You are on page 1of 10

XI'AN XU&HUI ELECTROMECHANICAL TECHNOLOGY CO.,LTD.

B8-01, Silk road Ronghao Industrial Park Gaoling District Xi'an Shaanxi,China
Email: bestxzh@xzhjdkj.com whatsapp/Skype/bip/wechat:+8618729960525

CATALOG Underground Cable Fault Locating System


Item Product name Main function Model Pictures Description
★12-inch industrial-grade computer control, touch operation mode
★With functions of distance measurement and speed measurement
★Sampling speed: 50/100/200/400MHz
★Fully automatic continuous sampling, never miss any discharge waveform
★Measuring method: flashover sampling method,low voltage impulse method
★Measuring distance:≤60km
★Pulse amplitude: 400Vpp
★Pulse width: adaptive
XHGG501A ★Reading resolution: 0.5m
★Measurement accuracy: rough measurement error: ±10m (absolute value) or 1% (relative value)
★There are three types of test cable length: <1Km (short distance); <3Km (medium distance); >3 Km (long
distance)
★It has a massive test waveform storage function: the waveforms tested on the spot can be conveniently
stored in the instrument in a prescribed order for recall and observation at any time.
Underground cable For underground cable fault ★Built-in polymer lithium battery power supply: It can work continuously for more than 4 hours after being
fault pre- rough distance fully charged. Fully meet the requirements of on-site testing. It can also work with an external AC power
locator(TDR) measurement supply.

★Industrial grade 7 inch LCD display-viewing angle>160°


★Single-chip centralized control, key operation mode, strong anti-interference ability
★With functions such as distance measurement, speed measurement, resistance measurement, etc.
★Test method: flashover sampling, low-voltage pulse sampling
★The micro-printer is integrated with the host, which can print test waveforms and test reports at any time
★Pulse amplitude: 100Vpp
XHGG501B
★Pulse width: 0.1uS and 2uS
★Measuring distance: ≤30km
★Measurement error: absolute error of rough measurement: ±10m relative error of rough measurement:
±1%
★Power supply mode: Built-in 24V/7Ah DC power supply, can work continuously for 6 hours, or external AC
1 220V 50Hz power supply

Industrial-grade 10" LCD display-viewing angle>160°,


working temperature –25℃~+65℃;
Single-chip centralized control, touch-control operation mode, strong anti-interference ability;
With functions such as distance measurement, speed measurement and resistance measurement;
Fully automatic continuous sampling, never miss any discharge waveform;
Test method: flash sampling, low voltage pulse sampling
Underground cable For underground cable fault
Main Specifications:
fault pre- rough distance XHGG501D
Pulse amplitude: 100Vpp
locator(TDR) measurement
Pulse width: 0.1uS and 2uS
Measuring distance: ≤30km
Measurement error: absolute error of rough measurement: ±10m relative error of rough measurement: ±1%
Power supply mode: built-in 12V/7Ah DC power supply, can work continuously for 6 hours, external connect
AC 220V 50Hz power supply
*It can detect the high and low resistance faults of all cables below 35KV, and it has a wide range of
applications.
*The pulse generator withstands impact high voltage: not less than 38KV
*Data sampling rate: 50/100/200/400MHz
*Test distance: ≤60Km
Underground cable For underground cable fault
*Reading resolution: 0.1m
fault pre- rough distance XHGG502
*System test accuracy is less than 20cm
locator(TDR) measurement
*The test cable length is set: <1Km (short distance); <3Km (medium distance); >3 Km (long distance)
*Low-voltage pulse amplitude: about 400VP-P.
*Built-in polymer lithium battery power supply, can test the open circuit and low resistance short circuit fault
of the cable in no power environment
*Measuring method: flashover sampling method,low voltage impulse method, multi-pulse method,

★It can synchronously receive the sound wave and electromagnetic wave generated when the fault point is
discharged, which is used to determine the location of the cable fault point.
★The magnification is 500,000 times.
For underground cable fault
Cable fault ★Working voltage: ±9V±20%
pinpointing detection(pointer XHDD503
pinpointing locator ★Quiescent current: <10mA
type)
★Receiving signal: vibration and magnetic field signal when the fault point is discharged
★Output impedance: 350Ω
★Positioning accuracy: 0.2m

