated. Surface roughness of the wall m 0.2
Roughness constant e 0.75
lp 2 Pressure outlet Pa 0
p ¼ kL Q (4)
A3 Turbulence intensity at drift Inlet % 5
Turbulence intensity at Duct Inlet % 5
here k, L, lp and A are friction factor, length, perimeter and area of Hydraulic diameter of drift m 6.013
Hydraulic diameter of Auxiliary duct m 1.07
the cross-section for the tunnel, respectively. Q is the flowrate
204 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

relationship between the system head (pressure drop) and flow the output variable for mesh insensitivity test. Results from Fig. 3
rate. The characteristic curve for the auxiliary ventilation system is show that mesh size of around 2.4 million strikes a fitting bal-
obtained by computing pressure drop across the auxiliary ventila- ance between mesh insensitivity and computational time. Hence a
tion duct for several volumetric flow rates varying in the range of mesh size of 2.4 million is used for all further flow simulations for
2.36e16.52 m3/s. Based on the obtained system characteristic underground ventilation.
curve, the fan curve for the model 3800-VAX-2100 with the blade A total of 304, 3-dimensional turbulent flow computations were
angle of 25 and impeller diameter of 38 in. was selected initially. carried out using the CFD software. Owing to a large number of
With this combination of fan curve and characteristic curve, how- cases to be computed, a python script was written to automate the
ever, the fan operating point lies in the 59% fan efficiency zone. repetitive tasks.
Thus, another fan with favorable characteristic curve was tested.
The 4200-VAX-2100 fan with 42 in impeller diameter operating at 2.2. Monte Carlo Simulation and regression analysis
980 RPM yields a more favorable operating point with a fan effi-
ciency of 73.5%. The pressure jump versus velocity relation for the Monte-Carlo simulation is an algorithm based on generating
selected fan is given by: random samples to calculate numeric possibilities such that risk
  analysis is implemented. The first step towards performing Monte
Dp ¼  6:9  109 Q 2  ð0:00033ÞQ  2 (6) Carlo Simulation (MCS) is to fit a probability distribution to un-
certain parameters. Rupture location (X1), size (X2) and orientation
The above equation is provided in CFD software as the fan (X3) on the auxiliary duct are uncertain or random variables whose
boundary condition for the inlet of the auxiliary duct. The same fan impact on volumetric flow rate at working face and fan operating
characteristic is used for all the cases of rupture during the CFD point is studied. The distributions are fitted using historical,
analysis. experience-based or experimental information. For X1, the study
assumes that probability of rupture over any length of the duct is
same. Hence a uniform distribution is fitted for X1 with a minimum
2.1.3. Numerics value of 0 m and the maximum value of 68.58 m. The range for X1
The CFD analysis for this study is performed using the fluid flow commensurates with the total length of the auxiliary duct which
toolbox in ANSYS Workbench 16.1. Geometry is developed and was chosen in accordance with current mining industry norms.
meshed in ANSYS design modeler and Mesh module respectively, Rupture size (X2) corresponds to the width of the rupture for fixed
whereas the governing equations of turbulent flow in the under- length of the size of semi-circle around the duct. A normal distri-
ground are discretized and solved using FLUENT 16.1. The govern- bution is assumed for the rupture size with a mean value of rupture
ing equation of the three-dimensional fluid flow are elliptic in width assumed to be 0.335 m (1.1 ft) with a standard deviation of
nature and are computed using segregated 3-D double precision 0.167 m (0.55 ft). For specified values of means and standard de-
parallel computing solver. In order to discretize the continuity, viation the range of the rupture, width comes out to be between
momentum, and turbulence equations, second order upwind 0.08 m and 0.6 m. 0.6 m rupture width was chosen as the upper
scheme is used. The coupling of pressure and velocity from mo- limit since it corresponds to about 70e80% leakage in the duct
mentum and continuity equation is solved using Semi-Implicit- according to preliminary computations. The average value of
Method-for-Pressure-Linked-Equation (SIMPLE) algorithm. 0.335 m was taken because CFD simulations with rupture size of
Before proceeding with the CFD analysis, grid independency test 0.335 m corresponded to around 13e17% leakage by volume which
has been carried out to mitigate the impact of numerical biases on is an average value for most duct leakages in ventilation systems
the result. Fig. 3 shows the result of the grid independency test for [30]. As for the rupture orientation, only four distinct possibilities
12 different mesh sizes ranging from 0.24 million to 4.9 million are assumed i.e. rupture at the top half, bottom half, inner half
elements. The mesh sensitivity analysis has been performed for the (facing the tunnel) and an outer half (facing the wall) of the duct.
leak-free auxiliary ventilation system. Also, the inlet of auxiliary Since X1, X2 and X3 are mutually independent, the correlation factor
ventilation duct is taken as velocity inlet with a volumetric flow in the MCS is taken to be zero.
rate of 2.359 m3/s (5000 CFM). Static pressure at the inlet is used as After assuming the probability distributions and associated
distribution parameters of the random variables, MCS simulation is
run for a sample size of 100 cases first. It is important to note here
that two different scenarios are used to ascertain the impact of
stochastic predictors on response variables. One scenario (referred
to as scenario A from here on) comprises of varying one random
variable 100 times while keeping the other 2 constants (equal to
their average values). This generates a total of 204 cases for CFD
software to compute. 100 cases each are generated for X1 and X2
since they have a continuous probability distribution function.
Since the orientation of rupture is assumed to be discrete in nature
and has only 4 distinct possibilities, X3 constitutes of only 4 cases.
The second scenario (referred to as Scenario B from here on) of MCS
comprises of varying all the parameters simultaneously in order to
analyze the combined effect of all random variables. This generates
another 100 cases, thus taking the total CFD cases to be computed,
equal to 304.
After determining all the input cases, transport equations of
mass, momentum, and turbulence are numerically computed
which yield the case specific values of response variables. The
important response variables (Yi) analyzed in this study are fan
Fig. 3. Mesh sensitivity study for the computational domain. power (Y1), the flow rate through the fan (Y2), the flow rate through
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 205

