You are on page 1of 4

Corrosion Control

in HRSGs
By Brad Buecker, Contributing Editor

D
ue to the uncertainty over fiiture car- larly if the plant cycles fi'equendy. This article examines a number
bon dioxide emissions regulations, many of the most important issues regarding corrosion mechanisms
power companies are turning to com- and prevention.
bined-cycle power technology for fiiture
generation. Of course, the combustion HRSG Design issues
turbine is the key component of a com- One factor that influences some of the corrosion issues in
bined-cycle plant, but so are the heat re- HRSGs is the steam generator design. Most HRSGs are of the
covery steam generator (HRSG) and steam turbine. Minimizing horizontal gas passage configuration with two or three drum-
corrosion in HRSGs can sometimes be a daunting task, particu- type pressure circuits. A common three-pressure HRSG out-

Figure 1 THREE-PRESSURE HRSG

RHIn-

LP Feedwater
IP Feedwater
HP Feedwater
HP Steam
RHOut

P O W E R E N G I N E E R I N G / JULY 2011 / www.power-eng.com


in HRSG waterwall tubes that have many
Figure 2 MAGNETITE DISSOLUTION BEHAVIOR tight-radius elbows. The low-pressure
circuits of HRSGs often operate near the
100 temperature of highest corrosion poten-
—•— 0,1 ppm
90 tial shown in Figure 2, which exacerbates
— • - 0,2 ppm
0,3 ppm
FAC mechanism.
80
-^»— 0,45 ppm
s- 7° —»— 1 ppm FAC Prevention
S 60 —•— 2 ppm The preferred method, from a chem-
^ \ istry standpoint, to address single-phase
I soi ^ \
FAC issues in HRSGs is to implement
a program developed by EPRI known
S 40 as all-volatile treatment (oxidizing), or
•^ 30 i its acronym AVT(O). The concept is
20 that AVT(O) establishes a différent pro-
tective oxide layer (ferric oxide hydrate,
10 FeOOH) on evaporator tubes and other

0 212 302 392 482 components. FeOOH is not only tougher
than magnetite, but the oxidizing envi-
Temperature (F)
ronment does not cause iron dissolution.
Magnetite dissolution as a function of ammonia concentration (actually pH)
AVT(O) is what might be called a
"natural" program. Where condenser air
Source: Date from 1986 EPRI Interim Consensus Guidelines, now out of print. in-leakage is minor and condensate dis-
solved oxygen levels stay at or below 10
line is shown in Figure 1. disturbances such as elbows or other fit- ppb, the FeOOH protective layer forms
The water/steam flow path is from tings. The graph in Figure 2 shows the naturally. Ammonia feed to the conden-
the low-pressure circuit to the interme- potential magnetite dissolution rates in sate is used to maintain LP economizer
diate- and high-pressure circuits, with solutions that have been treated with an inlet pH within a range of 9.2 to 9.6. For
attendant economizer, superheater and oxygen scavenger to remove all oxygen the program to work properly and not
reheater loops. The important concept and which establishes a reducing envi- influence corrosion, the feedwater cation
for this discussion is that the HRSG con- ronment. conductivity should remain at or below
tains many multiple-tube networks with Note that pH in high-purity water is 0.2 mS/cm, Excursions in dissolved oxy-
short-radius elbows at header inlets and a direct function of the ammonia con- gen concentration and cation conductiv-
outlets. Another important factor with centration. It is the lower pH, at low ity, particularly the former, indicate ex-
regard to now-accelerated corrosion, is ammonia concentrations in a reducing cess air in-leakage within the condenser.
that most HRSGs generally do not have environment, which is responsible for Increased air in-leakage also introduces
any feedwater heaters between the con- magnetite dissolu-
denser and the low-pressure (LP) drum, tion. This explains
with the common exception of a deaera- why corrosion can
tor.. Temperature is a critical influence to- be much higher at
wards flow-accelerated-corrosion (FAC), an N H , concen-
identified by the Electric Power Research tration of 0.1 ppm
Institute (EPRI) as the most prevalent than in any other
corrosion mechanism in HRSGs'. case. The ammonia
does not attack the
Flow Accelerated Corrosion magnetite directly.
I wrote on FAC in Power En^ineer- The effects of
inß magazine^ several years ago, after an this phenomenon,
FAC-induced failure caused two fatali- known as single-
ties in a coal-fired unit that was a sister phase FAC, are
at the plant where I was working at the shown in Figure 3,
time. In short, the condensate/feedwater FAC continually
treatment program that was once popu- erodes tube or pipe
lar fbr steam generators of all kinds, all- wall structure and
volatile reducing AVT(R), is now known eventually reduces
to cause dissolution of the protective pipe strength to
magnetite (Fe,O^) layer at a temperature the point of sudden
range and chemical conditions common failure.
to the fbedwater network of conventional Single-phase
boilers and the LP circuits of HRSGs. FAC has been a
Areas particularly susceptible are flow particular problem