By Acoustic-magnetic
Acoustic Magnetic Digital Display Synchronous Point Device , used with high-voltage signal generator to
synchronization method to
provide.
accurately locate the fault
★With precise point determination, path detection and step voltage fixed point multi-function.
point of the cable and
Cable fault ★Directly display the acousto-magnetic delay value through the intelligent algorithm
detect the path , with XHDD503D
pinpointing locator ★Adjustable filter parameters, suitable for complex environments to suppress environmental noise.
powerful background noise
★High-performance anti-noise monitor headphones to ensure that the discharge sound is not distorted.
reduction(BNR) and
★Fixed-point accuracy 0.1m, bandwidth 300-1500Hz arbitrary adjustment.
compass indication
★7 inch color touch LCD screen,with 3400mAH Lithium Ion Battery inside.
functions

★cable pipe locator is composed of a high-power path signal generator(transmitter) and receiver required
for detecting buried cable paths, used to find the path and laying depth of outage and faulty cables
★Output signal: intermittent: 0~50Vpp
★Output current: 0~2A
Underground cable For underground cable pipe ★Output frequency: 15kHz intermittent
XHLJ504(503.504)
pipe locator locating ★Receiving mode: Magnetic sound synchronization
★Receiving frequency: audio frequency
★Magnification: 50,0000 times
★Output impedance :350Ω
★Quiescent current: less than 10Ma
The path signal generator can generate high-power audio output signals, and the receiver receives the
audio signals to complete the path detection function.
★ Large output power, strong anti-vibration and anti-interference ability, stable and reliable;
★ It has reliable over-current, open-circuit, and short-circuit protection functions;
3 ★Output frequency: audio;
★ Output signal: intermittent, 0~50Vpp
★ Working power supply: 220V (1±10%) 50Hz (1±5%);
Cable path meter is ★Output power: 100W;
★ Output current: 0~2A;
a special instrument
Portable Path receiver
used to accurately detect
underground XHLJ504L Receive the audio signal sent by the cable, so as to accurately detect the buried depth and direction of the
the direction and depth of cable.
cable route tracer
buried cables within a ★ Gain ≥100dB, accurate and quick search
certain range ★LED display signal strength, observation is intuitive and concise
★Lithium battery power supply, longer battery life
★ One-key switch, easy to operate
★ Digital volume adjustment, the sound is clearer
★ Easy to use, you can use it when you turn on the probe and connect it
★Positioning accuracy: ±5% of depth
★Depth measurement accuracy: ±5% of depth
★Depth measurement range: 5 meters