rupture (Y3), the flow rate from discharge end (Y4), Percentage values smaller than 0.05 have a significant effect on the predictors.
leakage (Y5) and total fan pressure (Y6). The output results are again For the correlation to be statistically significant, the p-value should
probabilistically analyzed through MCS by developing probability be less than confidence interval, which is assumed to be 5% for this
distribution functions of the response variables. study [31].
In order to get a good level of goodness of fit for response Variance Inflation Factor (VIF) refers to the extent of correlation
probability distributions, the sample size of MCS was required to be between different predictor variables (also known as multi-
increased. More CFD simulations was an unrealistic option collinearity) in the regression analysis. High values of VIF repre-
considering that the sample size was to be increased as much as sents that the predictor variables are strongly correlated with each
10,000 points. Instead, another statistical tool was utilized to other and thus contribute largely towards the overall variance of
improve the accuracy of the fit of distributions without compro- the regression expression. Several studies in the literature [33]
mising on underlying physics. recommend values of VIF lower than 10 to avoid unnecessary
instability of regression coefficients.
2.2.1. Multiple regression analysis Table 2 summarizes the statistical results of 6 and 4 terms
Linear regression analysis was performed in MINITAB 17 to regression analysis of the CFD results for scenario B, whereas the
derive relationship among the dependent (response) and inde- regression results for the case of individual variation (rupture
pendent (predictor) variables with an acceptable statistical signif- location only) are shown in Table 3. It is important to mention here
icance. In other words, regression expression correlates the that the 7th term in equation (7) (c7X1X2X3) is not included since
response variables (Yi) with predictor variables (Xi) and its general initial computations resulted in a very high VIF. Results in Table 2
form is given by following equation [31]: for 6 term regression analysis show that predictors X3 (for Q duct
outlet only), X1*X3 and X2*X3 have a p-value higher than the sig-
Yi ¼ c1 X1 þ c2 X2 þ c3 X3 þ c4 X1 X2 þ c5 X1 X3 þ c6 X2 X3 nificance level of 0.05. This means that these predictors can be
safely neglected in the regression equation. It is important to note
þ c7 X1 X2 X3 þ b þ ε (7)
that for the sake of brevity, only two response variables, namely fan
Here, Xn denotes the predictor variables which can be in an power (Y1) and volume flow rate delivered at working face (Y4) are
individual (linear regression) or product (non-linear) form. To shown in Table 2. The VIF for different predictors is all less than 10,
elaborate, consider our particular case where we have three thus meeting the regression coefficient stability criteria. Coefficient
random variables (X1, X2, and X3). The first three terms of Equation of determination (R2) values for both of the response variables are
(7) will comprise of the single random variable as a predictor. The above the acceptable limit of 85% set for this study.
fourth term will be the product of X1 and X2, demonstrating the Based on statistical analysis of 6 term regression equation, the
interaction effect of two random variables on response and so on. analysis was re-run after omitting the redundant predictor terms
Hence the total number of predictor variables will be equal to 7 in with high p-values. The statistical summary for this run is also
this case (3 individual terms, 4 combined terms). Last two terms in presented in Table 2. A slight decrease in VIF values is observed
Equation (7) are regression constant and error term respectively. referring to the improved stability of regression coefficients.
Regression model summary mirrors the extent of accurate However, this decrease comes at a cost. The R2 values have
representation of the sample data through regression equation. decreased, albeit slightly, for 4-term regression equation. None-
Important parameters to consider in this category are coefficient of theless, the values remain above the recommended limit of 85%. An
determination (R2), p-value and Variance Inflation Factor. R2 value important conclusion to draw from the statistical results presented
determines the extent of variation of response variables, as pre- in Table 2 is that rupture orientation has a negligible effect on all
dicted by the regression equation, with sample data. P-value and response variables as demonstrated by high p-values. Hence it is
variation inflation factor in context with the current study are safe to posit that the consideration of the rupture orientation is
described in the next paragraphs. superfluous in this context and can be safely ignored in the
P-value in a statistical analysis refers to the probability of finding regression equations along with any further output data analysis.
data points in the regression equation which prove null hypothesis For scenario A (varying rupture location only) the regression
to be true [32]. Null hypothesis refers to regression result being expressions for all the output variables are shown in Table 3. The
statistically insignificant, or in simple words, predictors and regression expressions are relatively simpler since the predictor
response variables being unrelated. It is important to note that p variable reduces to one for this specific scenario.

Table 2
Statistical summary for 6 terms and 4 terms regression equations- Varying all parameters.

Response variables 6 terms 4 terms


2
Predictors Coefficients P-Value VIF R Coefficients P-Value VIF R2

Fan power (W) Constant 5365.4 0 94.93% 5347.2 0 94.71%


X1 5.117 0 5.9 5.212 0 5.8
X2 351.9 0 5.91 333.5 0 5.64
X3 0.628 0.042 7.82 0.071 0.525 1.02
X1*X2 1.582 0 9.91 1.488 0 9.72
X1*X3 0.00151 0.374 3.06 e e e
X2*X3 0.359 0.063 5.43 e e e

Q duct outlet Constant 11.489 0 87.18% 11.461 0 86.83%


X1 0.00556 0 5.9 0.00555 0 5.8
X2 1.388 0 5.91 1.347 0 5.64
X3 0.000346 0.717 7.82 0.000031 0.929 1.02
X1*X2 0.0053 0 9.91 0.00515 0 9.72
X1*X3 0.000005 0.32 3.06 e e e
X2*X3 0.000682 0.255 5.43 e e e
206 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

Table 3 on the response variables Yi.


