NX70/NX700 Series Analog Modules

(A/D, D/A, RTD, TC)


User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Because of these differences, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Samsung Automation be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Samsung Automation cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Samsung Automation. with respect to use
of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Samsung Automation. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.

Identifies information about practices or circumstances which may


WARNING
lead to serious personal injury or death, property damage, or
economic loss.

Identifies information that is critical for successful application and


IMPORTANT
understanding of the product.

Identifies information about practices or circumstances that can lead


ATTENTION
to minor personal injury, property damage, economic loss, or
product malfunction. However, depending on circumstances, failure
to follow the directions accompanying this symbol may also lead to
serious consequences.
Contents

1. Specifications ............................................................. 9
General Specifications.................................................................................... 9
NX70, NX700 Analog Modules (V2.1) ......................................................... 10
NX70, NX700 Analog Module (V2.1) Features ........................................... 12

2. A/D Conversion Module ............................................ 13


A/D Conversion Module Specifications ...................................................... 15
Hardware Features........................................................................................ 17
Input Range Selection .................................................................................. 19
I/O Method for CPU Module......................................................................... 21
I/O Conversion Characteristics..................................................................... 23
Shared Memory Usage for A/D Conversion Module ................................. 25
A/D Conversion Module Operating Procedure........................................... 27
Programming ................................................................................................ 28

3. D/A Conversion Module ............................................ 31


D/A Conversion Module Specifications ...................................................... 33
Hardware Features........................................................................................ 35
Selection Output Range ............................................................................... 39
I/O Method for CPU Module......................................................................... 41
I/O Conversion Characteristics..................................................................... 43
Shared Memory Type Programming
(SW8: ON) ..................................................................................................... 46
D/A Conversion Module Operating Procedure........................................... 48
D/A Module Wiring Diagram........................................................................ 49
Programming ................................................................................................ 50

4. RTD Conversion Module ........................................... 53


RTD Conversion Module Specifications ..................................................... 55
RTD Module................................................................................................... 56
For NX70 PLC System .................................................................................. 57
RTD Module Input Range Selection ............................................................ 58
I/O Method for CPU Module......................................................................... 59
I/O Conversion Characteristics..................................................................... 61
Shared Memory Usage for RTD Conversion Module ................................ 63
RTD Conversion Module Operating Procedure.......................................... 65
RTD Conversion Module Wiring Diagram .................................................. 66
Programming ................................................................................................ 67

3
Shared Memory Type Programming (SW8: ON) ....................................... 68

5. TC Conversion Module.............................................. 71
TC Conversion Module Specification.......................................................... 73
TC Conversion Module................................................................................. 74
TC Conversion Module Input Range Selection .......................................... 76
I/O Method for CPU Module......................................................................... 78
I/O Conversion Characteristics..................................................................... 80
Shared Memory Usage for TC Conversion Module................................... 82
TC Conversion Module Operating Procedure ............................................ 84
TC Conversion Module Wiring Diagram..................................................... 85
Programming ................................................................................................ 86

6. Product Dimensions and Installation........................ 89


NX700 PLC Product Dimensions ................................................................. 89
NX70 PLC Product Dimensions ................................................................... 91
Mounting/Dismounting Module .................................................................. 93

4
Safety Instructions
Please read this manual and the related documentation thoroughly
and familiarize yourself with product information, safety instructions
and other directions before installing, operating, performing
inspection and preventive maintenance. Make sure to follow the
directions correctly to ensure normal operation of the product and
your safety.

WARNING
• If this product is used in a situation that may cause
personal injury and/or significant product damage,
implement safe measures such as use of fault-safe
equipment.
• Do not use this product under any conditions exposed
to explosive gases. It may cause an explosion.

ATTENTION • Make sure to use an external device when configuring


the protective circuit breakers for emergencies or
interlock circuits.
• Fasten the terminal screws tightly to ensure that the
cable connection is secure. Incorrect cable connection
may cause overheating and product malfunction.
• Operate and keep the product under the allowed
conditions directed in product specifications.
Otherwise it may cause overheating and product
malfunction.
• Do not disassemble or remodel the product.
Otherwise it may cause an electric shock or
malfunction.
• Do not touch the terminals when the power is on.
Otherwise it may cause an electric shock.

5
Installation Environment

ATTENTION Do not install your unit if any of the following conditions


are present:
• Ambient temperature outside the range of 0 to 55 °C
(32 to 131 °F).
• Direct sunlight.
• Humidity outside the range of 30% to 85%
(Non-condensing).
• Chemicals that may affect electronic parts.
• Excessive or conductive dust, or salinity.
• High voltage, strong magnetic fields, or strong
electromagnetic influences.
• Direct impact and excessive vibration.

ATTENTION
Installing Modules on the System
1. Wire analog I/O cables to the terminal block.
2. Turn on the power connected to the analog I/O
module.
3. Turn on the main PLC power.

ATTENTION
Removing Modules from the System
1. Turn off the main PLC power.
2. Turn off the power to the I/O modules.
3. Remove the wirings from the terminal block.

6
ATTENTION Preventing PLC System Malfunctions
• Use an isolation transformer and line filter on the
incoming power to the PLC when there is equipment
using or producing high current, high voltage, or
large magnetic fields in the vicinity.
• Use analog sensor that meets the rated specifications
for module connection. Otherwise,
it may cause operation errors.
• Separate the main PLC power line ground from all
other power grounds. Always use class 3 grounding.
• Do not exceed the current and power rating of the
external 24 VDC provided by the PLC power supply.
• Avoid system faults due to programming errors by
reading and fully understanding this system manual
and the PLC instruction set.
• Perform regular preventive maintenance on installed
systems, checking devices and wiring for potential
breakdowns and failures.

ATTENTION Installing analog module


• Avoid installing analog module next to output module
or power supply modules.
• Install analog modules as near the right edge of the
motherboard as possible.

7
Precautions for A/D Conversion Module Operation
What is A.GND of A/D module?

A.GND A.GND

e On an analog circuit, the digital part and external signal part are
isolated with a photocoupler, and the power supply is isolated with
a DC/DC converter.
e Usually the A.GND terminal is used to maintain a stable potential
by connecting it to a FG terminal or a high impedance condenser.
However, in many cases, noises from F.G terminal still may cause
AD module to measure wrong values. To address this problem, our
A/D module provides external FG and G.AND terminals, allowing
for a connection fitting to each application.
e In addition, our A/D module maintains high impedance at +, −
terminal and A.GND terminal.

Handling A.GND on A/D module


N Under conditions with much noise
Connect A.GND terminal to the negative potential terminal, N24, of
the sensor power.
(To prevent an incorrect measure on +, - voltage by the charged
electric voltage on A.GND terminal. The actual input voltage or
current can be incorrectly read by the charged voltage.) If you wire
the circuit as above, you can prevent charging on A.GND terminal.
N Usually, A.GND terminal is connected to - node (N24) of the sensor
power.

8
1
Specifications

General Specifications
Item Specifications
Operating 0 °C to +55 °C (32 °F to 131 °F)
Temperature Storage -25 °C to +70 °C (-13 °F to 158 °F)
Operating 30 to 85 % RH (Non-condensing)
Humidity
Storage 30 to 85 % RH (Non-condensing)
Withstand voltage 500 V ac for 1 minute between I/O terminal (dc) and frame ground (power unit)
100 MΩ or more at 500 mega V dc between I/O terminal (dc) and frame ground
Insulation resistance
(power unit)
10 to 55Hz, 1 cycle/minute: double amplitude of 0.75 mm, 10 minutes per axis
Vibration immunity
(X, Y, Z)
Shock immunity Peak acceleration and duration 15g/11 ms, 3 times for each X, Y, Z direction.
Noise immunity 1500 Vp-p with 50ns to 1µs pulse width (generated by noise simulator)
Ambience No corrosive gas, no excessive dust

• Avoid installing analog module next to output


ATTENTION
module or power supply modules.
There can be indirect interference on the module.
• Install analog modules as near the right edge of the
motherboard as possible.

9
NX70, NX700 Analog Modules (V2.1)
NX700 Analog module (V2.1)
Catalog
Module Specifications Remarks
number
8CH, Voltage Input, 16-bit A/D Converter, ±5 V, ±10 V, 0 to 5 V,
0 to 10 V
NX-AI8V
Resolution: 0.153 mV to 1.0 mV
Analog input Conversion speed: 1.25 ms/Ch
(A/D) 8CH, Current Input, 16-bit A/D Converter, ±20 mA, 0 to 20 mA,
4 to 20 mA
NX-AI8C
Resolution: 0.519 uA to 2.0 uA
Conversion speed: 1.25 ms/Ch
4CH, Voltage Output, 14-bit D/A Converter, ±10 V, ±5 V, 0 to 10 V,
0 to 5 V
NX-AO4V
Resolution: 0.305 mV to 1.0 mV
Conversion: speed 2.5 ms/Ch
8CH, Voltage Output, 14-bit D/A Converter, ±10 V, ±5 V, 0 to 10 V,
0 to 5 V
NX-AO8V
Analog output Resolution: 0.305 mV to 1.0 mV
(D/A) Conversion speed: 2.5ms/Ch
4CH, Current Output, 14-bit D/A Converter, 0 to 20 mA, 4 to 20 mA 20-pin
NX-AO4C Resolution: 0.037 uA to 2.0 uA, 4uA terminal
Conversion speed: 2.5ms/Ch block
8CH, Current Output, 14-bit D/A Converter, 0 to 20 mA, 4 to 20 mA (removable
NX-AO8C Resolution: 0.037 uA to 2.0 uA, 4uA type)
Conversion speed: 2.5 ms/Ch
4CH, 3-Wire type, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
Upgraded
JPt500, JPt1000, NI100, NI120, CU50, 300 Ω,
performance
NX-RTD4 1.2k Ω, 2000 Ω
(Ver 2.1)
Resistance Resolution: 0.1 °C, 0.1 °F, 10 mΩ, 20 mΩ
temperature Conversion speed: 60 ms/Ch
detector input 8CH, 3-Wire type, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
(RTD) JPt500, JPt1000, NI100, NI120, CU50, 300 Ω,
NX-RTD8 1.2 kΩ, 2000 Ω
Resolution: 0.1 °C/ 0.1 °F, 10 mΩ, 20 mΩ
Conversion speed: 60 ms/Ch
4CH, Type: B/R/S/N/K/E/J/T (The temperature range differs
depending on the sensor type.) ±30 mV (1uV /Bit),
NX-TC4 ±60 mV (2 uV/Bit)
Resolution: 0.1 °C, 0.1 °F, 1 uV, 2 uV
Thermocouple
Conversion speed: 60 ms/Ch
input
8CH, Type: B/R/S/N/K/E/J/T (The temperature range differs
depending on the sensor type.) ±30 mV (1 uV/Bit),
NX-TC8 ±60 mV (2 uV/Bit)
Resolution: 0.1 °C, 0.1 °F, 1 uV, 2 uV
Conversion speed: 60 ms/Ch

10
NX70 Analog module (V2.1)
Catalog
Module Specifications Remarks
number
8CH Voltage Input, 16-bit A/D Converter, ±5 V, ±10 V, 0 to 5 V,
0 to 10 V
NX70-AI8V
Resolution: 0.153 MTV to 1.0 mV)
Conversion speed: 1.25 ms/Ch
8CH Current Input, 16-bit A/D Converter, ±20 mA, 0 to 20 mA,
4 to 20 mA
NX70-AI8C
Resolution: 0.519 uA to 2.0 uA
Analog input Conversion speed: 1.25 ms/Ch
(A/D) 4CH Voltage Input, 16-bit A/D Converter, ±5 V, ±10 V, 0 to 5 V,
0 to 10 V
NX70-AI4V
Resolution: 0.153 MTV to 1.0 mV
Conversion speed: 1.25 ms/Ch
4CH Current Input, 16-bit A/D Converter, ±20 mA, 0 to 20 mA,
4 to 20 mA
NX70-AI4C
Resolution: 0.519 uA to 2.0 uA
Conversion speed: 1.25 ms/Ch
4CH Voltage Output, 14-bit D/A Converter, ±10 V, ±5 V, 0 to 10 V, 20-pin
0 to 5V terminal
NX70-AO4V
Resolution: 0.305 mV to 1.0 mV block type
Conversion speed: 2.5 ms/Ch
4CH Current Output, 14-bit D/A Converter, 0 to 20 mA, 4 to 20 mA
NX70-AO4C Resolution: 0.037 uA to 2.0 uA, 4 uA Upgraded
Analog output Conversion speed: 2.5 ms/Ch performance
(D/A) (Ver 2.1)
2CH Voltage Output, 14-bit D/A Converter, ±10 V, ±5 V, 0 to 10 V,
0 to 5 V
NX70-AO2V
Resolution: 0.305 mV to 1.0 mV
Conversion speed: 2.5 ms/Ch
2CH Current Output, 14-bit D/A Converter, 0 to 20 mA, 4 to 20 mA
NX70-AO2C Resolution: 0.037 uA to 2.0 uA, 4uA
Conversion speed: 2.5 ms/Ch
4CH 3-Wire type, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
Resistance
JPt500, JPt1000, NI100, NI120, CU50, 300 Ω,
temperature
NX70-RTD4 1.2 kΩ, 2000 Ω
detector input
Resolution: 0.1 °C, 0.1 °F, 10 mΩ, 20 mΩ
(RTD)
Conversion speed: 60 ms/Ch
4CH Type: B/R/S/N/K/E/J/T (The temperature range differs
depending on the sensor type.)
Thermocouple
NX70 -TC4 ±30 mV (1 uV/Bit), ±60 mV (2 uV/Bit)
input
Resolution: 0.1 °C, 0.1 °F, 1 uV, 2 uV
Conversion speed : 60 ms/Ch

11
NX70, NX700 Analog Module (V2.1) Features
Analog module (V2.1) features
• Conversion speed and resolution, the deciding factor for the performance
of analog unit, are processed with high-speed and
high-accuracy. Two programming methods-a method using shared
memory and a method using I/O contacts-allow you to select an
appropriate method according to the occupied I/O points.
• NX70, NX700 PLC analog modules are isolated from the internal
circuit with a DC/DC converter and a photocoupler. Low current
consumption is another advantage.