★It is used to find the cable (live or uncharged) path, the direct buried cable fault, which can identify the
cable.
★Working mode: continue square wave signal output/receive signal: audio
★Working power supply: 220V (1±10%) 50Hz (1±5%); Output power: 100W;
★Working frequency: low frequency (815Hz), intermediate frequency (8kHz), high frequency (33 kHz), radio
frequency (83 kHz), 50Hz
★Antenna mode: valley method (zero value mode), crest method (peak mode) and step voltage method (A-
frame)
For underground cable ★Sound indicator: FM tone that changes with signal strength
pipeline locating ★Current indication: display the effective current value of the cable under test (unit: mA)
Cable comprehesive
find the cable (live or ★Working temperature: -10℃+55℃
tester(cable route XHGX507
uncharged) path, the direct ★Signal strength indication: ladder diagram, digital range 0-999
tracer)
buried cable fault, which ★Gain control: manual adjustment, dynamic range of 100dB
can identify the cable. ★Detection depth: the maximum detection depth is not less than 5 meters
★Depth measurement: press the depth key to display three digits, the maximum depth can be measured
up to 10 meters
★Accuracy: Low frequency: ±(1-5)%≤2.5m Radio frequency: ±(5-12)%≤2.5m
4 ★Depending on the site environment, the shape of the non-concentric lines, the number of adjacent
pipelines, and the return current of the soil
★transmitter Working frequency: low frequency (815Hz), intermediate frequency (8kHz), high frequency
(33 kHz), radio frequency (83 kHz)
★Working mode: direct connection method, coupling method (caliper method), induction method
★Matching load: 5 ohms—3000 ohms
1) It can quickly and effectively determine the direction and depth of underground cable /metal pipelines. It
can also identify power outages and live cables, and use the A-frame to accurately locate low-resistance
cable faults to ground.
For underground cable
2) It has signal strength indication, left and right arrow indication, and compass direction indication.
pipeline locating
3) The maximum depth of the detection pipeline can reach 20 meters.
find the cable (live or
Cable comprehesive 4) Automatic sounding: When the instrument is placed above the pipeline, it will automatically display the
uncharged) path, the direct
tester(cable route XHGX507X true depth of the target pipeline.
buried cable fault, which
tracer) 5) Signal identification: Accurate identification of cables from three dimensions of signal amplitude, signal
can identify the cable.
direction and signal phase.
multiple frequencies, a
6) Current direction indication: It can track the current direction and phase of the signal, effectively improving
compass indication function.
the accuracy of the search path.
7) The 70% sounding method of automatic prompting can easily determine the 70% signal point through
graphics and prompt sounds.
Integrate high-voltage power supply, pulse energy storage capacitor, and discharge ball gap into one,
professionally used for power cable fault testing.
XHHV535-2T ★sigle gear trolley
★XHHV535-2T: 0-35KV,2microfarad
Discharging for
underground cable fault
HV pulse
locating & DC high voltage
generator(Trolley) withstand voltage test
equipment.
Integrate high-voltage power supply, pulse energy storage capacitor, and discharge ball gap into one,
professionally used for power cable fault testing.
XHHV535-4T ★sigle gear trolley
★XHHV535-4T: 0-35KV,4microfarad

Integrate high-voltage power supply, pulse energy storage capacitor, and discharge ball gap into one,
professionally used for power cable fault testing.
★Three gear trolley
★XHHV535-2TS: 8KV/32microfarad, 16KV/8microfarad,32KV/2microfarad
★ impulse high voltage: 0 ~ 32kv, 0 ~ 16Kv and 0 ~ 8Kv three gear regulation
Discharging for
★ high voltage partial voltage: voltage accuracy level 1.5
underground cable fault
5 HV pulse ★ built in capacitor: 2 μ F/32kV、8 μ F/16kV、32 μ F / 8Kv three gear regulation, expandable
generator(Trolley)
locating & DC high voltage XHHV535-2TS ★ discharge power: 1024J
withstand voltage test
★ impact time: automatic impact for about 5 seconds, manual impact for any control time
equipment.
★ impact power: 2000W
★ volume: 534l × 444W × 805H
★ weight: no more than 100kg
★ working power supply: AC 220V ± 10%, 50Hz ± 2Hz
★ ambient temperature: - 20 ~ + 50 ℃