Statistical summary for regression analysis for X1- Varying rupture location. For scenario B, the spearman's rank correlation coefficient [34]
Response variables Predictors Coefficients P-Value R-squared is implemented in Minitab 17 to determine the relationship be-
Fan power (W) Constant 3327 e 96.53%
tween the predictor and response variables. The value of correla-
X1 14.833 0 tion coefficient varies from 1 (strong inverse dependency) to 1
X1*X1 0.0316 0 (strong increasing dependency) with the value of 0 referring to no
Leakage Percentage Constant 0.32787 e 94.33% dependency. It is important to note here that scripting capability of
X1 0.001362 0
Minitab 17 was utilized to automate the multiple regression anal-
Total Pressure jump (Pa) Constant 275.16 e 94.20%
X1 0.5631 0 ysis as well as rank coefficient evaluation of the data.
Q duct outlet (m3/s) Constant 9.9011 e 88.73% Probability distribution bar plots are developed from the sample
X1 0.01145 0 output. The statistical fits were drawn using the Scipy [35] and
Q fan inlet (m3/s) Constant 14.5852 e 95.99%
Matplotlib [36] modules as implemented in Python 3.5.1.
X1 0.008612 0

3. Model validation and verification

2.2.2. Sample output analysis Many literature studies have validated the numerical model for
Once the regression equations for response variables are final- the velocity field inside the tunnel against in-situ experimental
ized, all the response variables values (fan operating point and data. A previous study by the corresponding author [20] validated
power along with duct discharge flow rate and leakage) are the numerical model with the experimental results of Parra et al.
computed for 4 different sample sizes between 100 and 10,000. The [5]. Results show that the k-epsilon turbulence model yields an R2
reason for increasing the sample size is to get enough data points so value of 0.96 with the experimental data thus highlighting its
that the Cumulative Distribution Function comes out to be smooth. suitability for modeling the velocity flow field in an underground
The output variable selected for the sample sensitivity analysis tunnel. CFD validation conducted by other studies [24,25,37] reaf-
is volumetric flow rate at the discharge end of the auxiliary duct firm that k-epsilon suitably mirrors the 3-dimensional turbulent
(Y4). Fig. 4 shows the cumulative distribution function (CDF) of Y4 velocity field in an underground drift.
for different sample sizes. It is evident that the variation CDF de- It is important to mention here that fan boundary condition is
creases with the increase in sample size. Hence a sample size of verified for the base case configuration first. Base case configuration
10,000 is selected for output analysis. contains no ruptures what so ever in the auxiliary duct which
The output analysis for scenario A is carried out using the co- simplify the simulation for the purpose of fan boundary condition
efficient of variation as a prime indicator. The expression for the verification.
coefficient of variation is given by: In order to verify the validity of the fan boundary condition as
implemented in commercial CFD code, following two checks have
sy
cv;i ¼ (8) been implemented.
Y
1) For the base case, the operating point of a fan as calculated by
Y is the statistical mean of the sample whereas sy is the standard
ANSYS FLUENT fan boundary condition is compared with the
deviation of the sample output which is given by:
intersection point of fan equation and system characteristic
!1=2 curve.
1 XN 2) The implementation is then extended to the ruptured duct, and
sY ¼ ðY  YÞ2 (9)
N i¼1 i the behavior of the operating point is qualitatively compared
with that of the rupture-free duct.
Equation (9) quantifies the effect of each input random variable
The fan operating point for the base case, illustrated in Fig. 5 as
OP 1, corresponds to fan flow rate of 14.88 m3/s and a total pressure
of 385 Pa. The operating point as computed by the fan boundary
condition gives a flow rate of 14.15 m3/s and a pressure of 373 Pa.
Both flow rate and pressure agree within 5% value of each other.
This is reasonable agreement keeping in mind the statistical errors
that may have incurred due to the estimation of fan curve and
system characteristic equations. It is noteworthy that the theoret-
ical fan operating point e intersection between fan characteristic
curve (FCC) and system characteristic curve (SCC) e was derived
from experimental data. The FCC provided by fan manufacturer was
experimentally tested and measured. Similarly, the SCC was ob-
tained from Eq. (4) for which the k-factor used in the calculation k-
factor from Ref. [4] was experimentally measured from under-
ground drift. During the experiment, the airflow rate and pressure
in the underground drift were measured in order to get k-factor.
The SCC from CFD result (line) are in very good agreement with
theoretical SCC (x symbol).
Fig. 5 shows the difference in the operating point for fans
installed in leak-free versus leaky ducts. OP 1 corresponds to the
operating point (total pressure and volumetric flow rate through
Fig. 4. Cumulative Distribution Function of flow rate through discharge end for the fan) for a leak free duct. Total pressure here is the sum of static
different sample sizes. and dynamic pressure in the auxiliary duct. The solid black curve
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 207

Fig. 5. Characteristic curves and fan operating points for different duct topologies.

