Professional Documents
Culture Documents
ACMV
ACMV
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK.
CONCESSIONAIRE
SECTION DESCRIPTION
1.0 INTRODUCTION
1.0
INTRODUCTION
Introduction
The entire Air-Conditioning and Mechanical Ventilation system consist of the following:-
1. Carrier – 5 nos. of Air Handling Unit located at Bangunan Pentadbiran Level 1 and Level 2.
2. Carrier – 2 nos. of Air Handling Unit located at Bangunan Perpustakaan Level 1 and Level 2.
3. Carrier – 2 nos. of Air Handling Unit located at Dewan Peperiksaan Level 1.
4. Carrier – 12 nos. of Air Handling Unit located at Fakulti Perladangan dan Agroteknologi Level 1, Level
2 and Level 3.
5. Carrier – 12 nos. of Air Handling Unit located at Fakulti Sains Gunaan Level 1, Level 2 and Level 3.
6. Carrier – 2 nos. of Air Handling Unit located at Dewan Kuliah Level 1.
7. Carrier – 2 nos. of Air Handling Unit located at Unit Penyelenggaraan, Keselamatan, Kesihatan
Level 1.
8. Carrier – 2 nos. of Fan Coil Unit located at Bangunan Pentadbiran Level 1 and Level 2.
9. Carrier – 2 nos. of Fan Coil Unit located at Bangunan Perpustakaan Level 1 and Level 2.
10. Carrier – 2 nos. of Fan Coil Unit located at Dewan Peperiksaan Level 1.
11. Carrier – 48 nos. of Fan Coil Unit located at Fakulti Perladangan dan Agroteknologi Level 1, Level 2
and Level 3.
12. Carrier – 34 nos. of Fan Coil Unit located at Fakulti Sains Gunaan Level 1, Level 2 and Level 3.
13. Carrier – 59 nos. of Fan Coil Unit located at Fakulti Perniagaan Level 1 and Level 2.
14. Carrier – 7 nos. of Fan Coil Unit located at Unit Penyelenggaraan, Keselamatan, Kesihatan Level 1
and Level 2.
15. Carrier Split Unit – 8 nos. of Wall Mounted located at Fakulti Perladangan dan Agroteknologi Level 1,
Level 2 and Level 3.
16. Carrier Split Unit – 8 nos. of Ceiling Hanged located at Fakulti Sains Gunaan Level 1.
17. Carrier Split Unit – 1 no. of Wall Mounted located at Fakulti Sains Gunaan Level 1.
18. Carrier Split Unit – 1 no. of Ceiling Hanged located at Unit Penyelenggaraan, Keselamatan, Kesihatan
Level 1.
19. Carrier Split Unit – 1 no. of Wall Mounted located at Unit Penyelenggaraan, Keselamatan, Kesihatan
Level 1.
20. Carrier Split Unit – 1 no. of Wall Mounted located at Medan Selera dan Pusat Pelajar Level 1.
21. Carrier Split Unit – 6 nos. of Ceiling Hanged located at Medan Selera dan Pusat Pelajar Level 2.
22. Carrier Split Unit – 2 nos. of Wall Mounted located at Surau Level 1.
23. Carrier Split Unit – 13 nos. of Wall Mounted located at Citu Level 1 and Level 2.
24. Carrier Split Unit – 1 no. of Ceiling Cassette located at Citu Level 1.
25. Carrier Split Unit – 1 no. of Ceiling Hanged located at Citu Level 1.
26. Carrier Split Unit – 15 nos. of Wall Mounted located at Rumah Tetamu Level 1 and Level 2.
27. Carrier Split Unit – 2 nos. of Wall Mounted located at Pejabat Pengurusan Kolej Level 1.
28. Carrier Split Unit – 2 nos. of Ceiling Hanged located at Pejabat Pengurusan Kolej Level 1.
29. Carrier Split Unit – 1 no. of Ceiling Cassette located at Pejabat Pengurusan Kolej Level 1.
30. Carrier Split Unit – 1 no. of Wall Mounted located at Bengkel Kejuruteraan Akuatik dan Depo Ground
Floor.
31. Carrier Split Unit – 5 nos. of Wall Mounted located at Makmal Diagnostic Ground Floor.
32. Carrier Split Unit – 6 nos. of Ceiling Hanged located at Makmal Diagnostic Ground Floor.
33. Carrier Split Unit – 7 nos. of Wall Mounted located at Pejabat Pusat Akuakultur & Unit Perladangan
Ground Floor and First Floor.
34. Carrier Split Unit – 3 nos. of Ceiling Hanged located at Pejabat Pusat Akuakultur & Unit Perladangan
Ground Floor and First Floor.
35. Carrier Split Unit – 1 no. of Ceiling Cassette located at Pejabat Pusat Akuakultur & Unit Perladangan
Ground Floor and First Floor.
36. Carrier Split Unit – 1 no. of Wall Mounted located at Pusat Pemprosesan Ground Floor.
37. Carrier Split Unit – 4 nos. of Ceiling Hanged located at Pusat Pemprosesan Ground Floor.
38. Carrier Split Unit – 11 nos. of Wall Mounted located at Kemudahan Sokongan Akademik /
Penyelidikan - Pusat Jual Hasil & Stor Ground Floor.
39. Carrier Split Unit – 2 nos. of Ceiling Hanged located at Kemudahan Sokongan Akademik /
Penyelidikan - Pusat Jual Hasil & Stor Ground Floor.
40. Carrier Split Unit – 1 no. of Wall Mounted located at Pondok Pengawal Keselamatan Ground Floor.
41. KDK Exhaust Fan – 8 nos. of Ceiling Mounted located at Bangunan Pentadbiran Level 1 and Level 2.
42. KDK Exhaust Fan – 1 no. of Wall Mounted located at Bangunan Perpustakaan Level 1.
43. Nicotra Exhaust Fan – 4 nos. of Cabinet Fan located at Bangunan Perpustakaan Level 1 and Level
2.
44. KDK Exhaust Fan – 4 nos. of Wall Mounted located at Dewan Peperiksaan Level 1.
45. KDK Exhaust Fan – 1 no. of Ceiling Mounted located at Dewan Peperiksaan Level 1.
46. Nicotra Exhaust Fan – 1 no. of In Line Duct Fan located at Fakulti Perladangan dan Agroteknologi
Level 1.
47. KDK Exhaust Fan – 15 nos. of Ceiling Mounted located at Fakulti Perladangan dan Agroteknologi
Level 1, Level 2 and Level 3.
48. KDK Exhaust Fan – 30 nos. of Wall Mounted located at Fakulti Perladangan dan Agroteknologi Level
1, Level 2 and Level 3.
49. KDK Exhaust Fan – 26 nos. of Wall Mounted located at Fakulti Sains Gunaan Level 1, Level 2 and
Level 3.
50. KDK Exhaust Fan – 21 nos. of Ceiling Mounted located at Fakulti Sains Gunaan Level 1, Level 2 and
Level 3.
51. Nicotra Exhaust Fan – 1 no. of In Line Duct Fan located at Fakulti Sains Gunaan Level 1.
52. KDK Exhaust Fan – 13 nos. of Ceiling Mounted located at Fakulti Perniagaan Level 1 and Level 2.
53. KDK Exhaust Fan – 2 nos. of Ceiling Mounted located at Dewan Kuliah Level 1.
54. KDK Exhaust Fan – 2 nos. of Ceiling Mounted located at Unit Penyelenggaraan, Keselamatan,
Kesihatan Level 2.
55. KDK Exhaust Fan – 6 nos. of Wall Mounted located at Unit Penyelenggaraan, Keselamatan, Kesihatan
Level 1.
56. Nicotra Exhaust Fan – 1 no. of In Line Duct Fan located at Unit Penyelenggaraan, Keselamatan,
Kesihatan Level 1.
57. KDK Exhaust Fan – 2 nos. of Wall Mounted located at MSB Room Substation 2 and 3.
58. KDK Exhaust Fan – 6 nos. of Wall Mounted located at Medan Selera dan Pusat Pelajar Level 1 and
Level 2.
59. Nicotra Exhaust Fan – 9 nos. of Centrifugal located at Medan Selera dan Pusat Pelajar Level 1.
60. KDK Exhaust Fan – 3 nos. of Wall Mounted located at Surau Level 1.
61. KDK Exhaust Fan – 2 nos. of Wall Mounted located at Citu Level 1 and Level 2.
62. KDK Exhaust Fan – 14 nos. of Wall Mounted located at Rumah Tetamu Level 1, Level 3, Level 4 and
Level 5.
63. KDK Exhaust Fan – 13 nos. of Ceiling Mounted located at Rumah Tetamu Level 1 and Level 2.
64. KDK Exhaust Fan – 2 nos. of Wall Mounted located at Pejabat Pengurusan Kolej Level 1.
65. KDK Exhaust Fan – 5 nos. of Wall Mounted located at Bengkel Kejuruteraan Akuatik dan Depo
Ground Floor.
66. KDK Exhaust Fan – 5 nos. of Wall Mounted located at Makmal Diagnostic Ground Floor.
67. KDK Exhaust Fan – 6 nos. of Wall Mounted located at Pejabat Pusat Akuakultur & Unit Perladangan
Ground Floor and First Floor.
68. KDK Exhaust Fan – 1 no. of Wall Mounted located at Pusat Hatcheri.
69. KDK Exhaust Fan – 7 nos. of Wall Mounted located at Kemudahan Sokongan Akademik /
Penyelidikan - Pusat Jual Hasil & Stor Ground Floor.
70. Nicotra Exhaust Fan – 2 nos. of Axial Fan located at Central Utility Plant Level 1.
71. KDK Exhaust Fan – 5 nos. of Wall Mounted located at Central Utility Plant Level 1.
72. KDK Exhaust Fan – 1 no. of Wall Mounted located at Pondok Pengawal Keselamatan Ground Floor.
73. Carrier – 3 nos. of Centrifugal Chiller located at Central Utility Plant Level 1.
74. Carrier – 1 no. of Multiple Screw Compressor Chiller at Central Utility Plant Level 1.
75. Regent – 4 nos. of Horizontal Split Casing Pump at Central Utility Plant Level 1.
76. Regent – 4 nos. of End Suction Pump at Central Utility Plant Level 1.
77. Truwater – 2 nos. of Low Noise Type Cooling Tower at Central Utility Plant Roof
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
2.0
DESCRIPTION OF THE INSTALLATIONS
BANGUNAN PENTADBIRAN
SCHEDULE OF AIR HANDLING UNIT
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B1-L1-AHU-1 39G0912 Carrier 30 1767 2.3 3 2 1/2" 2 1/2" 1" 1.28 1450 1250 1050 258
B1-L1-AHU-2 39G1621 Carrier 86 5590 2.5 7.5 3" 3" 1" 3.69 1950 2150 1750 813
B1-L2-AHU-1 39G1621 Carrier 96 5910 2.6 11 3" 3" 1" 4.14 1950 2150 1750 873
B1-L2-AHU-2 39G1621 Carrier 114 6717 3.1 11 3" 3" 1" 4.89 1950 2150 1750 883
B1-L2-AHU-3 39G1621 Carrier 115 6669 2.8 11 3" 3" 1" 4.94 1950 2150 1750 900
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B1-L1-FCU-1 42CET003 Carrier 3.07 140 0.015 32W 3/4”FPT 3/4”FPT 3/4”MPT 0.13 770 557 242 21.5
B1-L2-FCU-1 42CET006 Carrier 4.79 282 0.015 72W 3/4”FPT 3/4”FPT 3/4”MPT 0.2 1170 557 242 30
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B1-L1-EF-1 CEILING MOUNTED 150 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L1-EF-2 CEILING MOUNTED 115 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L2-EF-1 CEILING MOUNTED 118 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L2-EF-2 CEILING MOUNTED 102 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B2-L1-AHU-1 39G1822 Carrier 174 7942 2.4 11 3" 3" 1" 7.47 2100 2250 1950 1080
B2-L2-AHU-1 39G2230 Carrier 286 13686 2.9 30 3" 3" 1" 12.28 2400 3050 2350 1831
B2-L1-FCU-1 40LM070 Carrier 21.6 900 0.6 0.9 1” 1” 3/4” 0.86 680 1200 480 95
B2-L2-FCU-1 42CET003 Carrier 3.1 137 0.015 32W 3/4”FPT 3/4”FPT 3/4”MPT 0.13 770 557 242 21.5
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B1-L1-EF-1 CEILING MOUNTED 150 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L1-EF-2 CEILING MOUNTED 115 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L2-EF-1 CEILING MOUNTED 118 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
B1-L2-EF-2 CEILING MOUNTED 102 1207 60 25.7 240/1/50 200mm KDK 20 CQT1
DEWAN PEPERIKSAAN
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B3-L1-AHU-1 39G1825 Carrier 237 8870 2.7 15 3" 3" 1" 10.17 2100 2550 1950 1213
B3-L1-AHU-2 39G1825 Carrier 237 8870 2.7 15 3" 3" 1" 10.17 2100 2550 1950 1213
B3-L1-FCU-1 42CET010 Carrier 7.9 472 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B3-L1-FCU-2 42CET003 Carrier 3.1 111 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B3-L1-EF-1 WALL MOUNTED 200 1109-1301 FREE 25.7 240/1/50 200mm KDK 20 AQM8
B3-L1-EF-2 WALL MOUNTED 175 1109-1301 FREE 25.7 240/1/50 200mm KDK 20 AQM8
B3-L1-EF-3 WALL MOUNTED 175 1109-1301 FREE 25.7 240/1/50 200mm KDK 20 AQM8
B3-L1-EF-4 WALL MOUNTED 200 1109-1301 FREE 25.7 240/1/50 200mm KDK 20 AQM8
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B4a-L1-AHU-1 39G0914 Carrier 237 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L1-AHU-2 39G0914 Carrier 237 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L1-AHU-3 39G1015 Carrier 54 2297 2.1 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L1-AHU-4 39G1015 Carrier 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L2-AHU-1 39G0914 Carrier 63 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L2-AHU-2 39G0914 Carrier 63 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L2-AHU-3 39G1015 Carrier 54 2297 2.1 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L2-AHU-4 39G1015 Carrier 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L3-AHU-1 39G0914 Carrier 63 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L3-AHU-2 39G0914 Carrier 63 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L3-AHU-3 39G1015 Carrier 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 406
B4a-L3-AHU-4 39G1015 Carrier 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 406
B4a-L1-FCU-1 42CET003 Carrier 3.1 79 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4a-L1-FCU-2 40LM060 Carrier 18.4 737 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-3 40LM060 Carrier 18.4 565 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-4 40LM060 Carrier 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-5 40LM070 Carrier 21.6 957 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4a-L1-FCU-6 40LM070 Carrier 21.6 957 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4a-L1-FCU-7 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-8 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-9 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-10 42CET004 Carrier 4.0 190 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-1 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-2 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-3 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-4 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-5 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-6 42CET010 Carrier 7.9 371 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L2-FCU-7 42CET010 Carrier 7.9 380 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L2-FCU-8 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-9 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-10 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-11 42CET008 Carrier 7.3 310 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4a-L2-FCU-12 40LM050 Carrier 14.2 428 0.5 0.55 1" 1" 3/4" 0.83 680 1000 480 70
B4a-L2-FCU-13 40LM060 Carrier 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L2-FCU-14 40LM090 Carrier 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L2-FCU-15 40LM090 Carrier 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L2-FCU-16 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-17 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-18 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-19 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-1 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-2 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-3 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-4 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4a-L3-FCU-5 42CET005 Carrier 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-6 42CET010 Carrier 7.9 371 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L3-FCU-7 42CET010 Carrier 7.9 380 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L3-FCU-8 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-9 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-10 42CET004 Carrier 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-11 42CET008 Carrier 7.3 310 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4a-L3-FCU-12 40LM050 Carrier 14.2 428 0.5 0.55 1" 1" 3/4" 0.83 680 1000 480 70
B4a-L3-FCU-13 40LM060 Carrier 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L3-FCU-14 40LM090 Carrier 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L3-FCU-15 40LM090 Carrier 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L3-FCU-16 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-17 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-18 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-19 42CET004 Carrier 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-A/C-1 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-2 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-3 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-4 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-5 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-6 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-7 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-A/C-8 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
SCHEDULE OF EXHAUST FAN
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4a-L1-EF-1 IN LINE DUCT FAN 359 1120 (H) 80 147 240/1/50 200mm NICOTRA CD 200
B4a-L1-EF-2 CEILING MOUNTED 172 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4a-L1-EF-4 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-5 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-6 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-7 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-8 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-9 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-10 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-11 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-12 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L1-EF-13 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-1 CEILING MOUNTED 172 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4a-L2-EF-4 CEILING MOUNTED 172 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4a-L2-EF-6 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-7 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-8 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-9 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-10 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-11 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-12 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4a-L2-EF-13 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-14 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L2-EF-15 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-1 CEILING MOUNTED 172 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4a-L3-EF-4 CEILING MOUNTED 172 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4a-L3-EF-6 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-7 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-8 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-9 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-10 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-11 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-12 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-13 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-14 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-L3-EF-15 WALL MOUNTED 288 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-a-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-a-A/C-2 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-a-A/C-3 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-a-A/C-4 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-a-A/C-5 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-a-A/C-6 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-a-A/C-7 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-a-A/C-8 WALL MOUNT Carrier 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B4a-a-A/C-9 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-a-A/C-10 CEILING Carrier 38CSR024/42XQ025 7.3 780 *3/8 *5/8 21mm
B4a-a-A/C-11 CASSETTE Carrier 38FN024/42TNC024 7 718 *3/8 *5/8 32mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4a-a-EF-1 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-a-EF-2 WALL MOUNTED 113 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-a-EF-3 WALL MOUNTED 113 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-a-EF-4 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-a-EF-5 WALL MOUNTED 183 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-a-EF-6 WALL MOUNTED 127 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
PUSAT PEMPROSESAN
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-c-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-c-A/C-2 CEILING EXPOSED Carrier 38VTA060/42XQ060 17.6 1300 *3/8 *3/4 21mm
B4a-c-A/C-3 CEILING EXPOSED Carrier 38VTA060/42XQ060 17.6 1300 *3/8 *3/4 21mm
B4a-c-A/C-4 CEILING EXPOSED Carrier 38VTA060/42XQ060 17.6 1300 *3/8 *3/4 21mm
B4a-c-A/C-5 CEILING EXPOSED Carrier 38VTA060/42XQ060 17.6 1300 *3/8 *3/4 21mm
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-d-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4a-d-EF-1 WALL MOUNTED 108 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-d-EF-2 WALL MOUNTED 108 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-d-EF-3 WALL MOUNTED 257 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-d-EF-4 WALL MOUNTED 257 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-d-EF-5 WALL MOUNTED 54 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
MAKMAL DIAGNOSTIC
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-e-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-e-A/C-2 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-e-A/C-3 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-e-A/C-4 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-5 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-6 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-7 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-8 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-9 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-e-A/C-10 WALL MOUNT Carrier 38KCV224/42KCV224 6.7 650 *3/8 *5/8 15.7mm
B4a-e-A/C-11 WALL MOUNT Carrier 38KCV224/42KCV224 6.7 650 *3/8 *5/8 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4e-d-EF-1 WALL MOUNTED 157 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4e-d-EF-2 WALL MOUNTED 157 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4e-d-EF-3 WALL MOUNTED 157 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4e-d-EF-4 WALL MOUNTED 157 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4e-d-EF-5 WALL MOUNTED 62 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
UNIT LADANG – KEMUDAHAN SOKONGAN AKADEMIK/ PENYELIDIKAN – PUSAT JUAL HASIL & STOR
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B4a-g-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-2 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-3 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-4 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-5 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-6 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-7 WALL MOUNT Carrier 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B4a-g-A/C-8 WALL MOUNT Carrier 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B4a-g-A/C-9 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-g-A/C-10 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B4a-g-A/C-11 CEILING Carrier 38VTA040/42XQ040 11.7 980 *3/8 *3/4 21mm
B4a-g-A/C-12 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B4a-g-A/C-13 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4a-g-EF-1 WALL MOUNTED 96 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-2 WALL MOUNTED 96 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-3 WALL MOUNTED 125 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-4 WALL MOUNTED 125 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-5 WALL MOUNTED 325 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-6 WALL MOUNTED 259 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4a-g-EF-7 WALL MOUNTED 60 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
FAKULTI SAINS GUNAAN
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B4b-L1-AHU-1 39G1015 Carrier 59 2,441 1.6 3 2 1/2” 2 1/2” 1" 2.56 1550 1550 1150 401
B4b-L1-AHU-2 39G0912 Carrier 40 1,779 1.9 3 2 1/2” 2 1/2” 1" 1.72 1450 1250 1050 273
B4b-L1-AHU-3 39G0914 Carrier 48 2,168 1.8 3 2 1/2” 2 1/2” 1" 2.06 1450 1450 1050 308
B4b-L1-AHU-4 39G0914 Carrier 48 2,168 1.8 2.2 2 1/2” 2 1/2” 1" 2.06 1450 1450 1050 308
B4b-L2-AHU-1 39G0914 Carrier 97 2,098 1.7 3 2 1/2” 2 1/2” 1" 4.17 1450 1450 1050 281
B4b-L2-AHU-2 3951015 Carrier 58 2,266 1.5 2.2 2 1/2” 2 1/2” 1" 2.5 1550 1550 1150 401
B4b-L2-AHU-3 39G1015 Carrier 67 2,450 1.8 3 2 1/2” 2 1/2” 1" 2.89 1550 1550 1150 417
B4b-L2-AHU-4 39G1015 Carrier 65 2,282 1.7 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 417
B4b-L3-AHU-1 39G0914 Carrier 55 2,139 2.0 4 2 1/2” 2 1/2” 1" 2.36 1450 1450 1050 288
B4b-L3-AHU-2 39G1015 Carrier 55 2,421 1.8 3 2 1/2” 2 1/2” 1" 2.39 1550 1550 1150 406
B4b-L3-AHU-3 39G1015 Carrier 68 2,519 2.1 4 2 1/2” 2 1/2” 1" 2.92 1550 1550 1150 424
B4b-L3-AHU-4 39G1015 Carrier 61 2,207 1.8 3 2 1/2” 2 1/2” 1" 2.64 1550 1550 1150 412
B4b-L1-FCU-1 40LM090 Carrier 29.1 978 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4b-L1-FCU-2 40LM060 Carrier 18.4 590 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L1-FCU-3 40LM090 Carrier 29.1 1,140 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4b-L1-FCU-4 40LM060 Carrier 18.4 873 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-1 42CET008 Carrier 7.3 377 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L2-FCU-2 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4b-L2-FCU-3 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-4 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-5 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-6 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-7 42CET010 Carrier 7.9 451 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4b-L2-FCU-8 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-9 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-10 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-11 42CET008 Carrier 7.3 336 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L2-FCU-12 40LM060 Carrier 18.4 780 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-13 40LM060 Carrier 18.4 461 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-14 40LM070 Carrier 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4b-L2-FCU-15 40LM070 Carrier 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4b-L3-FCU-1 42CET008 Carrier 7.3 377 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 410 557 242 41
B4b-L3-FCU-2 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-3 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-4 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-5 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-6 42CET005 Carrier 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-7 42CET010 Carrier 7.9 451 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4b-L3-FCU-8 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-9 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-10 42CET003 Carrier 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-11 42CET008 Carrier 7.3 336 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L3-FCU-12 40LM060 Carrier 18.4 780 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L3-FCU-13 40LM060 Carrier 18.4 461 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L3-FCU-14 40LM070 Carrier 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4b-L3-FCU-15 40LM070 Carrier 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4b-L1-EF-1 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-2 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-3 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L1-EF-4 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L1-EF-5 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L1-EF-6 IN-LINE DUCT FAN 210 700 (H) 80 147 240/1/50 200mm NICOTRA CD 200
B4b-L1-EF-7 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L1-EF-8 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L1-EF-9 WALL MOUNTED 303 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4b-L1-EF-10 WALL MOUNTED 303 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-11 WALL MOUNTED 401 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-12 WALL MOUNTED 292 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-13 WALL MOUNTED 292 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-14 WALL MOUNTED 80 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-15 WALL MOUNTED 292 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L1-EF-16 WALL MOUNTED 292 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-1 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-2 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-3 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L2-EF-4 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-5 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-6 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L2-EF-7 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L2-EF-10 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L2-EF-11 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L2-EF-12 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-13 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-15 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L2-EF-16 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-1 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-2 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-5 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-6 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-7 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L3-EF-8 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L3-EF-11 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L3-EF-12 CEILING MOUNTED 135 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4b-L3-EF-13 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-14 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-15 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B4b-L3-EF-16 WALL MOUNTED 308 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
FAKULTI PENGURUSAN PERNIAGAAN
