You are on page 1of 4

Doc.No.

dT-VRV-P1

Fresh Air Calcualtion REV 0

DATE 10/10/2010

# Floor Space Area in Sqmt Area in Sqft CFM/Sqft No of People CFM/Person FA CFM

1 GF CLASSROOM-01 800 0.12 28 10 376

2 GF CLASSROOM-02 600 0.12 21 10 282

3 GF CLASSROOM-03 600 0.12 21 10 282

4 GF LOBBY 700 0.06 42

5 GF COMP ROOM 800 0.12 28 10 376

6 1358.00

10

11

12

13

14

15

16

17

18

19 0

FA CFM = (CFM/PERSON X NO OF PEOPLE) + ( CFM/SQFT X SQFT)

www.deltaTmep.com Phone: 0091-8884437724 deltaTmep@gmail.com


Capacity of FAHU TR

QT = QS + QL (btu/hr) 1tr = 12000 btu/hr

QS = 1.08 X CFM X dT

QL = 0.68 x cfm x dW

cfm = (cfm/per x no of people ) + ( cfm/ft2 x ft2)


2.564103
Doc No dT-VRV-P1

Fresh Air Calculation Rev 0

Date 10/10/2010
Location Banglore
Outside DB 96 °F
Outside WB 78 °F
Season Summer
FLOW OF AIR ON COIL OFF COIL SH LH TH
#
CFM DBT WBT RH W DBT WBT RH W BTU/ HR TONS BTU/ HR BTU/ HR TONS
deg F deg F % GR/LB deg F deg F % GR/LB

FAHU 1 1358 96 78 46.2 130.7 76 63 50 73.7 29332.80 2.44 52636.08 81968.88 6.83

FAHU 2
Doc No dT-VRV-P1

FAHU SCHEDULE Rev 0

Date 10/10/2010

COOLING CAPACITY
ELECTRICAL
(TONS) E.A.T. ( °F ) L.A.T. (°F ) ESP
QTY FRESH AIR FLOW
# REF. LOCATION Nos. [CFM] (INCH OF MOTOR
TOTAL SENSIBLE WG) V/P/HZ POWER
D.B°F W.B°F DB°F W.B °F (WATTS)

1 FAHU-01 GF 1 6.83 2.44 1358 96 78 76 63