passing through OP 1 is the characteristic curve for the base case. scenarios. The following section presents some of the key findings
OP 2 and 3 show the fan operating points for a duct ruptured at the of the statistical and CFD analysis.
bend with an average width (0.335 m). OP 2 is based on the flow
rate through the fan in a ruptured duct whereas OP 3 refers to the 4. Results and discussion
operating point based on flow rate at the discharge end of the duct.
It is worthwhile to mention here that the fan characteristic curve This section elucidates on the results from a combined MCS and
(blue line in the figure) is kept constant while comparing the regression analysis of CFD model for ruptured ducts. It also sum-
operating points for different ducts. marizes the sensitivity of different rupture characteristics on fan
The difference between OP 1 and OP 2 is intuitive to predict. operating point, the flow rate at working face and fan power as
Since the fan curve is inputted into the CFD code, the operating characterized by a coefficient of variation and probability distri-
point would follow the fan curve regardless of the whether the duct butions for both scenarios (A and B) separately. For scenario A,
has leakage or not. The position of OP 1 as compared to OP 2 in Fig. 5 there are further two cases which are examined separately. The first
shows that for leaky duct the flow rate through fan increases which case comprises of varying rupture location along the auxiliary duct
leads to a subtle drop in the total pressure and consequently the fan of length 68.58 m while keeping the rupture size constant at
power. This observation, though insightful, is of little practical 0.3048 m. The rupture orientation was also assumed to be fixed at
consequence. A more practical approach shall attempt a compari- the bottom of the duct for this case. The second case comprises of
son of operating point based on flow rates at the discharge end of examining the impact of rupture size while keeping the location
the auxiliary duct. This is depicted by the difference between OP 1 and orientation constant.
and OP 3 in Fig. 5. OP 3 is defined as a virtual operating point for the
leaky duct based on its discharge flow rate. The dotted curve 4.1. Varying rupture location
passing through OP 3 is the characteristic curve of the leaky system
based on discharge flow rate. The purpose of this is to gain come Fig. 6(aed) visually represents the scatter of all the output var-
insights with regards to change in flow resistance with leakage in a iables for the case of varying rupture location under scenario A. A
duct. A comparison of OP 1 and OP 3 reveals a marked difference quick look on the visuals reveals that power, total pressure and flow
between the characteristic curves based on flow rate at the rate at discharge end generally rise with the increasing distance of
discharge ends for ruptured and non-leaky ducts. The resistance of rupture location along the length of the duct from the duct inlet.
the flow through leaky duct comes out to be significantly greater as The trend for other output variables namely fan flow rate and
compared with the leak-free duct. A direct corollary of this behavior percentage leakage are the opposite.
is a drastic reduction (almost 37% in this case) in the delivered air at In order to find out the physical reasoning behind the afore-
the working face for the ruptured duct. In order to offset this mentioned trends, a good starting point will be to examine the
reduction, the flow rate needs to be increased which ultimately percentage leakage trend with rupture position as illustrated in
entails using a fan with higher pressure, volumetric flow rate, and Fig. 6 (c). The plot shows that for ruptures close to the fan inlet, the
consequently higher power rating. leakage levels are low at first followed by an abrupt rise to the
The behavior of leak-free versus leaky ducts is consistent with maximum value. After the abrupt increase, the leakage percentage
observations made by previous studies [9]. This warrants the model starts decreasing uniformly, baring the region of the pipe bend. This
to be extensively applied to a wide gamut of ruptured duct peculiar behavior of the percentage leakage can be ascribed to the
208 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

Fig. 6. Scatter plots of (a) Fan and duct discharge flow rates, (b) Total fan pressure, (c) Percentage leakage and (d) Fan power consumption, for the case of varying rupture location
under scenario A.

mechanics of fluid flow inside the circular duct. Very near to the fan opposite trend. This decrease in fan operating flow rate results in a
inlet, the flow is undeveloped, thus resulting in low velocity gra- higher total operating pressure of the fan (Fig. 6 (b)) thus resulting
dients in the radial direction resulting in relatively low initial in higher power consumption for the fan (Fig. 6 (d)) for increasing
leakage values. The leakage % peaks at about 3.35 m downstream of rupture position. From these observations, it can be concluded that
the fan, indicating that the viscous forces are less effective near the the duct bend and portion of duct closer to the fan are critical areas
duct entrance. Further downstream, as boundary layer develops, in terms of discharge flow rate of the system. However, as far as the
the viscous forces characterized by friction factor start taking effect. fan power and operating pressure are concerned, the rupture on
This causes a reduction in the pressure along the duct which results duct length after the bend is an important consideration.
in reduced pressure differential between fluid in the duct and
rupture. This further ensues in low levels of the flow rate through 4.2. Varying rupture size
rupture as compared with fan flow rate. As the rupture position
moves towards the end of the duct the fan flow rate approaches the The discussion thus far has established that rupture on the bend
discharge flow rate as presented by the intersection point of two of the duct and near the entrance region is quite critical in terms of
plots in Fig. 6 a. the performance parameters of the auxiliary ventilation system.
Near the bend, there are some anomalous data points which Fig. 7(aed) presents the impact of varying rupture size on the
exhibit significant deviation from the general trend. Fig. 6 (c) shows output variables while keeping the location of the rupture in the
that as rupture position approaches the bend, the leakage per- middle of the bend. The trends shown by these figures are quite
centage decreases about 11% from the nominal value. Right at the intuitive. However, they do furnish some interesting quantitative
middle of the bend (at 22.86 m mark) the leakage percentage insights when compared with data in previous Fig. 6.
suddenly spikes to around 27%. This contrasting behavior can be Fig. 7 (c) shows the variation of % leakage with rupture size. The
attributed to the perturbations caused by velocity field due to the data shows that percentage leakage varies almost linearly with the
presence of the bend. At the middle of the bend (45 ), the flow is rupture size. Furthermore, the absolute values for the % leakage are
forced to change directions thus resulting in an enhanced collision approximately two-folds higher as compared with the data for
with the duct wall and resulting in minor flow recirculation. This variable rupture position. This accentuates the significant depen-
altered velocity field behavior results in enhanced air leakage dence of rupture size on percentage leakage. On the other hand, a
through the auxiliary duct. trend similar in magnitude but opposite in effect is observed for
The reduction in % leakage with rupture position has several discharge flow rate. Fig. 7 (a) shows that the discharge flow rate
implications on other output parameters. As illustrated in Fig. 6 a, varies sharply with rupture size as opposed to fan flow rate.
the fan flow rate follows exactly the same trend as that of per- The variation of fan flow rate with rupture size, on the other
centage leakage. Discharge flow rate contrarily follows an exactly hand, is relatively insignificant. This is highlighted in Fig. 7 (a)
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 209