B4c-L1-FCU-1 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-2 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-3 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-4 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-5 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-6 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-7 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-8 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-9 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-10 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-11 42CET008 Carrier 7.3 800 0.015 55wx3 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-12 42CET008 Carrier 7.3 800 0.015 55wx4 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-13 42CET008 Carrier 7.3 800 0.015 55wx5 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-14 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-15 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-16 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-17 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-18 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-19 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-20 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-21 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-22 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-23 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4c-L1-FCU-24 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-25 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-26 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-27 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-28 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-29 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-30 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-1 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-2 42CET008 Carrier 7.3 800 0.015 55wx3 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-3 42CET008 Carrier 7.3 800 0.015 55wx4 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-4 42CET008 Carrier 7.3 800 0.015 55wx5 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-5 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-6 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-7 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-8 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-9 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-10 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-11 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-12 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-13 42CET008 Carrier 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-14 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-15 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-16 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-17 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-18 42CET003 Carrier 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
18.05NP
B4c-L2-FCU-19 40LM120 Carrier 35.2 3,475 0.7 1.83 25.4 0.43 0.43 680 1600 480 120
T (MPT)
Total Fan Total Fan Fluid
Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Brand Cooling Static Motor Flow
(l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (Inch w.g) (kW) Rate, L/s
B4c-L2-FCU-20 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-21 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-22 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-23 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-24 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-25 40LM090 Carrier 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-26 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-27 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-28 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-29 40LM060 Carrier 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4c-L1-EF-1 CEILING MOUNTED 111 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L1-EF-2 CEILING MOUNTED 151 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L1-EF-3 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L1-EF-5 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L1-EF-6 CEILING MOUNTED 151 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L1-EF-7 CEILING MOUNTED 111 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L2-EF-1 CEILING MOUNTED 111 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L2-EF-2 CEILING MOUNTED 151 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L2-EF-3 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L2-EF-4 CEILING MOUNTED 121 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B4c-L2-EF-5 CEILING MOUNTED 151 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B4c-L2-EF-6 CEILING MOUNTED 111 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
DEWAN KULIAH
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B5-L1-AHU-1 39G1418 Carrier 108 4,607 2.5 7.5 3" 3" 1" 4.67 1750 1850 1550 710
B5-L1-AHU-2 39G1621 Carrier 139 5,627 2.4 7.5 3" 3" 1" 5.97 1950 2150 1750 862
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B5-L1-EF-1 CEILING MOUNTED 170 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
B5-L1-EF-2 CEILING MOUNTED 170 1207 70 25.7 240/1/50 200mm KDK 20 CQT1
UNIT PENYELENGGARAAN, KESELAMATAN, KESIHATAN
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Brand Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B8-L1-AHU-1 39G1418 Carrier 76 4,526 2.1 5.5 3" 3" 1" 3.25 1750 1850 1550 671
B9-L1-AHU-1 39G1317 Carrier 68 3,856 2.2 5.5 3" 3" 1" 2.92 1750 1750 1450 615
B7-L2-FCU-1 40LM070 Carrier 21.6 923 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B7-L2-FCU-2 42CET012 Carrier 9.8 486 0.015 73wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.42 1770 557 242 51
B7-L2-FCU-3 42CET004 Carrier 4.0 179 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B7-L2-FCU-4 40LM040 Carrier 11.6 603 0.4 0.57 1" 1" 3/4" 0.65 680 1000 480 68
B8-L1-FCU-1 42CET008 Carrier 7.3 359 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B9-L1-FCU-1 42CET006 Carrier 4.8 256 0.015 72w 3/4"FPT 3/4"FPT 3/4"MPT 0.2 1170 557 242 30
B9-L1-FCU-2 42CET004 Carrier 4.0 172 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B8-L1-EF-1 WALL MOUNTED 146 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B8-L1-EF-2 WALL MOUNTED 131 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B8-L1-EF-3 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B9-L1-EF-1 IN LINE DUCT FAN 218 700 (L) 70 147 240/1/50 200mm NICOTRA CD 200
B9-L1-EF-2 WALL MOUNTED 50 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B9-L1-EF-3 WALL MOUNTED 50 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B9-L1-EF-4 WALL MOUNTED 40 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
UTILITI - MSB ROOM SUBSTATION 2 & SUBSTATION 3
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
MSB2-EF-1 WALL MOUNTED 333 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
MSB3-EF-1 WALL MOUNTED 274 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
MEDAN SELERA & PUSAT PELAJAR
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B13-L1-EF-1 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B13-L1-EF-2 WALL MOUNTED 187 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B13-L1-EF-3 WALL MOUNTED 220 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B13-L1-EF-4 WALL MOUNTED 152 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B13-L1-KEF-1 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-2 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-3 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-4 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-5 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-6 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-7 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-8 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L1-KEF-9 CENTRIFUGAL 744 2138 380 750 415/3/50 315mm NICOTRA RSH 315R c/w Drivepak
B13-L2-EF-1 WALL MOUNTED 190 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B13-L2-EF-2 WALL MOUNTED 190 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
SURAU
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B15-L1-A/C-1 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B15-L1-A/C-2 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B15-L1-EF-1 WALL MOUNTED 175 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B15-L1-EF-2 WALL MOUNTED 175 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B15-L1-EF-3 WALL MOUNTED 187 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CITU
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B16-L1-A/C-1 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-2 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-3 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-4 CASSETTE Carrier 38FN033/42TNC033 9.7 971 *3/8 *3/4 32mm
B16-L1-A/C-5 CEILING Carrier 38CSR018/42XQ025 6.4 780 *1/4 *1/2 21mm
B16-L1-A/C-6 WALL MOUNT Carrier 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B16-L1-A/C-7 WALL MOUNT Carrier 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B16-L1-A/C-8 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B16-L2-A/C-1 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-2 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-3 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-4 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-5 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-6 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B16-L2-A/C-7 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B16-L1-EF-1 WALL MOUNTED 81 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B16-L2-EF-1 WALL MOUNTED 104 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
RUMAH TETAMU
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B17-L1-A/C-1 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B17-L1-A/C-2 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B17-L1-A/C-3 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-1 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-2 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-3 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-4 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-5 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-6 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-7 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-8 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-9 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-10 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-11 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-12 WALL MOUNT Carrier 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B17-L1-EF-1 WALL MOUNTED 106 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L1-EF-2 WALL MOUNTED 106 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B17-L3-EF-1 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L3-EF-2 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L3-EF-3 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L3-EF-4 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L4-EF-1 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L4-EF-2 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L4-EF-3 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L4-EF-4 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L5-EF-1 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L5-EF-2 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L5-EF-3 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B17-L5-EF-4 WALL MOUNTED 180 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
PEJABAT PENGURUSAN KOLEJ
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
B18-L1-A/C-1 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B18-L1-A/C-2 WALL MOUNT Carrier 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B18-L1-A/C-3 CEILING Carrier 38CSR024/42XQ025 7.3 780 *3/8 *5/8 21mm
B18-L1-A/C-4 CEILING Carrier 38CSR024/42XQ025 7.3 780 *3/8 *5/8 21mm
B18-L1-A/C-5 CASSETTE Carrier 38FN045/42TNC045 13.2 971 *3/8 *3/4 32mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B18-L1-EF-1 WALL MOUNTED 32 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B18-L1-EF-2 WALL MOUNTED 32 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
KAFETERIA
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
B20-GF-EF-1 WALL MOUNTED 165 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B20-GF-EF-2 WALL MOUNTED 165 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B20-GF-EF-3 WALL MOUNTED 40 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
B20-GF-KEF-1 CENTRIFUGAL 4000 1183 400 4000 240/1/50 630mm NICOTRA RSH 630R c/w Drivepak
Pipe Size
Cooling Capacity
A/C Split Tag No. Type Brand Model CFM
(kW)
Liquid Gas Drain Pipe
GH-A/C-1 WALL MOUNT Carrier 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
GH-EF-1 WALL MOUNTED 63 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CENTRAL UTILITY PLANT
SCHEDULE OF CHILLER
Chiller No. 1 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Duty) 550 R134a
Chiller No. 2 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Duty) 550 R134a
Chiller No. 3 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Standby) 550 R134a
Chiller No. 4 Carrier 30HXC260 Water Cooled Multiple Screw Compressor Liquid Chiller 250 R134a
Cooling Tower 1 Truwater TXS 800 – 4L Low Noise Type 800 TRS
Cooling Tower 2 Truwater TXS 800 – 4L Low Noise Type 800 TRS
SCHEDULE OF PUMP
Chilled Water Pump No. 1 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 2 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 3 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 4 Regent D100/38 Horizontal Split Casing Pump 38 L/s VS 38 meter head
Condenser Water Pump No. 1 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 2 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 3 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 4 Regent 150-260 End Suction Pump 79.45 L/s VS 20 meter head
SCHEDULE OF EXHAUST FAN
Speed
Exhaust Fan Marking Type Airflow (l/s) Static (Pa) Wattage (w) V/PH/Hz Fan Dia. Brand Model
(RPM)
ADT
CUP-EF-1 AXIAL FAN 3300 1440 130 1500 415/3/50 560mm NICOTRA
560/160/10B/35/ALU
ADT
CUP-EF-2 AXIAL FAN 3300 1440 130 1500 415/3/50 560mm NICOTRA
560/160/10B/35/ALU
CUP-EF-3 WALL MOUNTED 796 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CUP-EF-4 WALL MOUNTED 707 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CUP-EF-5 WALL MOUNTED 968 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CUP-EF-6 WALL MOUNTED 574 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CUP-EF-7 WALL MOUNTED 574 1109-1301 FREE 18.3 240/1/50 200mm KDK 20 AQM8
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.0
SYSTEM OPERATING PROCEDURE/INSTRUCTION
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.1
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
CHILLER PLANT
19XR
Hermetic Centrifugal Liquid Chillers
50/60 Hz
With PIC II Controls and HFC-134a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 211 Catalog No. 531-974 Printed in U.S.A. Form 19XR-3SS Pg 1 6-98 Replaces: New
Tab 5a
CONTENTS
Page Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . 1 Oil Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Remote Start/Stop Controls . . . . . . . . . . . . . . . . 36
Spare Safety Inputs . . . . . . . . . . . . . . . . . . . . . . . . 36
ABBREVIATIONS AND EXPLANATIONS . . . . . . 4 Spare Safety Alarm Contacts . . . . . . . . . . . . . . 36
CHILLER FAMILIARIZATION . . . . . . . . . . . . . . . . 5-7 Refrigerant Leak Detector . . . . . . . . . . . . . . . . . . . 36
Chiller Information Plate . . . . . . . . . . . . . . . . . . . . 5 Condenser Pump Control . . . . . . . . . . . . . . . . . . 36
System Components . . . . . . . . . . . . . . . . . . . . . . . . 5 Condenser Freeze Prevention . . . . . . . . . . . . . . 37
Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Tower Fan Relay Low and High . . . . . . . . . . . . . 37
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Auto. Restart After Power Failure . . . . . . . . . . . 37
Motor-Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Water/Brine Reset . . . . . . . . . . . . . . . . . . . . . . . . . 37
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • RESET TYPE 1
Factory-Mounted Starter (Optional) . . . . . . . . . . 7 • RESET TYPE 2
Storage Vessel (Optional) . . . . . . . . . . . . . . . . . . . 7 • RESET TYPE 3
REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . 7 Demand Limit Control Option . . . . . . . . . . . . . . . . 38
Surge Prevention Algorithm . . . . . . . . . . . . . . . . 38
MOTOR AND LUBRICATING OIL Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 39
COOLING CYCLE . . . . . . . . . . . . . . . . . . . . . . . . 7,8 Lead/Lag Control . . . . . . . . . . . . . . . . . . . . . . . . . . 39
LUBRICATION CYCLE . . . . . . . . . . . . . . . . . . . . . . 8 • COMMON POINT SENSOR INSTALLATION
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 • CHILLER COMMUNICATION WIRING
Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 • LEAD/LAG OPERATION
Oil Reclaim System . . . . . . . . . . . . . . . . . . . . . . . . . 8 • FAULTED CHILLER OPERATION
• PRIMARY OIL RECOVERY MODE • LOAD BALANCING
• SECONDARY OIL RECOVERY METHOD • AUTO. RESTART AFTER POWER FAILURE
Ice Build Control . . . . . . . . . . . . . . . . . . . . . . . . . . 41
STARTING EQUIPMENT . . . . . . . . . . . . . . . . . . . . . 8-10 • ICE BUILD INITIATION
Unit-Mounted Solid-State Starter • START-UP/RECYCLE OPERATION
(Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 • TEMPERATURE CONTROL DURING
Unit-Mounted Wye-Delta Starter ICE BUILD
(Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 • TERMINATION OF ICE BUILD
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-43 • RETURN TO NON-ICE BUILD OPERATIONS
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Attach to Network Device Control . . . . . . . . . . 42
• ANALOG SIGNAL • ATTACHING TO OTHER CCN MODULES
• DISCRETE SIGNAL Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . 43
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 • TO ACCESS THE SERVICE SCREENS
PIC II System Components . . . . . . . . . . . . . . . . . 10 • TO LOG OUT OF NETWORK DEVICE
• CHILLER VISUAL CONTROLLER (CVC) • HOLIDAY SCHEDULING
• INTEGRATED STARTER MODULE (ISM) START-UP/SHUTDOWN/RECYCLE
• CHILLER CONTROL MODULE (CCM) SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45
• OIL HEATER CONTACTOR (1C) Local Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
• OIL PUMP CONTACTOR (2C) Shutdown Sequence . . . . . . . . . . . . . . . . . . . . . . . 45
• HOT GAS BYPASS CONTACTOR RELAY (3C) Automatic Soft Stop Amps Threshold . . . . . . . 45
(Optional) Chilled Water Recycle Mode . . . . . . . . . . . . . . . . 45
• CONTROL TRANSFORMERS (T1, T2) Safety Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . 45
CVC Operation and Menus . . . . . . . . . . . . . . . . . 14
• GENERAL BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . 46-58
• ALARMS AND ALERTS Job Data Required . . . . . . . . . . . . . . . . . . . . . . . . . 46
• CVC MENU ITEMS Equipment Required . . . . . . . . . . . . . . . . . . . . . . . 46
• BASIC CVC OPERATIONS (Using the Softkeys) Using the Optional Storage Tank
• TO VIEW STATUS and Pumpout System . . . . . . . . . . . . . . . . . . . . 46
• OVERRIDE OPERATIONS Remove Shipping Packaging . . . . . . . . . . . . . . . 46
• TIME SCHEDULE OPERATION Open Oil Circuit Valves . . . . . . . . . . . . . . . . . . . . 46
• TO VIEW AND CHANGE SET POINTS Tighten All Gasketed Joints and
• SERVICE OPERATION Guide Vane Shaft Packing . . . . . . . . . . . . . . . . 46
PIC II System Functions . . . . . . . . . . . . . . . . . . . 32 Check Chiller Tightness . . . . . . . . . . . . . . . . . . . . 46
• CAPACITY CONTROL Refrigerant Tracer . . . . . . . . . . . . . . . . . . . . . . . . . 46
• ECW CONTROL OPTION Leak Test Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . 48
• CONTROL POINT DEADBAND Standing Vacuum Test . . . . . . . . . . . . . . . . . . . . . 48
• DIFFUSER CONTROL Chiller Dehydration . . . . . . . . . . . . . . . . . . . . . . . . 51
• PROPORTIONAL BANDS AND GAIN Inspect Water Piping . . . . . . . . . . . . . . . . . . . . . . . 51
• DEMAND LIMITING Check Optional Pumpout Compressor
• CHILLER TIMERS Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
• OCCUPANCY SCHEDULE Check Relief Valves . . . . . . . . . . . . . . . . . . . . . . . 51
Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Inspect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Shunt Trip (Option) . . . . . . . . . . . . . . . . . . . . . . . . 35 Carrier Comfort Network Interface . . . . . . . . . . 52
Default Screen Freeze . . . . . . . . . . . . . . . . . . . . . 35 Check Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Ramp Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 • MECHANICAL STARTER
Capacity Override . . . . . . . . . . . . . . . . . . . . . . . . . 35 • BENSHAW, INC. REDISTART MICRO
High Discharge Temperature Control . . . . . . . 35 SOLID-STATE STARTER
Oil Sump Temperature Control . . . . . . . . . . . . . 35 Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2
CONTENTS (cont)
Page Page
Power Up the Controls and After Extended Shutdown . . . . . . . . . . . . . . . . . . 60
Check the Oil Heater . . . . . . . . . . . . . . . . . . . . . 53 Cold Weather Operation . . . . . . . . . . . . . . . . . . . 60
• SOFTWARE VERSION Manual Guide Vane Operation . . . . . . . . . . . . . . 60
Software Configuration . . . . . . . . . . . . . . . . . . . . 53 Refrigeration Log . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Input the Design Set Points . . . . . . . . . . . . . . . . 53 PUMPOUT AND REFRIGERANT TRANSFER
Input the Local Occupied Schedule PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . 62-64
(OCCPC01S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Input Service Configurations . . . . . . . . . . . . . . . 53 Operating the Optional Pumpout Unit . . . . . . 62
• PASSWORD • TO READ REFRIGERANT PRESSURES
• INPUT TIME AND DATE Chillers with Storage Tanks . . . . . . . . . . . . . . . . 63
• CHANGE CVC CONFIGURATION • TRANSFER REFRIGERANT FROM
IF NECESSARY PUMPOUT STORAGE TANK TO CHILLER
• TO CHANGE THE PASSWORD • TRANSFER THE REFRIGERANT FROM
• TO CHANGE THE CVC DISPLAY FROM CHILLER TO PUMPOUT STORAGE TANK
ENGLISH TO METRIC UNITS Chillers with Isolation Valves . . . . . . . . . . . . . . . 64
• MODIFY CONTROLLER IDENTIFICATION • TRANSFER ALL REFRIGERANT TO
IF NECESSARY CHILLER CONDENSER VESSEL
• INPUT EQUIPMENT SERVICE PARAMETERS • TRANSFER ALL REFRIGERANT TO
IF NECESSARY CHILLER COOLER VESSEL
• CONFIGURE DIFFUSER CONTROL IF • RETURN CHILLER TO NORMAL
NECESSARY OPERATING CONDITIONS
• MODIFY EQUIPMENT CONFIGURATION
IF NECESSARY GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . 65,66
Perform a Control Test . . . . . . . . . . . . . . . . . . . . . . 56 Refrigerant Properties . . . . . . . . . . . . . . . . . . . . . 65
Check Optional Pumpout System Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . 65
Controls and Compressor . . . . . . . . . . . . . . . . 56 Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . 65
High Altitude Locations . . . . . . . . . . . . . . . . . . . . 56 Adjusting the Refrigerant Charge . . . . . . . . . . . 65
Charge Refrigerant Into Chiller . . . . . . . . . . . . . 56 Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . 65
• CHILLER EQUALIZATION WITHOUT A Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PUMPOUT UNIT Test After Service, Repair, or Major Leak . . . . 65
• CHILLER EQUALIZATION WITH • REFRIGERANT TRACER
PUMPOUT UNIT • TO PRESSURIZE WITH DRY NITROGEN
• TRIMMING REFRIGERANT CHARGE Repair the Leak, Retest, and Apply
Standing Vacuum Test . . . . . . . . . . . . . . . . . . . 65
INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . 58,59 Checking Guide Vane Linkage . . . . . . . . . . . . . . 65
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Trim Refrigerant Charge . . . . . . . . . . . . . . . . . . . 65
Dry Run to Test Start-Up Sequence . . . . . . . . . 58
Check Motor Rotation . . . . . . . . . . . . . . . . . . . . . . 58 WEEKLY MAINTENANCE . . . . . . . . . . . . . . . . . . . 66
• IF THE MOTOR ROTATION IS CLOCKWISE Check the Lubrication System . . . . . . . . . . . . . . 66
• IF THE MOTOR ROTATION IS NOT SCHEDULED MAINTENANCE . . . . . . . . . . . . . . 66-69
CLOCKWISE Service Ontime . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Check Oil Pressure and Compressor Inspect the Control Panel . . . . . . . . . . . . . . . . . . 66
Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Check Safety and Operating Controls
To Prevent Accidental Start-Up . . . . . . . . . . . . . 59 Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Check Chiller Operating Condition . . . . . . . . . . 59 Changing Oil Filter . . . . . . . . . . . . . . . . . . . . . . . . 66
Instruct the Customer Operator . . . . . . . . . . . . 59 Oil Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• COOLER-CONDENSER Oil Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• OPTIONAL PUMPOUT STORAGE TANK AND • TO CHANGE THE OIL
PUMPOUT SYSTEM Refrigerant Filter . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• MOTOR COMPRESSOR ASSEMBLY Oil Reclaim Filter . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• MOTOR COMPRESSOR LUBRICATION Inspect Refrigerant Float System . . . . . . . . . . . 67
SYSTEM Inspect Relief Valves and Piping . . . . . . . . . . . . 67
• CONTROL SYSTEM Compressor Bearing and Gear
• AUXILIARY EQUIPMENT Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• DESCRIBE CHILLER CYCLES Inspect the Heat Exchanger Tubes
• REVIEW MAINTENANCE and Flow Devices . . . . . . . . . . . . . . . . . . . . . . . . 68
• SAFETY DEVICES AND PROCEDURES • COOLER AND FLOW DEVICES
• CHECK OPERATOR KNOWLEDGE • CONDENSER AND FLOW DEVICES
• REVIEW THE START-UP, OPERATION, AND Water Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
MAINTENANCE MANUAL Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . 59-61 Inspect the Starting Equipment . . . . . . . . . . . . . 68
Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Check Pressure Transducers . . . . . . . . . . . . . . . 68
Prepare the Chiller for Start-Up . . . . . . . . . . . . . 59 Optional Pumpout System Maintenance . . . . . 68
To Start the Chiller . . . . . . . . . . . . . . . . . . . . . . . . 59 • OPTIONAL PUMPOUT COMPRESSOR OIL
Check the Running System . . . . . . . . . . . . . . . . 59 CHARGE
To Stop the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . 60 • OPTIONAL PUMPOUT SAFETY CONTROL
After Limited Shutdown . . . . . . . . . . . . . . . . . . . . 60 SETTINGS
Preparation for Extended Shutdown . . . . . . . . 60 Ordering Replacement Chiller Parts . . . . . . . . 69
3
CONTENTS (cont)
Page Page
Notes on Module Operation . . . . . . . . . . . . . . . . 80
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . 69-99 Chiller Control Module (CCM) . . . . . . . . . . . . . . . . 81
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 • INPUTS
Checking the Display Messages . . . . . . . . . . . . 69 • OUTPUTS
Checking Temperature Sensors . . . . . . . . . . . . 69 ISM Integrated Starter Module . . . . . . . . . . . . . . 81
• RESISTANCE CHECK • INPUTS
• VOLTAGE DROP • OUTPUTS
• CHECK SENSOR ACCURACY Replacing Defective Processor Modules . . . . 81
• DUAL TEMPERATURE SENSORS • INSTALLATION
Checking Pressure Transducers . . . . . . . . . . . . 70 Solid-State Starters . . . . . . . . . . . . . . . . . . . . . . . . 81
• COOLER AND CONDENSER PRESSURE • TESTING SILICON CONTROL RECTIFIERS
TRANSDUCER AND WATERSIDE FLOW DEVICE IN BENSHAW, INC. SOLID-STATE STARTERS
CALIBRATION • SCR REMOVAL/INSTALLATION
• TRANSDUCER REPLACEMENT Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Control Algorithms Checkout Procedure . . . . 70
Control Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100,101
Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 INITIAL START-UP CHECKLIST FOR
• RED LED (Labeled as STAT) 19XR HERMETIC CENTRIFUGAL
• GREEN LED (Labeled as COM) LIQUID CHILLER . . . . . . . . . . . . . . . . . . CL-1 to CL-12
4
CHILLER FAMILIARIZATION Motor-Compressor — This component maintains sys-
(Fig. 1 and 2) tem temperature and pressure differences and moves the heat-
carrying refrigerant from the cooler to the condenser.
Chiller Information Plate — The information plate is
located on the right side of the chiller control panel. Control Panel — The control panel is the user interface
for controlling the chiller. It regulates the chiller’s capacity
System Components — The components include the as required to maintain proper leaving chilled water tem-
cooler and condenser heat exchangers in separate vessels, perature. The control panel:
motor-compressor, lubrication package, control panel, and • registers cooler, condenser, and lubricating system
motor starter. All connections from pressure vessels have ex- pressures
ternal threads to enable each component to be pressure tested • shows chiller operating condition and alarm shutdown
with a threaded pipe cap during factory assembly. conditions
Cooler — This vessel (also known as the evaporator) is • records the total chiller operating hours
located underneath the compressor. The cooler is main- • sequences chiller start, stop, and recycle under micro-
tained at lower temperature/pressure so evaporating refrig- processor control
erant can remove heat from water flowing through its inter- • displays status of motor starter
nal tubes. • provides access to other CCN (Carrier Comfort Network)
devices
Condenser — The condenser operates at a higher
temperature/pressure than the cooler and has water flowing
through its internal tubes in order to remove heat from the
refrigerant.
