Vertiv™ eSure™ Rectifier

R48-5800e

Description
Benefits
The eSure™ R48-5800e rectifier converts 260 to 530 VAC 3-phase supply voltages into
stable nominal -48V DC voltage adjustable to the needs of the application. The
Rectifier, 48 VDC, 5800 W
R48-5800e is a constant power rectifier designed with the latest patented switch-mode
y Optimized depth - reduced technology using DSP (Digital Signal Processor) functionality for efficient operation.
footprint allows installation
in short-depth racks
For a higher load capacity, rectifiers can be connected in parallel and intelligent control
and cabinets can be added with the help of a separate controller.

y DSP (Digital Signal Processor)


- means fewer components,
optimized operation and
active load sharing for
increased reliability

y Compliant with global


standards - delivers quality,
performance and
reliability no matter
what the application
or location demands

y High efficiency, near R48-5800e


96.2% - reduces power
consumption for lower
operating costs

y Hot pluggable - facilitates


future extensions
98
y Wide input voltage
96
range - operates in the most
demanding environments 94
where input voltage changes 95% 96%
92
y Wide temperature operating
range from -40°C to +65°C 90
/ -40°F to +149°F meets
the harshest climatic 88
environment requirements 10 20 30 40 50 60 70 80 90 100 Load%

R48-5800e Efficiency Curve at 380 VAC Nominal


Vertiv™ eSure™ Rectifier

Technical Specifications Figures


AC Input R48-5800E
% Watts 260 305 530
260 VAC to 530 VAC (see figure 1)
Voltage 120
380 VAC to 480 VAC (nominal)
100
Frequency 45 Hz to 65 Hz
80
Maximum Current 13 A 60
Power Factor 0.99 40
20
DC Output

Voltage -42 VDC to -58 VDC 150 200 250 300 350 400 450 500 550 600 VAC

Maximum Power 5800 W @ Vout >48 VDC


Figure 1: Output Power vs. Input Voltage
Maximum Current 120A @ 48 VDC, limit set point 0 to 120 A (see figure 2) at Tamb < 45°C

Peak Efficiency 96.2%


VDC 100 122
Psophometric Noise (System) <2 mV typical; <32 dBrnc typical
60
Control and Monitoring 50

Alarm and status reported via CAN bus 40


Alarms and Signaling
to system controller 30

Green LED = Normal Operation 20


Yellow LED = Alarm 10
Visual Indications
Red LED = Failure; Flashing
Red LED = Fan Failure
40 50 60 70 80 90 100 110 120 130 Amps
Environmental
Figure 2: Output Voltage vs. Output Current
-40°C to +65°C / -40°F to +149°F at Maximum Output Power 5800 W
Operating Temperature
(see figure 3)

Storage Temperature -40°C to +70°C / -40°F to +158°F


% Watts 45 50 55 65
Relative Humidity 0 to 95%
120
Altitude 2000 m / 6560 ft at full power 100
80
Standards Compliance
60
Safety 60950 (EN and UL), Telcordia GR-63-CORE 40
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, 20
EMC
Telcordia GR-1089-CORE class B

Environment REACH, RoHS, WEEE 0 10 20 30 40 50 60 70 80 90 °C

Mechanics
Figure 3: Output Power vs. Temperature
at Uin > 304 VDC
Dimensions (H x W x D) 85.5 x 245 x 380 mm / 3.37 x 9.65 x 14.96 inches

Weight 6.5 kg / 14 lbs

Ordering information
Part Number Description

1R485800E eSure™ rectifier, 48 VDC, 5800 W

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA