EAc4: Refrigerant Management Calculator Key:

Abbreviation Factor Units System 1


Equipment Type Drop Down Window AC, heat pumps
N Number of Units # 4
Refrigerant Type Drop Down R-123
Q Tons of Cooling Tons 4
Total r Charge pounds lbs 8
Rc Normalized Refrigerant Charge lbs / ton 2.00
ODPr Ozone Depletion Potential NA 0.02
GWPr Global Warming Potential NA 76
Lr Annual Leakage Rate (1) % 2%
Mr End of Life Refrigerant Loss (2) % 10%
Life Equipment Life years 10
LCODP Lifecycle ODP NA 0.0012
LCGWP Lifecycle GWP NA 4.6
Score 124.6
Compliance (Score < 100 = Compliant) Non-Compliant

For Multiple System Types


Combination
Weighted Average Score
Compliance (Score < 100 = Compliant)

(1) default value is 2% (enter manufactuer's data to override)


(2) default value is 10% (enter manufactuer's data to override)

Lookup Tables
Refrigerant HCFC or HFC ODP GWP
R-123 HCFC 0.020 76
R-22 HCFC 0.040 1,780
R-23 HFC 0.000 12,240
R-32 HFC 0.000 550
R-134a HFC 0.000 1,320
R-152a HFC 0.000 120
R-245fa HFC 0.000 1,020
R-404a HFC 0.000 3,900
R-407c HFC 0.000 1,700
R-410a HFC 0.000 1,890
R-507a HFC 0.000 3,900

Default Equipment Life


Window AC, heat pumps 10
Unitary, Split, and Packaged AC 15
reciprocating compressors and rec 20
Centrifugal and absorption chiller 23
= input
= Key Result

System 2 System 3
Centrifugal and absorption chillers
1
R-410a
100
200
2.00
0
1890
2% 2%
10% 10%
23
0
92.0
92.0
Compliant

1 & 2 Combined 1, 2, & 3 Combined


96.52
Compliant
System 4 System 5

2% 2%
10% 10%

1, 2, 3, & 4 Combined 1, 2, 3, & 4 Combined


System 6 System 7

2% 2%
10% 10%

1, 2, 3, & 4 Combined 1, 2, 3, & 4 Combined


System 8

2%
10%

1, 2, 3, & 4 Combined