Integrate high-voltage power supply, pulse energy storage capacitor, and discharge ball gap into one,
professionally used for power cable fault testing.
★Three gear trolley
★XHHV535-4TS:8KV/64microfarad,16KV/16microfarad,32KV/4microfarad
★ impulse high voltage: 0 ~ 32kv, 0 ~ 16Kv and 0 ~ 8Kv three gear regulation
Discharging for
★ high voltage partial voltage: voltage accuracy level 1.5
underground cable fault
HV pulse ★ built in capacitor: 4 μ F/32kV、16 μ F/16kV、64 μ F / 8KVthree gear regulation
generator(Trolley)
locating & DC high voltage XHHV535-4TS ★ discharge power: 2048J
withstand voltage test
★ impact time: automatic impact for about 5 seconds, manual impact for any control time
equipment.
★ impact power: 2KVA
★ volume: 534l × 444W × 805H
★ weight: no more than 105kg
★ working power supply: AC 220V ± 10%, 50Hz ± 2Hz
★ ambient temperature: - 20 ~ + 50 ℃
Portable, with pull rod
★ High-voltage pulse output is uniform and controllable;
★ The super short-circuit protection function can make the high-voltage output directly short-circuit to the
ground;
★ With voltage 1.5 level pointer meter display, it is intuitive and clear, and the impact discharge process is
clear at a glance;
★ High-voltage side voltage measurement, real-time and accurate;
★ With zero start protection, and potentiometer return to zero output function, safe and reliable;
★ Unique high-voltage measurement design, in the stop state, the voltmeter can indicate the capacitor
voltage in real time;
surge discharging for
★ The discharge time can be arbitrarily set within an appropriate interval;
underground cable fault
★ Output DC voltage: 0~35kV optional
locating & DC high voltage XHHV 535-2L
★ High voltage divider: voltage accuracy level 1.5
withstand voltage test
★ Built-in capacitance: 2μF
equipment.
★ Maximum discharge energy: 1250J
★ Charging current: 80mA
★ Output voltage polarity: negative polarity
★ Capacity: 600W
★ Allowable impulse voltage: 0~35kV
HV pulse ★ Over temperature protection: 85℃
6
generator(Portable) ★ Volume: 520L×300W×390H
★ Weight: not more than 40kg (4uF/2uF)
★ Power supply: AC 220V±10% 50Hz±2Hz and DC power supply
★ Ambient temperature: -20~+50℃

★ Impact high voltage: 15/35kV optional


★ High voltage divider: voltage accuracy level 1.5
surge generator for
★ Built-in capacitor: 8/4μF
underground cable fault
XHHV535-2Z/4Z ★ Impact time: 1~10 seconds
locating & DC high voltage
XHHV535-2/4 ★ Impact power: 400W can be customized
withstand voltage test
★ Over temperature protection: 85℃
equipment.
*XHHV535-2Z/4Z:0-35KV,2/4microfarad, discharge power-1225J/2450J , Automatic discharge
★XHHV535-2/4::0-35KV,2/4microfarad, discharge power1225J/2450J ,Manual discharge
XHHV535-2/4
XHHV535-
2Z/4Z

It is simple in structure and


Impact high voltage: 0-30/35/40KV can be customized
ultra-light weight. This
Impact power:200/400 can be customized
power supply has the
Short circuit current:0-170/250/340/430mA can be customized
functions of overcurrent,
High voltage partial pressure: Voltage Accuracy 1.5
overvoltage, overheating,
External capacitor: 1-2/4/8/16microfarad
DC high voltage and zero start protection.
12 XHHV508-2/4 Impact time:1-8seconds
power supply High-voltage side voltage
Over tempreture protection: 85℃
measurement, real-time
Volume: 400Lx310Wx320H(400W or less)
display of residual voltage,
Weight: 12/19KG
real-time display of current
Power supply: AC 220V±10% 50Hz±2Hz
and voltage pointer meter,
Ambient temperature: -20~+50℃
intuitive and reliable.
Imported membrane, non-inductive winding structure, excellent self-healing performance and explosion-
proof performance, dry or oil structure, no leakage, no pollution, moisture-proof, fire-proof, long life, high-
quality steel plate shell, small size, light weight, Safe and reliable.
Used for rough ★capacitance:0.1~20μF
Pulse energy measurement and precise ★Precision:±5%
13 XHCC series
storage capacitor positioning of all faults of ★Rated voltage:1~200KV
various cables ★Loss value:≤0.006(1KHz)
★Insulation resistance:RC≥7500MΩ.μF
★Interelectrode withstand voltage:1.1~1.5Un.2s
★Ambient temperature:-25~40℃

It is designed based on the Murray bridge principle and can be used to measure the insulation defects of
wires and cables of various voltage levels. It is especially suitable for rough test of outer sheath failure.
★Manual boost, manual adjustment of bridge balance
Cable outer sheath ★ No-load voltage: 0-7.5/10KV(optional)
7 XHHG521
fault pre-locator ★ Short circuit current: ≥40mA
★ Positioning ratio accuracy: ±(0.2%•L±1) meter
★ Weight: 5.5kg
★ Power supply: AC 220V ±10% 50Hz± 1Hz