Fig. 7. Scatter plots of (a) Fan and duct discharge flow rates, (b) Total fan pressure, (c) Percentage leakage and (d) Fan power consumption, for the case of varying rupture size under
scenario A.

where the slope of fan flow rate trend is significantly lower than the plot also reaffirms the earlier deduction that discharge flow rate is
slope for discharge flow rate. Furthermore, the fan flow rate is more sensitive to rupture size as opposed to rupture location.
observed to be relatively insensitive to the rupture sizes in excess of So far the trends that have been observed are based on the
0.3048 m This effect is also evident from fan operating pressure and assumption that only one rupture characteristics vary while others
power as shown in Fig. 7 (b and d). remain constant. A more realistic approach towards the analysis of
When compared with the absolute discharge flow rates for the the ruptured ducts shall incorporate the cumulative effect of the
variable rupture location case, the flow rate for the variable rupture rupture parameters. This can be achieved by generating the cases
size comes out to be about 40% less in magnitude for the worst case. for CFD simulation with MCS while varying all parameters simul-
Furthermore, the relative change in fan power for the extreme taneously. The preceding sub-section presents the results for the
levels of rupture size comes out to be around 19% whereas for aforementioned scenario.
variable rupture position the relative change is approximately 47%.
A similar trend is observed for fan operating pressure as well. 4.3. Varying all parameters simultaneously
Hence it can be concluded that rupture size impacts the discharge
flow rate more adversely as compared to rupture location. To Fig. 9(aef) demonstrate the combined impact of all random
conclude, it can be stated that rupture size has relatively reduced input variables (Xi) on all of the output variables for CFD simulation
the impact on fan operating point and power consumption as in terms of their probability distribution function (PDF). Several
opposed to rupture position. However, this only holds true for the existing distribution functions are tried to fit the data including
average conditions i.e. for the cases where rupture location is in the Weibull minimum, Weibull maximum, Lognormal, Normal, Error,
middle of the bend (for different rupture sizes) and rupture size Chi-square, Maxwell, and Logistic. The Akaike Information Criteria
correspond to average leakage percentage (for different rupture (AIC) [38] is used as a measure of goodness of fit to cross-compare
locations). results of different distributions. Results show that for flow rate
The above-mentioned trends while useful, does not truly pro- through the fan, rupture, and leakage percentage (Fig. 9 (b, c and e))
vide the definitive means to cross compare the relative impact of the Weibull minimum distribution has the best fit. The normal
rupture location and size on the variability of output parameters. distribution yields acceptable fit for power and pressure (Fig. 9 (a
For this particular reason, the concept of coefficient of variance is and f)), whereas the flow rate at working face is accurately repre-
used to get insight with regards to the relative spread of output sented by Weibull maximum distribution.
parameters over their mean values. Fig. 8 (a) and (b) show the Fig. 9 (a) shows the PDF of fan power consumption alongside
coefficient of variation for scenario A. Results show that output with average and standard deviation of the sample output. The
variables show a wider spread relative to their mean values for average power consumption for the fan comes out to be around
rupture location as compared to rupture size. Furthermore, the bar 5.7 kW, whereas the least and highest fan consumptions were
210 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

Fig. 8. Coefficient of variance bar plots of different output parameters for scenario A.

Fig. 9. Probability distribution functions of (a) Fan Power, (b) Fan flow rate, (c) Rupture flow rate, (d) Flow rate through discharge end, (e) Leakage percentage and (f) Total fan
pressure, for the case of varying all rupture parameters simultaneously (Scenario B).
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 211

