2. "C" STANDS FOR "CONTROL CKT." 3. ``IC" STANDS FOR INCOMING CIRCUIT M. N. DASTUR & COMPANY (P) LTD 4. ``OG" STANDS FOR OUTGOING CIRCUIT 5. 75x10mm G.I STRIP FOR EARTHING PURPOSE SHALL BE INSTALLED ALONG THE CABLE TRAY CONSULTING ENGINEERS, KOLKATA 6. IN SOME CASES, POWER CABLES MAY HAVE TO BE PARTIALLY LAID IN DOUBLE LAYER IN CABLE TRAY DUE TO SPACE LIMITATION. 1:1 GPH ISPAT LIMITED 7. CONTROL CABLES WILL BE LAID IN 2 - 3 LAYER IN CABLE TRAY. 8. CABLE TRAY SUPPORT SHALL BE PROVIDED @1500mm FOR HORIZONTAL RUNS & @1000mm CHITTAGONG,BANGLADESH FOR VERTICAL RUNS. 9. 300mm GAP SHALL GENERALLY BE CONSIDERED BETWEEN TWO CABLE TRAYS INSTALLATION OF 0.8 MTPY INTEGRATED STEEL PLANT PROJECT 10. ALL BENDS SHALL HAVE 600mm BENDING RADIUS AT THE INNER SIDE OF BEND CABLE ROUTING IN ROLL SHOP