15 14
13
12
9
11 10
FRONT VIEW
18 19 20 21 22 LEGEND
18 — Condenser Auto. Reset Relief Valves
19 — Motor Circuit Breaker
20 — Solid-State Starter Control Display
21 — Unit-Mounted Starter (Optional),
34 Solid-State Starter Shown
22 — Motor Sight Glass
23
23 — Cooler Return-End Waterbox Cover
24 — ASME Nameplate (One Hidden)
25 — Typical Waterbox Drain Port
26 — Condenser Return-End Waterbox Cover
27 — Refrigerant Moisture/Flow Indicator
28 — Refrigerant Filter/Drier
29 — Liquid Line Isolation Valve (Optional)
30 — Linear Float Valve Chamber
31 — Vessel Take-Apart Connector
32 — Discharge Isolation Valve (Optional)
33 — Pumpout Valve
34 — Condenser Pressure Transducer
33 24
32
31 30 29 28 27 26 25 24
REAR VIEW
Fig. 2 — Typical 19XR Components
6
Factory-Mounted Starter (Optional) — The starter [37 to 40 C]) when it is discharged from the compressor into
allows for the proper start and disconnect of electrical en- the condenser.
ergy for the compressor-motor, oil pump, oil heater, and con- Relatively cool (typically 65 to 90 F [18 to 32 C]) water
trol panel. flowing into the condenser tubes removes heat from the re-
frigerant and the vapor condenses to liquid.
Storage Vessel (Optional) — There are 2 sizes of
storage vessels available. The vessels have double relief valves, The liquid refrigerant passes through orifices into the FLASC
a magnetically-coupled dial-type refrigerant level gage, a (Flash Subcooler) chamber (Fig. 3). Since the FLASC cham-
one-inch FPT drain valve, and a 1⁄2-in. male flare vapor ber is at a lower pressure, part of the liquid refrigerant flashes
connection for the pumpout unit. to vapor, thereby cooling the remaining liquid. The FLASC
vapor is recondensed on the tubes which are cooled by en-
NOTE: If a storage vessel is not used at the jobsite, factory- tering condenser water. The liquid drains into a float cham-
installed isolation valves on the chiller may be used to iso- ber between the FLASC chamber and cooler. Here a float
late the chiller charge in either the cooler or condenser. valve forms a liquid seal to keep FLASC chamber vapor from
An optional pumpout system is used to transfer refrigerant entering the cooler. When liquid refrigerant passes through
from vessel to vessel. the valve, some of it flashes to vapor in the reduced pressure
on the cooler side. In flashing, it removes heat from the re-
REFRIGERATION CYCLE maining liquid. The refrigerant is now at a temperature and
The compressor continuously draws refrigerant vapor from pressure at which the cycle began.
the cooler at a rate set by the amount of guide vane opening.
As the compressor suction reduces the pressure in the cooler, MOTOR AND LUBRICATING OIL
the remaining refrigerant boils at a fairly low temperature COOLING CYCLE
(typically 38 to 42 F [3 to 6 C]). The energy required for The motor and the lubricating oil are cooled by liquid re-
boiling is obtained from the water flowing through the cooler frigerant taken from the bottom of the condenser vessel
tubes. With heat energy removed, the water becomes cold (Fig. 3). Refrigerant flow is maintained by the pressure dif-
enough to use in an air conditioning circuit or for process ferential that exists due to compressor operation. After the
liquid cooling. refrigerant flows past an isolation valve, an in-line
After taking heat from the water, the refrigerant vapor is filter, and a sight glass/moisture indicator, the flow is split
compressed. Compression adds still more heat energy, and between the motor cooling and oil cooling systems.
the refrigerant is quite warm (typically 98 to 102 F
7
Flow to the motor cooling system passes through an ori- During shutdown, the oil pump will run for 60 seconds to
fice and into the motor. Once past the orifice, the refrigerant post-lubricate after the compressor shuts down. The oil pump
is directed over the motor by a spray nozzle. The refrigerant can also be energized for testing purposes during a Control
collects in the bottom of the motor casing and is then drained Test.
back into the cooler through the motor refrigerant drain line. Ramp loading can slow the rate of guide vane opening to
A back pressure valve or an orifice in this line maintains a minimize oil foaming at start-up. If the guide vanes open
higher pressure in the motor shell than in the cooler/oil sump. quickly, the sudden drop in suction pressure can cause any
The motor is protected by a temperature sensor imbedded in refrigerant in the oil to flash. The resulting oil foam can-
the stator windings. An increase in motor winding tempera- not be pumped efficiently; therefore, oil pressure falls off
ture past the motor override set point overrides the tempera- and lubrication is poor. If oil pressure falls below 15 psid
ture capacity control to hold, and if the motor temperature (103 kPad) differential, the PIC II will shut down the
rises 10° F (5.5° C) above this set point, closes the inlet guide compressor.
vanes. If the temperature rises above the safety limit, the com- If the controls are subject to a power failure that lasts more
pressor shuts down. than 3 hours, the oil pump will be energized periodically when
Refrigerant that flows to the oil cooling system is regu- the power is restored. This helps to eliminate refrigerant that
lated by thermostatic expansion valves (TXVs). The TXVs has migrated to the oil sump during the power failure. The
regulate flow into the oil/refrigerant plate and frame-type heat controls energize the pump for 60 seconds every 30 minutes
exchanger (the oil cooler in Fig. 3). The expansion valve until the chiller is started.
bulbs control oil temperature to the bearings. The refrigerant
leaving the oil cooler heat exchanger then returns to the chiller Oil Reclaim System — The oil reclaim system re-
cooler. turns oil lost from the compressor housing back to the oil
reservoir by recovering the oil from 2 areas on the chiller.
LUBRICATION CYCLE The guide vane housing is the primary area of recovery. Oil
is also recovered by skimming it from the operating refrig-
Summary — The oil pump, oil filter, and oil cooler make erant level in the cooler vessel.
up a package located partially in the transmission casting of
the compressor-motor assembly. The oil is pumped into a PRIMARY OIL RECOVERY MODE — Oil is normally
filter assembly to remove foreign particles and is then forced recovered through the guide vane housing on the chiller. This
into an oil cooler heat exchanger where the oil is cooled to is possible because oil is normally entrained with refrigerant
proper operational temperatures. After the oil cooler, part of in the chiller. As the compressor pulls the refrigerant up from
the flow is directed to the gears and the high speed shaft the cooler into the guide vane housing to be compressed, the
bearings; the remaining flow is directed to the motor shaft oil normally drops out at this point and falls to the bottom
bearings. Oil drains into the transmission oil sump to com- of the guide vane housing where it accumulates. Using dis-
plete the cycle (Fig. 4). charge gas pressure to power an eductor, the oil is drawn
from the housing and is discharged into the oil reservoir.
Details — Oil is charged into the lubrication system through SECONDARY OIL RECOVERY METHOD — The sec-
a hand valve. Two sight glasses in the oil reservoir permit oil ondary method of oil recovery is significant under light load
level observation. Normal oil level is between the middle of conditions, when the refrigerant going up to the compressor
the upper sight glass and the top of the lower sight glass suction does not have enough velocity in which to bring oil
when the compressor is shut down. The oil level should be along. Under these conditions, oil collects in a greater con-
visible in at least one of the 2 sight glasses during operation. centration at the top level of the refrigerant in the cooler.
Oil sump temperature is displayed on the CVC (Chiller This oil and refrigerant mixture is skimmed from the side of
Visual Control) default screen. During compressor opera- the cooler and is then drawn up to the guide vane housing.
tion, the oil sump temperature ranges between 125 to 150 F There is a filter in this line. Because the guide vane housing
(52 to 66 C). pressure is much lower than the cooler pressure, the refrig-
The oil pump suction is fed from the oil reservoir. An erant boils off, leaving the oil behind to be collected by the
oil pressure relief valve maintains 18 to 25 psid (124 to primary oil recovery method.
172 kPad) differential pressure in the system at the pump
discharge. This differential pressure can be read directly from STARTING EQUIPMENT
the CVC default screen. The oil pump discharges oil to the The 19XR requires a motor starter to operate the centrifu-
oil filter assembly. This filter can be closed to permit gal hermetic compressor motor, the oil pump, and various
removal of the filter without draining the entire oil system auxiliary equipment. The starter is the main field wiring in-
(see Maintenance sections, pages 65 to 69, for details). The terface for the contractor.
oil is then piped to the oil cooler heat exchanger. The oil See Carrier Specification Z-415 for specific starter re-
cooler uses refrigerant from the condenser as the coolant. quirements. All starters must meet these specifications in
The refrigerant cools the oil to a temperature between 120 order to properly start and satisfy mechanical safety require-
and 140 F (49 to 60 C). ments. Starters may be supplied as separate, free-standing
As the oil leaves the oil cooler, it passes the oil pressure units or may be mounted directly on the chiller (unit mounted)
transducer and the thermal bulb for the refrigerant expan- for low-voltage units only.
sion valve on the oil cooler. The oil is then divided. Part of Three separate circuit breakers are inside the starter. Cir-
the oil flows to the thrust bearing, forward pinion bearing, cuit breaker CB1 is the compressor motor circuit breaker.
and gear spray. The rest of the oil lubricates the motor shaft The disconnect switch on the starter front cover is connected
bearings and the rear pinion bearing. The oil temperature is to this breaker. Circuit breaker CB1 supplies power to the
measured in the bearing housing as it leaves the thrust and compressor motor.
forward journal bearings. The oil then drains into the oil res-
ervoir at the base of the compressor. The PIC II (Product
Integrated Control II) measures the temperature of the oil in
the sump and maintains the temperature during shutdown The main circuit breaker (CB1) on the front of the starter
(see Oil Sump Temperature Control section, page 35). This disconnects the main motor current only. Power is still
temperature is read on the CVC default screen. energized for the other circuits. Two more circuit break-
During the chiller start-up, the PIC II energizes the oil pump ers inside the starter must be turned off to disconnect
and provides 45 seconds of prelubrication to the bearings power to the oil pump, PIC II controls, and oil heater.
after pressure is verified before starting the compressor.
8
REAR MOTOR FWD MOTOR OIL SUPPLY TO
BEARING BEARING FORWARD HIGH
SPEED BEARING
LABYRINTH
GAS LINE
MOTOR
COOLING LINE
ISOLATION
VALVE
OIL FILTER
TXV BULB PRESSURE ISOLATION PUMP
TRANSDUCER VALVE
OIL SIGHT
OIL HEATER GLASS
COOLER OIL PUMP EDUCTOR FILTER
MOTOR ISOLATION
SIGHT GLASS VALVE
Circuit breaker CB2 supplies power to the control panel, torque required to get the motor moving. The voltage is re-
oil heater, and portions of the starter controls. duced by silicon controlled rectifiers (SCRs). The voltage
Circuit breaker CB3 supplies power to the oil pump. Both and current are then ramped up in a desired period of time.
CB2 and CB3 are wired in parallel with CB1 so that power Once full voltage is reached, a bypass contactor is energized
is supplied to them if the CB1 disconnect is open. to bypass the SCRs.
All starters must include a Carrier control module called
the Integrated Starter Module (ISM), excluding the
Benshaw solid-state starters. This module controls and moni- When voltage is supplied to the solid-state circuitry, the
tors all aspects of the starter. See the Controls section on heat sinks in the starter as well as the wires leading to
page 10 for additional ISM information. All starter replace- the motor and the motor terminal are at line voltage.
ment parts are supplied by the starter manufacturer exclud- Do not touch the heat sinks, power wiring, or motor
ing the ISM (contact Carrier’s Replacement Component terminals while voltage is present or serious injury will
Division [RCD]). result.
Unit-Mounted Solid-State Starter (Optional) There is a display on the front of the Benshaw, Inc., solid-
— The 19XR chiller may be equipped with a solid-state, state starters that is useful for troubleshooting and starter check-
reduced-voltage starter (Fig. 5 and 6). This starter’s primary out. The display indicates:
function is to provide on-off control of the compressor mo- • voltage to the SCRs
tor. This type of starter reduces the peak starting torque, • SCR control voltage
reduces the motor inrush current, and decreases mechanical • power indication
shock. This capability is summed up by the phrase ‘‘soft start- • proper phasing for rotation
ing.’’ The solid-state starter is available as a 19XR option • start circuit energized
(factory supplied and installed). The solid-state starters manu- • over-temperature
facturer name is located inside the starter access door. • ground fault
A solid-state, reduced-voltage starter operates by reduc- • current unbalance
ing the starting voltage. The starting torque of a motor at full • run state
voltage is typically 125% to 175% of the running torque. • software configuration
When the voltage and the current are reduced at start-up, the The starter is further explained in the Check Starter and
starting torque is reduced as well. The object is to reduce the Troubleshooting Guide sections, pages 52 and 66.
starting voltage to just the voltage necessary to develop the
9
Unit-Mounted Wye-Delta Starter (Optional)
— The 19XR chiller may be equipped with a wye-delta starter
mounted on the unit. This starter is intended for use with
low-voltage motors (under 600 v). It reduces the starting
6 current inrush by connecting each phase of the motor
windings into a wye configuration. This occurs during the
starting period when the motor is accelerating up to speed.
1 Once the motor is up to speed, the starter automatically con-
nects the phase windings into a delta configuration. Starter
control, monitoring, and motor protection is provided by
Carrier’s Integrated Starter Module (ISM).
2 CONTROLS
Definitions
3
5 ANALOG SIGNAL — An analog signal varies in propor-
tion to the monitored source. It quantifies values between
operating limits. (Example: A temperature sensor is an ana-
log device because its resistance changes in proportion to
the temperature, generating many values.)
DISCRETE SIGNAL — A discrete signal is a 2-position rep-
4
resentation of the value of a monitored source. (Example: A
switch produces a discrete signal indicating whether a value
is above or below a set point or boundary by generating an
on/off, high/low, or open/closed signal.)
LEGEND
General — The 19XR hermetic centrifugal liquid chiller
contains a microprocessor-based control center that moni-
1 — Ready-Start Micro Input/Output Card tors and controls all operations of the chiller (see Fig. 7).
2 — Circuit Breaker 2 (CB2):
Machine Control and Heater Power The microprocessor control system matches the cooling
3 — Circuit Breaker 3 (CB3): Oil Pump Power capacity of the chiller to the cooling load while providing
4 — Ready-Start Micro Central Processing Unit Card (CPU) state-of-the-art chiller protection. The system controls cool-
5 — Restart Micro Power Card (hidden, not depicted) ing load within the set point plus the deadband by sensing
6 — Restart Micro Bypass Card (hidden, not depicted)
the leaving chilled water or brine temperature and regula-
Fig. 5 — Solid-State Starter Box, ting the inlet guide vane via a mechanically-linked actuator
Internal View motor. The guide vane is a variable flow pre-whirl assem-
bly that controls the refrigeration effect in the cooler by
regulating the amount of refrigerant vapor flow into the com-
pressor. An increase in guide vane opening increases capac-
ity. A decrease in guide vane opening decreases capacity. The
microprocessor-based control center protects the chiller by
monitoring the digital and analog inputs and executing
capacity overrides or safety shutdowns, if required.
PIC II System Components — The chiller control
system is called the PIC II (Product Integrated Control II).
See Table 1. The PIC II controls the operation of the chiller
by monitoring all operating conditions. The PIC II can di-
agnose a problem and let the operator know what the prob-
lem is and what to check. It promptly positions the guide
vanes to maintain leaving chilled water temperature. It can
interface with auxiliary equipment such as pumps and cool-
ing tower fans to turn them on when required. It continually
checks all safeties to prevent any unsafe operating condi-
tion. It also regulates the oil heater while the compressor is
off and regulates the hot gas bypass valve, if installed. The
PIC II controls provide critical protection for the compres-
sor motor and controls the motor starter.
10
COOLER SCHRADER CONTROL GUIDE VANE POWER COMMUNICATION
FITTING (HIDDEN) PANEL ACTUATOR CABLE PANEL CABLE
WATER
SENSOR
CABLES WATER
SENSOR
CABLES
COOLER
PRESSURE
CONNECTION
TOP VIEW
11
The PIC II can interface with the Carrier Comfort Net- tower fan, spare alarm contacts, and the shunt trip. The ISM
work (CCN) if desired. It can communicate with other monitors starter inputs such as line voltage, motor current,
PIC I or PIC II equipped chillers and other CCN devices. ground fault, remote start contact, spare safety, condenser
The PIC II consists of 3 modules housed inside 3 major high pressure, oil pump interlock, starter 1M, and run con-
components. The component names and corresponding con- tacts. The ISM contains logic capable of safety shutdown. It
trol voltages are listed below (also see Table 1): shuts down the chiller if communications with the CVC
are lost.
• control panel
— all extra low-voltage wiring (24 v or less) CHILLER CONTROL MODULE (CCM) — This module
• power panel is located in the control panel. The CCM provides the input
— 230 or 115 v control voltage (per job requirement) and outputs necessary to control the chiller. This module moni-
— up to 600 v for oil pump power tors refrigerant pressure, entering and leaving water tem-
peratures, and outputs control for the guide vane actuator,
• starter cabinet oil heaters, and oil pump. The CCM is the connection point
— chiller power wiring (per job requirement) for optional demand limit, chilled water reset, remote tem-
perature reset, and refrigerant leak sensor.
Table 1 — Major PIC Components and
Panel Locations* OIL HEATER CONTACTOR (1C) — This contactor is lo-
cated in the power panel (Fig. 11) and operates the heater at
PIC II COMPONENT PANEL LOCATION either 115 or 230 v. It is controlled by the PIC II to maintain
Chiller Visual Controller (CVC) and Display Control Panel oil temperature during chiller shutdown.
Integrated Starter Module (ISM) Starter Cabinet OIL PUMP CONTACTOR (2C) — This contactor is located
Chiller Control Module (CCM) Control Panel in the power panel. It operates all 200 to 575-v oil pumps.
Oil Heater Contactor (1C) Power Panel The PIC II energizes the contactor to turn on the oil pump
Oil Pump Contactor (2C) Power Panel as necessary.
Hot Gas Bypass Relay (3C) (Optional) Power Panel HOT GAS BYPASS CONTACTOR RELAY (3C) (Op-
Control Transformers (T1, T2) Power Panel tional) — This relay, located in the power panel, controls the
Temperature Sensors See Fig. 7. opening of the hot gas bypass valve. The PIC II energizes
Pressure Transducers See Fig. 7. the relay during low load, high lift conditions.
*See Fig. 5 and Fig. 7-11.
CONTROL TRANSFORMERS (T1, T2) — These trans-
formers convert incoming control voltage to 24 vac power
for the 3 power panel contactor relays, CCM, and CVC.
CHILLER VISUAL CONTROLLER (CVC) — The CVC is
the ‘‘brain’’ of the PIC II. This module contains all the op-
erating software needed to control the chiller. The CVC is
mounted to the control panel (Fig. 10) and is the input center
for all local chiller set points, schedules, configurable
functions, and options. The CVC has a stop button, an alarm
light, four buttons for logic inputs, and a backlight display.
The backlight will automatically turn off after 15 minutes of
non-use. The functions of the four buttons or ‘‘softkeys’’ are
menu driven and are shown on the display directly above Fig. 8 — Control Sensors (Temperature)
the softkeys.
The viewing angle of the CVC can be adjusted for opti-
mum viewing. Remove the 2 bolts connecting the control
panel to the brackets attached to the cooler. Place them in
one of the holes to pivot the control panel forward to back-
ward to change the viewing angle. See Fig. 10. To change
the contrast of the display, access the adjustment on the back
of the CVC. See Fig. 10.
INTEGRATED STARTER MODULE (ISM) — This mod-
ule is located in the starter cabinet. This module initiates com- Fig. 9 — Control Sensors
mands from the CVC for starter functions such as starting (Pressure Transducers, Typical)
and stopping the compressor, condenser, chilled water pumps,
12
Fig. 10 — Control Panel
13
CVC Operation and Menus (Fig. 12-18) PRIMARY STATUS
MESSAGE
COMPRESSOR
ONTIME
DATE TIME
GENERAL SECONDARY
STATUS RUNNING TEMP CONTROL 01-01-95 11:48
• The CVC display automatically reverts to the default screen MESSAGE LEAVING CHILLED WATER 28.8 HOURS
CHW IN CHW OUT EVAP REF
after 15 minutes if no softkey activity takes place and if ALARM LIGHT
55.1 44.1 40.7
the chiller is not in the pumpdown mode (Fig. 12). (ILLUMINATED CDW IN CDW OUT COND REF
WHEN POWER ON) 85.0 95.0 98.1
• If a screen other than the default screen is displayed on the • BLINKS CONTINUOUSLY
ON FOR AN ALARM
OIL PRESS OIL TEMP AMPS %
CVC, the name of that screen is in the upper right corner 21.8 132.9 93
• CONFIRMONCE
BLINKS TO
A STOP CCN LOCAL RESET MENU
(Fig. 13).
• The CVC may be set to display either English or SI units.
Use the CVC configuration screen (accessed from the Serv-
ice menu) to change the units. See the Service Operation STOP BUTTON
• HOLD FOR ONE
section, page 43. SECOND TO STOP
14
• Press QUIT to leave the selected decision or field with- 2. Press NEXT or PREVIOUS to highlight the desired
out saving any changes. status table. The list of tables is:
• MAINSTAT — Overall chiller status
• STARTUP — Status required to perform startup of chiller
• COMPRESS — Status of sensors related to the
compressor
• HEAT_EX — Status of sensors related to the heat
• Press ENTER to leave the selected decision or field and exchangers
save changes. • POWER — Status of motor input power
• ISM_STAT — Status of motor starter
• CVC_PSWD — Service menu password forcing ac-
cess screen
OVERRIDE OPERATIONS
To Override a Value or Status
1. From any point status screen, press NEXT or
PREVIOUS to highlight the desired value.
TO VIEW STATUS (Fig. 14) — The status table shows the
actual value of overall chiller status such as CONTROL MODE,
RUN STATUS, AUTO CHILLED WATER, RESET, and RE-
MOTE RESET SENSOR.
1. On the menu screen, press STATUS to view the list of
point status tables. 2. Press SELECT to select the highlighted value. Then:
15
DEFAULT SCREEN
CCN LOCAL RESET MENU (SOFTKEYS)
ALARM HISTORY
CONTROL TEST
CONTROL ALGORITHM STATUS
EQUIPMENT CONFIGURATION
ISM (STARTER) CONFIG DATA
EQUIPMENT SERVICE
TIME AND DATE
ATTACH TO NETWORK DEVICE
LOG OUT OF DEVICE
CVC CONFIGURATION
NEXT PREVIOUS SELECT EXIT
SEE FIGURE 16
16
SERVICE TABLE
NEXT PREVIOUS SELECT EXIT
ALARM HISTORY
• CCM Thermistors
CONTROL ALGORITHM STATUS • CCM Pressure Transducers
• Pumps
• Discrete Outputs
List the Control Algorithm Status Tables • Guide Vane Actuator
• CAPACITY (Capacity Control) • Diffuser Actuator
• OVERRIDE (Override Status) • Pumpdown/Lockout
• LL_MAINT (Lead Lag Status) • Terminate Lockout
• ISM_HIST (ISM Alarm History) • Guide Vane Calibration
• LOADSHED Select a Test
• WSMDEFME (Water System Manager Control Status) NEXT PREVIOUS SELECT EXIT
• OCCDEFCM (Time Schedule Status)
Select a Table
NEXT PREVIOUS SELECT EXIT
• NET_OPT
• BRODEF
• OCCEFCS
• HOLIDAYS
• CONSUME
• RUNTIME
Select a Table
NEXT PREVIOUS SELECT EXIT
Select a Parameter
NEXT PREVIOUS SELECT EXIT
Modify a Parameter
INCREASE DECREASE QUIT ENTER (ANALOG VALUES)
17
SERVICE MENU CONTINUED
FROM PREVIOUS PAGE
ISM (STARTER CONFIG DATA)
EQUIPMENT SERVICE
4 4 4 4 (ENTER A 4-DIGIT PASSWORD)
Service Tables:
• OPTIONS Service Tables:
• SETUP1 • ISM (STARTER) CONFIG PASSWORD
• SETUP2 • ISM_CONFIG
• LEADLAG
• RAMP_DEM
• TEMP_CTL
Select a Service Table
NEXT PREVIOUS SELECT EXIT
Select a Service Table Parameter
NEXT PREVIOUS SELECT EXIT
Select a Device
NEXT PREVIOUS SELECT ATTACH
Default Screen
CCN LOCAL RESET MENU
CVC CONFIGURATION
CVC Configuration Table
INCREASE DECREASE ENTER EXIT
• To Modify — CVC CCN Address • To View — CVC Software Version
— English or S.I. Metric Units (last 2 digits of part number
— Password indicate software version)
LEGEND
CCN — Carrier Comfort Network
CVC — Chiller Visual Control
ISM — Integrated Starter Module
PIC II — Product Integrated Control II
Fig. 16 — 19XR Service Menu Structure (cont)
18
For Discrete Points — Press START or STOP to se- 2. Press NEXT or PREVIOUS to highlight the de-
lect the desired state. sired schedule.