recorded at 4.77 kW and 6.495 kW respectively. Important asser- with rupture size albeit around 2e3.5 times less than the rupture
tions can be made when these values are compared with the base location. This underscores the significance of rupture location in
case simulation (without rupture). For the base case, the power comparison to other input variables in affecting output variables.
consumption comes out to be 5.33 kW, which is higher than 24% of The data in Table 5 shows that rupture location is directly
the cases. Furthermore, for these 24% cases, the leakage percentage correlated with Power, discharge flow rate and total pressure
through the rupture is significantly higher than the average leakage whereas its correlation with leakage percentage, fan flow rate, and
value for the data. This is a surprising observation since the power rupture flow rate is inverse. The correlation dependence trend for
consumption for ruptured ducts is thought to be higher as rupture size, on the other hand, is the exact opposite of what is
compared to leak-free ducts. However, careful cross-comparison of observed for rupture location. Power, total pressure, and fan flow
output variables show that 24% of the leakage scenarios result in rate show a stronger quantitative dependence to rupture location,
shifting of the fan operating point such that the fan pressure yields whereas percentage leakage, discharge flow rate and flow rate
a lower magnitude. This ultimately translates into lower flow rate through rupture exhibit higher correlation with rupture size
at the discharge end of the duct leading towards working face. amongst all output variables.
Thus, the price of lower power consumption of fan for some cases of An important practical conclusion that can be drawn from these
ruptured ducts is ultimately paid by reduced ventilation air flow observations is that the relative importance of input variable de-
rate. pends on the output variable under consideration. For example, if
Flow rate at the discharge end of the duct (Y4) is an important the system is to be designed based on the flow rate through
consideration while designing the ducting systems. Fig. 9 (d) shows discharge duct than both input variables should be given near equal
that the sample output data for Y4 is best-fitted using the Weibull importance during the design stage since their correlation co-
distribution skewed towards the right (Weibull maximum). The efficients are close to each other. However, in the case of fan power
mean and extreme values of the output variable are shown in being the output variable under consideration, the rupture location
Table 4. Comparing the mean value for the Y4 for different rupture will be more critical towards the output and thus should be treated
scenarios with the base case value reveals that the average flow rate with more care.
is reduced by 27% for ruptured ducts. This observation can be
rephrased probabilistically by stating that under the stated input
limits of rupture location, size and orientation there is a 50% chance
that the delivered flow rate will fall short by 27% of the base case 4.4. Effect of leakage on fan operating point
value. It is also observed from Table 4 that the highest possible
value for different permutations of Xi is approximately 13% less This section presents a discussion on the scatter of fan operating
than the base case value. Hence, in contrast to power consumption, points for all the cases under scenario A and scenario B as computed
the flow rate at the discharge end is always less than the base case by CFD simulations. Fig. 10 (a, b) shows the fan operating points for
value for all ruptured ducts scenarios. the cases of (a) varying rupture position and (b) varying rupture
In order to quantify the sensitivity of each input parameter on sizes for scenario A on a pressure-flow rate of system characteristic
output variables, the concept of the correlation coefficient is curve.
employed. The matrix shown in Table 5 presents the spearman-rho In fluid flow, the resistance is defined as the ratio between
correlation coefficient and p-values for all 1-1 combinations of pressure drop and the square of volumetric flow rate. This resis-
input and output variables. Analysis of p-values in Table 5 reaffirms tance, as quantified by Equation (1), is dependent on fluid and flow
our earlier hypothesis about the irrelevance of rupture orientation properties such as density, viscosity, and flow rate along with
in the context of output variables. Further analysis of the data re- geometrical properties of the duct such as the area of cross-section,
veals that rupture location holds the strongest dependence on all wetted parameter etc. Thus the total resistance of the ventilation
output variables. The output variables are also strongly correlated system with leakage will be given by Ref. [4]:

Table 4
Mean and extreme values of output variables for scenario B versus leak free duct.

Variable Average value Lowest value Highest value Base case value

Power 5721.2 4489.8 6526.1 5330


Q fan 13.6 12.6 15.3 14.146
Q Rupture 2.48 0.082 7.29 e
Q Discharge 11.16 7.99 12.53 14.146
Leakage Percentage 17.77 1.34 50 e
Total Pressure 419.7 328.3 479.9 373

Table 5
Correlation coefficients matrix of input variables versus output variables.

Input variables (Xi)

Rupture location (X1) Rupture Size (X2) Rupture Orientation (X3)

Output Variables Correlation Coefficient P-Value Correlation Coefficient P-Value Correlation Coefficient P-Value

Power 0.96 0 0.293 0.003 0.029 0.777


Q fan 0.959 0 0.296 0.003 0.03 0.765
Q Rupture 0.894 0 0.422 0 0.033 0.742
Q Discharge 0.818 0 0.507 0 0.049 0.629
Leakage Percentage 0.885 0 0.434 0 0.035 0.729
Total Pressure 0.961 0 0.292 0.003 0.03 0.765
212 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

Fig. 10. Fan operating points for the cases of (a) varying rupture position and (b) varying rupture sizes for scenario A. Red markers depict plots of fan flow rate and total pressure,
whereas the plots of duct discharge flow rate versus total fan pressure are shown in yellow markers. The dotted line shows characteristic curve for the leak free duct. (For
interpretation of the references to colour in this figure legend, the reader is referred to the web version of this article.)

simultaneous variation of different rupture parameters, the likeli-


1 1 1 hood of higher flow resistance for leaky ventilation system in-
pffiffiffiffiffiffi ¼ qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi þ qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi (10)
RT RLeakage Rleakfree creases. Thus care must be taken while using the concept of flow
resistance in designing auxiliary ventilation systems.
The auxiliary ventilation system with leakage can be modeled as
a superposition of a virtual duct without leakage and leakage 5. Conclusion
component of the flow. This hypothetical duct, branching out from
the original duct and carrying all the leaked flow, is assumed in The effect of rupture position, size, and orientation has been
order to assign a physical meaning to the RLeakage term in equation studied, both separately and combined, on fan operating point,
(10). power consumption and discharge flow rate. MCS in conjunction
From equation (10) it can be deduced that the leakage causes the with linear regression and CFD is used to encompass both the
overall resistance of the ventilation system to reduce assuming that random nature of rupture parameters and complex 3-Dimensional
the leak free duct's flow resistance remains constant. However, turbulent fluid flow, into analyzing the performance of ventilation
since the flow resistance of the virtual duct is dependent on friction system. Statistical and CFD results showed that the output pa-
factor, which in turn is a function of Reynolds number, the rameters are a weak function of rupture orientation, possibly due to
assumption stated afore is tentative at best. This assertion is further the symmetry of the duct. However, rupture position and size
consolidated by the trend observed in Fig. 10. The figure illustrates strongly influence the fan operating point along with leakage per-
the spread of fan operating point for the ruptured duct in com- centage and duct flow rate towards working face.
parison with the characteristic curve for the leak free duct. The To summarize, the results highlight the qualitative and quanti-
relative magnitude of flow resistance can be gaged from the graph tative differences in the dependency of output variables (fan
by comparing the relative positions of the operating point. Ac- operating point and power along with discharge and leakage flow
cording to equation (1), the scenarios with higher resistances will rates) on rupture parameters (rupture size, location, and orienta-
lie above the black dotted line (characteristic curve of leak free tion) for both leakage scenarios (separate and simultaneous vari-
resistance) in Fig. 10. Correspondingly, the scenarios with lower ation). For an individual variation of the leakage parameters, fan
resistances would lie below the dotted black line. From the plots (a) operating point and power consumption was found out to be
and (b) it is evident that the duct resistance both can be greater or extremely sensitive to the location of the rupture on the duct. On
lower than the leak free duct case depending on the complex the other hand, rupture size showed a dominant impact on per-
interaction of rupture parameters with flow characteristics. The centage leakage and flow rate at the discharge end. Leakage
data points based on flow rate at the discharge end, however, al- magnitude as high as 60% and a decrease in discharge flow rate of
ways exhibit greater resistance for any combination of rupture around 47% were recorded across the extremities of rupture size.
variables. The data also shows that rupture at the center of the bend is critical
A similar trend is observed in Fig. 11 which depicts the fan and leads to higher flow rate loss and fan power consumption.
operating points for scenario B. In this particular case, however, For the simultaneous variation of parameters, the probability
most of the operating points lie above the characteristic curve for density functions of the output variables show a chance of 76% for
leak free duct as opposed to scenario A. This shows that for fan power consumption being greater than that for the leak free
S. Akhtar et al. / Building and Environment 121 (2017) 200e214 213