A/D module features

N Additional volume adjustment is not needed. 16-bit A/D Converter


enables a wider input range, faster conversion speed, and higher
Resolution (Selected with dip switch).
N Features high speed of 1.25ms/CH and high resolution. Provides
max. resolution of 0.153 mV for voltage type and 0.519 uA for
current type.
N Specifically, low current consumption has widened operation
range, and 20-pin terminal block is used for external connection.
(NX700 analog module uses removable terminal block.)

D/A module features


N Additional volume adjustment is not needed. 14-bit D/A Converter
enables a wider input range, faster conversion speed, and higher
resolution (Selected with dip switch).
N Wide channel range: For NX700, 4-channel and 8-channel D/A
modules are availalde. For NX70, 2-channel and 4-channel D/A
modules are available.
N Specifically, low current consumption has widened operation
range, and 20-pin terminal is used for external connection. (NX700
analog module uses removable terminal block.)

RTD/Thermocouple module features


N 24-bit Σ-∆ A/D Converter enables fast speed and high accuracy,
and wide I/O range. Self-calibration feature is also added. The
built-in analog & digital noise filter gives a good improves
resistance against environmental inferferences.
N RTD module implemented 3-wire connection type, which offsets
the wire resistance. The 3-wired platinum temperature sensors
(Pt100, Pt200, JPt100, JPt200....) support both Celsius (°C) and
Fahrenheit (°F) data.
N TC module provides temperature compensation feature, and
supports temperature sensor types of B, R, S, N, K, E, J, T, L, U, C
and D.
N Specifically, low current consumption has widened operation
range, and 20-pin terminal is used for external connection. (NX700
analog module uses removable terminal block.)

12
2
A/D Conversion Module

A/D Conversion Module

NX700 A/D Module (8CH) NX70 A/D Module (8, 4CH)


Voltage input: NX-AI8V Voltage input: NX70-AI8V, AI4V
Current input: NX-AI8C Current input: NX70-AI8C, AI4C

Temperature, speed,
1) Read data with the advanced instruction, READ, or Sensor
pressure, and flow
2) Read data from input contacts

Transducer Electric measurements


(Voltage, current, power,
TR OUT

RY OUT

ANALOG

NX-CPU750B NX-X64D NX-X32D NX-Y32T NX-Y16R NX-AI8C


DC IN

DC IN
CPU

POWER

and frequency)

COM
RS232C
Measurement Sensors
instrument
TOOL
RS232C

Displacement MQ laser sensor


sensor DSA displacement
sensor
Write data with the advanced instruction, WRITE

13
A/D Conversion Module Features
Additional volume adjustment is not required. Conversion speed and
resolution, the deciding factor for the performance of analog unit, are
processed with high-speed and high-accuracy.
1. NX700 A/D module: 8 channels/module
NX70 A/D module: 4 or 8 channels/module
2. Highly improved resolution
Provides max. resolution of 0.153 mV for voltage type, and 0.519 uA
for current type. You can select an appropriate resolution using the
DIP switch.
3. DC/DC converter and/or photocoupler isolation between the input
channels and the internal circuit.
4. Two programming methods
Provide two programming methods. You can select an appropriate
method according to the occupied I/O points:
c Using shared memory
d Using I/O contacts
5. High speed
The A/D module is equipped with 16-bit A/D converter, providing
high-accuracy conversion and high-speed processing of 1.25 ms per
channel.

14
A/D Conversion Module Specifications
Voltage Input Module
PLC Series NX700 Series NX70 Series
Catalog Number NX-AI8V NX70-AI8V NX70-AI4V
Analog input range Voltage: 0 to 10 V, 0 to 5 V, ±10 V, ±5 V
Digital conversion Signed 16-bit binary (2's complement)
Converter type 16-bit A/D converter
Number of analog
8 Channels 8 Channels 4 Channels
input channels
0 to 10 V (0 to 32767), (0 to 20000), ……
0 to 5 V (0 to 32767), (0 to 20000), ……
I/O characteristics *1
±10 V (-32767 to 32767), …………
±5 V (-32767 to 32767), …………
Max.
0.153 mV, (0.305 mV), ……
resolution *1
Overall accuracy ±0.2 %/F.S (25 °C)
Conversion speed 1.25 ms per channel
External input
500 kΩ
impedance
Absolute maximum
voltage: ±15 V, current: ±30 mA
input
Between input channel and internal circuit: DC/DC converter and photocoupler isolation
Isolation method
Between input channels: Non-isolation
I/O contact type:
NX700 (8 channels): 128 input points
Occupied I/O point NX70: 128 input points for 8-channel module, 64 input points for 4-channel module
Shared memory type: 16 points
Other functions Channel On/Off switching
Internal current
NX700: 5 V 270 mA or less NX70: 5 V 290 mA or less
consumption (5V)
External connection NX700: 20-pin removable
NX70: 20-pin terminal block (M3.0)
method terminal block (M3.5)
*1. Both I/O characteristics and maximum resolution can be set to from high to average by selecting the DIP switch
located on the bottom of the product. The conversion speed and stability for converted data depend on
resolution. See "Input Range Selection" in Chapter 2.

Voltage Input: NX-AI8V, NX70-AI8V, NX70-AI4V


A/D conversion module
Signal source: 0 to 10 V, 0 to 5 V, ±10 V, ±5 V

C stands for Common

A.GND must be connected


to sensor power
(-) terminal for stable
Shield operation.

15
Current Input Module
PLC series NX700 series NX70 series
Catalog number NX-AI8C NX70-AI8C NX70-AI4C
Number of analog
Voltage: 0 to 20 mA, 4 to 20 mA, ±20 mA
input channels
Digital conversion Signed 16-bit binary (2's complement)
Converter type 16-bit A/D converter
Analog input channels 8 Channels 8 Channels 4 Channels
0 to 20 mA(0 to 32767), (0 to 20000), ……
I/O characteristics *1 4 to 20 mA(0 to 32767), (0 to 20000), ……
20 mA(-32767 to 32767), …………
Max. resolution *1 0.519 uA (0.61 uA), ……
Overall accuracy ±0.3 %/F.S (25 °C)
Conversion speed 1.25 ms per channel
External input
249 Ω
impedance
Absolute maximum
Voltage: ±7.5 V, Current: ±30 mA
input
Between input channel and internal circuit: DC/DC converter and photocoupler isolation
Isolation method
Between input channels: Non-isolation
I/O contact type:
NX700 (8 channels): 128 input points
Occupied I/O point NX70: 128 input points for 8-channel module, 64 input points for 4-channel module
Shared memory type: 16 points
Other functions Channel On/Off switching
Internal current
NX700: 5 V 270 mA or less NX70: 5 V 290 mA or less
consumption (5V)
External connection NX700: 20-pin removable NX70: 20-pin terminal
method terminal block (M3.5) block (M3.0)
*1. Both I/O characteristics and maximum resolution can be set to from high to average by selecting the DIP switch
located on the bottom of the product. The conversion speed and stability for converted data depend on
resolution. See "Input Range Selection" in Chapter 2.

Current Input: NX-AI8C, NX70-AI8C, NX70-AI4C

A/D conversion module


Signal source: 0 to 20 mA, 4 to 20 mA, ±20 mA

C stands for Common

A.GND must be
connected to sensor
power (-) terminal for
stable operation.
Shield

16
Hardware Features
For NX700 PLC System
NX-AI8V (8CH, voltage input) NX-AI8C (8CH, current input)

RUN: A/D module normal operation


ERROR: A/D module ERROR

Input terminal (CH.0 to CH.7)


Select the range of input voltage and
current with the DIP switch on the
bottom of the module.

A.GND: Analog Ground


Connect to SENSOR POWER
(−) terminal for stable operation.
F.G: Frame Ground

Unused terminal (No Connection)

17
For NX70 PLC System
NX70-AI8V (8CH, voltage input) NX70-AI8C (8CH, current input)

NX70-AI8V RUN: A/D module normal operation NX70-AI8C


A /D

A /D
ERROR: A/D module error
RUN RUN
ERROR ERROR

V0 I0
C H .0 C H .0
C0 C0
V1 Input terminal (CH.0 to CH.7) I1
C H .1 C H .1
C1 Select the range of input voltage and C1
C H .2 V2 current with the DIP switch on the I2
C H .2
C2 bottom of the module. C2
V3 I3
C H .3 C H .3
C3 C3
V4 I4
C H .4 C H .4
C4 C4
C H .5 V5 C H .5
I5
C5 C5
A.GND: Analog Ground
V6 I6
C H .6 C H .6
C6 Connect to the (-) terminal of C6
V7 sensor power for stable operation. I7
C H .7 C H .7
C7 C7
F.G: Frame Ground
A.G ND A.G ND
F.G F.G
Unused terminal (No Connection)

NX70-AI4V (4CH, voltage input) NX70-AI4C (4CH, current input)

RUN: A/D module normal operation


ERROR: A/D module ERROR

Input terminal (CH.0 to CH.3)


Select the range of input voltage and
current with the DIP switch on the
bottom of the module.

Unused terminal (No Connection)

A.GND: Analog Ground


Connect to the (-) terminal of
sensor power for stable operation.
F.G: Frame Ground

18
Input Range Selection
Dip switch is located on the bottom of the module.

※ SW7 is currently not used.

SW8: Select conversion data I/O method


OFF: Set the I/O method to I/O contact type.
SW1 to SW4: SW5 to SW6: ON: Set the I/O method to shared memory type.
Input range Filter configuration

Dip Switch Settings


For Voltage input modules: NX700 A/D module (NX-AI8V), NX70 A/D
module (NX70-AI4V)
SW1 to SW4: Input range selection
SW1 SW2 SW3 SW4 Input range and conversion data Remarks

Factory
OFF OFF OFF OFF ±10 V: -10,000 to 10,000
default

ON OFF OFF OFF ±5 V: -10,000 to 10,000


OFF ON OFF OFF 0 to 10 V: 0 to 10,000

ON ON OFF OFF 0 to 5 V: 0 to 10,000

OFF OFF ON OFF ±10 V: -16,383 to 16,383


ON OFF ON OFF ±5 V: -16,383 to 16,383
OFF ON ON OFF 0 to 10 V: 0 to 16,383

ON ON ON OFF 0 to 5 V: 0 to 16,383

OFF OFF OFF ON ±10 V: -20,000 to 20,000


ON OFF OFF ON ±5 V: -20,000 to 20,000
OFF ON OFF ON 0 to 10 V: 0 to 20,000

ON ON OFF ON 0 to 5 V: 0 to 20,000

OFF OFF ON ON ±10 V: -32,767 to 32,767


ON OFF ON ON ±5 V: -32,767 to 32,767
OFF ON ON ON 0 to 10 V: 0 to 32,767

ON ON ON ON 0 to 5 V: 0 to 32,767

19
For Current Input Modules: NX700 A/D module (NX-AI8C), NX70 A/D
module (NX70-AI4C)
SW1 to SW4: Input range selection
SW1 SW2 SW3 SW4 Input range and conversion data Remarks

Factory
OFF OFF OFF OFF 0 to 20 mA: 0 to 10,000
default

ON OFF OFF OFF 4 to 20 mA: 0 to 10,000

OFF ON OFF OFF ±20 mA: -10,000 to 10,000

ON ON OFF OFF Not Used

OFF OFF ON OFF 0 to 20 mA: 0 to 16,383

ON OFF ON OFF 4 to 20 mA: 0 to 16,383

OFF ON ON OFF ±20 mA: -16,383 to 16,383

ON ON ON OFF Not Used

OFF OFF OFF ON 0 to 20 mA: 0 to 20,000

ON OFF OFF ON 4 to 20 mA: 0 to 20,000

OFF ON OFF ON ±20 mA: -20,000 to 20,000

ON ON OFF ON Not Used

OFF OFF ON ON 0 to 20 mA: 0 to 32,767

ON OFF ON ON 4 to 20 mA: 0 to 32,767

OFF ON ON ON ±20 mA: -32,767 to 32,767

ON ON ON ON Not Used

SW5 to SW6: Filter configuration selection


SW5 SW6 Filter configuration Remarks

OFF OFF Filter #0 (factory default)


Activating a filter that has
ON OFF Filter #1 a higher filter number
produces more stable
OFF ON Filter #2 conversion data but
slower conversion speed.
ON ON Filter #3

SW7: SW7 is currently not used.

SW8: Conversion data I/O method selection


A/D A/D Conversion data
SW8 Remarks
8CH 4CH input method

Factory default.
128 64
I/O contact type Easy to use.
OFF points points
(I/O conversion data) User programming for reading conversion
input input
data is not needed.

READ instruction on user program is needed


Shared memory type for reading conversion data.
ON 16 points
(I/O conversion data)
Range excess feature is available.

20
I/O Method for CPU Module
SW8 setting determines how the CPU module handles conversion data
from A/D module.
When SW8 is set to OFF, as many words of input contacts as the
channels are allocated and the CPU module updates these input
contacts every scan, which allows you to read conversion data of A/D
modules from these input contacts.
When SW8 is set to ON, only 1-word input contact is allocated and
conversion data are stored in shared memory. You should use the
READ instruction to read conversion data of A/D modules stored in this
shared memory. The 1-word input contact allocated is used as out-of-
range flags that indicate whether the conversion data of A/D modules
exceed the range or not.