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03 — CCN Time Schedule
19
2. There are 5 set points on this screen: BASE DEMAND
b. Press ENABLE to select days in the day-of-week LIMIT, LCW SETPOINT (leaving chilled water set point),
fields. Press DISABLE to eliminate days from the ECW SETPOINT (entering chilled water set point), ICE
period. BUILD SETPOINT, and TOWER FAN HIGH SET-
POINT. Only one of the chilled water set points can be
active at one time. The set point that is active is deter-
mined from the SERVICE menu. See the Service Opera-
tion section, page 43. The ice build (ICE BUILD) func-
tion is also activated and configured from the SERVICE
menu.
7. Press ENTER to register the values and to move
horizontally (left to right) within a period. 3. Press NEXT or PREVIOUS to highlight the desired
set point entry.
20
Table 2 — CVC Display Data
6. Reference Point Names shown in these tables in all capital letters
IMPORTANT: The following notes apply to all Table 2 can be read by CCN and BS software. Of these capitalized names,
examples.
those preceded by a dagger can also be changed (that is, written
1. Only 12 lines of information appear on the CVC screen at any one to) by the CCN, BS, and the CVC. Capitalized Reference Point
Names preceded by two asterisks can be changed only from the
time. Press the NEXT or PREVIOUS softkey to highlight a
CVC. Reference Point Names in lower case type can be viewed
point or to view items below or above the current screen. Press by CCN or BS only by viewing the whole table.
the NEXT softkey twice to page forward; press the 7. Alarms and Alerts: An asterisk in the far right field of a CVC status
screen indicates that the chiller is in an alarm state; an exclama-
PREVIOUS softkey twice to page back. tion point in the far right field of the CVC screen indicates an alert
2. To access the information shown in Examples 9 through 21, enter state. The asterisk (or exclamation point) indicates that the value
your 4-digit password after pressing the SERVICE softkey. If on that line has exceeded (or is approaching) a limit. For more
information on alarms and alerts, see the Alarms and Alerts
no softkeys are pressed for 15 minutes, the CVC automatically section, page 14.
logs off (to prevent unrestricted access to PIC II controls) and re-
LEGEND
verts to the default screen. If this happens, you must reenter your
password to access the tables shown in Examples 9 through 21. CCN — Carrier Comfort Network
3. Terms in the Description column of these tables are listed as they CHW — Chilled Water
appear on the CVC screen. CHWR — Chilled Water Return
CHWS — Chilled Water Supply
4. The CVC may be configured in English or Metric (SI) units using CVC — Chiller Visual Control
the CVC CONFIGURATION screen. See the Service Operation CT — Current Transformer
section, page 43, for instructions on making this change. ECW — Entering Chilled Water
5. The items in the Reference Point Name column do not appear on HGBP — Hot Gas Bypass
the CVC screen. They are data or variable names used in CCN or ISM — Integrated Starter Module
Building Supervisor (BS) software. They are listed in these tables LCW — Leaving Chilled Water
as a convenience to the operator if it is necessary to cross ref- LRA — Locked Rotor Amps
erence CCN/BS documentation or use CCN/BS programs. For more mA — Milliamps
P — Pressure
information, see the 19XR CCN literature. SS — Solid State
T — Temperature
VFD — Variable Frequency Drive
WSM — Water System Manager
21
Table 2 — CVC Display Data (cont)
EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press STATUS ( MAINSTAT will be highlighted).
3. Press SELECT .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations
for the CVC only.
22
Table 2 — CVC Display Data (cont)
EXAMPLE 4 — COMPRESS DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press STATUS .
3. Scroll down to highlight COMPRESS .
4. Press SELECT .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations
for the CVC only.
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations
for the CVC only.
23
Table 2 — CVC Display Data (cont)
EXAMPLE 6 — POWER DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press STATUS .
3. Scroll down to highlight POWER .
4. Press SELECT .
24
Table 2 — CVC Display Data (cont)
EXAMPLE 8 — SET POINT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SETPOINT (Base Demand Limit will be highlighted).
3. Press SELECT .
NOTE: All variables are available for CCN read operation; forcing shall not be supported on set point screens.
25
Table 2 — CVC Display Data (cont)
EXAMPLE 10 — OVERRIDE DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT .
5. Scroll down to highlight OVERRIDE .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
26
Table 2 — CVC Display Data (cont)
EXAMPLE 12 — ISM HIST DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT .
5. Scroll down to highlight ISM HIST .
27
Table 2 — CVC Display Data (cont)
EXAMPLE 14 — NET OPT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION .
4. Press SELECT .
5. Scroll down to highlight NET OPT .
28
Table 2 — CVC Display Data (cont)
EXAMPLE 16 — OPTIONS DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight OPTIONS .
NOTE: No variables are available for CCN read operation; forcing shall not be supported on service screens.
29
Table 2 — CVC Display Data (cont)
EXAMPLE 18 — SETUP2 DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight SETUP2 .
30
Table 2 — CVC Display Data (cont)
EXAMPLE 20 — RAMP_DEM DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight RAMP_DEM .
31
PIC II System Functions The Proportional Band — There are two response modes,
one for temperature response above the control point, the
NOTE: Words not part of paragraph headings and printed other for the response below the control point.
in all capital letters can be viewed on the CVC (e.g., LO-
CAL, CCN, RUNNING, ALARM, etc.). Words printed in The temperature response above the control point is called
both in all capital letters and italics can also be viewed on the PROPORTIONAL INC BAND, and it can slow or quicken
the CVC and are parameters (CONTROL MODE, COOL- guide vane response to chilled water/brine temperatures above
ING SET POINT, TARGET GUIDE VANE POS, etc.) with the DEADBAND. The PROPORTIONAL INC BAND can be
associated values (e.g., modes, temperatures, pressures, per- adjusted from a setting of 2 to 10; the default setting is 6.5.
centages, on, off, enable, disable, etc.). Works printed in all The response below the control point is called the
capital letters and in a box represent softkeys on the CVC PROPORTIONAL DEC BAND, and it can slow or quicken
(e.g., ENTER and EXIT ). See Table 2 for examples of the guide vane response to chilled water temperature below
the deadband plus the control point. The PROPORTIONAL
the type of information that can appear on the CVC screens. DEC BAND can be adjusted on the CVC from a setting of
Figures 12-18 give an overview of CVC operations and menus. 2 to 10. The default setting is 6.0.
CAPACITY CONTROL — The PIC II controls the chiller NOTE: Increasing either of these settings causes the guide
capacity by modulating the inlet guide vanes in response to vanes to respond more slowly than they would at a lower
chilled water temperature changes away from the CON- setting.
TROL POINT. The CONTROL POINT may be changed by
a CCN network device or is determined by the PIC II adding The PROPORTIONAL ECW GAIN can be adjusted on the
any active chilled water reset to the SET POINT. The PIC II CVC display for values of 1, 2, or 3; the default setting is 2.
uses the PROPORTIONAL INC (Increase) BAND, PRO- Increase this setting to increase guide vane response to a change
PORTIONAL DEC (Decrease) BAND, and the PROPOR- in entering chilled water temperature.
TIONAL ECW (Entering Chilled Water) GAIN to determine DEMAND LIMITING — The PIC II responds to the
how fast or slow to respond. CONTROL POINT may be viewed ACTIVE DEMAND LIMIT set point by limiting the opening
or overridden from the MAINSTAT screen. of the guide vanes. It compares the ACTIVE DEMAND LIMIT
ECW CONTROL OPTION — If this option is enabled, the set point to the DEMAND LIMIT SOURCE (either the
PIC II uses the ENTERING CHILLED WATER temperature AVERAGE LINE CURRENT or the MOTOR KW). Depend-
to modulate the vanes instead of the LEAVING CHILLED ing on how the control is configured. DEMAND LIMIT
WATER temperature. The ECW CONTROL OPTION may be SOURCE is on the RAMP_DEM screen. The default source
viewed on the TEMP_CTL screen, which is accessed from is the compressor motor current.
the EQUIPMENT SERVICE screen. CHILLER TIMERS — The PIC II maintains 2 runtime clocks,
CONTROL POINT DEADBAND — This is the tolerance known as COMPRESSOR ONTIME and SERVICE ON-
range on the chilled water/brine temperature control point. TIME. COMPRESSOR ONTIME indicates the total life-
If the water temperature goes outside the CHILLED WATER time compressor run hours. This timer can register up to
DEADBAND, the PIC II opens or closes the guide vanes un- 500,000 hours before the clock turns back to zero. The
til the temperature is within tolerance. The PIC II may be SERVICE ONTIME is a reset table timer that can be used to
configured with a 0.5 to 2 F (0.3 to 1.1 C) deadband. CHILLED indicate the hours since the last service visit or any other
WATER DEADBAND may be viewed or modified on the event. The time can be changed from the CVC to whatever
SETUP1 screen, which is accessed from the EQUIPMENT value is desired. This timer can register up to 32,767 hours
SERVICE table. before it rolls over to zero.
For example, a 1° F (0.6° C) deadband setting controls The chiller also maintains a start-to-start timer and a stop-
the water temperature within ±0.5° F (0.3° C) of the control to-start timer. These timers limit how soon the chiller can be
point. This may cause frequent guide vane movement if the started. START INHIBIT TIMER is displayed on the
chilled water load fluctuates frequently. A value of 1° F MAINSTAT screen. See the Start-Up/Shutdown/Recycle Se-
(0.6° C) is the default setting. quence section, page 44, for more information on this topic.
DIFFUSER CONTROL — On 19XR compressors equipped OCCUPANCY SCHEDULE — The chiller schedule, de-
with a variable discharge diffuser, the PIC II adjusts the dif- scribed in the Time Schedule Operation section (page 19),
fuser actuator position (DIFFUSER ACTUATOR on the COM- determines when the chiller can run. Each schedule consists
PRESS screen) to correspond to the actual guide vane po- of from 1 to 8 occupied or unoccupied time periods, set by
sition (ACTUAL GUIDE VANE POS on the COMPRESS the operator. The chiller can be started and run during an
screen). occupied time period (when OCCUPIED ? is set to YES on
the MAINSTAT display screen). It cannot be started or run
The diffuser control can be enabled or disabled from the during an unoccupied time period (when OCCUPIED ? is
SETUP2 screen. See Table 2, Example 18. In addition, the set to NO on the MAINSTAT display screen). These time
diffuser and guide vane load points may be viewed and modi- periods can be set for each day of the week and for holidays.
fied from this screen. These points must be correct for the The day begins with 0000 hours and ends with 2400 hours.
compressor size. The diffuser opening can be incremented The default setting for OCCUPIED ? is YES, unless an un-
from fully open to completely closed. A 0% setting is fully occupied time period is in effect.
open; a 100% setting is completely closed. To obtain the proper
settings for Diffuser Control, contact a Carrier Engineering These schedules can be set up to follow a building’s oc-
representative. cupancy schedule, or the chiller can be set so to run 100%
of the time, if the operator wishes. The schedules also can be
PROPORTIONAL BANDS AND GAIN — Proportional band bypassed by forcing the CHILLER START/STOP parameter
is the rate at which the guide vane position is corrected in on the MAINSTAT screen to START. For more information
proportion to how far the chilled water/brine temperature is on forced starts, see Local Start-Up, page 44.
from the control point. Proportional gain determines how The schedules also can be overridden to keep the chiller
quickly the guide vanes react to how quickly the tempera- in an occupied state for up to 4 hours, on a one time basis.
ture is moving from the CONTROL POINT. The propor- See the Time Schedule Operation section, page 19.
tional bands and gain may be viewed or modified from the
SETUP2 screen, which is accessed from the EQUIPMENT
SERVICE table.
32
Figure 17 shows a schedule for a typical office building • voltage imbalance
with a 3-hour, off-peak, cool-down period from midnight • current imbalance
to 3 a.m., following a weekend shutdown. Holiday periods
are in an unoccupied state 24 hours per day. The building • excessive motor acceleration time
operates Monday through Friday, 7:00 a.m. to 6:00 p.m., and • excessive starter transition time
Saturdays from 6:00 a.m. to 1:00 p.m. This schedule also • lack of motor current signal
includes the Monday midnight to 3:00 a.m. weekend cool- • excessive motor amps
down schedule.
• excessive compressor surge
NOTE: This schedule is for illustration only and is not in-
tended to be a recommended schedule for chiller operation. • temperature and transducer faults
Whenever the chiller is in the LOCAL mode, it uses *Superheat is the difference between saturation temperature
Occupancy Schedule 01 (OCCPC01S). When the chiller is and sensible temperature. The high discharge temperature
in the ICE BUILD mode, it uses Occupancy Schedule 02 safety measures only sensible temperature.
(OCCPC02S). When the chiller is in CCN mode, it uses Starter faults or optional protective devices within the starter
Occupancy Schedule 03 (OCCPC03S). can shut down the chiller. The protective devices you
The CCN SCHEDULE NUMBER is configured on the have for your application depend on what options were
NET_OPT display screen, accessed from the EQUIPMENT purchased.
CONFIGURATION table. See Table 2, Example 14.
SCHEDULE NUMBER can be changed to any value from
03 to 99. If this number is changed on the NET_OPT screen,
the operator must go to the ATTACH TO NETWORK DE- If compressor motor overload occurs, check the motor
VICE screen to upload the new number into the SCHED- for grounded or open phases before attempting a
ULE screen. See Fig. 16. restart.
Safety Controls — The PIC II monitors all safety con- If the PIC II control initiates a safety shutdown, it dis-
trol inputs and, if required, shuts down the chiller or limits plays the reason for the shutdown (the fault) on the CVC
the guide vanes to protect the chiller from possible damage display screen along with a primary and secondary message,
from any of the following conditions: energizes an alarm relay in the starter, and blinks the alarm
• high bearing temperature light on the control panel. The alarm is stored in memory
• high motor winding temperature and can be viewed on the ALARM HISTORY and
ISM_HIST screens on the CVC, along with a message for
• high discharge temperature troubleshooting. If the safety shutdown was also initiated by
• low discharge superheat* a fault detected in the motor starter, the conditions at the
• low oil pressure time of the fault will be stored in ISM_HIST.
• low cooler refrigerant temperature/pressure To give more precise information or warnings on the chill-
er’s operating condition, the operator can define alert limits
• condenser high pressure or low pressure on various monitored inputs. Safety contact and alert limits
• inadequate water/brine cooler and condenser flow are defined in Table 3. Alarm and alert messages are listed
• high, low, or loss of voltage in the Troubleshooting Guide section, page 69.
• ground fault
33
Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETER LIMIT APPLICABLE COMMENTS
TEMPERATURE SENSORS OUT OF –40 to 245 F (–40 to 118.3 C) Must be outside range for 2 seconds
RANGE
PRESSURE TRANSDUCERS OUT OF 0.06 to 0.98 Voltage Ratio Must be outside range for 3 seconds.
RANGE Ratio = Input Voltage ÷ Voltage Reference
COMPRESSOR DISCHARGE .220 F (104.4 C) Preset, alert setting configurable
TEMPERATURE
MOTOR WINDING TEMPERATURE .220 F (104.4 C) Preset, alert setting configurable
BEARING TEMPERATURE .185 F (85 C) Preset, alert setting configurable
EVAPORATOR REFRIGERANT ,33 F (for water chilling) (0.6° C) Preset, configure chilled medium for water
TEMPERATURE (SETUP1 table)
,EVAP REFRIG TRIPPOINT (set point Configure chilled medium for brine (SETUP1
adjustable from 0 to 40 F [–18 to 4 C] for table). Adjust EVAP REFRIG TRIPPOINT for
brine chilling) proper cutout
TRANSDUCER VOLTAGE ,4.5 vdc . 5.5 vdc Preset
CONDENSER PRESSURE — SWITCH .263 ± 7 psig (1813 ± 48 kPa), reset at Preset
180 ± 10 (1241 ± 69 kPa)
— CONTROL 165 psig (1138 kPa) Preset
OIL PRESSURE Cutout ,15 psid (103 kPad) Preset
Alert ,18 psid (124 kPad)
LINE VOLTAGE — HIGH .110% for one minute Preset, based on transformed line voltage to
— LOW ,90% for one minute or <85% for 3 seconds ISM. Also monitored at CVC and CCM power
input.
— SINGLE-CYCLE ,50% for one cycle
COMPRESSOR MOTOR LOAD .110% for 30 seconds Preset
,15% with compressor running Preset
.15% with compressor off Preset
STARTER ACCELERATION TIME .45 seconds For chillers with reduced voltage mechanical
(Determined by inrush current and solid-state starters
going below 100% compressor .10 seconds For chillers with full voltage starters
motor load) (Configured on ISM_CONFIG table)
STARTER TRANSITION .75 seconds Reduced voltage starters only
CONDENSER FREEZE PROTECTION Energizes condenser pump relay if condenser CONDENSER FREEZE POINT configured in
refrigerant temperature or condenser entering SETUP1 table with a default setting of
water temperature is below the configured 34 F (1 C).
condenser freeze point temperature. Deener-
gizes when the temperature is 5 F (3 C)
above condenser freeze point temperature.
DISCHARGE SUPERHEAT Minimum value calculated based on Calculated minimum required superheat and
operating conditions and then compared actual superheat are shown on OVERRIDE
to actual superheat. screen.
VARIABLE DIFFUSER OPERATION Detects discharge pulses caused by incorrect Preset, no calibration needed.
diffuser position.
34
Shunt Trip (Option) — The function of the shunt trip If kilowatts is selected for the DEMAND LIMIT SOURCE,
option on the PIC II is to act as a safety trip. The shunt trip the MOTOR RATED KILOWATTS must be entered (infor-
is wired from an output on the ISM to a shunt trip equipped mation found on the chiller Requisition form).
motor circuit breaker. If the PIC II tries to shut down the The TEMP PULLDOWN DEG/MIN may be viewed or modi-
compressor using a normal shutdown procedure but is un- fied on the TEMP_CTL screen which is accessed from the
successful for 30 seconds, the shunt trip output is energized EQUIPMENT SERVICE screen. PULLDOWN RAMP TYPE,
and causes the circuit breaker to trip off. If ground fault pro- DEMAND LIMIT SOURCE, and MOTOR LOAD RAMP
tection has been applied to the starter, the ground fault trip %/MIN may be viewed or modified on the RAMP_DEM screen.
also energizes the shunt trip to trip the circuit breaker. Pro-
tective devices in the starter can also energize the shunt trip. Capacity Override (Table 4) — Capacity overrides
The shunt trip feature can be tested using the Control Test can prevent some safety shutdowns caused by exceeding the
feature. motor amperage limit, refrigerant low temperature safety limit,
motor high temperature safety limit, and condenser high pres-
Default Screen Freeze — When the chiller is in an sure limit. In all cases there are 2 stages of compressor vane
alarm state, the default CVC display ‘‘freezes,’’ that is, it control.
stops updating. The first line of the CVC default screen dis-
plays a primary alarm message; the second line displays a 1. The vanes are prevented from opening further, and
secondary alarm message. the status line on the CVC indicates the reason for the
override.
The CVC default screen freezes to enable the operator to
see the conditions of the chiller at the time of the alarm. If 2. The vanes are closed until the condition decreases to be-
the value in alarm is one normally displayed on the default low the first step set point. Then the vanes are released to
screen, it flashes between normal and reverse video. The CVC normal capacity control.
default screen remains frozen until the condition that caused Whenever the motor current demand limit set point
the alarm is remedied by the operator. (ACTIVE DEMAND LIMIT) is reached, it activates a capac-
Knowledge of the operating state of the chiller at the time ity override, again, with a 2-step process. Exceeding 110%
an alarm occurs is useful when troubleshooting. Additional of the rated load amps for more than 30 seconds will initiate
chiller information can be viewed on the status screens and a safety shutdown.
the ISM_HIST screen. Troubleshooting information is re- The compressor high lift (surge prevention) set point will
corded in the ALARM HISTORY table, which can be ac- cause a capacity override as well. When the surge preven-
cessed from the SERVICE menu. tion set point is reached, the controller normally will only
To determine what caused the alarm, the operator should prevent the guide vanes from opening. If so equipped, the
read both the primary and secondary default screen mes- hot gas bypass valve will open instead of holding the vanes.
sages, as well as the alarm history. The primary message See the Surge Prevention Algorithm section, page 38.
indicates the most recent alarm condition. The secondary mes-
sage gives more detail on the alarm condition. Since there High Discharge Temperature Control — If the dis-
may be more than one alarm condition, another alarm mes- charge temperature increases above 160 F (71.1 C), the guide
sage may appear after the first condition is cleared. Check vanes are proportionally opened to increase gas flow through
the ALARM HISTORY screen for additional help in deter- the compressor. If the leaving chilled water temperature is
mining the reasons for the alarms. Once all existing alarms then brought 5° F (2.8° C) below the control set point tem-
perature, the PIC II will bring the chiller into the recycle
are cleared (by pressing the RESET softkey), the default mode.
CVC display returns to normal operation.
Oil Sump Temperature Control — The oil sump tem-
Ramp Loading — The ramp loading control slows down perature control is regulated by the PIC II, which uses the
the rate at which the compressor loads up. This control can oil heater relay when the chiller is shut down.
prevent the compressor from loading up during the short pe-
riod of time when the chiller is started and the chilled water As part of the pre-start checks executed by the controls,
loop has to be brought down to CONTROL POINT. This helps the oil sump temperature (OIL SUMP TEMP) is compared
reduce electrical demand charges by slowly bringing the chilled to the cooler refrigerant temperature (EVAPORATOR
water to CONTROL POINT. The total power draw during REFRIG TEMP). If the difference between these 2 tempera-
this period remains almost unchanged. tures is 50 F (27.8 C) or less, the start-up will be delayed
until the oil temperature is 50 F (27.8 C) or more. Once this
There are two methods of ramp loading with the PIC II. temperature is confirmed, the start-up continues.
Ramp loading can be based on chilled water temperature or
on motor load. Either method is selected from the The oil heater relay is energized whenever the chiller com-
RAMP__DEM screen. pressor is off and the oil sump temperature is less than
140 F (60.0 C) or the oil sump temperature is less than
1. Temperature ramp loading (TEMP PULLDOWN DEG/ the cooler refrigerant temperature plus 53° F (11.7° C). The
MIN) limits the degrees per minute rate at which either oil heater is turned off when the oil sump temperature is
leaving chilled water or entering chilled water tempera- either
ture decreases. This rate is configured by the operator on
the TEMP_CTL screen. The lowest temperature ramp rate • more than 152 F (66.7 C), or
will also be used if chiller power has been off for 3 hours • more than 142 F (61.1 C) and more than the cooler
or more (even if the motor ramp load is selected as the refrigerant temperature plus 55° F (12.8° C).
ramp loading method. The oil heater is always off during start-up or when the
2. Motor load ramp loading (LOAD PULLDOWN) limits the compressor is running.
degrees per minute rate at which the compressor motor The oil pump is also energized during the time the oil
current or compressor motor load increases. The LOAD is being heated (for 60 seconds at the end of every
PULLDOWN rate is configured by the operator on the 30 minutes).
RAMP_DEM screen in amps or kilowatts.
35
Table 4 — Capacity Overrides
SECOND STAGE OVERRIDE
FIRST STAGE SET POINT SET POINT TERMINATION
OVERRIDE
CAPACITY CONTROL View/Modify Default Configurable Value Value
on CVC Screen Value Range
HIGH CONDENSER 125 psig 90 to 165 psig .Override ,Override
PRESSURE SETUP1 (862 kPa) (620 to 1138 kPa) Set Point Set Point
+ 2.4 psid (16.5 kPad)
HIGH MOTOR .200 F 150 to 200 F .Override ,Override
SETUP1 Set Point
TEMPERATURE (93.3 C) (66 to 93 C) +10° F (6° C) Set Point
LOW REFRIGERANT
TEMPERATURE <Trippoint .Trippoint
(Refrigerant SETUP1 3° F (1.6° C) 2° to 5° F + Override + Override
Override Delta (1° to 3° C) DT –1° F (0.56° C) DT +2° F (1.2° C)
Temperature)
Min: T1 — 1.5° F 0.5° to 15° F
(0.8° C) (0.3° to 8.3° C)
HIGH COMPRESSOR P1 — 50 psid 30 to 170 psid Within Lift Limits
(345 kPad) (207 to1172 kPad)
LIFT OPTIONS Max: T2 — 10° F 0.5° to 15° F None Plus Surge/HGBP
(Surge Prevention) (5.6° C) (0.3° to 8.3° C) Deadband Setting
P2 — 85 psid 50 to 170 psid
(586 kPad) (348 to 1172 kPad)
MANUAL GUIDE VANE CAPACITY Automatic 0 to 100% None Release of
TARGET Manual Control
MOTOR LOAD — MAINSTAT 100% 40 to 100% >5% of 2% Lower
ACTIVE DEMAND LIMIT Set Point Than Set Point
LOW DISCHARGE Calculated Minimum 2° F (1.1° C) 1° F (0.56° C)
SUPERHEAT OVERRIDE Superheat None Below Calculated Above Calculated
for Conditions Minimum Superheat Minimum Superheat
Oil Cooler — The oil must be cooled when the com- factory-installed jumper. (Wire multiple inputs in series.) The
pressor is running. This is accomplished through a small, opening of any contact will result in a safety shutdown and
plate-type heat exchanger (also called the oil cooler) located a display on the CVC. Refer to the certified drawings for
behind the oil pump. The heat exchanger uses liquid con- safety contact ratings.
denser refrigerant as the cooling liquid. Refrigerant thermo- Analog temperature sensors may also be added to the mod-
static expansion valves (TXVs) regulate refrigerant flow to ule (SPARE TEMP #1 and #2). The analog temperature sen-
control the oil temperature entering the bearings. The bulbs sors may be configured to cause an alert or alarm on the CCN
for the expansion valves are strapped to the oil supply line network. The alert will not shut the chiller down. Config-
leaving the heat exchanger, and the valves are set to main- uring for alarm state will cause the chiller to shut down.
tain 110 F (43 C).