For underground cable


sheath fault locating
The step voltage method and the clamp current method are mainly used for the precise location of the fault
of the outer sheath of the single-core cable, and the precise location of the ground fault of the unarmored
wire and cable.
★Main features: adjustable voltage, adjustable frequency, overcurrent protection, fixed-point, withstand
voltage one-key switch, no blind zone in the test range, adjustable receiver sensitivity, signal frequency
Cable outer sheath
8 XHHG523 adjustment, zero protection.
fault pinpoint locator
1. Input voltage: 220V (1±10%), 50Hz (1±5%)
2. Output voltage: 0~10kV (square wave) adjustable
3. Output current: max200mA
4. Output capacity: 2kVA
5. Frequency adjustment: Min: 0.4 Hz, Max: 1 Hz (adjustable range)

locate all cable insulation ①The equipment adopts switching power supply to form high voltage constant current source, high voltage
and sheath faults except and stable current.
some short line faults. ②The bridge detection module is integrated with a large LCD screen display at high potential. The operating
especially suitable for the button on the panel is at ground potential and the bridge is operated through the insulation rod.
insulation fault location of
③The special custom-made four-core high-voltage measuring cable with shield, the copper mesh braided
high voltage,
Underground Cable shield layer is reliably grounded and safe to use. The four - end resistance measurement method avoids the
Rated power: 1000W
9 Fault Locator HV XHGS52-60Q error of lead resistance.
Short circuit current: 600mA
Bridge+Burnthrough ④The high voltage constant current source and bridge are integrated in a portable pull rod plastic box. High
Burn through function
Output voltage: 0~60kV voltage, light weight, easy to operate.
continuously adjustable ⑤The bridge method has no blind spot compared with the wave reflection method, and is especially suitable
Display error: <±2% for determining the breakdown points of short cables and near the ends.
Bridge function ⑥High voltage and high current are especially suitable for the fault locating of insulation and sheath of
Output voltage: 0~4kV complex high-voltage cable systems with large length and large section.
Accurate and safe indentification
Large identification jaws for various cables
The operation is extremely simple
The instructions are clear and intuitive
The owner, accessories are portable
Receiver sensitivity adjustable.
electromagnetic induction
Signal frequency adjustment
principle , accurately
XHSB505 Technical data
identify the lived or faulty
★ Recognition method: Judging by the direction of hand wobble
cables. ★ Clamp: Φ125mm
★ Power: 1.5kVA (intermittent instantaneous)
★ Impulse current: 0-50A
★ Weight: 11.00kg
★ Dimensions: 700mm×300mm×220mm
★ Impulse frequency: 0.1Hz-5Hz ( adjustable)

★ Both uncharged and charged cables can be identified


★ Recognition method: judge by the swing direction of the hand
cable fault ★ Clamp mouth: Φ125mm
10 Accurately identify outage
XHSB505D ★ Power rate: 1.5kVA (intermittent instantaneous)
identifier or faulty cables ★ Weight: 11.00kg
★ Dimensions: 700×300×220mm
★ Signal sending frequency: Min: 0.4 Hz, Max: 1 Hz (adjustable range)

It is composed of a transmitter, a transmitting current clamp, a receiver, and a receiving flexible


current clamp.
★cable voltage range : AC 0.00V~600V (50Hz/60Hz),
★AC current range: 0.00A~5000A (50Hz/60Hz),
★current frequency:45Hz~70Hz.
live (energy) cable
★Handheld type receiver has 3.5inch color LCD Screen
identification, de-energy
★ Transmitter adopts integrated special toolbox design, Good wear resistance, heat resistance
cable identification, AC XHSB505DS
and insulation performance.
current test, and AC
★Large-diameter clamp size Φ120mm
voltage test.
★ Multiple frequency to identify energy cable625Hz、1562Hz、2500Hz、10kHz
★1V large-capacity rechargeable lithium battery, fully charged and continuously working for about
8 hours
★ De-energy cable identifying distance up to 10km, energy cable indentifying distance up to 5km
★ International standard IEC61010-1 CAT Ⅲ 600V,IEC61010-031, Pollution degree 2