Fig. 11. Fan operating points for the case of simultaneous variation of all rupture parameters.

duct. However, the discharge end flow rate will always be less than u Velocity field of the air throughout the computational
the leak free duct for any case of the ruptured duct. The probability domain
distribution for the discharge flow rate is skewed to the right which m Dynamic viscosity of air
demonstrates a higher likelihood for the flow rate to lie towards the s Deviatoric stress tensor
higher end of the range. x Cartesian coordinate
The results also elucidate that for a given fan, the overall resis- Y Response variable
tance of the leaky duct can be both greater and lower than that of X Input variable
the leak free duct. The reasoning for this lies in challenging the cv Coefficient of variation
assumption which presumes that in a parallel resistance network of sy Standard Deviation
the leaky duct, the flow resistance of virtual leak free duct is con- Y Statistical mean of the sample
stant. However, since the rupture characteristics influence the fan N Sample size
operating point which in turn impact the flow behavior of the duct, R Leakage resistance
the assumption of constant duct resistance is tenuous. Thus care
must be taken while basing the ventilation system design and fan Subscripts
selection based on the traditional resistance concept for leaky i, j, k Free index referring to Cartesian coordinate
ducts. i, n Number of response/input variables
T Total
Leakage Duct with leakage
Acknowledgment
Leak-free Leak free duct
turb Turbulent
The authors thank the Natural Sciences and Engineering
Research Council of Canada (NSERC) for supporting this research
Abbreviations
(241001 NSERC RGPIN-2015-03945). The simulations were con-
CDF Cumulative Distribution Function
ducted at McGill HPC facility under Calcul-Quebec and Compute-
CFD Computational Fluid Dynamics
Canada with contribution from CFI-JELF. The first author thanks
CFM Cubic Foot per Minute
to McGill Engineering Doctoral Award (MEDA) for supporting this
GB Giga Byte
research.
MCS Monte Carlo Simulations
PDF Probability Distribution Function
Nomenclature RAM Random Access Memory
RPM Revolutions Per Minute
p pressure SIMPLE Semi-Implicit Method for Pressure Linked Equations
k Darcy Weisbach friction factor VIF Variance Inflation Factor
L Length of the tunnel
per Perimeter of the tunnel's cross-section References
A Cross-section area of the tunnel
Q Air flow rate [1] T. Kalamees, Ü. Alev, M. Parnalaas, Air leakage levels in timber frame building
envelope joints, Build. Environ. 116 (2017) 121e129.
v Velocity through fan [2] G. Guyot, J. Ferlay, E. Gonze, M. Woloszyn, P. Planet, T. Bello, Multizone air
r Density of air leakage measurements and interactions with ventilation flows in low-energy
214 S. Akhtar et al. / Building and Environment 121 (2017) 200e214