NOTE: The TXVs are not adjustable. The oil sump temper- Spare Safety Alarm Contacts — One set of alarm
ature may be at a lower temperature during compressor contacts is provided in the starter. The contact ratings are
operations. provided in the certified drawings. The contacts are located
on terminal strip JP, terminals 15 and 16.
Remote Start/Stop Controls — A remote device, such
as a timeclock that uses a set of contacts, may be used to Refrigerant Leak Detector — An input is available
start and stop the chiller. However, the device should not be on the CCM module [terminal 15-5 (−) and J5-6 (+)] for a
programmed to start and stop the chiller in excess of 2 or refrigerant leak detector. Enabling REFRIGERANT LEAK
3 times every 12 hours. If more than 8 starts in 12 hours (the OPTION (OPTIONS screen) will allow the PIC II controls
STARTS IN 12 HOURS parameter on the MAINSTAT screen) to go into an alarm state at a user configured level
occur, an excessive starts alarm displays, preventing the chiller (REFRIGERANT LEAK ALARM mA). The input is con-
figured for 4 to 20 mA by setting the DIP switch 1 on SW2
from starting. The operator must press the RESET softkey at the ON position, or configured for 0 to 5 vdc by setting
on the CVC to override the starts counter and start the chiller. switch 1 at the OFF position. The output of the refrigerant
If the chiller records 12 starts (excluding recycle starts) in a leak detector is displayed as REFRIGERANT LEAK SEN-
sliding 12-hour period, it can be restarted only by pressing SOR on the MAINSTAT screen. For a 0 to 5 vcd input, 0 vdc
the RESET softkey followed by the LOCAL or CCN input represents 4 mA displayed and 5 vdc input represents
20 mA displayed.
softkey. This ensures that, if the automatic system is mal-
functioning, the chiller will not repeatedly cycle on and off. Condenser Pump Control — The chiller will moni-
If the automatic restart after a power failure option (AUTO tor the condenser pressure (CONDENSER PRESSURE) and
RESTART OPTION on the OPTIONS screen) is not acti- may turn on the condenser pump if the condenser pressure
vated when a power failure occurs, and if the remote contact becomes too high while the compressor is shut down. The
is closed, the chiller will indicate an alarm because of the condenser pressure override (COND PRESS OVERRIDE)
loss of voltage. parameter is used to determine this pressure point. COND
The contacts for remote start are wired into the starter at PRESS OVERRIDE is found in the SETUP1 display screen,
terminal strip J2, terminals 5 and 6 on the ISM. See the cer- which is accessed from the EQUIPMENT SERVICE table.
tified drawings for further details on contact ratings. The con- The default value is 125 psig (862 kPa).
tacts must have 24 vac rating. If the CONDENSER PRESSURE is greater than or equal
to the COND PRESS OVERRIDE, and the entering con-
Spare Safety Inputs — Normally closed (NC) dis- denser water temperature (ENTERING CONDENSER
crete inputs for additional field-supplied safeties may be wired WATER) is less than 115 F (46 C), the condenser pump will
to the spare protective limits input channel in place of the
36
energize to try to decrease the pressure. The pump will
turn off when the condenser pressure is 3.5 psi (24.1 kPa)
less than the pressure override or when the condenser re-
frigerant temperature (CONDENSER REFRIG TEMP) is within The tower fan relay control is not a substitute for a
3° F (1.7° C) of the entering condenser water temperature condenser water temperature control. When used with
(ENTERING CONDENSER WATER). a water temperature control system, the tower fan relay
control can be used to help prevent low condenser
Condenser Freeze Prevention — This control water temperatures.
algorithm helps prevent condenser tube freeze-up by ener-
gizing the condenser pump relay. The PIC II controls the Auto. Restart After Power Failure — This option
pump and, by starting it, helps to prevent the water in the may be enabled or disabled and may be viewed or modified
condenser from freezing. The PIC II can perform this func- on the OPTIONS screen, which is accessed from the EQUIP-
tion whenever the chiller is not running except when it is MENT CONFIGURATION table. If the AUTO. RESTART
either actively in pumpdown or in pumpdown/lockout with option is enabled, the chiller will start up automatically after
the freeze prevention disabled. a power failure has occurred (after a single cycle dropout;
When the CONDENSER REFRIG TEMP is less than low, high, or loss of voltage; and the power is within ± 10%
or equal to the CONDENSER FREEZE POINT, the of normal). The 15- and 3-minute inhibit timers are ignored
CONDENSER WATER PUMP is energized until the during this type of start-up.
CONDENSER REFRIG TEMP is greater than the CON- When power is restored after the power failure and if the
DENSER FREEZE POINT plus 5° F (2.7° C) and the compressor had been running, the oil pump will energize for
ENTERING CONDENSER WATER TEMPERATURE is less one minute before energizing the cooler pump. AUTO.
than or equal to the CONDENSER FREEZE POINT. An alarm RESTART will then continue like a normal start-up.
is generated if the chiller is in PUMPDOWN mode and the
pump is energized. An alert is generated if the chiller is not If power to the CVC module has been off for more than
in PUMPDOWN mode and the pump is energized. If the 3 hours or the timeclock has been set for the first time, start
chiller is in RECYCLE SHUTDOWN mode, the mode will the compressor with the slowest temperature-based ramp load
transition to a non-recycle shutdown. rate possible in order to minimize oil foaming.
The oil pump is energized occasionally during the time
Tower Fan Relay Low and High — Low condenser the oil is being brought up to proper temperature in order to
water temperature can cause the chiller to shut down when eliminate refrigerant that has migrated to the oil sump dur-
refrigerant temperature is low. The tower fan relays, located ing the power failure. The pump turns on for 60 seconds at
in the starter, are controlled by the PIC II to energize and the end of every 30-minute period until the chiller is started.
deenergize as the pressure differential between cooler and
condenser vessels changes. This prevents low condenser wa- Water/Brine Reset — Three types of chilled water or
ter temperature and maximizes chiller efficiency. The tower brine reset are available and can be viewed or modified on
fan relay can only accomplish this if the relay has been added the TEMP_CTL screen, which is accessed from the EQUIP-
to the cooling tower temperature controller. MENT SERVICE table.
The tower fan relay low is turned on whenever the con- The CVC default screen indicates when the chilled water
denser water pump is running, flow is verified, and the dif- reset is active. RESET TEMPERATURE on the MAIN-
ference between cooler and condenser pressure is more than STAT screen indicates the amount of reset. The CONTROL
30 psid (207 kPad) for entering condenser water tempera- POINT will be determined by adding the RESET
ture greater than 65 F (18.3 C). TEMPERATURE to the SETPOINT.
The tower fan relay low is turned off when the condenser To activate a reset type, access the TEMP_CTL screen and
pump is off, flow is stopped, or the cooler refrigerant tem- input all configuration information for that reset type. Then,
perature is less than the override temperature for ENTER- input the reset type number (1, 2, or 3) in the SELECT/
ING CONDENSER WATER temperature less than 62 F ENABLE RESET TYPE input line.
(16.7 C), or the differential pressure is less than 25 psid
(172.4 kPad) for entering condenser water less than RESET TYPE 1: 4 to 20 mA (0 to 5 vdc) TEMPERATURE
80 F (27 C). RESET — Reset Type 1 is an automatic chilled water tem-
perature reset based on a remote temperature sensor input
The tower fan relay high is turned on whenever the con- configured for either an externally powered 4 to 20 mA or a
denser water pump is running, flow is verified and the dif- 0 to 5 vcd signal. Reset Type 1 permits up to ±30 F (±16 C)
ference between cooler and condenser pressure is more than of automatic reset to the chilled water set point.
35 psid (241.3 kPa) for entering condenser water tempera-
ture greater than the TOWER FAN HIGH SETPOINT (SET- The auto, chilled water reset is hardwired to terminals
POINT menu, default 75 F [23.9 C]). J5-3 (−) and J5-4 (+) on the CCM. Switch setting number 2
on SW2 will determine the type of input signal. With the
The tower fan relay high is turned off when the condenser switch set at the ON position the input is configured for an
pump is off, flow is stopped, or the cooler refrigerant tem- externally powered 4 to 20 mA signal. With the switch in the
perature is less than the override temperature and ENTER- OFF position the input is configured for an external
ING CONDENSER WATER is less than 70 F (21.1 C), or the 0 to 5 vdc signal.
difference between cooler and condenser pressure is less than
28 Psid (193 kPa), or ENTERING CONDENSER WATER tem- RESET TYPE 2: REMOTE TEMPERATURE RESET — Re-
perature is less than TOWER FAN HIGH SETPOINT minus set Type 2 is an automatic chilled water temperature reset
3 F (−16.1 C). based on a remote temperature sensor input signal. Reset Type
2 permits ± 30° F (± 16° C) of automatic reset to the set
The TOWER FAN RELAY LOW and HIGH parameter is point based on a temperature sensor wired to the CCM mod-
accessed from the STARTUP screen. ule (see wiring diagrams or certified drawings). The tem-
IMPORTANT: A field-supplied water temperature con- perature sensor must be wired to terminal J4-13 and J4-14.
trol system for condenser water should be installed. To configure Reset Type 2, enter the temperature of
The system should maintain the leaving condenser the remote sensor at the point where no temperature reset
water temperature at a temperature that is 20° F will occur (REMOTE TEMP [NO RESET]). Next, enter the
(11° C) above the leaving chilled water temperature. temperature at which the full amount of reset will occur
37
(REMOTE TEMP [FULL RESET]). Then, enter the maxi- PREVENTION is on, the point must pass through the dead-
mum amount of reset required to operate the chiller band region before the HOT GAS BYPASS/SURGE PRE-
(DEGREES RESET). Reset Type 2 can now be activated. VENTION is turned off. Information on modifying the de-
fault set points of the minimum and full load points may be
RESET TYPE 3 — Reset Type 3 is an automatic chilled wa- found in the Input Service Configurations section, page 53.
ter temperature reset based on cooler temperature differ-
ence. Reset Type 3 adds ± 30° F (± 16° C) based on the Corrective action can be taken by making one of 2 choices.
temperature difference between the entering and leaving chilled If a hot gas bypass line is present and the hot gas option
water temperature. is selected on the OPTIONS table (SURGE LIMIT/HGBP
To configure Reset Type 3, enter the chilled water tem- OPTION is set to 1), the hot gas bypass valve can be ener-
perature difference (the difference between entering and gized. If the hot gas bypass option is not selected (SURGE
leaving chilled water) at which no temperature reset occurs LIMIT/HGBP OPTION is set to 0), hold the guide vanes.
(CHW DELTA T [NO RESET]). This chilled water temper- See Table 4, Capacity Overrides. Both of these corrective
ature difference is usually the full design load temper- actions try to reduce the lift experienced by the compressor
ature difference. Next, enter the difference in chilled water and help prevent a surge condition.
temperature at which the full amount of reset occurs (CHW
DELTA T [FULL RESET]). Finally, enter the amount of re-
set (DEGREES RESET). Reset Type 3 can now be activated.
Demand Limit Control Option — The demand limit
control option (20 mA DEMAND LIMIT OPT) is externally
controlled by a 4 to 20 mA or 0 to 5 vdc signal from an
energy management system (EMS). The option is set up on
the RAMP_DEM screen. When enabled, 4 mA is the 100%
demand set point with an operator-configured minimum de-
mand at a 20 mA set point (DEMAND LIMIT AT 20 mA).
The auto. demand limit is hardwired to terminals J5-5 (−)
and J5-6 (+) on the CCM. Switch setting number 1 on SW2
will determine the type of input signal. With the switch set
at the ON position the input is configured for an externally
powered 4 to 20 mA signal. With the switch in the OFF
position the input is configured for an external 0 to 5 vdc
signal.
LEGEND
Surge Prevention Algorithm — This is an operator-
ECW — Entering Chilled Water
configurable feature that can determine if lift conditions are HGBP — Hot Gas Bypass
too high for the compressor and then take corrective action. LCW — Leaving Chilled Water
Lift is defined as the difference between the pressure at the DP = (Condenser Psi) − (Cooler Psi)
impeller eye and at the impeller discharge. The maximum DT = (ECW) − (LCW)
lift a particular impeller wheel can perform varies with the Fig. 19 — 19XR Hot Gas Bypass/Surge
gas flow across the impeller and the size of the wheel. Prevention with Default English Settings
A surge condition occurs when the lift becomes so
high the gas flow across the impeller reverses. This condi-
tion can eventually cause chiller damage. The surge preven-
tion algorithm notifies the operator that chiller operating
conditions are marginal and to take action to help prevent
chiller damage such as lowering entering condenser water
temperature.
The surge prevention algorithm first determines if cor-
rective action is necessary. The algorithm checks 2 sets of
operator-configured data points, the minimum load points (MIN.
LOAD POINT [T1/P1]) and the full load points (FULL
LOAD POINT [T2/P2]). These points have default settings
as defined on the OPTIONS screen or on Table 4.
The surge prevention algorithm function and settings are
graphically displayed in Fig. 19 and 20. The two sets of load
points on the graph (default settings are shown) describe a
line the algorithm uses to determine the maximum lift of the
compressor. When the actual differential pressure between
the cooler and condenser and the temperature difference be-
tween the entering and leaving chilled water are above the
line on the graph (as defined by the minimum and full load
points), the algorithm goes into a corrective action mode. If
the actual values are below the line and outside of the dead-
band region, the algorithm takes no action. When the point LEGEND
defined by the ACTIVE DELTA P and ACTIVE DELTA T, ECW — Entering Chilled Water
moves from the region where the HOT GAS BYPASS/ HGBP — Hot Gas Bypass
SURGE PREVENTION is off, the point must pass through LCW — Leaving Chilled Water
the deadband region to the line determined by the config- DP = (Condenser kPa) − (Cooler kPa)
ured valves before the HOT GAS BYPASS/SURGE DT = (ECW) − (LCW)
PREVENTION will be turned on. As the point moves from Fig. 20 — 19XR Hot Gas Bypass/Surge
the region where the HOT GAS BYPASS/SURGE Prevention with Default Metric Settings
38
Surge Protection — The PIC II monitors surge, which If the entering chilled water control option (ECW CON-
is a fluctuation in compressor motor amperage. Each time TROL OPTION) is enabled (configured in TEMP_CTL screen)
the fluctuation exceeds an operator-specified limit (SURGE and a common point sensor is desired (COMMON SENSOR
DELTA % AMPS), the PIC II counts the surge. If more than OPTION in LEADLAG screen selected as 1) then the sensor
5 surges occur within an operator-specified time (SURGE is wired in Spare Temp #2 position on the CCM.
TIME PERIOD), the PIC II initiates a surge protection shut- When installing chillers in series, a common point sensor
down of the chiller. should be used. If a common point sensor is not used, the
The surge limit can be adjusted from the OPTIONS screen. leaving chilled water sensor of the upstream chiller must be
moved into the leaving chilled water pipe of the downstream
Scroll down to the SURGE DELTA % AMPS parameter, and chiller.
use the INCREASE or DECREASE softkey to adjust the
If return chilled water control is required on chillers piped
percent of surge. The default setting is 10% amps. in series, the common point return chilled water sensor should
The surge time period can also be adjusted from the be installed. If this sensor is not installed, the return chilled
OPTIONS screen. Scroll to the SURGE TIME PERIOD water sensor of the downstream chiller must be relocated to
parameter, and use the INCREASE or DECREASE soft- the return chilled water pipe of the upstream chiller.
key to adjust the amount of time. The default setting is To properly control the common supply point temperature
8 minutes. sensor when chillers are piped in parallel, the water flow through
the shutdown chillers must be isolated so no water bypass
Access the display screen (COMPRESS) to monitor the around the operating chiller occurs. The common point sen-
surge count (SURGE PROTECTION COUNTS). sor option must not be used if water bypass around the
Lead/Lag Control — The lead/lag control system operating chiller is occurring.
automatically starts and stops a lag or second chiller in a CHILLER COMMUNICATION WIRING — Refer to the
2-chiller water system. A third chiller can be added to the chiller’s Installation Instructions, Carrier Comfort Network
lead/lag system as a standby chiller to start up in case Interface section for information on chiller communication
the lead or lag chiller in the system has shut down during wiring.
an alarm condition and additional cooling is required. LEAD/LAG OPERATION — The PIC II not only has the
Refer to Fig. 15 and 16 for menu, table, and screen selection ability to operate 2 chillers in lead/lag, but it can also start
information. a designated standby chiller when either the lead or lag chiller
NOTE: The lead/lag function can be configured on the LEAD- is faulted and capacity requirements are not met. The lead/
LAG screen, which is accessed from the SERVICE menu lag option only operates when the chillers are in CCN mode.
and EQUIPMENT SERVICE table. See Table 2, If any other chiller configured for lead/lag is set to the
Example 19. Lead/lag status during chiller operation can be LOCAL or OFF modes, it will be unavailable for lead/lag
viewed on the LL_MAINT display screen, which is ac- operation.
cessed from the SERVICE menu and CONTROL ALGO-
RITHM STATUS table. See Table 2, Example 11. Lead/Lag Chiller Configuration and Operation
• A chiller is designated the lead chiller when its LEAD/
Lead/Lag System Requirements: LAG CONFIGURATION value on the LEADLAG screen
• all chillers in the system must have software capable of is set to ‘‘1.’’
performing the lead/lag function • A chiller is designated the lag chiller when its LEAD/LAG
• water pumps MUST be energized from the PIC II controls CONFIGURATION value is set to ‘‘2.’’
• water flows should be constant
• the CCN time schedules for all chillers must be identical • A chiller is designated as a standby chiller when its LEAD/
LAG CONFIGURATION value is set to ‘‘3.’’
Operation Features: • A value of ‘‘0’’ disables the lead/lag designation of a chiller.
• 2 chiller lead/lag
• addition of a third chiller for backup To configure the LAG ADDRESS value on the LEAD-
• manual rotation of lead chiller LAG screen, always enter the address of the other chiller on
• load balancing if configured the system. For example, if you are configuring chiller A,
• staggered restart of the chillers after a power failure enter the address for chiller B as the lag address. If you are
• chillers may be piped in parallel or in series chilled water configuring chiller B, enter the address for chiller A as the
flow lag address. This makes it easier to rotate the lead and lag
chillers.
COMMON POINT SENSOR INSTALLATION — Lead/ If the address assignments in the LAG ADDRESS and
lag operation does not require a common chilled water point STANDBY ADDRESS parameters conflict, the lead/lag func-
sensor. Common point sensors (Spare Temp #1 and #2) can tion is disabled and an alert (!) message displays. For
be added to the CCM module, if desired. Spare Temp #1 and example, if the LAG ADDRESS matches the lead chiller’s
#2 are wired to plug J4 terminals 25-26 and 27-28 (J4 lower, address, the lead/lag will be disabled and an alert (!)
respectively). message displayed. The lead/lag maintenance screen
NOTE: If the common point sensor option is chosen on a (LL_MAINT) displays the message ‘INVALID CONFIG’ in
chilled water system, each chiller should have its own com- the LEAD/LAG CONFIGURATION and CURRENT MODE
mon point sensor installed. Each chiller uses its own com- fields.
mon point sensor for control when that chiller is designated The lead chiller responds to normal start/stop controls such
as the lead chiller. The PIC II cannot read the value of com- as the occupancy schedule, a forced start or stop, and remote
mon point sensors installed on the other chillers in the chilled start contact inputs. After completing start-up and ramp load-
water system. ing, the PIC II evaluates the need for additional capacity. If
If leaving chilled water control (ECW CONTROL OP- additional capacity is needed, the PIC II initiates the start-up
TION is set to 0 [DSABLE] TEMP_CTL screen) and a com- of the chiller configured at the LAG ADDRESS. If the lag
mon point sensor is desired (COMMON SENSOR OPTION chiller is faulted (in alarm) or is in the OFF or LOCAL modes,
in LEADLAG screen selected as 1) then the sensor is wired the chiller at the STANDBY ADDRESS (if configured) is
in Spare Temp #1 position on the CCM. requested to start. After the second chiller is started and is
39
running, the lead chiller monitors conditions and eval- start. If the lag chiller fails to start, the standby chiller, if
uates whether the capacity has been reduced enough for the configured is started.
lead chiller to sustain the system alone. If the capacity is Lag Chiller Shutdown Requirements — The following con-
reduced enough for the lead chiller to sustain the CONTROL ditions must be met in order for the lag chiller to be stopped.
POINT temperatures alone, then the operating lag chiller is
stopped. 1. Lead chiller compressor motor average line current or load
value (MOTOR PERCENT KILOWATTS on the MAIN-
If the lead chiller is stopped in CCN mode for any reason STAT screen) is less than the lead chiller percent
other than an alarm (*) condition, the lag and standby chill- capacity.
ers are also stopped. If the configured lead chiller stops for
an alarm condition, the configured lag chiller takes the lead NOTE: Lead chiller percent capacity = 115 – LAG PER-
chiller’s place as the lead chiller, and the standby chiller serves CENT CAPACITY. The LAG PERCENT CAPACITY
as the lag chiller. parameter is on the LEADLAG screen, which is accessed
from the EQUIPMENT SERVICE table on the SERV-
If the configured lead chiller does not complete the start-up ICE menu.
before the PRESTART FAULT TIMER (a user-configured
value) elapses, then the lag chiller starts and the lead chiller 2. The lead chiller chilled water temperature is less than
shuts down. The lead chiller then monitors the start request the CONTROL POINT temperature (see the MAINSTAT
from the acting lead chiller. The PRESTART FAULT TIMER screen) plus 1⁄2 the CHILLED WATER DEADBAND tem-
is initiated at the time of a start request. The PRESTART FAULT perature (see the SETUP1 screen).
TIMER provides a timeout if there is a prestart alert condi- 3. The configured LAG STOP TIME entry has elapsed. The
tion that prevents the chiller from starting in a timely man- LAG STOP TIMER starts when the lead chiller chilled
ner. The PRESTART FAULT TIMER parameter is on the LEAD- water temperature is less than the chilled water
LAG screen, which is accessed from the EQUIPMENT SERV- CONTROL POINT plus 1/2 of the CHILLED WATER
ICE table of the SERVICE menu. DEADBAND and the lead chiller compressor motor load
If the lag chiller does not achieve start-up before the (MOTOR PERCENT KILOWATT or AVERAGE LINE CUR-
PRESTART FAULT TIMER elapses, the lag chiller stops, and RENT on the MAINSTAT screen) is less than the lead
the standby chiller is requested to start, if configured and chiller percent capacity.
ready. NOTE: Lead chiller percent capacity = 115 – LAG PER-
Standby Chiller Configuration and Operation — A chiller is CENT CAPACITY. The LAG PERCENT CAPACITY param-
designated as a standby chiller when its LEAD/LAG eter is on the LEADLAG screen, which is accessed from the
CONFIGURATION value on the LEADLAG screen is set to EQUIPMENT SERVICE table on the SERVICE menu.
‘‘3.’’ The standby chiller can operate as a replacement for FAULTED CHILLER OPERATION — If the lead chiller
the lag chiller only if one of the other two chillers is in an shuts down because of an alarm (*) condition, it stops com-
alarm (*) condition (as shown on the CVC panel). If both municating to the lag and standby chillers. After 30 seconds,
lead and lag chillers are in an alarm (*) condition, the standby the lag chiller becomes the acting lead chiller and starts and
chiller defaults to operate in CCN mode, based on its con- stops the standby chiller, if necessary.
figured occupancy schedule and remote contacts input. If the lag chiller goes into alarm when the lead chiller is
Lag Chiller Start-Up Requirements — Before the lag chiller also in alarm, the standby chiller reverts to a stand-alone CCN
can be started, the following conditions must be met: mode of operation.