I/O Contact Type (SW8, OFF)


Data conversion method is set to I/O contact type. (SW8 is set to OFF.)
N When an A/D module is mounted onto the first I/O slot (slot 0) and
SW8 is set to OFF (I/O contact type), 4-word (64 points) input
contacts are allocated for 4-channel A/D module and 8-word (128
points) for 8-channel A/D module.
For 8-channel A/D module (NX700: NX-AI8V, NX-AI8C) (NX70 :
NX70-AI8V, NX70-AI8C)
1. NX-series: 8 words (128 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), .........WX7 (Ch7)
2. NX-plus series: 8 words (128 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), .......R7 (Ch7)
For 4-channel A/D module (NX70: NX70-AI4V, NX70-AI4C)
1. NX-series: 4 words (64 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), WX3 (Ch3)
2. NX-plus series: 4 words (64 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), R3 (Ch3)
N If the data conversion method is set to I/O contact type, many input
contacts are used but you need not to use the READ (or RMRD)
instruction to read A/D conversion data because the CPU module
automatically updates them every scan. Therefore, no additional
programming is required to read A/D conversion data.

21
Shared Memory Type (SW8, ON)
Data conversion method is set to shared memory type. (SW8 is set to
ON.)
N When an A/D module is mounted onto the first I/O slot (slot 0) and
SW8 is set to ON (Shared memory type), 1-word (16 points) input
contacts are allocated regardless the number of A/D modules
mounted, and the conversion data is stored in the shared memory.
See "Shared Memory Usage for A/D Conversion Module" in Chapter 2.
You have to use the READ (or RMRD) instruction in your program to
read the conversion data stored in shared memory.
N The 16 input contacts allocated are used as out-of-range flags for
conversion data. They will be set as shown in the table below.
1. N-series: 1-word input contact (16SX, 16 points input with shared
memory)
2. N-plus series: 1-word input contact
N If data conversion method is set to shared memory type, only
16 points are allocated for A/D modules regardless of the number of
A/D modules mounted. In addition, many features designed for
shared memory are available.
When A/D module is inserted in slot 0: Values in ( ) are applicable to N-plus series

Input signal
Event Remarks
(Bit contact)
X0 (R0.0) ON when CH0 range is exceeded
X1 (R0.1) ON when CH1 range is exceeded
X2 (R0.2) ON when CH2 range is exceeded
X3 (R0.3) ON when CH3 range is exceeded

… ……………
X7 (R0.7) ON when CH7 range is exceeded

NOTE The out-of-range flag is set to ON in the case of no wiring or current of about 3.987
mA or less.

22
I/O Conversion Characteristics
Voltage Input Module (NX-AI8V, NX70-AI8V, NX70-AI4V)

-10 to 10 V Conversion data ※ Set the input range with the setting switches, SW1 to SW4.

32,767

16,383
SW3, SW4: ON, ON
(±10 V, -32767 to 32767)

-10 V -5 V 0
Input voltage
0 +5 V +10 V

Conversion data
-16,383
-10 V = -32,767
-5 V = -16,383
0V = 0
+5 V = 16,383
+10 V = 32,767
-32,767

0 to 5 V Conversion data ※ Set the input range with the setting switches, SW1 to SW4.

32,767

16,383 ON 1 2 3 4 5 6 7 8

SW1 to SW4: ON
(0 to 5 V, 0 to 32767)

-5 V 0
Input voltage
0 +2.5 V +5 V

Conversion data
0V= 0
2.5 V= 16,383
5 V = 32,767

23
Current Input Module (NX-AI8C, NX70-AI8C, NX70-AI4C)

0 to 20 mA ※ Set the input range with the setting switches, SW1 to SW4.

Conversion data

10,000
ON 1 2 3 4 5 6 7 8

SW1: ON
6,000 (0 to 20 mA, 0 to 10000)

2,000

Input current
0 +4 mA +12 mA +20 mA

Conversion data
Input current (mA) * 500 = Conversion data
0 mA = 0
4 mA x 500 = 2,000
12 mA x 500 = 6,000
20 mA x 500 = 10,000
>20 mA = 10,000

-20 to 20 mA ※ Set the input range with the setting switches, SW1 to SW4.

Conversion data

32,767

ON 1 2 3 4 5 6 7 8

SW2, SW3, SW4: ON, ON, ON


(-20 mA to 20 mA, -32767 to 32767)
16,383

-20 mA -10 mA 0
Input current
0 +10 mA +20 mA

Conversion data
-16,383
Input current (mA) = Conversion data
-20 mA = -32,767
-10 mA = -16.383
0 = 0
10 mA = 16,383
-32,767 20 mA = 32,767

24
Shared Memory Usage for A/D Conversion
Module
To use shared memory type for data processing of A/D conversion
module, set SW8 to ON.

Addressing of Shared Memory


A/D Module (NX700: NX-AI8V, NX-AI8C, NX70: NX70-AI8V, NX70-AI4V,
NX70-AI8C, NX70-AI4C)
Address Shared memory allocated for Remarks
0 CH0 A/D conversion value
1 CH1 A/D conversion value
2 CH2 A/D conversion value
3 CH3 A/D conversion value
4 CH4 A/D conversion value
Applicable for
5 CH5 A/D conversion value 8-channel A/D modules
6 CH6 A/D conversion value only (NX-AI8V, NX-AI8C,
NX70-AI8V, NX70-AI8C)
7 CH7 A/D conversion value
8 to 32 Reserved
33 Out-of-range flags for channels
34 to 45 Reserved
46 Analog module ROM Version H0200 = Ver 2.0
Other areas Reserved

NOTE The unit word of shared memory designated by an address consists of 16-bit.
For NX70 4-channel analog modules, there are no effective data in address 4 to 7.
The data in those addresses should be ignored.

25
Values and Data Configuration of Shared Memory
A/D conversion value (addresses 0 to 7: CH0 to CH7)
$xx denote hexadecimal representation.

The digital conversion value of A/D module will be shown as 1 Word (16BIT) of signed binary.
MSB (Most Significant Bit) =1 means (-) value, and MSB =0 means (+) value.
Negative values in hexadecimal (MSB = 1)
Ex) HFFFE ($FFFE)
1. Inverse each bit. HFFFE → H0001
2. Add 1. H0001 + 1 = H0002
3. HFFFE means -2 in decimal
Converting a negative decimal to hexadecimal
Ex) -3
1. Inverse the absolute value. H0003 → HFFFC
2. Add 1. HFFFC + 1 = HFFFD
3. "-3" is represented as HFFFD in hexadecimal.

Out-of-range flags allocation for channels (address 33)

Set to ON when the digital conversion value exceeds the set range. (Set to OFF when the input
value is between 4 to 20 mA.)

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


CH7 CH6 CH5 CH4 CH3 CH2 CH1 CH0

1: Out-of-range
0: Within range
Applicable only to 4 to 20 mA configuration
The flag is set to ON in the case of no wiring or current of about 3.987 mA or less.

26
A/D Conversion Module Operating Procedure
Conversion data I/O Procedure Operation
method setting
(SW8 setting) 1. Select conversion data input method with SW8.
Conversion OFF: I/O contact type
data input ON: Shared memory type
method setting 2. SW8 is only recognized on power-on, so input
Input range selection (SW8) method cannot be changed during PLC
(SW1 to SW4 setting)
operation.

1. Set the input range of the module.


Input range 2. Select voltage or current input.
Installation selection 3. Set the voltage or current range.
(SW1 to SW4)
4. Input range can be changed during PLC
operation.

Installation See "Mounting/Dismounting Module" on page 93.


Wiring
1. Refer to wiring diagram for the A/D module.
Wiring 2. In some cases, the wiring method for voltage
and current can be different. Please be cautious.
Reading conversion
data 1. When SW8 is set to ON (shared memory type),
use READ instruction to read conversion data
Reading from the shared memory.
conversion data 2. When SW8 is set to OFF (I/O contact type), no
additional instruction is needed.
N-series: WX area
N-plus series: R area

Please do not disassemble or modify internal components of the A/D


module.

27
Programming
N Programming methods are different for N-Series and N-plus Series.
N-series: NX70 (NX70-CPU750, NX70-CPU70), NX700 (NX-CPU700,
NX-CPU750A to NX-CPU750D) PLC CPU module
Use WinFPST for programing
N-plus series: NX70 (NX-CPU70p1, NX70-CPU70p2),
NX700 (NX-CPU700p) PLC CPU module
Use WinGPC for programing
N I/O contact type
No additional instruction is needed for I/O contact type. (ex. Slot
0 installation)
N-series: WX0 (Ch0), WX1 (Ch1), WX2 (Ch2), WX3 (Ch3),....
N-plus series: R0 (Ch0), R1 (Ch1), R2 (Ch2), R3 (Ch3),...
N Shared memory type
READ instruction is used for reading conversion data. Out-of-range
flags are provided.

I/O Contact Type Programming (SW8: OFF)


When A/D conversion module is installed in "slot 0"

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A,B,C,D): WinFPST S/W

[A/D conversion data]


WX0: CH0 conversion data
[ F0 MV, WX0, DT0 ]
WX1: CH1 conversion data
WX2: CH2 conversion data
WX3: CH3 conversion data
.
.
.
WX7: CH7 conversion data

N-pulse series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W
[A/D conversion data]
LET
D = W0 R0: CH0 conversion data
S = R0 R1: CH1 conversion data
R2: CH2 conversion data
R3: CH3 conversion data
.
.
.
R7: CH7 conversion data

N A/D conversion data is allocated to input contacts. Additional programming is not


needed for reading conversion data.
N CPU periodically updates the allocated input contacts with conversion data at every
scan.

28
Shared Memory Type Programming (SW8: ON)
Shared Memory Instruction - READ

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A,B,C,D): WinFPST S/W

S1: Installation slot number of A/D


module .
[ F150 READ, S1, S2, n, D ]
S2: Starting address of shared memory
where source data is stored.
n: The number of words of source data
to read.
D: Starting address of the destination to
store the read data to.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

TO: Starting address of the destination to


READ
store the read data to (To).
TO =
SZ = SZ: The number of words of source data
to read (Size).
FR =
FR: Installation slot number of A/D
module and starting address of
shared memory where source data is
stored (From).

Shared Memory Instruction - WRITE

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A, B, C, D): WinFPST S/W

S1: Installation slot number of A/D


module .
[ F151 WRITE, S1, S2, n, D ] S2: Starting address of the source data
to write to the destination.
n: The number of words of source data
to write to the destination.
D: Starting address of the destination in
shared memory to which the source
data is written.
N-plus series (NX70: NX70-CPU70p1, NX70-CPU70p2, NX700: NX-CPU700p):
WinGPC S/W

TO: Installation slot number of A/D


WRITE
module and starting address of the
TO = destination in shared memory to
SZ = which the source data is written (To).
FR =
SZ: The number of words of source data
to write to the destination (Size).
FR: Starting address of the source data
to write to the destination (From).

29
Example) Reading conversion data (READ)

N A/D conversion data is read as 1-word (16 bits) signed binary decimal.
N A/D module is installed onto slot 3.
N The following two instructions store conversion data of CH0 to CH7 to data memory
starting from DT0 and W0, respectively.

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A, B, C, D): WinFPST S/W

K3: Slot 3
K0: Starting address of the source data
[ F150 READ, K3, K0, K8, DT0 ] to read is address 0 of shared
memory in A/D module.
K8: Read 8 words starting from KO.
DT0: Store the read data to the
destination starting from DT0.
(Stored to DT0 to DT7)

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2, NX700: NX-CPU700p):


WinGPC S/W

READ TO = Store the read data to the


destination starting from W0.
TO= W0
(Stored to W0 to W7)
SZ= 8
FR= 3 : 0 SZ = Read 8 words from the starting
address designated by FR.
FR = Starting address of the source data
to read is address 0 of shared
memory in the A/D module installed
onto slot 3.

30
3
D/A Conversion Module

D/A Conversion Module

NX700 D/A module (8CH) NX70 D/A module (4CH)


Voltage output: NX-AO8V Voltage output: NX70-AO4V
Current output: NX-AO8C Current output: NX70-AO4C
NX700 D/A module (4CH) NX70 D/A module (2CH)
Voltage output: NX-AO4V Voltage output: NX70-AO2V
Current output: NX-AO4C Current output: NX70-AO2C

Inverter
Read data with the advanced instruction, READ

Motor speed controller

Thermometer

1) Write data with the advanced instruction, WRITE, or


2) Write data to output contacts

31
D/A Conversion Module Features
Additional volume adjustment is not required. Conversion speed and
resolution, the deciding factor for the performance of analog unit, are
processed with high-speed and high-accuracy.
1. NX700 D/A module: 8 channels or 4 channels/module
NX70 D/A module: 4 channels or 2 channels/module
2. DC/DC converter and/or photocoupler isolation between the input
channels and the internal circuit.
3. Highly improved resolution
Provides max. resolution of 0.6 mV for voltage type, and 0.12 uA for
current type.
4. Two programming methods
Provide two programming methods. You can select an appropriate
method according to the occupied I/O points:
c Using shared memory
d Using I/O contacts.
5. High speed
The D/A module is equipped with 14-bit D/A converter, providing
high-accuracy conversion and high-speed processing of 1.25 ms per
channel.

32
D/A Conversion Module Specifications

Voltage Output Module


PLC Series NX700 NX70
Catalog number NX-AO8V NX-AO4V NX70-AO4C NX70-AO2C
Analog output range ±10 V, 0 to 10 V, ±5 V, 0 to 5 V
Number of output
8 Channels 4 Channels 4 Channels 2 Channels
channels
Digital conversion Signed 16-bit binary (2's complement)
Converter type 14-bit D/A converter
1) ±10 V (-16,383 to 16,383), (-10,000 to 10,000)
2) 0 to 10 V (0 to 16,383), (0 to 10,000)
I/O characteristics *1
3) ±5 V (-16,383 to 16,383), (-10,000 to 10,000)
4) 0 to 5 V (0 to 16,383), (0 to 10,000)
Max.resolution *1 0.6 mV (0.305 mV, 0.5 mV, 1 mV)
Overall accuracy ±0.2 %/F.S (25 °C)
Conversion speed 2.5 ms per channel
Output impedance 0.1 Ω or less
Allowable output
5 K Ω or more
load resistance
Between output channel and internal circuit: DC/DC converter and photocoupler isolation
Isolation method
Between output channels: Non-insulation
Number of I/O I/O contact type, 8CH: 128 points output, 4CH: 64 points output, 2CH: 32 points output
points Shared memory type: 16 points
Internal current 5 V 420 mA or less 5 V 380 mA or less 5 V 350 mA or less 5 V 340 mA or less
consumption (5 V) (80 mA/CH at D/A (80 mA/CH at D/A (80 mA/CH at D/A (80 mA/ CH at D/A
*2 output) output) output) output)
External connection NX700: 20-pin removable terminal block
NX70: 20-pin terminal block (M3.0)
method (M3.5)

*1. Both I/O characteristics and maximum resolution can be set to from high to average by selecting the DIP switch
located on the bottom of the product. The conversion speed and stability for converted data depend on
resolution. See "Selection Output Range" in Chapter 3.
*2. It is recommended not to use more than eight voltage output D/A modules on the motherboard. (You can still
mount more than eight voltage output D/A modules. However, the number of modules that operate at the
same time should be equal to or less than eight due to limitation on total current consumption.)