P O W E R E N G I N E E R I N G / JULY 2011 / www,power-eng,com


excess carbon dioxide, which influences sometimes even mono-sodium phos- reasonable chemistry, corrosion fatigue
corrosion. Thus, for a unit on AVT(O) phate (NaHjPO^) to produce what were often develops in various locations. In this
any air in-leakage difficulties that raise known as coordinated or congruent mechanism, areas that are stressed become
condensate dissolved oxygen concentra- phosphate programs. Evidence has since more vulnerable to attack by impurities in
tions significantly above 10 ppb should shown that the propensity for phosphates the water. These may include chloride, sul-
be investigated and corrected as quickly to precipitate at high temperatures would fate or even the hydroxide ions generated
as possible. One point needs to be noted, set up direct corrosion of tube metal by by chemical treatment programs.
however. Recent research suggests some these phosphate blends. Steam chemistry should not be over-
areas in the condensate/teedwater sys- Phosphate treatment has evolved in looked. Research over the last tew de-
tem, such as boiler feed pump discharge almost all cases to EPRI's phosphate cades has shown that even minor car-
nossles, may sufter from single-phase continuum (PC), where tri-sodium ryover (>2 parts per billion) of chloride,
FAC even when AVT(O) is maintained phosphate is the only chemical used, ex- sulfate and caustic can induce pitting,
within the current guidelines.' Further cept for perhaps a small amount of caus- corrosion fatigue and stress corrosion
data hopefully will be forthcoming with tic (NaOH) at startup. The program is cracking in turbine components. Of
regard to this issue. defined as either PC(L) for phosphate course, chemistry control in the evapora-
One issue that has become much bet- continuum (low) and PC(H) for phos- tors can influence impurity transport to
ter known regarding flow-accelerated phate continuum (high), where the ap- the turbine. However, other factors in-
corrosion is that of two-phase FAC. At proximate demarcation point between cluding equipment design and operation
a number of points in the steam generat- the two is a 3.0 ppm phosphate con- can cause ditBculties. Excessive ramp
ing system, zones of physical separation centration. The lower control limit for rates can cause fluctuations in boiler
between water and steam will develop; PC(L) or (H) is a sodium-to-phosphate drum levels that mechanically push im-
deaerators in particular come to mind. ratio of 3.0 to 1, with an upper control purities into the steam.
With a program such as AVT(O), the limit of 1 ppm free sodium hydroxide. The upshot is that good water/steam
oxygen will separate with the steam and Many utility personnel have opted sampling and monitoring is critical to-
leave a less protective fluid that contacts for the PC(L) program to minimize wards maintaining HRSG reliability and
water-touched components. Particularly phosphate hideout. Careful control of longevity. A second part of this article, to
susceptible location are LP economizer the 1 ppm free hydroxide limit is im- be published in a future issue, will cover
and evaporator elbows, and, generally to portant to prevent caustic gouging. sampling and monitoring guidelines.
a much lesser extent, IP elbows. Thus, However, the low phosphate/alkalin-
FAC can occur when chemistry param- ity concentrations provide only minor References
eters are seemingly in acceptable ranges. protection against contaminant ingress. 1. Cycle Chemistry Guidelines for
Two-phase FAC is difficult to control Also, at these low concentrations, am- Combined Cycle/Heat Recovery
chemically, but the issue can be ad- monia introduced to the feedwater for Steam Generators (HRSGs). The
dressed mechanically in the design phase pH control in the LP evaporator circuit Electric Power Research Institute,
by using 1.25-chrome steel in affected can influence pH readings, such that Palo Alto, California, 2006.
areas, particularly LP elbows. protection may not be adequate to pre- 2. B. Buecker, "Flow Accelerated Cor-
vent chloride-induced hydrogen dam- rosion: A Critical Issue Revisited";
The Rest Of the HRSG age. Conversely, excess hydroxide can Power Engineering, July 2007
What about corrosion prevention in cause direct caustic damage of evapora- 3. Information presented at the ASME
the intermediate- and high-pressure tor tubes. Research Committee on Power Pnant
circuits.' For the multi-pressure drum Alternatives to phosphate programs & Environmental Chemistry Commit-
HRSG examined here, boiler water treat- include caustic treatment or reliance tee sprinß meeting, April 2008, Austin,
ment for the IP and HP evaporators has simply on the AVT(O) utilized in the Texas.
largely evolved from the chemistry de- LP economizer inlet and evaporator Author: Brad Buecker is a contributing
veloped for conventional steam genera- circuit. Caustic treatment is a consider- editorfor Vowcr Engineering. He serves as
tors. The critical issue in these circuits is ation for units where condenser leaks or a Process Specialist for Kiewit Power En-
operation at a suitably alkaline pH with other impurity ingress is problematic, as ¿fineers of Lenexa, Kan. Buecker has over
chemistry that can prevent hydrogen sulfates and particualrly chlorides can 30 years of experience in or affiliated with
damage by even trace levels of chloride lead to corrosion and hydrogen dam- the power industry, much of it in chemis-
(Cl) or sulfate (SO^ ^). age of waterwall tubes. Caustic is also try, water treatment, air quality control,
For decades, some form of phosphate an alternative for units that suffer from and results en£Íneerin¿ipositions with City
treatment has been most popular for phosphate carryover to superheater and Water, Li^ht &• Power (Sprinßfield, III.)
steam generation chemistry control. The reheater tubes. and Kansas City Power &Li^ht Co.'s La
backbone of any program was feed of tri- Cy£[ne, Kansas station. He has an A.A. in
sodium phosphate (NajPO^) to generate Additional HRSG Corrosion Factors pre-en¿fineerin£[ from Sprinßfield College
an alkaline pH. Although combined-cycle units can in Illinois and a B.S. in chemistry from
now achieve 60 precent efficiency, they Iowa State University. He has written
« Na.HPO^ + NaOH are still often used for cycling operations. many articles and three booksfor PennWell
Naturally, this imposes thermal stress on Publishing on steam generation topics.
For many years, chemists would blend the HRSG. Simple fatigue will reduce Buecker is a member of the ACS, AIChE,
di-sodium phosphate (Na^HPO^) and component life. Furthermore, even with ASME and NACE.

POWERENGINEERING -' JULY 2011 / www.power-eng.com


Copyright of Power Engineering is the property of PennWell Corporation and its content may not be copied or
emailed to multiple sites or posted to a listserv without the copyright holder's express written permission.
However, users may print, download, or email articles for individual use.

You might also like