1. Lead chiller ramp loading must be complete. If the lead chiller is in an alarm (*) condition (as shown
2. Lead chilled water temperature must be greater than the on the CVC panel), press the RESET softkey to clear the
CONTROL POINT temperature (see the MAINSTAT screen) alarm. The chiller is placed in CCN mode. The lead chiller
plus 1/2 the CHILLED WATER DEADBAND tempera- communicates and monitors the RUN STATUS of the lag
ture (see the SETUP1 screen). and standby chillers. If both the lag and standby chillers are
NOTE: The chilled water temperature sensor may be the running, the lead chiller does not attempt to start and does
leaving chilled water sensor, the return water sensor, the not assume the role of lead chiller until either the lag or standby
common supply water sensor, or the common return wa- chiller shuts down. If only one chiller is running, the lead
ter sensor, depending on which options are configured and chiller waits for a start request from the operating chiller.
enabled. When the configured lead chiller starts, it assumes its role as
3. Lead chiller ACTIVE DEMAND LIMIT (see the lead chiller.
MAINSTAT screen) value must be greater than 95% of If the lag chiller is the only chiller running when the lead
full load amps. chiller assumes its role as a lead chiller then the lag chiller
4. Lead chiller temperature pulldown rate (TEMP PULL- will perform a RECOVERY START REQUEST (LL_MAINT
DOWN DEG/MIN on the TEMP_CTL screen) of the chilled screen). The lead chiller will start up when the following
water temperature is less than 0.5° F (0.27° C) per minute. conditions are met.
5. The lag chiller status indicates it is in CCN mode and is 1. Lag chiller ramp loading must be complete.
not in an alarm condition. If the current lag chiller is in 2. Lag CHILLED WATER TEMP (MAINSTAT screen) is
an alarm condition, the standby chiller becomes the ac- greater than CONTROL POINT plus 1/2 the CHILLED
tive lag chiller, if it is configured and available. WATER DEADBAND temperature.
6. The configured LAG START TIMER entry has elapsed. 3. Lag chiller ACTIVE DEMAND LIMIT value must be greater
The LAG START TIMER starts when the lead chiller than 95% of full load amps.
ramp loading is completed. The LAG START TIMER 4. Lag chiller temperature pulldown rate (TEMP PULL-
entry is on the LEADLAG screen, which is accessed DOWN DEG/MIN) of the chilled water temperature is less
from the EQUIPMENT SERVICE table of the than 0.5 F (0.27 C) per minute.
SERVICE menu.
5. The standby chiller is not running as a lag chiller.
When all the above requirements have been met, the lag
chiller is commanded to a STARTUP mode (SUPVSR flash- 6. The configured LAG START TIMER has elapsed. The LAG
ing next to the point value on the STATUS table). The START TIMER is started when ramp loading is
PIC II control then monitors the lag chiller for a successful completed.
40
LOAD BALANCING — When the LOAD BALANCE • the chilled water temperature is less than the ice build set
OPTION (see LEADLAG screen) is enabled, the lead chiller point and the remote contact inputs from an ice level in-
sets the ACTIVE DEMAND LIMIT in the lag chiller to the dicator are open. In this case, the operator sets the ICE
lead chiller’s compressor motor load value MOTOR PER- BUILD TERMINATION parameter to 2 on the OPTIONS
CENT KILOWATTS or AVERAGE LINE CURRENT on the screen.
MAINSTAT screen). This value has limits of 40% to 100%. • the end of the ice build time schedule has been reached.
When the lag chiller ACTIVE DEMAND LIMIT is set, the
CONTROL POINT must be modified to a value of 3° F ICE BUILD INITIATION — The ice build time schedule
(1.67° C) less than the lead chiller’s CONTROL POINT value. (OCCPC02S) is the means for activating the ice build
If the LOAD BALANCE OPTION is disabled, the ACTIVE option. The ice build option is enabled if:
DEMAND LIMIT and the CONTROL POINT are forced to • a day of the week and a time period on the ice build time
the same value as the lead chiller. schedule are enabled. The SCHEDULE screen shows an
AUTO. RESTART AFTER POWER FAILURE — When an X in the day field and ON/OFF times are designated for
auto. restart condition occurs, each chiller may have a delay the day(s),
added to the start-up sequence, depending on its lead/lag • and the ICE BUILD OPTION is enabled.
configuration. The lead chiller does not have a delay. The The following events take place (unless overridden by a
lag chiller has a 45-second delay. The standby chiller has a higher authority CCN device).
90-second delay. The delay time is added after the chiller 1. CHILLER START/STOP is forced to START.
water flow is verified. The PIC II ensures the guide vanes 2. The CONTROL POINT is forced to the ICE BUILD
are closed. After the guide vane position is confirmed, the SETPOINT.
delay for lag and standby chillers occurs prior to energizing
the oil pump. The normal start-up sequence then continues. 3. Any force (Auto) is removed from the ACTIVE
The auto. restart delay sequence occurs whether the chiller DEMAND LIMIT.
is in CCN or LOCAL mode and is intended to stagger the NOTE: A parameter’s value can be forced, that is, the value
compressor motor starts. Preventing the motors from start- can be manually changed at the CVC by an operator, changed
ing simultaneously helps reduce the inrush demands on the from another CCN device, or changed by other algorithms
building power system. in the PIC II control system.
Ice Build Control — The ice build control option NOTE: Items 1-3 (shown above) do not occur if the chiller
automatically sets the CONTROL POINT of the chiller to a is configured and operating as a lag or standby chiller for
temperature that allows ice building for thermal storage. lead/lag operation and is actively being controlled by a lead
chiller. The lead chiller communicates the ICE BUILD SET
NOTE: For ice build control to operate properly, the PIC II POINT, the desired CHILLER START/STOP state, and the
must be in CCN mode. ACTIVE DEMAND LIMIT to the lag or standby chiller as
NOTE: See Fig. 15 and 16 for more information on ice build- required for ice build, if configured to do so.
related menus.
START-UP/RECYCLE OPERATION — If the chiller is not
The PIC II can be configured for ice build operation. running when ice build activates, the PIC II checks the fol-
• From the SERVICE menu, access the EQUIPMENT SERV- lowing conditions, based on the ICE BUILD TERMINA-
ICE table. From there, select the OPTIONS screen to en- TION value, to avoid starting the compressor unnecessarily:
able or disable the ICE BUILD OPTION. See • if ICE BUILD TERMINATION is set to the TEMP option
Table 2, Example 16. and the ENTERING CHILLED WATER temperature is less
• The ICE BUILD SETPOINT can be configured from the than or equal to the ICE BUILD SETPOINT;
SETPOINT display, which is accessed from the PIC II main • if ICE BUILD TERMINATION is set to the CONTACTS
menu. See Table 2, Example 8. option and the remote contacts are open;
• The ice build schedule can be viewed or modified from • if the ICE BUILD TERMINATION is set to the BOTH (tem-
the SCHEDULE table. From this table, select the ice build perature and contacts) option and the ENTERING CHILLED
schedule (OCCPC02S) screen. See Fig. 17 and the section WATER temperature is less than or equal to the ICE BUILD
on Time Schedule Operation, page 19, for more informa- SETPOINT and the remote contacts are open.
tion on modifying chiller schedules.
The ICE BUILD RECYCLE on the OPTIONS screen de-
The ice build time schedule defines the period(s) during termines whether or not the chiller will go into an ice build
which ice build is active if the ice build option is RECYCLE mode.
enabled. If the ice build time schedule overlaps other sched-
• If the ICE BUILD RECYCLE is set to DSABLE (disable),
ules, the ice build time schedule takes priority. During the
the PIC II reverts to normal temperature control when the
ice build period, the CONTROL POINT is set to the ICE ice build function terminates.
BUILD SETPOINT for temperature control. The ICE BUILD
RECYCLE and ICE BUILD TERMINATION parameters, ac- • If the ICE BUILD RECYCLE is set to ENABLE, the
cessed from the OPTIONS screen, allow the chiller operator PIC II goes into an ICE BUILD RECYCLE mode and the
to recycle or terminate the ice build cycle. The ice build cycle chilled water pump relay remains energized to keep the
can be configured to terminate if: chilled water flowing when the ice build function termi-
• the ENTERING CHILLED WATER temperature is less than nates. If the temperature of the ENTERING CHILLED
the ICE BUILD SETPOINT. In this case, the operator sets WATER increases above the ICE BUILD SETPOINT plus
the ICE BUILD TERMINATION parameter to 0 on the the RECYCLE RESTART DELTA T value, the compressor
restarts and controls the chilled water/brine temperature to
OPTIONS screen.
the ICE BUILD SETPOINT.
• the REMOTE CONTACT inputs from an ice level indi-
cator are opened. In this case, the operator sets the ICE TEMPERATURE CONTROL DURING ICE BUILD — Dur-
BUILD TERMINATION parameter to 1 on the OPTIONS ing ice build, the capacity control algorithm shall use the
screen. CONTROL POINT minus 5 F (−2.8 C) for control of the
LEAVING CHILLED WATER temperature. See Table 2, ex-
ample 9, the CAPACITY CONTROL parameter on the CA-
PACITY screen.) The ECW CONTROL OPTION and any
41
temperature reset option shall be ignored, if enabled, dur- address of the chiller on which it is mounted. Whenever the
ing ice build. The AUTO DEMAND LIMIT INPUT shall controller identification of the CVC changes, the change is
also be ignored if enabled during ice build. reflected automatically in the BUS and ADDRESS columns
• ECW CONTROL OPTION and any temperature reset for the local device. See Fig. 16. Default address for local
options (configured on TEMP_CTL screen). device is BUS 0 ELEMENT 1.
• 20 mA DEMAND LIMIT OPT (configured on
RAMP_DEM screen).
TERMINATION OF ICE BUILD — The ice build function
terminates under the following conditions:
1. Time Schedule — When the current time on the ice build
time schedule (OCCPC02S) is not set as an ice build time
period.
2. Entering Chilled Water Temperature — Compressor
operation terminates, based on temperature, if the ICE
BUILD TERMINATION parameter is set to 0 (TEMP),
the ENTERING CHILLED WATER temperature is less than
the ICE BUILD SETPOINT, and the ICE BUILD Fig. 21 — Example of Attach to Network
RECYCLE is set to DSABLE. If the ICE BUILD RE- Device Screen
CYCLE OPTION is set to ENABLE, a recycle shutdown
occurs and recycle start-up depends on the LEAVING
CHILLED WATER temperature being greater than the
WATER/BRINE CONTROL POINT plus the RECYCLE When the ATTACH TO NETWORK DEVICE screen is
RESTART DELTA T temperature. accessed, information can not be read from the CVC on any
3. Remote Contacts/Ice Level Input — Compressor opera- device until one of the devices listed on that screen is
tion terminates when the ICE BUILD TERMINATION attached. The CVC erases information about the module to
parameter is set to 1 CONTACTS) and the remote con- which it was attached to make room for information on
tacts are open and the ICE BUILD RECYCLE is set to another device. Therefore, a CCN module must be attached
DSABLE (0). In this case, the contacts provide ice level when this screen is entered.
termination control. The contacts are used to stop the To attach any CCN device, highlight it using the
ice build function when a time period on the ice build SELECT softkey and press the ATTACH softkey. The mes-
schedule (OCCPC02S) is set for ice build operation. The sage ‘‘UPLOADING TABLES, PLEASE WAIT’’ displays.
remote contacts can still be opened and closed to start The CVC then uploads the highlighted device or module. If
and stop the chiller when a specific time period on the ice the module address cannot be found, the message ‘‘COM-
build schedule is not set for ice build. MUNICATION FAILURE’’ appears. The CVC then reverts
4. Entering Chilled Water Temperature and ICE BUILD Con- back to the ATTACH TO DEVICE screen. Try another de-
tacts — Compressor operation terminates when the ICE vice or check the address of the device that would not at-
BUILD TERMINATION parameter is set to 2 (BOTH) tach. The upload process time for each CCN module is dif-
and the conditions described above in items 2 and 3 for ferent. In general, the uploading process takes 1 to 2 minutes.
entering chilled water temperature and remote contacts Before leaving the ATTACH TO NETWORK DEVICE screen,
have occurred. select the local device. Otherwise, the CVC will be unable
NOTE: It is not possible to override the CHILLER START/ to display information on the local chiller.
STOP, CONTROL POINT, and ACTIVE DEMAND LIMIT ATTACHING TO OTHER CCN MODULES — If the chiller
variables from CCN devices (with a priority 4 or greater) CVC has been connected to a CCN Network or other PIC
during the ice build period. However, a CCN device can over- controlled chillers through CCN wiring, the CVC can be used
ride these settings during 2-chiller lead/lag operation. to view or change parameters on the other controllers. Other
RETURN TO NON-ICE BUILD OPERATIONS — The ice PIC II chillers can be viewed and set points changed (if the
build function forces the chiller to start, even if all other sched- other unit is in CCN control), if desired, from this particular
ules indicate that the chiller should stop. When the ice build CVC module.
function terminates, the chiller returns to normal tempera- If the module number is not valid, the ‘‘COMMUNICA-
ture control and start/stop schedule operation. The CHILLER TION FAILURE’’ message will show and a new address num-
START/STOP and CONTROL POINT return to normal op- ber must be entered or the wiring checked. If the module is
eration. If the CHILLER START/STOP or CONTROL POINT communicating properly, the ‘‘UPLOAD IN PROGRESS’’
has been forced (with a device of less than 4 priority) before message will flash and the new module can now be viewed.
the ice build function started, when the ice build function Whenever there is a question regarding which module on
ends, the previous forces (of less than 4 priority) are not au- the CVC is currently being shown, check the device name
tomatically restored. descriptor on the upper left hand corner of the CVC screen.
See Fig. 21.
Attach to Network Device Control — The Service
menu includes the ATTACH TO NETWORK DEVICE screen. When the CCN device has been viewed, the ATTACH TO
From this screen, the operator can: NETWORK DEVICE table should be used to attach to the
PIC that is on the chiller. Move to the ATTACH TO NET-
• enter the time schedule number (if changed) for OCCPC03S, WORK DEVICE table (LOCAL should be highlighted) and
as defined in the NET_OPT screen
• attach the CVC to any CCN device, if the chiller has been press the ATTACH softkey to upload the LOCAL device.
connected to a CCN network. This may include other PIC- The CVC for the 19XR will be uploaded and default screen
controlled chillers. will display.
• upgrade software NOTE: The CVC will not automatically reattach to the local
Figure 21 shows the ATTACH TO NETWORK DEVICE module on the chiller. Press the ATTACH softkey to attach
screen. The LOCAL parameter is always the CVC module to the LOCAL device and view the chiller operation.
42
Service Operation — An overview of the tables and HOLIDAY SCHEDULING (Fig. 22) — The time schedules
screens available for the SERVICE function is shown in may be configured for special operation during a holiday
Fig. 16. period. When modifying a time period, the ‘‘H’’ at the end
of the days of the week field signifies that the period is
TO ACCESS THE SERVICE SCREENS — When the applicable to a holiday. (See Fig. 17.)
SERVICE screens are accessed, a password must be
entered. The broadcast function must be activated for the holidays
configured on the HOLIDEF screen to work properly.
1. From the main MENU screen, press the SERVICE soft- Access the BRODEF screen from the EQUIPMENT CON-
key. The softkeys now correspond to the numerals 1, 2, FIGURATION table and select ENABLE to the activated
3, 4. function. Note that when the chiller is connected to a CCN
2. Press the four digits of the password, one at a time. An Network, only one chiller or CCN device can be configured
asterisk (*) appears as each digit is entered. as the broadcast device. The controller that is configured
as the broadcaster is the device responsible for transmitting
holiday, time, and daylight-savings dates throughout the
network.
To access the BRODEF screen, see the SERVICE menu
structure, Fig. 16.
NOTE: The initial factory-set password is 1 - 1- 1 - 1. If To view or change the holiday periods for up to 18 dif-
the password is incorrect, an error message is displayed. ferent holidays, perform the following operation:
1. At the Menu screen, press SERVICE to access the Serv-
ice menu.
2. If not logged on, follow the instructions for To Log On
or To Log Off. Once logged on, press NEXT until Equip-
ment Configuration is highlighted.
If this occurs, return to Step 1 and try to access the SERV-
ICE screens again. If the password is correct, the softkey 3. Once Equipment Configuration is highlighted, press
labels change to: SELECT to access.
4. Press NEXT until HOLIDAYS is highlighted. This is
the Holiday Definition table.
5. Press SELECT to enter the Data Table Select screen.
This screen lists 18 holiday tables.
NOTE: The SERVICE screen password can be changed 6. Press NEXT to highlight the holiday table that is to be
by entering the CVC CONFIGURATION screen under
SERVICE menu. The password is located at the bottom viewed or changed. Each table is one holiday period,
of the menu. starting on a specific date, and lasting up to 99 days.
The CVC screen displays the following list of available 7. Press SELECT to access the holiday table. The Con-
SERVICE screens: figuration Select table now shows the holiday start month
• Alarm History and day, and how many days the holiday period will last.
• Control Test 8. Press NEXT or PREVIOUS to highlight the
• Control Algorithm Status month, day, or duration.
• Equipment Configuration
• ISM (STARTER) Config Data 9. Press SELECT to modify the month, day, or
• Equipment Service duration.
• Time and Date 10. Press INCREASE or DECREASE to change the
• Attach to Network Device selected value.
• Log Out of Device
• CVC Configuration 11. Press ENTER to save the changes.
See Fig. 16 for additional screens and tables available from 12. Press EXIT to return to the previous menu.
the SERVICE screens listed above. Use the EXIT softkey
to return to the main MENU screen.
NOTE: To prevent unauthorized persons from accessing the
CVC service screens, the CVC automatically signs off and
password-protects itself if a key has not been pressed for
15 minutes. The sequence is as follows. Fifteen minutes
after the last key is pressed, the default screen displays, the
CVC screen light goes out (analogous to a screen saver),
and the CVC logs out of the password-protected SERVICE
menu. Other screen and menus, such as the STATUS screen
can be accessed without the password by pressing the ap-
propriate softkey.
TO LOG OUT OF NETWORK DEVICE — To access this
screen and log out of a network device, from the default CVC
screen, press the MENU and SERVICE softkeys. Enter
the password and, from the SERVICE menu, highlight LOG
OUT OF NETWORK DEVICE and press the SELECT Fig. 22 — Example of Holiday Period Screen
softkey. The CVC default screen will now be displayed.
43
START-UP/SHUTDOWN/RECYCLE WATER FLOW VERIFY TIME (operator-configured, default
SEQUENCE (Fig. 23) 5 minutes) expires to confirm flow. After flow is verified, the
chilled water temperature is compared to CONTROL POINT
Local Start-Up — Local start-up (or a manual start-up) plus 1/2 CHILLED WATER DEADBAND. If the temperature
is initiated by pressing the LOCAL menu softkey on the is less than or equal to this value, the PIC II turns off the
condenser pump relay and goes into a RECYCLE mode.
default CVC screen. Local start-up can proceed when the
chiller schedule indicates that the current time and date have If the water/brine temperature is high enough, the start-up
been established as a run time and date, and after the inter- sequence continues and checks the guide vane position. If
nal 15-minute start-to-start and the 1-minute stop-to-start the guide vanes are more than 4% open, the start-up waits
inhibit timers have expired. These timers are represented in until the PIC II closes the vanes. If the vanes are closed and
the START INHIBIT TIMER and can be viewed on the MAIN- the oil pump pressure is less than 4 psi (28 kPa), the oil
STAT screen and DEFAULT screen. The timer must expire pump relay energizes. The PIC II then waits until the oil pres-
before the chiller will start. If the timers have not expired sure (OIL PRESS VERIFY TIME, operator-configured,
the RUN STATUS parameter on the MAINSTAT screen now default of 40 seconds) reaches a maximum of 18 psi
reads TIMEOUT. (124 kPa). After oil pressure is verified, the PIC II waits
40 seconds, and the compressor start relay (1CR) energizes
NOTE: The time schedule is said to be ‘‘occupied’’ if the to start the compressor.
OCCUPIED ? parameter on the MAINSTAT screen is set to Compressor ontime and service ontime timers start, and
YES. For more information on occupancy schedules, see the the compressor starts in 12 hours counter and the number of
sections on Time Schedule Operation (page 19), Occupancy starts over a 12-hour period counter advance by one.
Schedule (page 32), and To Prevent Accidental Start-Up
(page 59), and Fig. 17. Failure to verify any of the requirements up to this point
will result in the PIC II aborting the start and displaying the
If the OCCUPIED ? parameter on the MAINSTAT screen applicable pre-start mode of failure on the CVC default screen.
is set to NO, the chiller can be forced to start as follows. A pre-start failure does not advance the starts in 12 hours
From the default CVC screen, press the MENU and counter. Any failure after the 1CR relay has energized
STATUS softkeys. Scroll to highlight MAINSTAT. Press results in a safety shutdown, advances the starts in the
12 hours counter by one, and displays the applicable shut-
the SELECT softkey. Scroll to highlight CHILLER START/ down status on the CVC display.
STOP. Press the START softkey to override the schedule
and start the chiller.
NOTE: The chiller will continue to run until this forced start
is released, regardless of the programmed schedule. To
release the forced start, highlight CHILLER START/STOP from
the MAINSTAT screen and press the RELEASE softkey.
This action returns the chiller to the start and stop times
established by the schedule.
The chiller may also be started by overriding the time sched-
ule. From the default screen, press the MENU and
SCHEDULE softkeys. Scroll down and select the current
schedule. Select OVERRIDE, and set the desired override
time.
Another condition for start-up must be met for chillers that
have the REMOTE CONTACTS OPTION on the EQUIP-
MENT SERVICE screen set to ENABLE. For these chillers,
the REMOTE CONTACTS INPUT parameter on the MAIN- A — START INITIATED — Prestart checks made; evaporator
STAT screen must be CLOSED. From the CVC default screen, pump started.
B — Condenser water pump started (5 seconds after A).
press the MENU and STATUS softkeys. Scroll to high- C — Water flows verified (30 seconds to 5 minutes maximum
after B). Chilled water temperatures checked against con-
light MAINSTAT and press the SELECT softkey. Scroll trol point. Guide vanes checked for closure. Oil pump started;
down the STATUS01 screen to highlight REMOTE CON- tower fan control enabled.
D — Oil pressure verified (15 seconds minimum, 300 seconds
TACTS INPUT and press the SELECT softkey. Then, press maximum after C).
E — Compressor motor starts, compressor ontime and service
the CLOSE softkey. To end the override, select REMOTE ontime start, 15-minute inhibit timer starts (10 seconds
CONTACTS INPUT and press the RELEASE softkey. after D), total compressor starts advances by one, and the
number of starts over a 12-hour period advances by one.
Once local start-up begins, the PIC II performs a series of F — SHUTDOWN INITIATED — Compressor motor stops, com-
pre-start tests to verify that all pre-start alerts and safeties pressor ontime and service ontime stops, and 1-minute
are within the limits shown in Table 3. The RUN STATUS inhibit timer starts.
G — Oil pump and evaporator pumps deenergized (60 seconds
parameter on the MAINSTAT screen line now reads after F). Condenser pump and tower fan control may con-
PRESTART. If a test is not successful, the start-up is de- tinue to operate if condenser pressure is high. Evaporator
layed or aborted. If the tests are successful, the chilled water/ pump may continue if in RECYCLE mode.
brine pump relay energizes, and the MAINSTAT screen line O/A — Restart permitted (both inhibit timers expired: minimum of
15 minutes after E; minimum of 1 minute after F).
now reads STARTUP.
Five seconds later, the condenser pump relay energizes. Fig. 23 — Control Sequence
Thirty seconds later the PIC II monitors the chilled water
and condenser water flow devices and waits until the
44
Shutdown Sequence — Chiller shutdown begins if Chilled Water Recycle Mode — The chiller may cycle
any of the following occurs: off and wait until the load increases to restart when
• the STOP button is pressed for at least one second (the the compressor is running in a lightly loaded condition. This
alarm light blinks once to confirm the stop command) cycling is normal and is known as 9recycle.9 A recycle shut-
• a recycle condition is present (see Chilled Water Recycle down is initiated when any of the following conditions
Mode section) are true:
• the time schedule has gone into unoccupied mode • the chiller is in LCW control, the difference between the
• the chiller protective limit has been reached and chiller is LEAVING CHILLED WATER temperature and ENTER-
in alarm ING CHILLED WATER temperature is less than the
• the start/stop status is overridden to stop from the CCN RECYCLE SHUTDOWN DELTA T (found in the
network or the CVC SETUP1 table) and the LEAVING CHILLED WATER tem-
When a stop signal occurs, the shutdown sequence first perature is below the CONTROL POINT, −5 F (−15.0 C)
stops the compressor by deactivating the start relay (1CR). the CONTROL POINT has not increased in the last 5 min-
A status message of ‘‘SHUTDOWN IN PROGRESS, COM- utes and ICE BUILD is not active.