Wiring Diagram: Voltage output

D/A conversion module


Input impedance: 1 kΩ or more
Load
< Output range >
±10V
0 to 10V
±5V
± to 5V

Shield C stands for Common

33
Current Output Module
PLC series NX700 NX70
Catalog number NX-AO8V NX-AO4V NX70-AO4V NX70-AO2V
Analog output range 0 to 20 mA, 4 to 20 mA
Output channels 8 Channels 4 Channels 4 Channels 2 Channels
Digital conversion Signed 16-bit binary (2's complement)
Converter type 14-bit D/A converter
0 to 20 mA (0 to 16,383), (-0 to 10,000)
I/O range *1
4 to 20 mA (0 to 16,383), (-0 to 10,000)
Maximum
1.2 uA (1.037 uA, 1.7 uA, 2 uA)
resolution *1
Overall accuracy ±0.4 %/F.S (25 °C)
Conversion speed 2.5 ms/CH
Output impedance 500 Ω or less
Allowable output
5 KΩ or more
load resistance
Between output channel and internal circuit: DC/DC converter and photocoupler isolation
Isolation method
Between output channels: No insulation
Number of I/O I/O contact type, 8CH: 128 points output, 4CH: 64 points output, 2CH: 32 points output
points Shared memory type: 16 points
Internal current 5 V 1000 mA or less 5 V 680 mA or less 5 V 650 mA or less 5 V 500 mA or less
consumption (5 V) (20 mA/CH at D/A (20 mA/CH at D/A (20 mA/CH at D/A (20 mA/CH at D/A
*2 output) output) output) output)
External connection NX700: 20-pin removable terminal block
NX70: 20-pin terminal block (M3.0)
method (M3.5)

*1. For I/O range and maximum resolution, you can select the suitable resolution from a wide range, with dip
switch on the bottom of the module. The conversion speed and conversion data stability can differ depending
on resolution. See "Selection Output Range" in Chapter 3.ed
*2. It is recommended not to use more than five D/A modules on the motherboard. (You can still mount more than
five D/A modules. However, the number of modules that operate at the same time should be equal to or less
than five due to limitation on total current consumption.)

Wiring Diagram: Current output


D/A conversion module
Input impedance: 500 Ω or less
Load
<Output range>
h0 to 20 mA
h4 to 20 mA

Shield C stands for Common

34
Hardware Features
For NX700 PLC System (1)
Voltage Output System

NX-AO8V (8CH, Voltage output) NX-AO4V (4CH, Voltage output)

RUN: D/A module normal operation


ERROR: D/A module ERROR

Output terminal (CH.0 to CH.7)


Set the output voltage range with the
DIP switch on the bottom of the
module.

Unused terminals

A.GND: Analog Ground


F.G: Frame Ground

Unused terminals

IMPORTANT In the illustrations above, “Unused terminals” are not


intended for use as connection points.

35
For NX700 PLC System (2)
Current Output Module

NX-AO8C (8CH, Current output) NX-AO4C (4CH, Current output)

RUN: D/A module normal operation


ERROR: D/A module ERROR

Output terminal (CH.0 to CH.7)


Set the output voltage range with
the DIP switch on the bottom of the
module.

Unused terminals

A.GND: Analog Ground


F.G: Frame Ground

Unused terminals

IMPORTANT In the illustrations above, “Unused terminals” are not


intended for use as connection points.

36
For NX70 PLC System (1)
Voltage Output Module

NX70-AO4V (4CH, Voltage output) NX70-AO2V (2CH, Voltage output)

RUN: D/A module normal operation


ERROR: D/A module ERROR

Input terminal (CH.0 to CH.3)


Set the output voltage range with
the DIP switch on the bottom of the
module.

Unused terminals

A.GND: Analog Ground


F.G: Frame Ground
Unused terminals

IMPORTANT In the illustrations above, “Unused terminals” are not


intended for use as connection points.

37
For NX70 PLC System (2)
Current output module

NX70-AO4C (4CH, Current output) NX70-AO2C (2CH, Current output)

RUN: D/A module normal operation


ERROR: D/A module ERROR

Input terminal (CH.0 to CH.3)


Set the output voltage range with
the DIP switch on the plane of the
module.

Unused terminals

A.GND: Analog Ground


F.G: Frame Ground

IMPORTANT In the illustrations above, “Unused terminals” are not


intended for use as connection points.

38
Selection Output Range
Dip switch is on the bottom of the module.

JSW4, SW5 and SW7 are currently not used.

SW8: Select conversion data I/O method


OFF: Set the I/O method to I/O contact type.
SW1 to SW3: SW6: ON: Set the I/O method to shared memory type.
Output range Output retention
setting

Dip switch settings


For Voltage output modules: NX700 PLC (NX-AO8V, NX-AO4V),
NX70 PLC (NX70-AO4V, NX70-AO2V)
SW1 to SW4: Output range setting
SW1 SW2 SW3 Output range and conversion data Remarks
OFF OFF OFF ±10 V: -10,000 to 10,000
ON OFF OFF ±5 V: -10,000 to 10,000
OFF ON OFF 0 to 10 V: 0 to 10,000
ON ON OFF 0 to 5 V: 0 to 10,000
OFF OFF ON ±10 V: -16,383 to 16,383
ON OFF ON ±5 V: -16,383 to 16,383
OFF ON ON 0 to 10 V: 0 to 16,383
ON ON ON 0 to 5 V: 0 to 16,383

Current output, NX700 PLC (NX-AO8C, NX-AO4C),


NX70 PLC (NX70-AO4C, NX70-AO2C)
SW1 to SW4: Output range setting
SW1 SW2 SW3 Output range and conversion data Remarks
OFF OFF OFF 0 to 20 mA: 0 to 10,000
ON OFF OFF 4 to 20 mA: 0 to 10,000
OFF ON OFF 4 to 20 mA: 2,000 to 10,000
ON ON OFF Not Used
OFF OFF ON 0 to 20 mA: 0 to 16,383
ON OFF ON 4 to 40 mA: 0 to 16,383
OFF ON ON 4 to 20 mA: 3,276 to 16,383
ON ON ON Not Used

39
SW6: Output retention setting
SW8 Output retention Remarks
ON Maintain the last output value on PLC stop
OFF Clear output value on PLC stop

SW8: Select conversion data I/O method


D/A D/A D/A Conversion data
SW8 Remarks
8CH 4CH 2CH input method
128 Easy to use.
64 points 32 points I/O contact type
OFF points User programming for reading conversion
output output (I/O conversion data)
output data is not needed.
Shared memory type WRITE instruction on user program is
ON 16 points
(I/O conversion data) needed for writing conversion data.

NOTE SW4, SW5 and SW7 are currently not used.

40
I/O Method for CPU Module
SW8 setting determines how the CPU module handles conversion data
from D/A module.
When SW8 is set to OFF, as many words of output contacts as the
channels are allocated and the CPU module updates these output
contacts every scan, which allows you to read conversion data of D/A
modules from these input contacts.
When SW8 is set to ON, only 1-word input contact is allocated and
conversion data are stored in shared memory. You should use the
READ instruction to read conversion data of D/A modules stored in this
shared memory. The 1-word input contact allocated is used as out-of-
range flags that indicate whether the conversion data of D/A modules
exceed the range or not.

I/O Contact Type (SW8, OFF)


Data conversion method is set to I/O contact type. (SW8 is set to OFF.)
N When an D/A module is mounted onto the first I/O slot (slot 0) and
SW8 is set to OFF (I/O contact type), 2-word (32 points) output
contacts are allocated for 4-channel D/A module and 8-word
(128 points) for 8-channel D/A module.
For 2-channel D/A module (NX70: NX70-AO2V, NX70-AO2C)
1. NX-series: 2 words (32 points output): WY0 (Ch0), WY1 (Ch1)
2. NX-plus series: 2 words (32 points output): R0 (Ch0), R1 (Ch1)
For 4-channel D/A module (NX70-AO4V, NX70-AO4C,
NX700: NX-AO4V, NX-AO4C))
1. NX-series: 4 words (64 points output): WY0 (Ch0), WY1 (Ch1),
WY2 (Ch2), WY3 (Ch3)
2. NX-plus series: 4 words (64 points output): R0 (Ch0), R1 (Ch1),
R2 (Ch2), R3 (Ch3)
For 8-channel D/A module (NX700: NX-AO8V, NX-AO8C)
1. NX-series: 8 words (128 points output): WY0 (Ch0), WY1 (Ch1),
WY2 (Ch2), ... WY7 (Ch7)
2. NX-plus series: 8 words (128 points output): R0 (Ch0), R1 (Ch1),
R2 (Ch2), ... R7 (Ch7)
N If the data conversion method is set to I/O contact type, many
output contacts are used but you need not to use the READ (or
RMRD) instruction to read D/A conversion data because the CPU
module automatically updates them every scan. Therefore, no
additional programming is required to read D/A conversion data.

41
Shared Memory Type (SW8, ON)
Data conversion method is set to shared memory type.
(SW8 is set to ON.)
N When an D/A module is mounted onto the first I/O slot (slot 0) and
SW8 is set to ON (Shared memory type), 1-word (16 points) input
contacts are allocated regardless the number of D/A modules
mounted and the conversion data is stored in the shared memory.
See "Shared Memory Type Programming (SW8: ON)" in Chapter 3.
You have to use the READ (or RMRD) instruction in your program to
read the conversion data stored in shared memory.
N The 16 input contacts allocated are used as out-of-range flags for
conversion data. They will be set as shown in the table below.
1.N-series: 1-word input contact (16SX, 16 points input with shared
memory)
2.N-plus series: 1-word input contact
N If data conversion method is set to shared memory type, only 16
points are allocated for D/A modules regardless of the number of
D/A modules mounted. In addition, many features designed for
shared memory are available.

When D/A module is inserted in slot 0: Values in ( ) are applicable to N-plus series.

Input signal (Bit contact) Event Remarks


X0 (R0.0) CH0 range is exceeded
X1 (R0.1) CH1 range is exceeded
X2 (R0.2) CH2 range is exceeded
X3 (R0.3) CH3 range is exceeded
X4 (R040) CH4 range is exceeded
X5 (R0.5) CH5 range is exceeded Applicable to only NX700 D/A
X6 (R0.6) CH6 range is exceeded module

X7 (R0.7) CH7 range is exceeded


X8(R0.8) to XF(R0.15) Currently not used

42
I/O Conversion Characteristics
Voltage output module (NX700: NX-AO8V, NX-AO4V,
NX70: NX70-AO4V, NX70-AO2V)

-10 to 10 V Output voltage ※ Set the output range with the setting switches, SW1 to SW3.

+10.000 V

+5.123 V SW1, 2, 3: OFF


(±10 V, -10,000 to 10,000)

-10,000 -4,321 0
Conversion data
0 5,123 10,000

Conversion data / 1,000 = output voltage (V)


ex) < -10000 = -10.000 V
-4.321 V -10000 / 1000 = -10.000 V
-4321 / 1000 = -4.321 V
0 / 1000 = 0V
5123 / 1000 = +5.123 V
10000 / 1000 = +10.000 V
> 10000 = +10.000 V
-10.000 V

-5 to 5 V ※ Set the output range with the setting switches, SW1 to SW3.
Output voltage

+5.0 V

+3.0 V
SW1, 2, 3: ON, OFF, OFF
(±5V, -10,000 to 10,000)

-10,000 -6,000
Conversion data
0 6,000 10,000

Conversion data / 2,000 = output voltage (V)


-3.0 V ex) < -10,000 = -5.0 V
-5000 / 2000 = -2.5 V
-6000 / 2000 = -3.0 V
0 / 2000 = 0 V
-5.0 V
4000 / 2000 = +2.0 V
5000 / 2000 = +2.5 V
> 10,000 = +5.0 V

43
Voltage output module (NX700: NX-AO8V, NX-AO4V, NX70:
NX70-AO4V, NX70-AO2V)

0 to 10 V ※ Set the output range with the setting switches, SW1 to SW3.
Output voltage

+10.000 V

SW1, 2, 3: OFF, ON, OFF


(0 to 10V, 0 to 10,000)
+5.123 V

-10.000 V
Conversion data
0 5,123 10,000

Conversion data / 1,000 = output voltage (V)


ex) < 0=0V
0 / 1000 = 0 V
5123 / 1000 = +5.123 V
10000 / 1000 = +10.000 V
> 10000 = +10.000 V

0 to 5 V ※ Set the output range with the setting switches, SW1 to SW3.
Output voltage

+5.0 V

SW1, 2, 3: ON, ON, OFF


(0 to 5 V, 0 to 10,000)
+2.5 V

Conversion data
0 5,000 10,000

Conversion data / 2,000 = output voltage (V)


ex) < 0=0V
0 / 2000 = 0 V
5000 / 2000 = +2.5 V
10000 / 2000 = +5.0 V
> 10000 = +5.000 V

44
Current output module (NX700: NX-AO8C, NX-AO4C,
NX70: NX70-AO4C, NX70-AO2C)
$xx denote hexadecimal representation.

4 to 20 mA ※ Set the input range according to SW (setting switch) status.