homes, Build. Environ. 107 (2016) 52e63. [20] R. Whalley, A. Abdul-Ameer, The dynamics of cyclic ventilation systems, Appl.
[3] S. Krishnamoorthy, M. Modera, Impacts of duct leakage on central outdoor-air Math. Model. 35 (2011) 93e108.
conditioning for commercial-building VAV systems, Energy Build. 119 (2016) [21] G.K. Batchelor, An Introduction to Fluid Dynamics, Cambridge university
340e351. press, 2000.
[4] M.J. Mc Pherson, Subsurface Ventilation and Environmental Engineering, [22] A.P. Sasmito, J.C. Kurnia, E. Birgersson, A.S. Mujumdar, Computational evalu-
Springer Science & Business Media, 2012. ation of thermal management strategies in an underground mine, Appl.
ndez, Numerical and experimental
[5] M.T. Parra, J.M. Villafruela, F. Castro, C. Me Therm. Eng. 90 (2015) 1144e1150.
analysis of different ventilation systems in deep mines, Build. Environ. 41 [23] J.C. Kurnia, A.P. Sasmito, A.S. Mujumdar, Simulation of a novel intermittent
(2006) 87e93. ventilation system for underground mines, Tunn. Undergr. Space Technol. 42
[6] A. Widiatmojo, K. Sasaki, N.P. Widodo, Y. Sugai, A.Y. Sahzabi, R. Nguele, Pre- (2014) 206e215.
dicting gas dispersion in large scale underground ventilation: a particle [24] J.A. Toran~ o, R. Rodriguez, I. Diego, J.M. Rivas, A. Pelegry, Influence of the pile
tracking approach, Build. Environ. 95 (2016) 171e181. shape on wind erosion CFD emission simulation, Appl. Math. Model. 31 (2007)
[7] M. Bascompta Massane s, L. Sanmiquel Pera, J. Oliva Moncunill, Ventilation 2487e2502.
management system for underground environments, Tunn. Undergr. Space [25] J.C. Kurnia, A.P. Sasmito, A.S. Mujumdar, Dust dispersion and management in
Technol. 50 (2015) 516e522. underground mining faces, Int. J. Min. Sci. Technol. 24 (2014) 39e44.
[8] A.P. Sasmito, E. Birgersson, H.C. Ly, A.S. Mujumdar, Some approaches to [26] J.C. Kurnia, A.P. Sasmito, A.S. Mujumdar, CFD simulation of methane disper-
improve ventilation system in underground coal mines environment e a sion and innovative methane management in underground mining faces,
computational fluid dynamic study, Tunn. Undergr. Space Technol. 34 (2013) Appl. Math. Model. 38 (2014) 3467e3484.
82e95. [27] J. Toran~ o, S. Torno, M. Mene ndez, M. Gent, Auxiliary ventilation in mining
[9] G. Auld, An estimation of fan performance for leaky ventilation ducts, Tunn. roadways driven with roadheaders: validated CFD modelling of dust behav-
Undergr. Space Technol. 19 (2004) 539e549. iour, Tunn. Undergr. Space Technol. 26 (2011) 201e210.
[10] S.J. Schatzel, R.B. Krog, A. Mazzella, C. Hollerich, E. Rubinstein, A study of [28] D.M. Hargreaves, I.S. Lowndes, The computational modeling of the ventilation
leakage rates through mine seals in underground coal mines, Int. J. Min. flows within a rapid development drivage, Tunn. Undergr. Space Technol. 22
Reclam. Environ. 30 (2016) 165e179. (2007) 150e160.
[11] F. Colella, G. Rein, R. Borchiellini, R. Carvel, J.L. Torero, V. Verda, Calculation [29] B.R. Munson, D.F. Young, T.H. Okiishi, Fundamentals of Fluid Mechanics, vol. 3,
and design of tunnel ventilation systems using a two-scale modelling 1990. New York.
approach, Build. Environ. 44 (2009) 2357e2367. [30] C. Aydin, B. Ozerdem, Air leakage measurement and analysis in duct systems,
[12] E. Topuz, S. Bhamidipati, M. Bartkoski, Improvement of ventilation system Energy Build. 38 (2006) 207e213.
efficiency through the analysis of air leakage, Proceedings of the first mine [31] R.A. Johnson, D.W. Wichern, Applied Multivariate Statistical Analysis, Prentice
ventilation symposium, 1982. hall Englewood Cliffs, NJ, 1992.
[13] T. Kalamees, Air tightness and air leakages of new lightweight single-family [32] J.F. Hair, W.C. Black, B.J. Babin, R.E. Anderson, R.L. Tatham, Multivariate Data
detached houses in Estonia, Build. Environ. 42 (2007) 2369e2377. Analysis, Pearson Prentice Hall Upper Saddle River, NJ, 2006.
[14] C. Belleudy, A. Kayello, M. Woloszyn, H. Ge, Experimental and numerical in- [33] R.M. O’brien, A caution regarding rules of thumb for variance inflation factors,
vestigations of the effects of air leakage on temperature and moisture fields in Qual. Quantity 41 (2007) 673e690.
porous insulation, Part 2, Build. Environ. 94 (2015) 457e466. [34] J.H. Zar, Significance testing of the Spearman rank correlation coefficient,
[15] J. Jokisalo, J. Kurnitski, M. Korpi, T. Kalamees, J. Vinha, Building leakage, J. Am. Stat. Assoc. 67 (1972) 578e580.
infiltration, and energy performance analyses for Finnish detached houses, [35] E. Jones, T. Oliphant, P. Peterson, SciPy: Open Source Scientific Tools for Py-
Build. Environ. 44 (2009) 377e387. thon, vol 73, 2001, 2015, p. 86. http://www.scipy.org.
[16] J.-K. Lee, Y.J. Wang, Effects of stopping leakage on coal mine ventilation sys- [36] J.D. Hunter, Matplotlib: a 2D graphics environment, Comput. Sci. Eng. 9 (2007)
tems, Int. J. Min. Eng. 2 (1984) 253e259. 90e95.
[17] J. Wolski, J. Barry, Analysis of Multi-Fan Ventilation Duct Line: Resistance, [37] S. Torno, J. Toran ~ o, M. Ulecia, C. Allende, Conventional and numerical models
Leakage, Fan Performance, 6th International Mine Ventilation Congress, 1997. of blasting gas behaviour in auxiliary ventilation of mining headings, Tunn.
[18] M. Onder, S. Sarac, E. Cevik, The influence of ventilation variables on the Undergr. Space Technol. 34 (2013) 73e81.
volume rate of airflow delivered to the face of long drivages, Tunn. Undergr. [38] K. Yamaoka, T. Nakagawa, T. Uno, Application of Akaike's information crite-
Space Technol. 21 (2006) 568e574. rion (AIC) in the evaluation of linear pharmacokinetic equations,
[19] M. Onder, E. Cevik, Statistical model for the volume rate reaching the end of J. Pharmacokinet. Biopharm. 6 (1978) 165e175.
ventilation duct, Tunn. Undergr. Space Technol. 23 (2008) 179e184.

You might also like