PRESSOR DEENERGIZED’’ is displayed, and the com- • the ECW CONTROL OPTION is enabled, the difference
pressor ontime and service ontime stop. The guide vanes are between the ENTERING CHILLED WATER temperature
then brought to the closed position. The oil pump relay and and the LEAVING CHILLED WATER temperature is less
the chilled water/brine pump relay shut down 60 seconds than the RECYCLE SHUTDOWN DELTA T (found in the
after the compressor stops. The condenser water pump shuts SETUP1 table), and the ENTERING CHILLED WATER
down at the same time if the ENTERING CONDENSER temperature is below the CONTROL POINT −5 F
WATER temperature is greater than or equal to 115 F (−15.0 C) and the CONTROL POINT has not increased in
(46.1 C) and the CONDENSER REFRIG TEMP is greater the last 5 minutes.
than the CONDENSER FREEZE POINT plus 5 F (−15.0 C). • the LEAVING CHILLED WATER temperature is within
The stop-to-start timer now begins to count down. If the start- 3° F (2° C) of the EVAP REFRIG TRIPPOINT.
to-start timer value is still greater than the value of the start- When the chiller is in RECYCLE mode, the chilled water
to-stop timer, then this time displays on the CVC. pump relay remains energized so the chilled water temper-
Certain conditions that occur during shutdown can change ature can be monitored for increasing load. The recycle
this sequence. control uses RECYCLE RESTART DELTA T to check when
• If the AVERAGE LINE CURRENT is greater than 15% af- the compressor should be restarted. This is an operator-
ter shutdown, or the starter contacts remain energized, the configured function which defaults to 5° F (3° C). This value
oil pump and chilled water pump remain energized and can be viewed or modified on the SETUP1 table. The com-
the alarm is displayed. pressor will restart when the chiller is:
• The condenser pump shuts down when the CONDENSER • in LCW CONTROL and the LEAVING CHILLED
PRESSURE is less than the CONDENSER PRESSURE WATER temperature is greater than the CONTROL POINT
OVERRIDE threshold minus 3.5 psi (24.1 kPa) and the plus the RECYCLE RESTART DELTA T.
CONDENSER REFRIG TEMP is less than or equal to the • in ECW CONTROL and the ENTERING CHILLED
ENTERING CONDENSER WATER temperature plus WATER temperature is greater than the CONTROL POINT
3° F (−1.6° C). plus the RECYCLE RESTART DELTA T.
• If the chiller shuts down due to low refrigerant tempera-
ture, the chilled water pump continues to run until the LEAV- Once these conditions are met, the compressor initiates a
ING CHILLED WATER temperature is greater than the start-up with a normal start-up sequence.
CONTROL POINT temperature, plus 5° F (3° C). An alert condition may be generated if 5 or more recycle
start-ups occur in less than 4 hours. Excessive recycling can
Automatic Soft Stop Amps Threshold — The soft reduce chiller life; therefore, compressor recycling due to
stop amps threshold feature closes the guide vanes of the extremely low loads should be reduced.
compressor automatically if a non-recycle, non-alarm stop To reduce compressor recycling, use the time schedule to
signal occurs before the compressor motor is deenergized. shut the chiller down during known low load operation
If the STOP button is pressed, the guide vanes close to a period, or increase the chiller load by running the fan sys-
preset amperage percent until the guide vane is less than tems. If the hot gas bypass is installed, adjust the values to
4% open or 4 minutes have passed. The compressor then ensure that hot gas is energized during light load condi-
shuts off. tions. Increase the RECYCLE RESTART DELTA T on the
If the chiller enters an alarm state or if the compres- SETUP1 table to lengthen the time between restarts.
sor enters a RECYCLE mode, the compressor deenergizes The chiller should not be operated below design mini-
immediately. mum load without a hot gas bypass installed.
To activate the soft stop amps threshold feature, scroll to
the bottom of OPTIONS screen on the CVC. Use the Safety Shutdown — A safety shutdown is identical to
a manual shutdown with the exception that, during a safety
INCREASE or DECREASE softkey to set the SOFT shutdown, the CVC displays the reason for the shutdown,
STOP AMPS THRESHOLD parameter to the percent of amps the alarm light blinks continuously, and the spare alarm con-
at which the motor will shut down. The default setting is tacts are energized.
100% amps (no soft stop). The range is 40 to 100%. After a safety shutdown, the RESET softkey must be
When the soft stop amps threshold feature is being
applied, a status message, ‘‘SHUTDOWN IN PROGRESS, pressed to clear the alarm. If the alarm condition is still present,
COMPRESSOR UNLOADING’’ displays on the CVC. the alarm light continues to blink. Once the alarm is cleared,
The soft stop amps threshold function can be terminated the operator must press the CCN or LOCAL softkeys to
and the compressor motor deenergized immediately by de- restart the chiller.
pressing the STOP button twice.
45
BEFORE INITIAL START-UP To determine if there are any leaks, the chiller should
be charged with refrigerant. Use an electronic leak detector
Job Data Required to check all flanges and solder joints after the chiller is
• list of applicable design temperatures and pressures (prod- pressurized. If any leaks are detected, follow the leak test
uct data submittal) procedure.
• chiller certified prints If the chiller is spring isolated, keep all springs blocked in
both directions to prevent possible piping stress and dam-
• starting equipment details and wiring diagrams age during the transfer of refrigerant from vessel to vessel
• diagrams and instructions for special controls or options during the leak test process, or any time refrigerant is being
• 19XR Installation Instructions transferred. Adjust the springs when the refrigerant is in
• pumpout unit instructions operating condition and the water circuits are full.
46
47
48
Fig. 26 — Typical Optional Pumpout System Piping Schematic with Storage Tank
Fig. 27 — Typical Optional Pumpout System Piping Schematic without Storage Tank
49
Table 5A — HFC-134a Pressure — Table 5B — HFC-134a Pressure —
Temperature (F) Temperature (C)
TEMPERATURE, PRESSURE TEMPERATURE, PRESSURE GAGE
F (psig) C (kPa)
0 6.50 -18.0 44.8
2 7.52 -16.7 51.9
4 8.60 -15.6 59.3
6 9.66 -14.4 66.6
8 10.79 -13.3 74.4
10 11.96 -12.2 82.5
12 13.17 -11.1 90.8
14 14.42 -10.0 99.4
16 15.72 -8.9 108.0
18 17.06 -7.8 118.0
20 18.45 -6.7 127.0
22 19.88 -5.6 137.0
24 21.37 -4.4 147.0
26 22.90 -3.3 158.0
28 24.48 -2.2 169.0
30 26.11 -1.1 180.0
32 27.80 0.0 192.0
34 29.53 1.1 204.0
36 31.32 2.2 216.0
38 33.17 3.3 229.0
40 35.08 4.4 242.0
42 37.04 5.0 248.0
44 39.06 5.6 255.0
46 41.14 6.1 261.0
48 43.28 6.7 269.0
50 45.48 7.2 276.0
52 47.74 7.8 284.0
54 50.07 8.3 290.0
56 52.47 8.9 298.0
58 54.93 9.4 305.0
60 57.46 10.0 314.0
62 60.06 11.1 329.0
64 62.73 12.2 345.0
66 65.47 13.3 362.0
68 68.29 14.4 379.0
70 71.18 15.6 396.0
72 74.14 16.7 414.0
74 77.18 17.8 433.0
76 80.30 18.9 451.0
78 83.49 20.0 471.0
80 86.17 21.1 491.0
82 90.13 22.2 511.0
84 93.57 23.3 532.0
86 97.09 24.4 554.0
88 100.70 25.6 576.0
90 104.40 26.7 598.0
92 108.18 27.8 621.0
94 112.06 28.9 645.0
96 116.02 30.0 669.0
98 120.08 31.1 694.0
100 124.23 32.2 720.0
102 128.47 33.3 746.0
104 132.81 34.4 773.0
106 137.25 35.6 800.0
108 141.79 36.7 828.0
110 146.43 37.8 857.0
112 151.17 38.9 886.0
114 156.01 40.0 916.0
116 160.96 41.1 946.0
118 166.01 42.2 978.0
120 171.17 43.3 1010.0
122 176.45 44.4 1042.0
124 181.83 45.6 1076.0
126 187.32 46.7 1110.0
128 192.93 47.8 1145.0
130 198.66 48.9 1180.0
132 204.50 50.0 1217.0
134 210.47 51.1 1254.0
136 216.55 52.2 1292.0
138 222.76 53.3 1330.0
140 229.09 54.4 1370.0
55.6 1410.0
56.7 1451.0
57.8 1493.0
58.9 1536.0
60.0 1580.0
50
Chiller Dehydration — Dehydration is recommended
if the chiller has been open for a considerable period of time,
if the chiller is known to contain moisture, or if there has
been a complete loss of chiller holding charge or refrigerant
pressure.
51
2. On low-voltage compressors (600 v or less) connect a 10. Tighten all wiring connections to the plugs on the ISM
voltmeter across the power wires to the compressor starter and CCM modules.
and measure the voltage. Compare this reading to the 11. On chillers with free-standing starters, inspect the power
voltage rating on the compressor and starter panel to ensure that the contractor has fed the wires into
nameplates. the bottom of the panel. Wiring into the top of the panel
3. Compare the ampere rating on the starter nameplate to can cause debris to fall into the contactors. Clean and
rating on the compressor nameplate. The overload trip inspect the contactors if this has occurred.
amps must be 108% to 120% of the rated load amps.
4. The starter for a centrifugal compressor motor must con- Carrier Comfort Network Interface — The Carrier
tain the components and terminals required for PIC II Comfort Network (CCN) communication bus wiring is sup-
refrigeration control. Check the certified drawings. plied and installed by the electrical contractor. It consists of
shielded, 3-conductor cable with drain wire.
5. Check the voltage to the following components and
compare it to the nameplate values: oil pump contact, The system elements are connected to the communication
pumpout compressor starter, and power panel. bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
6. Ensure that fused disconnects or circuit breakers have the positive pins of the system element on either side of it.
been supplied for the oil pump, power panel, and The negative pins must be wired to the negative pins. The
pumpout unit. signal ground pins must be wired to the signal ground pins.
7. Ensure all electrical equipment and controls are prop- See installation manual.
erly grounded in accordance with job drawings, certi- NOTE: Conductors and drain wire must be 20 AWG
fied drawings, and all applicable electrical codes. (American Wire Gage) minimum stranded, tinned copper. In-
8. Ensure the customer’s contractor has verified proper op- dividual conductors must be insulated with PVC, PVC/
eration of the pumps, cooling tower fans, and associated nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester
auxiliary equipment. This includes ensuring motors are 100% foil shield and an outer jacket of PVC, PVC/nylon,
properly lubricated and have proper electrical supply and chrome vinyl, or Teflon with a minimum operating tempera-
proper rotation. ture range of −4 F to 140 F (−20 C to 60 C) is required. See
9. For field-installed starters only, test the chiller compres- table below for cables that meet the requirements.
sor motor and its power lead insulation resistance with
a 500-v insulation tester such as a megohmmeter. (Use MANUFACTURER CABLE NO.
a 5000-v tester for motors rated over 600 v.) Factory- Alpha 2413 or 5463
mounted starters do not require a megohm test. American A22503
a. Open the starter main disconnect switch and follow Belden 8772
lockout/tagout rules. Columbia 02525
52
MECHANICAL STARTER energizes the oil heater and the control circuit. When first
1. Check all field wiring connections for tightness, clear- powered, the CVC should display the default screen within
ance from moving parts, and correct connection. a short period of time.
2. Check the contactor(s) to ensure they move freely. Check The oil heater is energized by powering the control cir-
the mechanical interlock between contactors to ensure that cuit. This should be done several hours before start-up to
1S and 2M contactors cannot be closed at the same time. minimize oil-refrigerant migration. The oil heater is con-
Check all other electro-mechanical devices, such as trolled by the PIC II and is powered through a contactor in
relays, for free movement. If the devices do not move the power panel. Starters contain a separate circuit breaker
freely, contact the starter manufacturer for replacement to power the heater and the control circuit. This arrangement
components. allows the heater to energize when the main motor circuit
breaker is off for service work or extended shutdowns. The
3. Some dashpot-type magnetic overload relays must be filled oil heater relay status (OIL HEATER RELAY) can be viewed
with oil on the jobsite. If the starter is equipped with de- on the COMPRESS table on the CVC. Oil sump tempera-
vices of this type, remove the fluid cups from these mag- ture can be viewed on the CVC default screen.
netic overload relays. Add the dashpot oil to the cups
according to the instructions supplied with the starter. The SOFTWARE VERSION — The software part number is la-
oil is usually shipped in a small container attached to the beled on the backside of the CVC module. The software ver-
starter frame near the relays. Use only the dashpot oil sup- sion also appears on the CVC configuration screen as the
plied with the starter. Do not substitute. last two digits of the software part number.
Solid-state overload relays do not have oil. Software Configuration
4. Reapply starter control power (not main chiller power) to
check the electrical functions.
Ensure the starter (with relay 1CR closed) goes through Do not operate the chiller before the control configu-
a complete and proper start cycle. rations have been checked and a Control Test has been
BENSHAW, INC. REDISTART MICRO SOLID-STATE satisfactorily completed. Protection by safety controls
STARTER cannot be assumed until all control configurations have
been confirmed.
53
INPUT TIME AND DATE — Access the TIME AND DATE INPUT EQUIPMENT SERVICE PARAMETERS IF NEC-
table on the SERVICE menu. Input the present time of day, ESSARY — The EQUIPMENT SERVICE table has six serv-
date, and day of the week. The HOLIDAY TODAY param- ice tables.
eter should only be configured to YES if the present day is Configure SERVICE Tables — Access the SERVICE tables,
a holiday. depicted on the next page, to modify or view the following
NOTE: Because a schedule is integral to the chiller control to job site parameters:
sequence, the chiller will not start until the time and date
have been set. PARAMETER TABLE
Starter Type ISM_CONF — Select 0 for full voltage,
CHANGE CVC CONFIGURATION IF NECESSARY — 1 for reduced voltage, or 2 for solid state/
From the SERVICE table, access the CVC CONFIGU- variable frequency drive.
RATION screen. From there, view or modify the CVC CCN Motor Rated Line ISM_CONF — Enter actual line voltage
address, change to English or SI units, and change the pass- Voltage from power screen.
word. If there is more than one chiller at the jobsite, change Volt Transformer ISM_CONF — Enter ratio (reduced to a
the CVC address on each chiller so that each chiller has its Ratio ratio to 1) of power transformer wired to
own address. Note and record the new address. Change the terminal J3 of ISM. If no transformer is
used enter 1.
screen to SI units as required, and change the password if
Motor Rated Load ISM_CONF — Per chiller identification
desired. Amps nameplate data.
TO CHANGE THE PASSWORD — The password may be Motor Locked Rotor ISM_CONF — Per chiller identification
changed from the CVC CONFIGURATION screen. Trip nameplate data. Enter locked rotor delta
amps (LR AMPS D-).
1. Press the MENU and SERVICE softkeys. Enter the cur- Starter LRA Rating ISM_CONF — Enter value from name-
rent password and highlight CVC CONFIGURATION. plate in starter cabinet.
Motor Current ISM_CONF — Enter ratio (reduced to a
Press the SELECT softkey. Only the last 5 entries on CT Ratio ratio to 1) of current transformers wired
the CVC CONFIG screen can be changed: BUS #, to terminal J4 of ISM.
ADDRESS #, BAUD RATE, US IMP/METRIC, and Ground Fault ISM_CONF — Enter 0 if three ground
PASSWORD. Current fault CTs are wired to terminal J5 of ISM.
Transformers Enter 1 if one ground fault CT is used.
2. Use the ENTER softkey to scroll to PASSWORD. The Ground Fault CT ISM_CONF — Enter ratio (reduced to a
Ratio ratio to 1) of ground fault CT.
first digit of the password is highlighted on the screen.
Single Cycle ISM_CONF — ENABLE if motor protec-
3. To change the digit, press the INCREASE or Dropout tion required from drop in line voltage
within one cycle.
DECREASE softkey. When the desired digit is seen, press
Line Frequency ISM_CONF — Enter YES for 60 Hz or
the ENTER softkey. NO for 50 Hz.
4. The next digit is highlighted. Change it, and the third and Line Frequency ISM_CONF — ENABLE if motor protec-
Faulting tion required for drop in line frequency.
fourth digits in the same way the first was changed.
Surge LImiting or OPTIONS — Enter 1 if HGBP is
5. After the last digit is changed, the CVC goes to the BUS Hot Gas Byapss installed.
Option
parameter. Press the EXIT softkey to leave that screen
Minimum Load OPTIONS — Per job data — See modify
and return to the SERVICE menu. Points (T1/P1) load points section.
Full (Maximum) OPTIONS — Per job data — See modify
Load Points load points section.
(T2/P2)
Be sure to remember the password. Retain a copy Chilled Medium SEETUP1 — Enter water or brine.
for future reference. Without the password, access Evaporator SETUP1 — Usually 3° F (1.7° C) below
to the SERVICE menu will not be possible unless Refrigerant design refrigerant temperature.
the CVC_PSWD menu on the STATUS screen is Trippoint
accessed by a Carrier representative. Evaporator Flow SETUP1 — Enter 50% of design
Delta P Cutout pressure drop to 0.5 psi (3.4 kPa).*
Condenser Flow SETUP1 — Enter 50% of design
TO CHANGE THE CVC DISPLAY FROM ENGLISH TO Delta P Cutout pressure drop to 0.5 psi (3.4 kPa).*
METRIC UNITS — By default, the CVC displays informa- Diffuser Option SETUP2 — ENABLE for 5 size
tion in English units. To change to metric units, access the compressor only. See model number
CVC CONFIGURATION screen: nomenclature.
Diffuser Full Span SETUP2 — Enter diffuser actuator full
1. Press the MENU and SERVICE softkeys. Enter the mA Rating span mA rating for 5 size compressor
password and highlight CVC CONFIGURATION. Press only. Value is located on label on side of
diffuser actuator motor.
the SELECT softkey. Motor Rated RAMP_DEM — Enter value from chiller
2. Use the ENTER softkey to scroll to US IMP/METRIC. Kilowatts requisition form (product data submittal) if
kilowatt ramp demand is enabled.
3. Press the softkey that corresponds to the units desired for
display on the CVC (e.g., US or METRIC). *With variable flow systems this point may be configured to the lower
end of the range.
MODIFY CONTROLLER IDENTIFICATION IF NECES- NOTE: Other parameters on these screens are normally left at the
SARY — The CVC module address can be changed from default settings; however, they may be changed by the operator as
the CVC CONFIGURATION screen. Change this address required. The time and persistence settings on the ISM_CONF table
for each chiller if there is more than one chiller at the job- can be adjusted to increase or decrease the sensitivity to a fault
site. Write the new address on the CVC module for future condition. Increasing time or persistence decreases sensitivity. De-
creasing time or persistence increases sensitivity to the fault
reference. condition.
54
Modify Minimum and Maximum Load Points (DT1/P1; If surge prevention occurs too soon or too late:
D T2/P2) If Necessary — These pairs of chiller load points,
located on the OPTIONS screen, determine when to limit LOAD SURGE PREVENTION SURGE PREVENTION
guide vane travel or open the hot gas bypass valve when OCCURS TOO SOON OCCURS TOO LATE
surge prevention is needed. These points should be set based At low
loads Increase P1 by 10 psid Decrease P1 by 10 psid
on individual chiller operating conditions. (,50%) (70 kPad) (70 kPad)
If after configuring a value for these points, surge preven- At high Decrease P2 by 10 psid
tion is operating too soon or too late for conditions, these loads Increase P2 by 10 psid (70 kPad)
(.50%) (70 kPad)
parameters should be changed by the operator.
An example of such a configuration is shown below. The differential pressure (DP) and temperature (DT) can
Refrigerant: HCFC-134a be monitored during chiller operation by viewing ACTIVE
Estimated Minimum Load Conditions: DELTA P and ACTIVE DELTA T (HEAT_EX screen). Com-
44 F (6.7 C) LCW paring SURGE/AGBP DELTA T to active DETLA T will de-
45.5 F (7.5 C) ECW termine when the SURGE PREVENTION function will oc-
43 F (6.1 C) Suction Temperature cur. The smaller the difference between the SURGE/AGBP
70 F (21.1 C) Condensing Temperature DELTA T and the ACTIVE DELTA T values, the closer to
surge prevention.
Estimated Maximum Load Conditions:
44 F (6.7 C) LCW CONFIGURE DIFFUSER CONTROL IF NECESSARY —
54 F (12.2 C) ECW If the compressor is equipped with a variable diffuser,
42 F (5.6 C) Suction Temperature (5 size compressor) access the SETUP2 screen. Scroll to DIF-
98 F (36.7 C) Condensing Temperature FUSER CONTROL and press the ENABLE softkey. Enter
Calculate Maximum Load — To calculate the maximum load the correct diffuser and guide vane values (GUIDE VANE
points, use the design load condition data. If the chiller 25% LOAD PT, GUIDE VANE 50 % LOAD PT, GUIDE VANE
full load cooler temperature difference is more than 15 F 75% LOAD PT, DIFFUSER 25% LOAD PT, DIFFUSER 50%
(8.3 C), estimate the refrigerant suction and condensing tem- LOAD PT, DIFFUSER 75% LOAD PT). Default values are
peratures at this difference. Use the proper saturated pres- located on the label inside the control panel. See Fig. 10. To
sure and temperature for the particular refrigerant used. obtain proper settings for diffuser control, contact a Carrier
Engineering representative.
Suction Temperature:
42 F (5.6 C) = 37 psig (255 kPa) saturated Compressors with variable diffuser control have actuators
refrigerant pressure (HFC-134a) tested and stamped with the milliamp (mA) value that
results in 100% actuator rotation. This valve is configured
Condensing Temperature: on the SETUP2 screen. It is labeled DIFFUSER FULL
98 F (36.7 C) = 120 psig (1827 kPa) saturated SPAN mA.
refrigerant pressure (HFC-134a)
MODIFY EQUIPMENT CONFIGURATION IF NECES-
Maximum Load DT2: SARY — The EQUIPMENT SERVICE table has screens to
54 – 44 = 10° F (12.2 – 6.7 = 5.5° C) select, view, or modify parameters. Carrier’s certified draw-
Maximum Load DP2: ings have the configuration values required for the jobsite.
120 – 37 = 83 psid (827 – 255 = 572 kPad) Modify these values only if requested.
To avoid unnecessary surge prevention, add about 10 psid SERVICE Screen Modifications — Change the values on these
(70 kPad) to DP2 from these conditions: screens according to specific job data. See the certified draw-
DT2 = 10° F (5.5° C) ings for the correct values. Modifications can include:
DP2 = 93 psid (642 kPad) • chilled water reset
Calculate Minimum Load — To calculate the minimum load • entering chilled water control (Enable/Disable)
conditions, estimate the temperature difference the cooler will • 4 to 20 mA demand limit
have at 10% load, then estimate what the suction and con- • auto restart option (Enable/Disable)
densing temperatures will be at this point. Use the proper • remote contact option (Enable/Disable)
saturated pressure and temperature for the particular refrig- Owner-Modified CCN Tables— The following EQUIP-
erant used. MENT CONFIGURATION screens are described for refer-
Suction Temperature: ence only.
43 F (6.1 C) = 38 psig (262 kPa) saturated OCCDEFCS — The OCCDEFCS screen contains the Local
refrigerant pressure (HFC-134a) and CCN time schedules, which can be modified here or on
the SCHEDULE screen as described previously.
Condensing Temperature:
70 F (21.1 C) = 71 psig (490 kPa) saturated HOLIDAYS — From the HOLIDAYS screen, the days of the
refrigerant pressure (HFC-134a) year that holidays are in effect can be configured. See the
holiday paragraphs in the Controls section for more
Minimum Load DT1 (at 20% Load): 2 F (1.1 C) details.
Minimum Load DP1: BRODEF — The BRODEF screen defines the start and end
71 – 38 = 33 psid (490 – 262 = 228 kPad) of daylight savings time. Enter the dates for the start and end
Again, to avoid unnecessary surge prevention, add 20 psid of daylight savings if required for your location. BRODEF
(140 kPad) at DP1 from these conditions: also activates the Broadcast function which enables the holi-
DT1 = 2 F (1.1 C) day periods that are defined on the CVC to take effect.
DP1 = 53 psid (368 kPad) Other Tables — The CONSUME, and RUNTIME screens
contain parameters used with a CCN system. See the appli-
cable CCN manual for more information on these screens.
These tables can only be defined from a CCN Building
Supervisor.
55
Perform a Control Test — Check the safety controls Table 6 — Control Test Menu Functions
status by performing an automated control test. Access the
CONTROL TEST table and select a test to be performed TESTS TO BE DEVICES TESTED
PERFORMED
function (Table 6).