Output voltage

+20.00 mV ON 1 2 3 4 5 6 7 8

SW1, 2, 3: OFF, ON, OFF


(4 to 20 mA, 2,000 to 10,000)
+12.00 mV

Conversion data
0 2,000 6,000 10,000

Conversion data / 500 = output current (V)


ex) < 2000 = +4.00 mA
3000 / 500 = +6.00 mA
6000 / 500 = +12.00 mA
10000 / 500 = +20.00 mA
> 10000 = +20.00 mA

0 to 20 mA ※ Set the input range according to SW (setting switch) status.


Output voltage

+20.00 mV

SW1, 2, 3: OFF, OFF, OFF


+12.00 mV (0 to 20 mA, 0 to 10,000)

+2.00 mV

Conversion data
0 1,000 6,000 10,000

Conversion data / 2,000 = output current (V)


ex) < 0 = 0 mA
1000 / 500 = +2.00 mA
6000 / 500 = +12.00 mA
10000 / 500 = +20.00 mA
> 10000 = +20.00 mA

45
Shared Memory Type Programming
(SW8: ON)
To use shared memory type for data processing of D/A conversion
module, set SW8 to ON.

Addressing of Shared Memory


Address Shared memory allocated for Remarks
0 CH.0 D/A digital value to convert
1 CH.1 D/A digital value to convert
2 CH.2 D/A digital value to convert
3 CH.3 D/A digital value to convert
4 CH.4 D/A digital value to convert
5 CH.5 D/A digital value to convert
Applicable to only NX700 D/A module
6 CH.6 D/A digital value to convert
7 CH.7 D/A digital value to convert
8 to 32 Reserved
32 Out-of-range flags for channels
34 Change per channel setting = OxFFFF (Default)
46 Analog module ROM Version H0200 = Ver 2.0
Other areas Reserved

NOTE The unit word of shared memory designated by an address consists of 16-bit.

46
Values and Data Configuration of Shared Memory
D/A conversion value (Addresses 0 to 7: CH0 to CH7)
$xx denote hexadecimal representation.

The digital conversion value of D/A module will be shown as 1 Word (16BIT) of signed binary.
MSB (Most Significant Bit) =1 means (-) value, and MSB =0 means (+) value.
Negative values in hexadecimal (MSB = 1)
Ex) HFFFE ($FFFE)
1. Inverse each bit. HFFFE → H0001
2. Add 1. H0001 + 1 = H0002
3. HFFFE means -2 in decimal
Converting a negative decimal to hexadecimal
Ex) -3
1. Inverse the absolute value.. H0003 → HFFFC
2. Add 1. HFFFC + 1 = HFFFD
3. "-3" is represented as HFFFD in hexadecimal.

Out-of-range flags allocation for channels (address 33)

Turned to ON when the digital value to output exceeds the set range.

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


CH7 CH6 CH5 CH4 CH3 CH2 CH1 CH0

1: Out-of-range
±10V 0: Within range
: < -10100 or > 10100, ............
±5V
: < -10100 or > 10100, ............
0 to 10V
: < -100 or > 10100, ............
0 to 5V
: < -100 or > 10100, ...........
4 to 20 mA
: < -100 or > 10100, ...........
0 to 20 mA
: < -100 or > 10100, ............
NOTE Other exceeded range area is determined by dip switch settings.

47
D/A Conversion Module Operating Procedure

Conversion data input Procedure Operation


method setting
(SW8) 1.Select conversion data input method with SW8.
Conversion data OFF: I/O contact type
I/O method ON: Shared memory type
setting (SW8) 2.SW8 is only recognized on power-on, so input method
cannot be changed during PLC operation.
Output retention
setting(SW6) 1.Retain the last output value on PLC STOP: The last
Output retention output value on PLC STOP will be maintained.
setting (SW6) 2.SW7 is only recognized on power-on, so the settings
cannot be changed during PLC operation.
Output range setting
(SW1 to SW3) Output range
1.Set the output range of the module.
setting
2.Output range can be changed during PLC operation.
(SW1 to SW3)

Installation
Installation See Mounting/Dismounting Module on page 93.

Wiring Refer to wiring diagram for the D/A module.


Wiring
1.When SW8 is set to ON (shared memory type), use
WRITE instruction to write conversion data to the
shared memory.
Writing
2.When SW8 is set to OFF (I/O contact type),
conversion data
Writing conversion data no additional instruction is needed.
N-series: WY area
N-plus series: R area

Please do not disassemble or modify internal components of the D/A


module.

48
D/A Module Wiring Diagram
Voltage Output (Voltage)

D/A conversion module


Input impedance: 1 KΩ or more
Load

<Output range>
±10V
0 to 10V
±5V
0 to 5V

Shield C stands for Common

Current Output (Current)

D/A conversion module


Input impedance: 500 Ω or more
Load

<Output range>
0 to 20 mA
4 to 20 mA

Shield C stands for Common

N Use 2-core twisted shield cable for analog output signal wire.
N Do not place analog output signal wire near to wires other than
PLC, such as AC cables or high voltage cables. Do not tie cables.
N Ground the shield of shield cable near to the load.
N Do not use same cables for signal wire and AC wire to outside
devices.

49
Programming
• Programming methods are different for N-Series and N-plus Series.
N-series: NX70 (NX70-CPU750, NX70-CPU70), NX700(NX-CPU700,
NX-CPU750A to NX-CPU750D) PLC CPU module
Use WinFPST for programing
N-plus series: NX70 (NX-CPU70p1, NX70-CPU70p2),
NX700 (NX-CPU700p)
Use WinGPC for programing
• I/O contact type
No additional instruction is needed for I/O contact type. (ex. Slot 0
installation)
N-series: WY0 (Ch0), WY1 (Ch1), WY2 (Ch2), WY3 (Ch3),....
N-plus series: R0 (Ch0), R1 (Ch1), R2 (Ch2), R3 (Ch3),...
• Shared memory type
WRITE instruction is used for writing the data to convert, and
READ instruction is used for reading conversion data. Out-of-range
flags are provided.

I/O Contact Type Programming (SW8: OFF)


When D/A conversion unit is installed in "slot 0"
N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,
NX-CPU750A, B, C, D): WinFPST S/W

[D/A conversion data]


WY0: CH0 data to convert
[ F0 MV, DT0, WY0 ] WY1: CH1 data to convert
WY2: CH2 data to convert
WY3: CH3 data to convert
.
.
.
WY7: CH7 data to convert

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2, NX700:


NX-CPU700p): WinGPC S/W

[D/A conversion data]


LET
D = R0 R0: CH0 data to convert
R1: CH1 data to convert
S = W0
R2: CH2 data to convert
R3: CH3 data to convert
.
.
.
R7: CH7 data to convert

N D/A conversion data is allocated to output contact. Additional programming is not


needed for writing conversion data.
N CPU periodically updates the allocated input contacts with conversion data at every
scan.

50
Shared Memory Type Programming (SW8: ON)
Shared Memory Instruction- READ
N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,
NX-CPU750A, B, C, D): WinFPST S/W

S1: Installation slot number of D/A


module.
S2: Starting address of shared memory
[ F150 READ, S1, S2, n, D ] where source data is stored.
n: The number of words of source data
to read.
D: Starting address of the destination to
store the read data to.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W
TO: Starting address of the
READ
destination to store the read data
TO = to (To).
SZ =
SZ: The number of words of source
FR =
data to read (Size).
FR: Installation slot number of D/A
module and starting address of
shared memory where source
data is stored (From).

Shared Memory Instruction - WRITE

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A, B, C, D): WinFPST S/W

S1: Installation slot number of D/A


module .
[ F150 WRITE, S1, S2, n, D ] S2: Starting address of the source
data to write to the destination
n: The number of words of source
data to write to the destination.
D: Starting address of the
destination in shared memory to
which the source data is written.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W
TO: Installation slot number of D/A
WRITE
module and starting address of the
TO =
destination in shared memory to
SZ = which the source data is written
FR = (To).
SZ: The number of words of source
data to write to the destination
(Size).
FR: Starting address of the source data
to write to the destination(From).

51
Example: Writing conversion data (WRITE)

N D/A conversion data is read as 1-word (16 bits) signed binary decimal.
N D/A module is installed onto slot 3.
N When the digital value of DT0 to DT3 is converted to D/A value (current or voltage) of
CH0 to CH7.

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A, B, C, D): WinFPST S/W
K3: Slot 3
DT0: Values of DT0 to DT3
[ F151 WRITE, K3, DT0, K4, K0 ] (data to convert)
K4: Read 4 words starting from KO.
K0: Shared memory 0 (From D/A
shared memory 0)

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

WRITE TO = 3: 0: From shared memory


0 on slot 3
TO = 3 : 0
SZ = 4 SZ = 4: 4 words written
FR = W0 W0: Values of W0 to W3 (data to
convert)

52
4
RTD Conversion Module

RTC Conversion Module

NX700 RTD Module (4CH)


NX-RTD4
NX70 RTD Module (4CH)
NX700 RTD module (8CH)
NX70-RTD4
NX-RTD8

1) Read data with the advanced instruction, READ, or


2) Read data from input contacts
3-wired RTD sensor
(Pt100, JPt100,
Pt200, JPt200.....)

-200 to 850 °C
-200 to 640 °C
Write data with the advanced instruction, WRITE

53
RTD Conversion Module Features
24-bit Σ−D A/D converter enables high accuracy and fast speed. Wide
I/O range and self-calibration feature are also implemented.
1. NX700 RTD module: 4 channels or 8 channels/module
NX70 RTD module: 4 channels/module
2. Type of temperature sensor
3-wire platinum sensor is available. (Pt100, Pt200, Jpt100,
Jpt200......)
3. Data both in Celsius (°C) and Fahrenheit (°F) are usable.
You can select this with DIP switch on the bottom of the module.
4. Two programming methods
Provide two programming methods. You can select an appropriate
method according to the occupied I/O points:
c Using shared memory
d Using I/O contacts
5. Designed for strong noise immunity
The built-in analog & digital noise filter provides superior immunity
against interference from outside.

54
RTD Conversion Module Specifications
RTD (Resistive Temperature Detectors)

NX700 PLC, NX-RTD8 NX700 PLC, NX-RTD4 NX70 PLC, NX70-RTD4


Catalog number
(8 channels / module) (4 channels / module) (4 channels / module)

RTD sensor 3-Wire


Number of RTD
8 Channels 4 Channels 4 Channels
input channels
Digital conversion Signed 16-bit binary (2's complement)
Converter type 24-bit Σ−D A/D Converter
c Pt100 (a=0.00385, -200 to 850 °C => -2,000 to 8,500) g 300 Ω (10m Ω/BIT)
I/O characteristics
(Temperature d Pt200, Pt500, Pt1000 h 1.2K Ω (20m Ω/BIT)
sensor and e JPt100 (a=0.00385, -200 to 640 °C => -2,000 to 6,400 i 2000 Ω (100m Ω/BIT)
digital output)
f Jpt200, Jpt500, Jpt1000 j NI100, NI120, CU10
Max. resolution 0.1 °C, 0.1 °F, 10 mΩ, 20 mΩ
Overall accuracy ±0.1 %/F.S (25 °C)
Conversion speed 60 ms/CH
External input
10 MΩ
impedance
Current source 1 mA (Excitation Current)
Between input channel and internal circuit: DC/DC converter and photocoupler Isolation
Isolation method
Between input channels: Non-isolation
I/O contact type: 128
Number of I/O points input I/O contact type: 64 points input
points Shared memory type: 16 Shared memory type: 16 points input
points input
Internal current Internal power 5 V 330 mA or
Internal power 5 V 340 mA or less
consumption (5 V) less
External
connection 20-pin removable terminal block (M3.5) 20-pin terminal block (M3.0)
method

NX700/NX70 RTD (Resistive Temperature Detectors) Input

RTD Sensor
(Pt100, JPt100) RTD conversion module

3-Wire of +, -, GND
Conversion to
temperature (°C, °F)

-200 to 850 °C 3- Wire type for the correction


-200 to 640 °C of resistance between the
lines.

55
RTD Module
For NX700 PLC System
NX-RTD8 (8CH, RTD input) NX-RTD4 (4CH, RTD input)

RUN: RTD module normal operation


ERROR: RTD module ERROR

RTD input terminal (CH.0 to CH.7)


- 3-Wire of (+), (-), GND
- Select the input sensor type
with the DIP switch on the bottom of
the module

Unused terminal (No Connection)

56
For NX70 PLC System
NX70-RTD4 (4CH, RTD input)

RUN: RTD module normal operation


ERROR: RTD module ERROR

RTD input terminal (CH.0 to CH.3)


- 3-Wire of (+), (-), GND
- Select the input sensor type with
the DIP switch on the bottom of the
module

Unused terminal (No Connection)

57
RTD Module Input Range Selection
Dip switch is located on the bottom of the module.

SW8: Select conversion data I/O method


OFF: Set the I/O method to I/O contact type.
ON: Set the I/O method to shared memory type.

SW7: Temperature unit setting


OFF: °C
SW1 to 4: SW5 and 6: ON: °F
Input range Filter setting

Dip Switch Settings


SW1 to SW4: Input range setting
SW1 SW2 SW3 SW4 Input range and conversion data Remarks
OFF OFF OFF OFF PT100, 0.00385, -200 to 850 °C, 0.1 °C or 0.1 °F/count
ON OFF OFF OFF PT200, 0.00385, -200 to 850 °C, 0.1 °C or 0.1 °F/count
OFF ON OFF OFF PT500, 0.00385, -200 to 850 °C, 0.1 °C or 0.1 °F/count
ON ON OFF OFF PT1000, 0.00385, -200 to 270 °C, 0.1 °C or 0.1 °F/count
OFF OFF ON OFF JPT100, 0.003916, -200 to 640 °C, 0.1 °C or 0.1 °F/count
ON OFF ON OFF JPT200, 0.003916, -200 to 640 °C, 0.1 °C or 0.1 °F/count
OFF ON ON OFF JPT500, 0.003916, -200 to 640 °C, 0.1 °C or 0.1 °F/count
ON ON ON OFF NI100, 0.00618, -60 to 250 °C, 0.1 °C or 0.1 °F/count
OFF OFF OFF ON NI200, 0.00618, -60 to 250 °C, 0.1 °C or 0.1 °F/count
ON OFF OFF ON NI500, 0.00618, -60 to 250 °C, 0.1 °C or 0.1 °F/count
OFF ON OFF ON NI120, 0.00672, -80 to 250 °C, 0.1 °C or 0.1 °F/count
ON ON OFF ON CU10, 0.00427, -200 to 260 °C, 0.1 °C or 0.1 °F/count
OFF OFF ON ON Resistance Input, 1 to 2,000 Ω, 100 mΩ/1count
ON OFF ON ON Resistance Input, 1 to 327 Ω, 10 mΩ/1count
OFF ON ON ON Resistance Input, 1 to 1.2 KΩ, 50 mΩ/1count
ON ON ON ON Not Used

SW5 to SW6: Filter setting SW7: Temperature unit setting


SW5 SW6 Filter setting Remarks SW7 Temperature unit
OFF OFF Filter #0 Activating a filter that has a OFF 0.1 °C
ON OFF Filter #1 higher filter number
produces more stable 0.1 °F
OFF ON Filter #2 conversion data but slower ON
°F = (9/5) x °C + 32
ON ON Filter #3 conversion speed.

SW8: Conversion data I/O method setting


RTD RTD Conversion data input
SW8 Input range and conversion data
8CH 4CH method

128 64 Easy to use.


I/O contact type
OFF points points User programming for reading conversion data
(I/O conversion data)
input input is not needed.
READ instruction on user program is needed for
Shared memory type reading conversion data.
ON 16 points
(I/O conversion data)
Range excess feature available.

58
I/O Method for CPU Module
SW8 setting determines how the CPU module handles conversion data
from RTD module.
When SW8 is set to OFF, as many words of input contacts as the
channels are allocated and the CPU module updates these input
contacts every scan, which allows you to read conversion data of RTD
modules from these input contacts.
When SW8 is set to ON, only 1-word input contact is allocated and
conversion data are stored in shared memory. You should use the
READ instruction to read conversion data of RTD modules stored in
this shared memory. The 1-word input contact allocated is used as out-
of-range flags that indicate whether the conversion data of RTD
modules exceed the range or not.

I/O Contact Type (SW8, OFF)


Data conversion method is set to I/O contact type. (SW8 is set to OFF.)
N When an RTD module is mounted onto the first I/O slot (slot 0) and
SW8 is set to OFF (I/O contact type), 4-word (64 points) input
contacts are allocated for 4-channel RTD module and 8-word (128
points) for 8-channel RTD module.
For 8-channel RTD module (NX700: NX-RTD8)
1. NX-series: 8 words (128 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), .........WX7 (Ch7)
2. NX-plus series: 8 words (128 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), .......R7 (Ch7)
For 4-channel RTD module (NX700: NX-RTD4, NX70: NX70-RTD4)
1. NX-series: 4 words (64 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), WX3 (Ch3)
2. NX-plus series: 4 words (64 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), R3 (Ch3)
N If the data conversion method is set to I/O contact type, many input
contacts are used but you need not to use the READ (or RMRD)
instruction to read RTD conversion data because the CPU module
automatically updates them every scan. Therefore, no additional
programming is required to read RTD conversion data.

59
Shared Memory Type (SW8, ON)
Data conversion method is set to shared memory type. (SW8 is set to
ON.)
N When an RTD module is mounted onto the first I/O slot (slot 0) and
SW8 is set to ON (Shared memory type), 1-word (16 points) input
contacts are allocated regardless the number of RTD modules
mounted and the conversion data is stored in the shared memory.
See "Shared Memory Usage for RTD Conversion Module" in Chapter 4.
You have to use the READ (or RMRD) instruction in your program to
read the conversion data stored in shared memory.
N The 16 input contacts allocated are used as out-of-range flags for
conversion data. They will be set as shown in the table below.
1. N-series: 1-word input contact (16SX, 16 points input with shared
memory)
2. N-plus series: 1-word input contact
N If data conversion method is set to shared memory type, only
16 points are allocated for RTD modules regardless of the number
of RTD modules mounted. In addition, many features designed for
shared memory are available.

When RTD module is inserted in slot 0 Values in ( ) are applicable to N-plus series.

Input signal
Event Remarks
(BIT contact)
X0 (R0.0) ON when CH0 range is exceeded
X1 (R0.1) ON when CH1 range is exceeded
X2 (R0.2) ON when CH2 range is exceeded
X3 (R0.3) ON when CH3 range is exceeded
...... Reserved
X7 (R0.7) ON when CH7 range is exceeded

60
I/O Conversion Characteristics
$xx denote hexadecimal representation.

Pt100 (α=0.00385) ※ Set the input range with the setting switches, SW1 to SW4.

Range: -200 to 850 °C


Resolution: 0.1 °C/0.1 °F Conversion data

8,500
(850.0 °C)

°F = −
9 °C + 32
5
SW1 to SW4: OFF
1,000 (PT100, 0.00385, -200 to 850)
(100.0 °C)

18.49

100 138.5 322.66

Conversion data/10 = temperature (°C)


ex) 8500 / 10 = 850.0 °C
1000 / 10 = 100.0 °C
-2,000 0 / 10 = 0.0 °C
(-200.0 °C) -2000 / 10 = -200.0 °C
-2000 = HF830 = $F830

Conversion data without RTD sensor = H8000 = 32768

JPt100 (α=0.003916) ※ Set the input range with the setting switches, SW1 to SW4.

Range: -200 to 640 °C


Resolution: 0.1 °C/0.1 °F Conversion data

6,400
(640.0 °C)

°F = −
9
5 °C + 32 SW1 to SW4: OFF, OFF, ON, OFF
(PT100, 0.00385, -200 to 850)
1,000
(100.0 °C)

18.49

100 139.16 284.02
Conversion data/10 = temperature (°C)
ex) 6400 / 10 = 640.0 °C
1000 / 10 = 100.0 °C
0 / 10 = 0.0 °C
-2,000 -2000 / 10 = -200.0 °C
(-200.0 °C) -2000 = HF830 = $F830

Conversion data without RTD sensor = H8000 = 32768

61
327 Ω (10 mΩ/1count) ※ Set the input range with the setting switches, SW1 to SW4.

Resolution: 10 mΩ(=0.01 Ω) Conversion data

32,700
(327.00 Ω) SW1 to SW4: ON, OFF, ON, ON
(Resistance input, 1 to 327 Ω,
10 mΩ/Bit)
1,000
(150.00 Ω)

139.16 284.02

100

Conversion data / 100 = Resistance(Ω)


ex) 32700 / 100 = 327.00 Ω
15020 / 100 = 150.20 Ω
0 / 100 = 0.00 Ω

※ Set the input range with the setting switches, SW1 to SW4.
2000 Ω (100 mΩ/1count)
Resolution: 100 mΩ(=0.1 Ω) Conversion data

20,000 SW1 to SW4: OFF, OFF, ON, ON


(200.0 Ω) (Resistance input, 1~2000 Ω,
100 mΩ/Bit)

10,004
(1000.4 Ω)


0 1000.4 2000.0

Conversion data / 100 = Resistance(Ω)


ex)
20000 / 100 = 2000.0 Ω
10004 / 100 = 1000.40 Ω
0 / 100 = 0.00 Ω

62
Shared Memory Usage for RTD Conversion
Module
To use shared memory type for data processing of RTD conversion
module, set SW8 to ON.

Addressing of Shared Memory


RTD Module (NX700: NX-RTD4, NX-RTD8, NX70: NX70-RTD4)
Address Shared memory allocated for Remarks
0 CH0 RTD conversion value
1 CH1 RTD conversion value
2 CH2 RTD conversion value
3 CH3 RTD conversion value
4 CH4 RTD conversion value
5 CH5 RTD conversion value Applicable to only
6 CH6 RTD conversion value NX700 A/D
7 CH7 RTD conversion value
8 to 15 Reserved
16 Out-of-range flags for channels
17 to 45 Reserved
46 Analog module ROM Version H0200 = Ver 2.0
Other areas Reserved

NOTE The unit word of shared memory designated by an address consists of 16-bit.
For NX70 RTD module, there are no effective data in address 4 to 7. The data in
those addresses should be ignored.

63
Values and Data Configuration of Shared Memory
RTD conversion value (addresses 0 to 7: CH0 to CH7)
$xx denote hexadecimal representation.

The digital conversion value of RTD module will be shown as 1 Word (16-bit) of signed binary.
MSB (Most Significant Bit) =1 means (-) value, and MSB =0 means (+) value.
Negative values in hexadecimal (MSB = 1)
Ex) HFFFE ($FFFE)
1. Inverse each bit. HFFFE → H0001
2. Add 1. H0001 + 1 = H0002
3. HFFFE means -2 in decimal
Converting a negative decimal to hexadecimal
Ex) -3
1. Inverse the absolute value. H0003 → HFFFC
2. Add 1. HFFFC + 1 = HFFFD
3. "-3" is represented as HFFFD in hexadecimal.

Out-of-range flags allocation for channels (address 16)

Set to ON when the digital conversion value exceeds the set range.
Indicated when the RTD sensor is not connected at Pt100, JPt100 input.
Not indicated when the input range is 327 Ω, 1200 Ω, 2000 Ω.

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


CH7 CH6 CH5 CH4 CH3 CH2 CH1 CH0

1: RTD sensor not connected, Out-of-range


0: RTD sensor connected

64
RTD Conversion Module Operating Procedure
Conversion data I/O Procedure Operation
method setting
(SW8 setting) 1. Select conversion data input method with SW8.
Conversion OFF: I/O contact type
data input ON: Shared memory type
method setting 2. SW8 is only recognized on power-on, so input
Input range setting (SW8) method cannot be changed during PLC
(SW1 to SW4 setting)
operation.

1. Set the sensor type (input range).


Input range
2. Set the temperature unit (°C or °F).
setting
Installation (SW1 to SW4) 3. Input range can be changed during PLC
operation.

Installation See "Mounting/Dismounting Module" on page 93.

Wiring 1. Refer to wiring diagram for the RTD module.


Wiring
2. Use 3-Wire RTD sensor to connect (+), (-), GND

1. When SW8 is set to ON (shared memory type),


Reading conversion use READ instruction to read conversion data
data Reading from the shared memory.
conversion data 2. When SW8 is set to OFF (I/O contact type), no
additional instruction is needed.
N-series: WX area
N-plus series: R area

Please do not disassemble or modify internal components of the RTD


module.

65
RTD Conversion Module Wiring Diagram
RTD Input
RTD sensor
(Pt100, JPt100) RTD conversion module

3-Wire of +, -, GND
Conversion to
temperature (°C, °F)

-200 to 850 °C
-200 to 640 °C 3-Wire type for the correction
of resistance between the lines.

Resistance input
RTD conversion module

3-Wire of +, -, GND
Conversion to resistance
(10 mΩ, 20 mΩ)

0 to 327 °C
3-Wire type for the correction
0 to 2000 °C
of resistance between the lines.

NOTE Do not place RTD input signal wire near wires other than PLC, such as AC cables or high voltage cables.
Do not tie RTD input signal wire.
Do not use same cables for signal wire and AC wire to outside devices.

IMPORTANT • Resistance Temperature Detector (RTD): RTD utilizes the resistance


change induced by temperature change. It passes constant current
through changing resistance and measure the voltage. V = I * R
• Converter type: (24-bit Σ−∆ A/D with Digital & Analog Noise Filter)
• Sensor Excitation Current: 1 mA
• α: Temperature constant, unit = (Ω/Ω)/°C
For Pt100, resistance changes by 0.385 Ohm(Ω) per 1 °C temperature
change.
For JPt100, resistance changes by 0.3916 Ohm(Ω) per 1 °C temperature
change.
• Pt100 standards: IEC751, DIN43760, JIS1604-1989
(Most RTD sensors at present)
• JPt100 standards: JIS1604-1981, D100.
• Temperature sensor types: RTD, Thermocouple, Thermistor, Silicon
Sensor

66
Programming
N Programming methods are different for N-Series and N-plus Series.
N-series: NX70 (NX70-CPU750, NX70-CPU70), NX700 (NX-CPU700,
NX-CPU750A to NX-CPU750D) PLC CPU module
Use WinFPST for programing
N-plus series: NX70 (NX-CPU70p1, NX70-CPU70p2),
NX700 (NX-CPU700p) PLC CPU module
Use WinGPC for programing
N I/O contact type
No additional instruction is needed for I/O contact type.
(ex. Slot 0 installation)
N-series: WX0 (Ch0), WX1 (Ch1), WX2 (Ch2), WX3 (Ch3),....
N-plus series: R0 (Ch0), R1 (Ch1), R2 (Ch2), R3 (Ch3),...
N Shared memory type
READ instruction is used for reading conversion data. Out-of-range
flags are provided.

I/O Contact Type Programming (SW8: OFF)


When RTD conversion module is installed in "slot 0"

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A, B, C, D): WinFPST S/W

[RTD conversion data]


WX0: CH0 conversion data
[ F0 MV, WX0, DT0 ] WX1: CH1 conversion data
WX2: CH2 conversion data
WX3: CH3 conversion data
.
.
.
WX7: CH7 conversion data

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

[RTD conversion data]


LET
R0: CH0 conversion data
D = W0
S = R0 R1: CH1 conversion data
R2: CH2 conversion data
R3: CH3 conversion data
.
.
.
R7: CH7 conversion data

N RTD conversion data is allocated to input contacts. Additional programming is not


needed for reading conversion data.
N CPU periodically updates the allocated input contacts with conversion data at every
scan.

