I-0801,18-V1.

SPECIFICATION SHEET
EMERGENCY LIGHTING EMD8 Series

F
02

I-0801,18-V1.0

Features
Standard Feature Electrical Feature
Flame retardant ABS housing and Polycarbonate lens SUPPLY: 220-240VAC 50/60Hz
Ceiling moun ng, Flush moun ng ,Embedded moun ng Luminaire Power consumption: 5.0W(AC)/3.0W(DC)
LED: SMD 2835 , 6000K LED power consumption:2.4W(AC&DC)
IP65 ingress protec on, suit for indoor or outdoor LED source:12W(0.2W*60)
CE SAA cer fica on,Rohs compliance Operate: Maintained, Switchable Maintained ,and Non-maintained
over charge and over discharge protec on Test: Button self-test +Auto self-test
Working/fault status bi-color indicator and test bu on Battery: Self contained Li-ion battery
Fault self- diagnos cs test and alert func on Charge time: 24hours and 16hours for SAA
Discharge duration: 1hour, 2hours, 3hours

Dimensions (unit: mm)


363

35.3
62.8

348.7

154.9 180

Mounting type

Embedded moun ng

ceiling moun ng

Flush moun ng

Ordering Guide

Model No Duration Battery Test Flux(AC/DC) Type Illumina on


EMD8/1H/AT 1 hour 3.7V,1200mAH
Button self-test +
EMD8/2H/AT 2 hours 3.7V,2000mAH
Auto self-test+
Fault self-diagnostics Maintained
EMD8/3H/AT 3.7V,2600mAH Escape route
3 hours Non-Maintained
260LM and
Switchable
open area
EMD8/1H/MT 1 hour 3.7V,1200mAH Maintained(ACEG)

EMD8/2H/MT 2 hours 3.7V,2000mAH Manual-test

EMD8/3H/MT 3 hours 3.7V,2600mAH


03

I-0801,18-V1.0

OPERATION
The luminaries can realize Maintained ,Non-Maintained, ACEG opera on type
Opera on and condi on Func on Green Indicator
Maintained opera on type: luminaries is general ligh ng and charged mode Green Indicator Permanent light
Non-Maintained opera on type: luminaries is charged mode, luminaries will Green Indicator Permanent light
the main supply is normal not be illuminated
ACEG opera on type: luminaries is general ligh ng and charged mode , Green Indicator Permanent light
and can be on /off by switch
Green Indicator flash 1 flashe within
the main supply Isolated Enter to emergency mode, luminaries is illuminated from its ba ery pack
1 second

Luminaries default opera on is Maintained.Installer can change the luminaries to Non-Maintained and
ACEG opera on easily by jumper cable.
Please reference below instruc on

Non-Maintained Maintained ACEG

Permanet Live Permanet Live Permanet Live


L L L
Jumper
On/off
Cable
switch
SL SL SL

Neutral N Neutral N Neutral N


Terminals Terminals Terminals

Button self test---by test button can realize emergency lighting self test
operation Function Green Indicator
Press once test button 180seconds Emergency lighting self testing 10 flashes 1 second

Press twice test button within 2 seconds 1hours Emergency lighting self testing 5 flashes 1 second

Press 3 times test button within 2 seconds 2hours Emergency lighting self testing 2 flashes 1 second

Press 4 times test button within 2 seconds 3hours Emergency lighting self testing 1 flash 2 seconds

Press 5 times test button within 2 seconds Quit to Emergency lighting self testing Permanent light

To achieve the 1-3 hour emergency testing, you only need to press 1-4times the test button

Auto self-test--- regular automatic carry out emergency test function


operation Func on Green Indicator
Self-test every month after installation 180seconds Emergency lighting self testing 10 flashes 1 second

1hour Emergency lighting self testing 5 flashes 1 second(1hour Emergency)


Self-test every 6 months after installation
or 3hours Emergency lighting self testing or 1 flash 2 seconds(3hour Emergency)

this panel will regular automatic carry out emergency test function In accordance with the preset program software,
no need for manual operation
04

I-0801,18-V1.0

Fault self- diagnostics test and alert function

operation Fault Response Red Indicator


Battery is not connected or voltage is too low Alert and Enter the dormant Permanent light

self- diagnostics test Battery voltage rises more than acceptable value Alert and stop the charge 2 flashes 1 second
every 5seconds Battery voltage drops below than acceptable value Alert and quit the emergency 5 flashes 1 second
Lamp or load is not connected Alert 1 flash 2 seconds

Emergency driver/ luminaries will automatic diagnose fault and give an alarm by red Indicator

Illumination of escape routes EN1838N 4.2.1

135° 135°
200
b1 b2
160
120° 120°
120

105°
80
105°
Height h (m) a1 a2 b1 b2
2.00 3.40 7.12 3.90 9.28
90° 90°
2.50 4.20 8.60 4.45 9.82
75° 75°
3.00 4.78 10.00 4.64 9.97
60° 60°
3.50 3.04 8.55 4.72 11.98

cd/klm
4.00 1.12 8.30 4.56 12.40
45° 45°
30° 15° 0° 15° 30°
C0-C180 C90-C270

Illumination of open area>60 mm² (anti-panic Illumination) EN1838

Height
h (m) a (m) b (m) c (m) d (m)
3.00 2.70 7.76 5.66 10.92
4.00 2.12 7.24 7.12 13.88

5.00 3.45 8.86 2.02 10.40

Packaging
QTY: 10PCS
N.W: 0.85KGS
76

G.W: 9.65KGS
405

19 MEA’S: CUFT
0 378
40
0
395
380

38
0 378

10PCS/Master carton
05

I-0801,18-V1.0

Notice You are asked to read the instruction manual carefully before use to ensure that the use condition
meets use requirement of the product and relevant technical specification.
Forbid hot-line work. Don’t touch the lamp unless the power supply is disconnected to avoid electric
shock.
Please check whether the lamp is damaged during transportation after opening the package or before
use. If there is damage, please stop use and inform the suppliers. The product can only be used at the
intact condition.
In order to ensure safe use of the product, please follow the instruction manual strictly for product
installation. The supplier will not undertake any responsibility for any loss caused by illegal operation.

Yijia Industrial Park, Fuqian Road, Guanlan


Town, Baoan, Shenzhen, Guangdong, China
Tel:+86-755-27608650
Fax:+86-755-27608651
www.signcomplex.com
sales@signcomplex.com

You might also like