For further destructive


judgment of the cable after Can be remotely controlled across the wall
the cable is identified before Timing/remote control two working modes, using voice prompt and LCD display synchronization function
Cable stabbed XHZS506SY(with
sawing. It is 100% ★ Wireless remote control distance: ≤20m
11 device(Cable pricker double guns,
confirmed whether the cable ★ Wired control distance: ≤5 meters
device) voiced)
is live, and the personal ★ Applicable cables: various power cables ≤Φ125mm
safety of the staff is ★ Voice prompt operation
absolutely guaranteed.
1. TDR cable fault tester
• Sampling frequency: 100MHz;
integrates TDR cable fault • Pulse width: 0.1uS/2uS;
tester, cable path meter • Minimum resolution 0.5m;
transmitter module, high 2.Cable path meter
voltage pulse generator, ●Transmitter:
rechargeable battery pack Output signal: 15kHz intermittent
Cable Fault and cable fault pinpoint Output power: 100W
14 Locating testing locator. It is used to detect XHHV535-2TS Output current: 0~2A
system the main insulation fault of 3. Rechargeable lithium battery pack
power cables with voltage The portable cable fault location system is a internal power supply instrument.
levels of 35kV and below; to 4. High voltage surge generator
calibrate the cable length; to ●Impulse high voltage: 0~35kV optional
accurately detect the cable ●Built-in capacitor: 2μF
burial direction and depth. ●Discharge power: 1225J
5. Cable fault pinpoint locator
●Detection: vibration waves, sound waves, magnetic waves

High Voltage Test(Hipot test kit)


It mainly carries out DC withstand voltage test or DC leakage current test for high-voltage electrical
equipment such as zinc oxide arrester, power cable, transformer, circuit breaker and generator
XHZG-60/2: 60KV, 2mA
XHZG-60/3: 60KV,3mA
XHZG-60/5: 60KV,5mA
DC high voltage XHZG-120/2:120KV,2mA
generator/DC Hipot DC withstand voltage test XHZG-120/3:120KV,3mA
14 XHZG Series
Tester or DC leakage current test XHZG-120/5:120KV,5mA
XHZG-200/2: 200KV, 2mA
XHZG-200/3: 200KV, 3mA
XHZG-200/5: 200KV, 5mA
XHZG-300/2: 300KV, 2mA
XHZG-300/3: 300KV, 3mA
XHZG-300/5: 300KV, 5mA

It is applicable to withstand
voltage test of electrical
VLF Hipot equipment with large
★XHDP-30: 30KV: 0.1Hz, ≤1.1microfarad ;0.05Hz,≤2.2microfarad; 0.02Hz,≤5.5microfarad Accuracy:3%
Tester(Ultra low insulation equivalent
15 XHDP Series ★XHDP-50: 50KV: 0.1Hz, ≤1.1microfarad ;0.05Hz,≤2.2microfarad; 0.02Hz,≤5.5microfarad
frequency high capacitance (power cable,
Accuracy:3%
voltage generator) power capacitor, large and
★XHDP-80: 80KV: 0.1Hz, ≤0.5microfarad ;0.05Hz,≤1microfarad; 0.02Hz,≤2microfarad Accuracy:3%
medium-sized generator
and engine).
▲XHDB-50: 50KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5% optional
▲XHDB-100:100KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5% or AC1.5%,DC1.0% optional
High voltage Widely used in the field and ▲XHDB-150:150KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5% ,AC1.5%,DC1.0% optional
16 divider(high voltage laboratory AC/DC high XHDB Series ▲XHDB-200:200KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5%,AC1.5%,DC1.0% optional
voltmeter) voltage measurement ▲XHDB-300:300KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5%,AC1.5%,DC1.0% optional
▲XHDB-400:400KV,Accuracy AC1.0%,DC0.5%;or AC0.5%,DC0.5%,AC1.5%,DC1.0% optional
▲XHDB-500:500KV,Accuracy AC1.5%,DC1.0%;or AC1.0%,DC0.5% optional