67
Shared Memory Type Programming (SW8: ON)
Shared Memory instruction - READ

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NXCPU750A, B, C, D): WinFPST S/W
S1: Installation slot number of RTD
module.
[ F150 READ, S1, S2, n, D ] S2: Starting address of shared memory
where source data is stored.
n: The number of words of source
data to read.
D: Starting address of the destination
to store the read data to.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W
TO: Starting address of the destination
READ
to store the read data to (To).
TO =
SZ: The number of words of source
SZ =
data to read (Size).
FR =
FR: Installation slot number of RTD
module and starting address of
shared memory where source data
is stored (From).

Shared Memory instruction - WRITE

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A,B,C,D): WinFPST S/W
S1: Installation slot number of RTD
module.
S2: Starting address of the source
data to write to the destination.
[ F151 WRT, S1, S2, n, D ]
n: The number of words of source
data to write to the destination.
D: Starting address of the destination
in shared memory to which the
source data is written.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W
TO: Installation slot number of RTD
WRITE module and starting address of the
TO = destination in shared memory to
SZ = which the source data is written
FR = (To).
SZ: The number of words of source
data to write to the destination
(Size).
FR:Starting address of the source data
to write to the destination(From).

68
Reading conversion data (READ)

N RTD conversion data is read as 1-word (16 bits) signed binary decimal.
N RTD module is installed onto slot 3.
N The following two instructions store conversion data of CH0 to CH7 to data memory
starting from DT0 and W0, respectively.

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A,B,C,D): WinFPST S/W

K3: Slot 3
K0: Starting address of the source
[ F150 READ, K3, K0, K8, DT0 ] data to read is address 0 of
shared memory in RTD module.
K8: Read 8 words starting from KO.
DT0: Store the read data to the
destination starting from DT0.
(Stored to DT0 to DT7)

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

TO = Store the read data to the


READ
destination starting from W0.
TO = W0 (Stored to W0 to W3)
SZ = 4
FR = 3 : 0 SZ = Read 4 words from the starting
address designated by FR.
FR = Starting address of the source
data to read is address 0 of
shared memory in the RTD
module installed onto slot 3.

69
70
5
TC Conversion Module

TC Conversion Module

NX700 TC module (4CH)


NX-TC4

NX700 TC module (8CH) NX70 TC module (4CH)


NX-TC8 NX70-TC4

1) Read data with the advanced instruction, READ, or


2) Read data from input contacts

Sensor types
B, R, S, N, K, E, J, TL, U, C, D

Sensor type determines


temperature ranges.

Write data with the advanced instruction, WRITE

71
TC Conversion Module Features
24-bit Σ-∆ A/D converter enables high accuracy and fast speed. Wide
I/O range and self-calibration feature are also implemented.
1. NX700 TC module: 4 channels or 8 channels/module
NX70 TC module: 4 channel/module
2. Temperature sensor types
Available types: B, R, S, N, K, E, J, T, L, U, C, D, 10 mV....
3. Data both in Celsius (°C) and Fahrenheit (°F) are usable.
You can select this with dip switch on the bottom plane of the
module.
4. Two programming methods
Provide two programming methods. You can select an appropriate
method according to the occupied I/O points:
c Using shared memory
d Using I/O contacts
5. Temperature compensation feature of TC module
When using Thermocouple with the module, temperature
compensation is needed because of the difference between actually
measured temperature and module temperature. To handle this
problem, the built-in temperature sensor provides temperature
compensation feature.

72
TC Conversion Module Specification
ThermoCouple

Catalog NX700 PLC, NX-TC8 NX700 PLC, NX-TC4 NX70 PLC, NX70-TC4
number (8 channels) (4 channels) (4 channels)

Digital
signed 16-bit binary (2’s complement)
conversion
TC input channel 8 Channels 4 Channels 4 Channels
DC/DC converter
and
24BIT Σ-∆ A/D Converter
photocoupler
Isolation
I/O Type B/R/S/N/K/E/J/T/L/U/C/D (Sensor type determines the temperature range)
characteristics
±32.7 mV (1 uV/Bit)
(Temperature
sensor and ±65.5 mV (2 uV/Bit)

digital output) ±75.0 mV (10 uV/Bit)

Max. resolution 0.1 °C, 0.1 °F, 1 uV, 2 uV, 10 uV


Overall accuracy ±0.1 %/F.S (25 °C)
Conversion
60 ms/CH
speed
External input
10 MΩ
impedance
Temperature
compensation 0 to 85 °C (Cold junction compensation)
sensor
Between input channel and internal circuit: DC/DC converter and photocopier Isolation
Isolation method
Between input channels: Non-isolation
I/O contact type: 128 points
Number of input I/O contact type: 64 points input
I/O points Shared memory type: 16 Shared memory type: 16 points input
points input
Internal current
consumption 5 V 340 mA or less 5 V 340 mA or less 5 V 330 mA or less
(5 V)
External
connection 20-pin removable terminal block (M3.5) 20-pin terminal block (M3.0)
method

NX700/ NX70 TC Conversion input

Sensor types
TC conversion module
B, R, S, N, K, E, J, T, L, U, C, D

Conversion to temperature
(0.1 °C, 0.1 °F)

JUNCTION

The sensor type determines the


temperature range Use thermocouple cable

73
TC Conversion Module
For NX700 PLC System
NX-TC8 (8CH, TC input) NX-TC4 (4CH, TC input)

NX-TC8 RUN: TC module normal operation NX-TC4


ERROR: TC module ERROR

TC

TC
RUN RUN
ERROR ERROR

TC input terminal (CH.0 to CH.7)


+ Select the input sensor type
+
CH 0 CH 0
- with the DIP switch on the bottom of -
+ the module +
CH 1 CH 1
- -
+ +
CH 2 CH 2
- -
+ +
CH 3 CH 3
- -
A.GND A.GND
A.GND A.GND
+
CH 4
- Unused terminals (No Connection)
+
CH 5
-
+
CH 6
-
+
CH 7
-
Analog Ground
A.GND
A.GND

NOTE Set the (-) terminal of CH and A.GND to COMMON when there is too much hunting on
the channel.

74
For NX70 PLC System

NX70-TC4 (4CH, TC input)

RUN: TC module normal operation


ERROR: TC module ERROR

TC input terminal (CH.0 to CH.3)


Select the input sensor type
with the DIP switch on the bottom of
the module.

Unused terminal (No Connection)

Analog Ground

NOTE Set the (-) terminal of CH and A.GND to COMMON when there is too much
hunting on the channel.

75
TC Conversion Module Input Range Selection
Switch is located on the bottom of the module.
SW7: Temperature unit
OFF: °C
ON: °F

SW8: Conversion data I/O method setting


OFF: I/O contact type
SW1 to 4: SW5: ON: Shared memory type
Input range Filter setting
SW6: Temperature compensation setting
OFF: Temperature compensation
ON : No temperature compensation

Dip switch Settings


SW1 to SW4: Input range setting
SW1 SW2 SW3 SW4 Input range and conversion data Remarks
OFF OFF OFF OFF Type K, 0.1 °C or 0.1 °F/count
ON OFF OFF OFF Type J, 0.1 °C or 0.1 °F/count
OFF ON OFF OFF Type T, 0.1 °C or 0.1 °F/count
ON ON OFF OFF Type B, 0.1 °C or 0.1 °F/count
OFF OFF ON OFF Type R, 0.1 °C or 0.1 °F/count
ON OFF ON OFF Type S, 0.1 °C or 0.1 °F/count
OFF ON ON OFF Type E, 0.1 °C or 0.1 °F/count
ON ON ON OFF Type N, 0.1 °C or 0.1 °F/count
OFF OFF OFF ON Type L, 0.1 °C or 0.1 °F/count
ON OFF OFF ON Type U, 0.1 °C or 0.1 °F/count
OFF ON OFF ON Type C, 0.1 °C or 0.1 °F/count
ON ON OFF ON Type D, 0.1 °C or 0.1 °F/count
OFF OFF ON ON 10 uV Input, -78.0 to 78.0 mV, 10 uV/1count
ON OFF ON ON 1 uV Input, -32.7 to 32.7 mV, 1 uV/1count
OFF ON ON ON 2 uV Input, -65.5 to 65.5 mV, 2 uV/1count
ON ON ON ON Not Used

SW5: Filter setting


SW5 Filter setting Remarks
OFF Filter #0
ON ON Filter #1

SW6: Temperature compensation setting


SW6 Filter setting Remarks
OFF Temperature compensation
ON No temperature compensation

76
SW7: Temperature unit
SW7 Filter setting Remarks
OFF °C
ON °F

SW8: Conversion data I/O method setting


Conversion data
SW8 RTD 8CH RTD 4CH Remarks
input method
Easy to use.
128 points 64 points I/O contact type
OFF User programming for reading conversion data
input input (I/O conversion data)
is not needed.
READ instruction on user program is needed
Shared memory type for reading conversion data.
ON 16 points
(I/O conversion data)
Range excess feature available.

Temperature range for each sensor type


Sensor Accuracy Accuracy
Materials Remarks
type Not Guaranteed Guaranteed
B 0 to 1820 °C -600 to 1700 °C Platinum/Platinum-30 % Rhodium
R -50 to 1768 °C 0 to 1600 °C Platinum/Platinum-13 % Rhodium
S -50 to 1768 °C 0 to 1600 °C Platinum/Platinum-10 % Rhodium
N -270 to 1300 °C -200 to 1250 °C Nicrosil/Nisil
K -270 to 1372 °C -200 to 1200 °C Chromel/Alumel
E -270 to 1000 °C -200 to 800 °C Chromel/Constantan
J -210 to 1200 °C -40 to 750 °C Iron/Constantan
T -270 to 400 °C -200 to 350 °C Copper/Constantan
L -200 to 900 °C -150 to 700 °C
U -200 to 600 °C -150 to 500 °C
C 0 to 2310 °C 0 to 2000 °C
D 0 to 2490 °C 0 to 2000 °C

77
I/O Method for CPU Module
SW8 setting determines how the CPU module handles conversion data
from TC module.
When SW8 is set to OFF, as many words of input contacts as the
channels are allocated and the CPU module updates these input
contacts every scan, which allows you to read conversion data of TC
modules from these input contacts.
When SW8 is set to ON, only 1-word input contact is allocated and
conversion data are stored in shared memory. You should use the
READ instruction to read conversion data of TC modules stored in this
shared memory. The 1-word input contact allocated is used as out-of-
range flags that indicate whether the conversion data of TC modules
exceed the range or not.

I/O Contact Type (SW8, OFF)


Data conversion method is set to I/O contact type. (SW8 is set to OFF.)
N When an TC module is mounted onto the first I/O slot (slot 0) and
SW8 is set to OFF (I/O contact type), 4-word (64 points) input
contacts are allocated for 4-channel TC module and 8-word (128
points) for 8-channel TC module.
For 8-channel TC module (NX700: NX-TC8)
1. NX-series: 8 words (128 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), .........WX7 (Ch7)
2. NX-plus series: 8 words (128 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), .......R7 (Ch7)
For 4-channel TC module (NX700: NX-TC4, NX70: NX70-TC4)
1. NX-series: 4 words (64 points input): WX0 (Ch0), WX1 (Ch1),
WX2 (Ch2), WX3 (Ch3)
2. NX-plus series: 4 words (64 points input): R0 (Ch0), R1 (Ch1),
R2 (Ch2), R3 (Ch3)
N If the data conversion method is set to I/O contact type, many input
contacts are used but you need not to use the READ (or RMRD)
instruction to read TC conversion data because the CPU module
automatically updates them every scan. Therefore, no additional
programming is required to read TC conversion data.

78
Shared Memory Type (SW8, ON)
Data conversion method is set to shared memory type. (SW8 is set to
ON.)
N When an TC module is mounted onto the first I/O slot (slot 0) and
SW8 is set to ON (Shared memory type), 1-word (16 points) input
contacts are allocated regardless the number of TC modules
mounted and the conversion data is stored in the shared memory.
See "Shared Memory Usage for TC Conversion Module" in Chapter 5.
You have to use the READ (or RMRD) instruction in your program to
read the conversion data stored in shared memory.
N The 16 input contacts allocated are used as out-of-range flags for
conversion data. They will be set as shown in the table below.
1. N-series: 1-word input contact (16SX, 16 points input with shared
memory)
2. N-plus series: 1-word input contact
N If data conversion method is set to shared memory type, only
16 points are allocated for TC modules regardless of the number of
TC modules mounted. In addition, many features designed for
shared memory are available.
When TC module is inserted in slot 0 Values in ( ) are applicable to N-plus series.

Input signal
Event Remarks
(BIT contact)
CH.0 No sensor connected, Burn-Out, Range is
X0 (R0.0)
exceeded
CH.1 No sensor connected, Burn-Out, Range is
X1 (R0.1)
exceeded
CH.2 No sensor connected, Burn-Out, Range is
X2 (R0.2)
exceeded
CH.3 No sensor connected, Burn-Out, Range is
X3 (R0.3)
exceeded
CH.4 No sensor connected, Burn-Out, Range is
X4 (R0.4)
exceeded
CH5 No sensor connected, Burn-Out, Range is
X5 (R0.5)
exceeded
CH.6 No sensor connected, Burn-Out, Range is
X6 (R0.6)
exceeded
CH.7 No sensor connected, Burn-Out, Range is
X7 (R0.7)
exceeded

79
I/O Conversion Characteristics
$xx denote hexadecimal representation.

Thermocouples Characteristic Curve


B, R, S, N, K, E, J, T, U, L, C, D Resolution: 0.1 °C/0.1 °F
Range differs for each type.
No connected TC sensor or burn out Curved, not straight lines.
Conversion data = H8000 = 32768

Conversion data / 10 = temperature (°C)


ex) 6600 / 10 = 660.0 °C
1000 / 10 = 100.0 °C
0 / 10 = 0.0 °C
°F = −
9
5 °C + 32 -2000 / 10 = -200.0 °C
-2000 = HF830 = $F830

NOTE The chart above shows the temperature characteristics of each thermocouple type.
The temperature range and accuracy differ depending on the thermocouple type.
The temperature conversion value will be calculated according to ITS-90 Table.

