Professional Documents
Culture Documents
Fresh Air Handling Unit
Fresh Air Handling Unit
dT-VRV-P1
DATE 10/10/2010
# Floor Space Area in Sqmt Area in Sqft CFM/Sqft No of People CFM/Person FA CFM
6 1358.00
10
11
12
13
14
15
16
17
18
19 0
QS = 1.08 X CFM X dT
QL = 0.68 x cfm x dW
Date 10/10/2010
Location Banglore
Outside DB 96 °F
Outside WB 78 °F
Season Summer
FLOW OF AIR ON COIL OFF COIL SH LH TH
#
CFM DBT WBT RH W DBT WBT RH W BTU/ HR TONS BTU/ HR BTU/ HR TONS
deg F deg F % GR/LB deg F deg F % GR/LB
FAHU 1 1358 96 78 46.2 130.7 76 63 50 73.7 29332.80 2.44 52636.08 81968.88 6.83
FAHU 2
Doc No dT-VRV-P1
Date 10/10/2010
COOLING CAPACITY
ELECTRICAL
(TONS) E.A.T. ( °F ) L.A.T. (°F ) ESP
QTY FRESH AIR FLOW
# REF. LOCATION Nos. [CFM] (INCH OF MOTOR
TOTAL SENSIBLE WG) V/P/HZ POWER
D.B°F W.B°F DB°F W.B °F (WATTS)