This series of products are designed using the principle of electromagnetic induction, high magnetic
conductivity materials, new structure, and so on, so in the case of ensuring that the output current is large
Suitable for up-flow and enough: coil leakage flux is small, ampere-turns balance is good, strong resistance to electric power, safe
load testing of frequency and reliable, stable performance, easy to use, high precision, light weight, small volume and so on.
Large current
17 50HZ switch, current XHDL Series ★Output current: 500A~4000A optional
generator
transformer or other ★Output voltage:5V/6V
electrical equipment. ★Precision grade:0.2/0.5/1.0/1.5
★Working power supply:220V+/-10% / 380V+/-10% 50Hz+/-5%
★Working temperature:-10ºC~50ºC humidity:RH<90%

★It is used for the frequency internal tooth test and cable fault detection of various electrical equipment.
Separately output 0~250/400V AC power.
★There are AC/AC series/AC/DC dual-use/series AC/DC dual-use, etc.
★Oil type, dry type, inflatable type
★It has functions such as over-current, zero start, etc.; it can display values such as voltage and current.
★Equipped with over-current relay, electric/manual adjustment of output voltage (according to
requirements)
XHYB Series ★Rated nominal capacity:1kVA~500kVA
★Transformer input: 0.2/0.4/3/6/10KV
★The output voltage:1kV~1000Kv
★Control box input:AC220/380V output voltage:AC0~250/400V
★unload loss:≤15% Load loss:≤15% Total loss≤10%
★No-load current:≤30% Impedance voltage≤15% Ratio error≤±1%
★Display: number/pointer 0.5/1.0/1.5/2.5 level timing:0~9999s
★Overcurrent protection: continuously adjustable, manual setting

XHYB
Power frequency oil immersed
18 high voltage test AC/DC hipot test kit Console 221kg, 680mm* 450mm* 1150mm,
device 100KV Transformer 235kg 560mm * 440mm *1280mm
/50KVA
light weight, small volume, stable performance, easy to use and carry, no oil leakage, etc. It effectively
weakens the magnetic flux leakage and improves the insulation strength and moisture resistance. It is
XH series especially suitable for testing the insulation performance, AC/DC withstand voltage and leakage current of
AC / DC dry various electrical equipment on site.
transformer 1. Output voltage: 10 ~ 100 kV
2. Output capacity: 0.5 ~ 20 KVA
with manual 3. Impedance voltage: 12%
operation box 4. Output voltage waveform: power frequency: sine wave
XH GB 5. Surface temperature rise: < 70 ℃
resin/dry 6. No load loss: 0.2% - 0.35%
7. Allowable continuous operation time: 1 hour
8. Indirect running time: continuous

mainly designed and


manufactured for the AC
withstand voltage test of
primary electrical equipment Main Features:
for substations of 220kV ★ Reactors of the same voltage class and same capacity are smaller in size and lighter in weight;
and below. It can meet the ★The temperature rise is small at rated load;
AC withstand voltage test of ★ Dry epoxy casting, high mechanical strength, good electrical insulation performance, beautiful and
capacitive equipment such reliable;
Frequency as transformer, GIS system, ★The frequency conversion control source has a large capacity margin;
conversion SF6 switch, cable and ★Strong protection function; good output waveform; good stability;
resonance test casing according to the ★ With a variety of working modes, easy to operate; 220V or 380V single-phase power supply, convenient
19 device regulations. XHBP Series for on-site power.
This series of devices is Main Specifications:
( AC withstand mainly composed of ★Rated output voltage: 500kV and below (AC RMS); output frequency: 20 ~ 300Hz;
voltage tester ) variable frequency control ★ Resonant voltage waveform: pure sine wave, waveform distortion rate <1.0%;
power supply, excitation ★Maximum test capacity: 1000kVA and below;
transformer, reactor and ★ Working time: under full power output, one continuous working time is 60min; quality factor: 30~90;
capacitor voltage divider. ★ Frequency adjustment: sensitivity: 0.1Hz, instability: <0.05%;
After the capacitor divider, ★ Working power supply: 380/220V ± 15% / 50Hz ± 5%;
the rectifier silicon stack is
connected to complete the
DC withstand voltage test of
the device.