Comparison of Resistance Temperature Detector (RTD) and


Thermocouple (TC) modules
Resistance Temperature
TC (Thermocouple) Remarks
Detector (RTD)
Sensor cost average cheap
System cost average expensive
Accuracy high low
Stability high low
Noise sensitivity low high
Temperature range narrow (-200 to 850 °C) wide (-270 to 1800 °C)
Correction for resistance Temperature compensation
Others
between wires is needed. (CJC) is needed.

80
$xx denote hexadecimal representation.

±75 mV(10 uV/Bit) Conversion data


Resolution: 10 uV/Bit
7499

5,123

0
-7499 mV -4.321 mV mV
0 +5.123 mV +74.99 mV

Conversion data / 100 = input voltage(mV)


-4,321
ex) -7499 / 100 = -74.99 mV
-4321 / 100 = -4.321 mV
0 / 100 = 0 mV
5123 / 100 = +5.123 mV
7499 / 100 = 74.99 mV
-74,99 -32768 = H8000 = $8000
-4321 = HEF1F = $EF1F

±32.7 mV(1 uV/Bit) Conversion data


Resolution:1 uV /Bit

32,767

5,123

0
-32.767 mV -8.642 mV
mV
0 +5.123 mV +32.767 mV

Conversion data / 100 = input voltage(mV)


-8.642
ex) -32768 / 100 = -65.536mV
-4321 / 100 = -8.642mV
0 / 100 = 0mV
5123 / 100 = +10.246mV
-32.767 32767 / 100 = 65.534mV
-32768 = H8000 = $8000
-4321 = HEF1F = $EF1F

81
Shared Memory Usage for TC Conversion
Module
To use shared memory type for data processing of TC conversion
module, set SW8 to ON.

Addressing of Shared Memory


TC Module (NX700: NX-TC4, NX-TC8, NX70: NX70-TC4)
Address Shared memory allocated for Remarks
0 CH0 TC conversion value
1 CH1 TC conversion value
2 CH2 TC conversion value
3 CH3 TC conversion value
4 CH4 TC conversion value
5 CH5 TC conversion value Applicable to only
6 CH6 TC conversion value NX700 TC module

7 CH7 TC conversion value


8 to 15 Reserved
16 Out-of-range warning channel
Temperature compensation (Cold Junction Compensation),
17
0.1 °C or 0.1 °F
18 Current temperature, 0.1 °C or 0.1 °F
19 Out-of-range warning channel
20 to 45 Reserved
46 Analog module ROM Version H0200 = Ver 2.0
Other areas Reserved

NOTE The unit word of shared memory designated by an address consists of 16-bit.
For NX70 analog module, there are no effective data in address 4 to 7. The data in
those addresses should be ignored.
There is an additional temperature sensor inside the TC module. When the
temperature variation is too large, adjust OFFSET to correct the value. (By using
shared memory programming process of F151/PF151 or WRITE/READ, shared
memory programming processing is available at contact type.)

82
Values and Data Configuration of Shared Memory
TC conversion value (addresses 0 to 7: CH0 to CH7)
$xx denote hexadecimal representation.

The digital conversion value of D/A module will be shown as 1 Word (16BIT) of signed binary.
MSB (Most Significat Bit) =1 means (-) value, and MSB =0 means (+) value.
Negative values in hexadecimal (MSB = 1)
Ex) HFFFE ($FFFE)
1. Inverse each bit. HFFFE → H0001
2. Add 1. H0001 + 1 = H0002
3. HFFFE means -2 in decimal
Converting a negative decimal to hexadecimal
Ex) -3
1. Inverse the absolute value. H0003 → HFFFC
2. Add 1. HFFFC + 1 = HFFFD
3. "-3" is represented as HFFFD in hexadecimal.

Out-of-range flags allocation for channels (address 16)

N Set to ON when the digital conversion value exceeds the set range.
N Indicated when thermocouple input (B, R, S, N, K, E, J, TL, U, C, D input), no TC sensor
connected, or burn-out.
N Not indicated when the input range is ±32.7 mV (1 uV/Bit), ±65.5 mV (2 uV/Bit),
±78.0 mV (10 uV/Bit).

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


CH7 CH6 CH5 CH4 CH3 CH2 CH1 CH0

1: TC sensor not connected, Out-of-range


0: TC sensor connected

83
TC Conversion Module Operating Procedure

Conversion data Procedure Operation


I/Omethod setting
(SW8 setting) 1. Select conversion data input method with
SW8.
Conversion
OFF: I/O contact type
data input
ON: Shared memory type
method setting
Input range setting (SW8) 2. SW8 is only recognized on power-on,
(SW1 to SW4 setting) so input method cannot be changed
during PLC operation.

Input range 1. Set the sensor type (input range).


setting 2. Input range can be changed during PLC
Installation (SW1 to SW4) operation.

See "Mounting/Dismounting Module" on


Installation
page 93.
Wiring Wiring Refer to wiring diagram for the TC module.

1. When SW8 is set to ON (shared memory


type), use READ command to read
Reading
conversion data from the shared memory.
Reading conversion conversion data
2. When SW8 is set to OFF (I/O contact type),
data
no additional instruction is needed.
N-series: WX area
N-plus series: R area

Please do not disassemble or modify internal components of


the TC module.

84
TC Conversion Module Wiring Diagram
TC(ThermoCouple) Input
Sensor type
TC conversion module
B, R, S, N, K, E, J, T, L, U, C, D

Conversion to
temperature
(0.1 °C, 0.1 °F)

Sensor type determines


Use thermocouple cable
the temperature range

Voltage (mV) Input

TC conversion module

Conversion to
voltage
(1 uV, 2 uV)

±32.768 mV
±75 mV

N Use standard expansion cable for accurate measurement of


temperature.
N Do not expose TC unit to external noise because the module
measures micro-level voltage.
N Do not place TC input signal wire near to wires other than PLC,
such as AC cables or high voltage cables. Do not tie the cables.
N Do not use same cables for signal wire and AC wire to outside
devices.

IMPORTANT • TC (Thermocouple)
TC utilized micro voltage generated at the non
contacted side of two contacting metals by the
temperature variation on the contact point.
• Converter type: (24-bit Σ−∆ A/D with Digital & Analog
Noise Filter)
• Built-in temperature sensor for temperature
compensation: 0 to 85 °C.
• Temperature sensor types: RTD, Thermocouple,
Thermistor, Silicon Sensor.

85
Programming
N Programming methods are different for N-Series and N-plus
Series.
N-series: NX70 (NX70-CPU750, NX70-CPU70), NX700
(NX-CPU700, NX-CPU750A to NX-CPU750D)
PLC CPU module
Use WinFPST for programing
N-plus series: NX70 (NX-CPU70p1, NX70-CPU70p2),
NX700 (NX-CPU700p) PLC CPU module
Use WinGPC for programing
N I/O contact type
No additional instruction is needed for I/O contact type.
(ex. Slot 0 installation)
N-series: WX0 (Ch0), WX1 (Ch1), WX2 (Ch2), WX3 (Ch3),....
N-plus series: R0 (Ch0), R1 (Ch1), R2 (Ch2), R3 (Ch3),...
N Shared memory type
READ instruction is used for reading conversion data. Out-of-range
I/O Contact Type Programming (SW8: OFF)
When TC conversion module is installed in "slot 0"

N-series (NX70: NX70-CPU70, NX70-CPU750, NX700: NX-CPU700,


NX-CPU750A,B,C,D): WinFPST S/W

[TC conversion data]


WX0: CH0 conversion data
[ F0 MV, WX0, DT0 ]
WX1: CH1 conversion data
WX2: CH2 conversion data
WX3: CH3 conversion data
.
.
.
WX7: CH7 conversion data

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

[TC conversion data]


LET
D = W0 R0: CH0 conversion data
S = R0 R1: CH1 conversion data
R2: CH2 conversion data
R3: CH3 conversion data
.
.
.
R7: CH7 conversion data

N TC conversion data is allocated to input contacts. Additional programming is not


needed for reading conversion data.
N CPU periodically updates the allocated input contacts with conversion data at every
scan.

86
Shared memory type of programming (SW8: ON)
Shared Memory instruction - READ

N-series (NX70: NX70-CPU70, NX70-CPU750,


NX700: NX-CPU700, NX-CPU750A, B, C, D): WinFPST S/W

S1: Installation slot number of TC


module.

[ F150 READ, S1, S2, n, D ] S2: Starting address of shared memory


where source data is stored.
n: The number of words of source
data to read.
D: Starting address of the destination
to store the read data to.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

TO : Starting address where read


READ data is stored.
TO =
SZ : The number of words of
SZ =
data to read (Size).
FR =
FR: Installation slot number of TC
module and starting address of
shared memory where source
data is stored (From).

Shared Memory instruction - WRITE

N-series (NX70: NX70-CPU70, NX70-CPU750,


NX700: NX-CPU700, NX-CPU750A,B,C,D): WinFPST S/W
S1: Installation slot number of TC
module.
[ F151 WRT, S1, S2, n, D ] S2: Starting address of the source data
to write to the destination.
n: The number of words of source
data to write to the destination.
D: Starting address of the destination
in shared memory to which the
source data is written.

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

TO: Installation slot number of TC


WRITE module and starting address of the
TO = destination in shared memory to
SZ = which the source data is written
FR = (To).
SZ: The number of words of source
data to write to the destination
(Size).
FR: Starting address of the source data
to write to the destination (From).

87
Example) Reading conversion data - READ
N TC conversion data is read as 1-word (16 bits) signed binary decimal.
N TC module is installed onto slot 3.
N The following two instructions store conversion data of CH0 to CH7 to data memory
starting from DT0 and W0, respectively.

N-series (NX70: NX70-CPU70, NX70-CPU750,


NX700: NX-CPU700, NX-CPU750A, B, C, D): WinFPST S/W

K3: Slot 3
K0: Starting address of the source
[ F150 READ, K3, K0, K8, DT0 ] data to read is address 0 of
shared memory in TC module.
K8: Read 8 words starting from KO.
DT0: Store the read data to the
destination starting from DT0.
(Stored to DT0 to DT7)

N-plus Series (NX70: NX70-CPU70p1, NX70-CPU70p2,


NX700: NX-CPU700p): WinGPC S/W

TO = Store the read data to the


destination starting from W0.
READ (Stored to W0 to W3)
TO = W0
SZ = 4 SZ = Read 4 words from the starting
FR = 3 : 0 address designated by FR.
FR = Starting address of the source
data to read is address 0 of
shared memory in the TC module
installed onto slot 3.

88
6
Product Dimensions and Installation

NX700 PLC Product Dimensions


System Dimensions (mm)
A

B
TR OUT

TR OUT

TR OUT

TR OUT

TR OUT
NX-CPU750B NX-X64D NX-X64D NX-X32D NX-Y32T NX-Y16T NX-Y16T NX-Y16T NX-Y16T
DC IN

DC IN
DC IN
CPU

115.5 118.5

unit (mm)
Dimensions
Slot Types
A B
111.0 3-slot type 205.0 184.0
5-slot type 276.0 254.0
8-slot type 381.0 360.0
10-slot type 452.0 430.0
12-slot type 522.0 501.0

Motherboard Installation Diagram (mm)

5.0 * 4
¥ı
27.5
81.0

unit (mm)
SLOT P L
3-slot type 205.0 153.8
5-slot type 276.0 224.2
7.0

22.5 L
8-slot type 381.0 329.8
10-slot type 452.0 400.2
A 12-slot type 522.0 470.6

89
CPU, I/O, Analog Module Dimensions (mm)

NX-CPU750B NX-X16D NX-Y64T

OUTPUT
INPUT
CPU
115.5

35.0 104.0

Special Module Dimensions (mm)


MWLINK

EtherNet

NX-MWLINK NX-SCU NX-EtherNet


SCU

AUI

115.5 COM1
RS232C
RS485

T
+
- COM2
RS232C
12V
RS485
F.G

35.0 35.0 35.0 104.0

90
NX70 PLC Product Dimensions
System Dimensions (mm)

A
10 5. 0

30.0

38.0

C
4 - M5
B
unit (mm)

Slot Types Catalog Number Dimensions (A) Dimensions (B) Dimensions (C)
2-slot type NX70-BASE02 149.5 129.5 115.5
3-slot type NX70-BASE03 185.0 165.0 151.0
5-slot type NX70-BASE05 256.0 236.0 222.0
6-slot type NX70-BASE06 291.5 271.5 257.5
8-slot type NX70-BASE08 362.5 342.5 328.5
10-slot type NX70-BASE10 398.0 378.0 364.0
12-slot type NX70-BASE12 433.5 413.5 399.5

91
CPU, I/O, Analog Module Dimensions (mm)

Special Module Dimensions (mm)

92
Mounting/Dismounting Module
Mounting Dismounting
1. Insert the module by inserting the tab 1. Unfasten the screw that holds the
into the groove first and pushing the module in place using a screwdriver.
module against the backplane.

2. Push the top of the module toward the 2. Hold on pressing the locking button on
backplane until it is clamped in place. the top edge of the module, and pull
the module from the backplane.

Locking button

3. Ensure that the module is in place


against the backplane, and then fasten
the screw using a screwdriver.

1 screwdriver

93
94
NX70/NX700 Series Analog Modules (A/D, D/A, RTD, TC) User Manual

www.samsungautomation.co.kr

Rockwell Samsung Automation Technical Support

447-6, Gongse-Ri, Giheung-Eup, Youngin-City, Export Sales Team


Gyeonggi-Do, South Korea, 449-902 Tel: 82-31-280-4768 Fax: 82-31-280-4900
Tel: 82-31-280-4700 Fax: 82-31-280-4900 Trademarks not belonging to Rockwell Samsung
Automation are property of their respective companies.