1. CCM Thermistors Entering Chilled Water
The Automated Control Test checks all outputs and inputs Leaving Chilled Water
for function. The compressor must be in the OFF mode to Entering Condenser Water
operate the controls test. The compressor can be put in OFF Leaving Condenser Water
Remote Reset Sensor
mode by pressing the STOP push-button on the CVC. Each Comp Discharge Temp
test asks the operator to confirm the operation is occurring Comp Thrust Bearing Temp
and whether or not to continue. If an error occurs, the op- Oil Sump Temp
erator can try to address the problem as the test is being done Comp Motor Winding Temp
Spare Temperature 1
or note the problem and proceed to the next test. Space Temperature 2
NOTE: Enter guide vane calibration to calibrate guide 2. CCM Pressure Evaporator Pressure
input on CCM (Plug J4 upper terminal 9 and 10). Transducers Condenser Pressure
Oil Pump Delta P
NOTE: If during the control test the guide vanes do not open, Spare Pressure Delta P
verify the low pressure alarm is not active. (An active low Condenser Water Delta P
pressure alarm causes the guide vanes to close.) Transducer Voltage Ref
NOTE: The oil pump test will not energize the oil pump if 3. Pumps Oil Pump — Confirm pressure
Chilled Water — Confirm Delta P
cooler pressure is below –5 psig (–35 kPa). Condenser Water — Confirm
Delta P
When the control test is finished or the EXIT softkey is
4. Discrete Outputs Oil Heater Relay
pressed, the test stops, and the CONTROL TEST menu dis- Hot Gas Bypass Relay
plays. If a specific automated test procedure is not com- Tower Fan Relay Low
pleted, access the particular control test to test the function Tower Fan Relay High
Alarm Relay
when ready. The CONTROL TEST menu is described in the Shunt Trip Relay
table below. 5. Guide Vane Actuator Open/Close
6. Diffuser Actuator Open/Close
CCM Pressure Thermistors Check of all thermistors. 7. Pumpdown/Lockout When using pumpdown/lockout,
CCM Pressure Transducers Check of all transducers. observe freeze up precautions when
Pump Checks operation of pump out- removing charge:
puts; pumps are activated. Also Instructs operator which valves to
tests associated inputs such as close and when.
flow or pressure. Starts chilled water and condenser
Discrete ouputs Activation of all on/off outputs water pumps and confirms flows.
individually. Monitors
Guide Vane Check of the guide vane Evaporator pressure
operation. Condenser pressure
Diffuser Actuator* Check of the diffuser actuator. Evaporator temperature during
pumpout procedures
Pumpdown/Lockout Pumpdown prevents the low re-
frigerant alarm during evacuation Turns pumps off after pumpdown.
so refrigerant can be removed Locks out compressor.
form the unit. Also locks the 8. Terminate Lockout Starts pumps and monitors flows.
compressor off and starts the
water pumps. Instructs operator which valves to
open and when.
Terminate Lockout To charge refrigerant and enable
the chiller to run after pumpdown Monitors
lockout. Evaporator pressure
Condenser pressure
Guide Vane Calibration Calibrates guide vane input on Evaporator temperature during
CCM. charging process
*Diffuser tests function only on size 5 compressor with diffuser con- Terminates compressor lockout.
trol enabled.
NOTE: During any of the tests, an out-of-range reading will have an High Altitude Locations — Because the chiller is ini-
asterisk (*) next to the reading and a message will be displayed. tially calibrated at sea level, it is necessary to recalibrate
the pressure transducers if the chiller has been moved to a
Check Optional Pumpout System Controls and high altitude location. See the calibration procedure in the
Compressor — Controls include an on/off switch, a 3-amp Troubleshooting Guide section.
fuse, the compressor overloads, an internal thermostat, a com-
pressor contactor, and a refrigerant high pressure cutout. Charge Refrigerant into Chiller
The high pressure cutout is factory set to open at 161 psig
(1110 kPa) and reset at 130 psig (896 kPa). Ensure the water-
cooled condenser has been connected. Loosen the The transfer, addition, or removal of refrigerant in spring
compressor holddown bolts to allow free spring travel. Open isolated chillers may place severe stress on external pip-
the compressor suction and discharge the service valves. En- ing if springs have not been blocked in both up and down
sure oil is visible in the compressor sight glass. Add oil if directions.
necessary.
See the Pumpout and Refrigerant Transfer Procedures and
Optional Pumpout System Maintenance sections, pages 62
and 68, for details on the transfer of refrigerant, oil speci-
fications, etc.
56
4. Once the pressures have equalized, the discharge isola-
tion valve, cooler isolation valve, optional hot gas bypass
Always operate the condenser and chilled water pumps isolation valve, and the refrigerant isolation valve can be
during charging operations to prevent freeze-ups. opened. Close valves 1a and 1b, and all pumpout unit
valves.
The standard 19XR chiller is shipped with the refrigerant
already charged in the vessels. However, the 19XR may be
ordered with a nitrogen holding charge of 15 psig (103 kPa). Whenever turning the discharge isolation valve, be
Evacuate the nitrogen from the entire chiller, and charge the sure to reattach the valve locking device. This pre-
chiller from refrigerant cylinders. vents the valve from opening or closing during serv-
CHILLER EQUALIZATION WITHOUT A PUMPOUT ice work or during chiller operation.
UNIT
The full refrigerant charge on the 19XR will vary with
chiller components and design conditions, as indicated on
the job data specifications. An approximate charge may be
When equalizing refrigerant pressure on the 19XR chiller determined by adding the condenser charge to the cooler charge
after service work or during the initial chiller start-up, as listed in Table 7.
do not use the discharge isolation valve to equalize.
Either the motor cooling isolation valve or the charging
hose (connected between the pumpout valves on top of Table 7 — Refrigerant (HFC-134a) Charge
the cooler and condenser) should be used as the equal-
ization valve. REFRIGERANT REFRIGERANT
COOLER CHARGE CONDENSER CHARGE
CODE CODE
To equalize the pressure differential on a refrigerant iso- lb kg lb kg
lated 19XR chiller, use the terminate lockout function of the 10 290 132 10 200 91
11 310 141 11 200 91
CONTROL TEST on the SERVICE menu. This helps to turn 12 330 150 12 200 91
on pumps and advises the operator on proper procedures. 15 320 145 15 250 113
The following steps describe how to equalize refrigerant 16 340 154 16 250 113
17 370 168 17 250 113
pressure in an isolated 19XR chiller without a pumpout unit. 20 345 157 20 225 102
1. Access terminate lockout function on the CONTROL TEST 21 385 175 21 225 102
22 435 197 22 225 102
screen. 30 350 159 30 260 118
2. IMPORTANT: Turn on the chilled water and con- 31 420 190 31 260 118
32 490 222 32 260 118
denser water pumps to prevent freezing. 35 400 181 35 310 141
36 480 218 36 310 141
37 550 250 37 310 141
3. Slowly open the refrigerant cooling isolation valve. The 40 560 254 40 280 127
chiller cooler and condenser pressures will gradually equal- 41 630 286 41 280 127
ize. This process takes approximately 15 minutes. 42 690 313 42 280 127
45 640 290 45 330 150
4. Once the pressures have equalized, the cooler isolation 46 720 327 46 330 150
valve, the condenser isolation valve, and the hot gas iso- 47 790 358 47 330 150
lation valve may now be opened. Refer to Fig. 26 and 27, 50 750 340 50 400 181
for the location of the valves. 51 840 381 51 400 181
52 900 408 52 400 181
55 870 395 55 490 222
56 940 426 56 490 222
57 980 445 57 490 222
Whenever turning the discharge isolation valve, be 60 940 426 60 420 190
sure to reattach the valve locking device. This pre- 61 980 445 61 420 190
vents the valve from opening or closing during serv- 62 1020 463 62 420 190
65 1020 463 65 510 231
ice work or during chiller operation. 66 1060 481 66 510 231
67 1090 494 67 510 231
70 1220 553 70 780 354
CHILLER EQUALIZATION WITH PUMPOUT UNIT — 71 1340 608 71 780 354
The following steps describe how to equalize refrigerant pres- 72 1440 653 72 780 354
sure on an isolated 19XR chiller using the pumpout unit. 75 1365 619 75 925 420
76 1505 683 76 925 420
1. Access the terminate lockout function on the CONTROL 77 1625 737 77 925 420
TEST screen. 80 1500 680 80 720 327
81 1620 735 81 720 327
2. IMPORTANT: Turn on the chilled water and con- 82 1730 785 82 720 327
85 1690 766 85 860 390
denser water pumps to prevent possible freezing. 86 1820 825 86 860 390
87 1940 880 87 860 390
3. Open valve 4 on the pumpout unit and open valves 1a
and 1b on the chiller cooler and condenser, Fig. 26 and
27. Slowly open valve 2 on the pumpout unit to equalize
the pressure. This process takes approximately
15 minutes.
57
2. Observe the default screen on the CVC: the Status mes-
sage in the upper left-hand corner reads, ‘‘Manually
Always operate the condenser and chilled water pumps Stopped.’’ Press the CCN or LOCAL softkey to start.
whenever charging, transferring, or removing refrig- If the chiller controls do not go into a start mode, go to
rant from the chiller. the Schedule screen and override the schedule or change
the occupied time. Press the LOCAL softkey to begin
Use the CONTROL TEST terminate lockout function to the start-up sequences.
monitor conditions and start the pumps. 3. Verify the chilled water and condenser water pumps
If the chiller has been shipped with a holding charge, the have energized.
refrigerant is added through the refrigerant charging valve 4. Verify the oil pump has started and is pressurizing the
(Fig. 26 and 27, valve 7) or to the pumpout charging con- lubrication system. After the oil pump has run about
nection. First evacuate the nitrogen holding charge from the 11 seconds, the starter energizes and goes through its start-up
chiller vessels. Charge the refrigerant as a gas until the sys- sequence.
tem pressure exceeds 35 psig (141 kPa) for HFC-134a. After
the chiller is beyond this pressure the refrigerant should be 5. Check the main contactor for proper operation.
charged as a liquid until all the recommended refrigerant charge 6. The PIC II eventually shows an alarm for motor amps
has been added. not sensed. Reset this alarm and continue with the initial
TRIMMING REFRIGERANT CHARGE — The 19XR is start-up.
shipped with the correct charge for the design duty of the Check Motor Rotation
chiller. Trimming the charge can best be accomplished when
the design load is available. To trim the charge, check the 1. Engage the main motor disconnect on the front of the starter
temperature difference between the leaving chilled water tem- panel. The motor is now ready for a rotation check.
perature and cooler refrigerant temperature at full load 2. After the default screen status message states ‘‘Ready
design conditions. If necessary, add or remove refrigerant to for Start’’ press the LOCAL softkey. The PIC II control
bring the temperature difference to design conditions or mini- performs start-up checks.
mum differential.
3. When the starter is energized and the motor begins to turn,
Table 7 lists the 19XR chiller refrigerant charges for each check for clockwise motor rotation (Fig. 29).
cooler and condenser code. Total refrigerant charge is the
sum of the cooler and condenser charge. IF THE MOTOR ROTATION IS CLOCKWISE, allow the
compressor to come up to speed.
IF THE MOTOR ROTATION IS NOT CLOCKWISE
INITIAL START-UP (as viewed through the sight glass), reverse any 2 of the 3
incoming power leads to the starter and recheck the rotation.
Preparation — Before starting the chiller, verify:
NOTE: Solid-state starters have phase protection and do not
1. Power is on to the main starter, oil pump relay, tower fan permit a start if the phase is not correct. If this happens, a
starter, oil heater relay, and the chiller control panel. fault message appears on the CVC.
2. Cooling tower water is at proper level and at-or-below
design entering temperature.
3. Chiller is charged with refrigerant and all refrigerant and Do not check motor rotation during coastdown. Rota-
oil valves are in their proper operating positions. tion may have reversed during equalization of vessel
4. Oil is at the proper level in the reservoir sight glasses. pressures.
5. Oil reservoir temperature is above 140 F (60 C) or re-
frigerant temperature plus 50° F (28° C).
6. Valves in the evaporator and condenser water circuits are
open.
NOTE: If the pumps are not automatic, ensure water is
circulating properly.
58
Check Oil Pressure and Compressor Stop REVIEW MAINTENANCE — Scheduled, routine, and
extended shutdowns, importance of a log sheet, importance
1. When the motor is at full speed, note the differential oil of water treatment and tube cleaning, and importance of main-
pressure reading on the CVC default screen. It should be taining a leak-free chiller.
between 18 and 30 psid (124 to 206 kPad).
2. Press the Stop button and listen for any unusual sounds SAFETY DEVICES AND PROCEDURES — Electrical dis-
from the compressor as it coasts to a stop. connects, relief device inspection, and handling refrigerant.
To Prevent Accidental Start-Up — A chiller STOP CHECK OPERATOR KNOWLEDGE — Start, stop, and shut-
override setting may be entered to prevent accidental start-up down procedures, safety and operating controls, refrigerant
and oil charging, and job safety.
during service or whenever necessary. Access the MAIN-
REVIEW THE START-UP, OPERATION, AND MAINTE-
STAT screen and using the NEXT or PREVIOUS soft- NANCE MANUAL.
keys, highlight the CHILLER START/STOP parameter. Override
the current START value by pressing the SELECT softkey.
Press the STOP softkey followed by the ENTER softkey. OPERATING INSTRUCTIONS
The word SUPVSR! displays on the CVC indicating the over-
ride is in place. Operator Duties
To restart the chiller the STOP override setting must be 1. Become familiar with the chiller and related equipment
removed. Access the MAINSTAT screen and using before operating the chiller.
NEXT or PREVIOUS softkeys highlight CHILLER 2. Prepare the system for start-up, start and stop the chiller,
START/STOP. The 3 softkeys that appear represent 3 choices: and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any
• START — forces the chiller ON abnormal readings.
• STOP — forces the chiller OFF 4. Inspect the equipment, make routine adjustments, and per-
• RELEASE — puts the chiller under remote or schedule form a Control Test. Maintain the proper oil and refrig-
erant levels.
control.
5. Protect the system from damage during shutdown
To return the chiller to normal control, press the periods.
RELEASE softkey followed by the ENTER softkey. For 6. Maintain the set point, time schedules, and other PIC
more information, see Local Start-Up, page 44. functions.
The default LID screen message line indicates which com-
mand is in effect. Prepare the Chiller for Start-Up — Follow the steps
described in the Initial Start-Up section, page 58.
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and To Start the Chiller
oil and refrigerant levels indicate the system is functioning 1. Start the water pumps, if they are not automatic.
properly. 2. On the CVC default screen, press the LOCAL or
Instruct the Customer Operator — Ensure the CCN softkey to start the system. If the chiller is in the
operator(s) understand all operating and maintenance pro- OCCUPIED mode and the start timers have expired, the
cedures. Point out the various chiller parts and explain their start sequence will start. Follow the procedure described
function as part of the complete system. in the Start-Up/Shutdown/Recycle section, page 44.
COOLER-CONDENSER — Float chamber, relief valves, re-
frigerant charging valve, temperature sensor locations, pres- Check the Running System — After the compres-
sure transducer locations, Schrader fittings, waterboxes and sor starts, the operator should monitor the CVC display and
tubes, and vents and drains. observe the parameters for normal operating conditions:
OPTIONAL PUMPOUT STORAGE TANK AND PUMP- 1. The oil reservoir temperature should be above 120 F
OUT SYSTEM — Transfer valves and pumpout system, (49 C) during shutdown and above 125 F (58 C) during
refrigerant charging and pumpdown procedure, and relief compressor operation.
devices. 2. The bearing oil temperature accessed on the COM-
MOTOR COMPRESSOR ASSEMBLY — Guide vane PRESS table should be 120 to 165 F (49 to 74 C). If the
actuator, transmission, motor cooling system, oil cooling bearing temperature reads more than 180 F (83 C) with
system, temperature and pressure sensors, oil sight glasses, the oil pump running, stop the chiller and determine the
integral oil pump, isolatable oil filter, extra oil and motor cause of the high temperature. Do not restart the chiller
temperature sensors, synthetic oil, and compressor until corrected.
serviceability. 3. The oil level should be visible anywhere in one of the
MOTOR COMPRESSOR LUBRICATION SYSTEM — Oil two sight glasses. Foaming oil is acceptable as long as
pump, cooler filter, oil heater, oil charge and specification, the oil pressure and temperature are within limits.
operating and shutdown oil level, temperature and pressure, 4. The oil pressure should be between 18 and 30 psid
and oil charging connections. (124 to 207 kPad) differential, as seen on the CVC de-
CONTROL SYSTEM — CCN and LOCAL start, reset, menu, fault screen. Typically the reading will be 18 to 25 psid
softkey functions, CVC operation, occupancy schedule, set (124 to 172 kPad) at initial start-up.
points, safety controls, and auxiliary and optional controls. 5. The moisture indicator sight glass on the refrigerant
AUXILIARY EQUIPMENT — Starters and disconnects, sepa- motor cooling line should indicate refrigerant flow and a
rate electrical sources, pumps, and cooling tower. dry condition.
DESCRIBE CHILLER CYCLES — Refrigerant, motor cool- 6. The condenser pressure and temperature varies with
ing, lubrication, and oil reclaim. the chiller design conditions. Typically the pressure will
range between 100 and 210 psig (690 to 1450 kPa)
59
with a corresponding temperature range of 60 to 105 F Check the cooler pressure on the CVC default screen and
(15 to 41 C). The condenser entering water temperature compare it to the original holding charge that was left in the
should be controlled below the specified design entering chiller. If (after adjusting for ambient temperature changes)
water temperature to save on compressor kilowatt any loss in pressure is indicated, check for refrigerant leaks.
requirements. See Check Chiller Tightness section, page 46.
7. Cooler pressure and temperature also will vary with the Recharge the chiller by transferring refrigerant from the
design conditions. Typical pressure range will be be- pumpout storage tank (if supplied). Follow the Pumpout and
tween 60 and 80 psig (410 and 550 kPa), with tempera- Refrigerant Transfer Procedures section, this page. Observe
ture ranging between 34 and 45 F (1 and 8 C). freeze-up precautions.
8. The compressor may operate at full capacity for a short Carefully make all regular preliminary and running sys-
time after the pulldown ramping has ended, even though tem checks. Perform a Control Test before start-up. If the
the building load is small. The active electrical demand compressor oil level appears abnormally high, the oil may
setting can be overridden to limit the compressor IkW, or have absorbed refrigerant. Ensure that the oil temperature is
the pulldown rate can be decreased to avoid a high above 140 F (60 C) or above the cooler refrigerant tempera-
demand charge for the short period of high demand ture plus 50° F (27° C).
operation. Pulldown rate can be based on load rate or tem-
perature rate. It is accessed on the Equipment SERVICE Cold Weather Operation — When the entering con-
screen, RAMP_DEM table (Table 2, Example 20). denser water temperature drops very low, the operator should
automatically cycle the cooling tower fans off to keep the
To Stop the Chiller temperature up. Piping may also be arranged to bypass the
1. The occupancy schedule starts and stops the chiller cooling tower. The PIC II controls have a low limit tower
automatically once the time schedule is configured. fan output that can be used to assist in this control (terminal
11 and 12 on ISM).
2. By pressing the STOP button for one second, the alarm
light blinks once to confirm the button has been pressed. Manual Guide Vane Operation — It is possible to
The compressor will then follow the normal shutdown manually operate the guide vanes in order to check con-
sequence as described in the Controls section. The chiller trol operation or to control the guide vanes in an emergency.
will not restart until the CCN or LOCAL softkey is Manual operation is possible by overriding the target guide
pressed. The chiller is now in the OFF control mode. vane position. Access the COMPRESS screen on the CVC
and scroll down to highlight TARGET GUIDE VANE
IMPORTANT: Do not attempt to stop the chiller by POS. To control the position, use the INCREASE or
opening an isolating knife switch. High intensity DECREASE softkey to adjust to the percentage of guide
arcing may occur.
vane opening that is desired. Zero percent is fully closed;
100% is fully open. To release the guide vanes to automatic
Do not restart the chiller until the problem is diagnosed
and corrected. control, press the RELEASE softkey.
NOTE: Manual control increases the guide vane openings
After Limited Shutdown — No special preparations and overrides the pulldown rate during start-up. Motor cur-
should be necessary. Follow the regular preliminary checks rent above the electrical demand setting, capacity overrides,
and starting procedures. and chilled water temperature below the control point over-
Preparation for Extended Shutdown — The ride the manual target and close the guide vanes. For
refrigerant should be transferred into the pumpout storage descriptions of capacity overrides and set points, see the
tank (if supplied; see Pumpout and Refrigerant Transfer Controls section.
Procedures) to reduce chiller pressure and the possibility Refrigeration Log — A refrigeration log (as shown in
of leaks. Maintain a holding charge of 5 to 10 lbs (2.27 to Fig. 30), is a convenient checklist for routine inspection and
4.5 kg) of refrigerant or nitrogen to prevent air from leaking maintenance and provides a continuous record of chiller
into the chiller. performance. It is also an aid when scheduling routine main-
If freezing temperatures are likely to occur in the chiller tenance and diagnosing chiller problems.
area, drain the chilled water, condenser water, and the pump- Keep a record of the chiller pressures, temperatures, and
out condenser water circuits to avoid freeze-up. Keep the liquid levels on a sheet similar to the one in Fig. 30. Auto-
waterbox drains open. matic recording of PIC II data is possible by using CCN
Leave the oil charge in the chiller with the oil heater devices such as the Data Collection module and a Build-
and controls energized to maintain the minimum oil reser- ing Supervisor. Contact a Carrier representative for more
voir temperature. information.
After Extended Shutdown — Ensure the water sys-
tem drains are closed. It may be advisable to flush the water
circuits to remove any soft rust which may have formed. This
is a good time to brush the tubes and inspect the Schrader
fittings on the waterside flow devices for fouling, if
necessary.
60
Date
REMARKS: Indicate shutdowns on safety controls, repairs made, oil or refrigerant added or removed, air exhausted and water
drained from dehydrator. Include amounts.
Fig. 30 — Refrigeration Log
PUMPOUT AND REFRIGERANT 3. Refer to Fig. 26, 27, and 32 for valve locations and
TRANSFER PROCEDURES numbers.
Preparation — The 19XR may come equipped with an
optional pumpout storage tank, pumpout system, or pump-
out compressor. The refrigerant can be pumped for service Transfer, addition, or removal of refrigerant in spring-
work to either the chiller compressor vessel or chiller con- isolated chillers may place severe stress on external pip-
denser vessel by using the optional pumpout system. If a ing if springs have not been blocked in both up and down
pumpout storage tank is supplied, the refrigerant can be iso- directions.
lated in the storage tank. The following procedures describe
how to transfer refrigerant from vessel to vessel and perform
chiller evacuations.
62
Chillers with Storage Tanks — If the chiller has iso- TRANSFER REFRIGERANT FROM CHILLER TO
lation valves, leave them open for the following procedures. PUMPOUT STORAGE TANK
The letter ‘‘C’’ describes a closed valve. See Fig. 15, 16, 26, 1. Equalize refrigerant pressure.
and 27. a. Valve positions:
TRANSFER REFRIGERANT FROM PUMPOUT STOR- VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
AGE TANK TO CHILLER CONDITION C C C C C
1. Equalize refrigerant pressure.
a. Use the PIC II terminate lockout function on the PUMP- b. Slowly open valve 5. When the pressures are equal-
DOWN LOCKOUT screen, accessed from the CON- ized, open liquid line valve 7 to allow liquid refrig-
TROL TEST table to turn on the water pumps and erant to drain by gravity into the pumpout storage tank.
monitor pressures. VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C
If the chilled water and condenser water pumps are 2. Transfer the remaining liquid.
not controlled by the PIC II, these pumps must be a. Turn off the pumpout condenser water. Place the valves
started and stopped manually at the appropriate times in the following positions:
during the refrigerant transfer procedure. VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C
b. Close pumpout unit valves 2, 4, 5, 8, and 10, and close
chiller charging valve 7; open chiller isolation valves b. Run the pumpout compressor for approximately 30 min-
11, 12, 13, and 14 (if present). utes; then close valve 10.
c. Open pumpout unit/storage tank valves 3 and 6, open VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
chiller valves 1a and 1b. CONDITION C C C C
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C C C C
c. Turn off the pumpout compressor.
3. Remove any remaining refrigerant.
d. Slowly open valve 5 to increase chiller pressure to a. Turn on the chiller water pumps using the PUMP-
68 psig 35 psig (141 kPa) for HFC-134a. Feed refrig- DOWN LOCKOUT screen, accessed from the CON-
erant slowly to prevent freeze up. TROL TEST table. Turn on the pumps manually, if
e. Open valve 5 fully after the pressure rises above the they are not controlled by the PIC II.
freeze point of the refrigerant. Open liquid line valves b. Turn on the pumpout condenser water.
7 and 10 until refrigerant pressure equalizes.
c. Place valves in the following positions:
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C
CONDITION C C C C
2. Transfer the remaining refrigerant.
d. Run the pumpout compressor until the chiller pres-
a. Close valve 5 and open valve 4. sure reaches 30 psig (207 kPa) for HFC-134a. Then,
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
shut off the pumpout compressor. Warm condenser
CONDITION C C C
water will boil off any entrapped liquid refrigerant and
the chiller pressure will rise.
b. Turn off the chiller water pumps using the CVC (or e. When the pressure rises to 40 psig (276 kPa) for
manually, if necessary). HFC-134a, turn on the pumpout compressor until the
c. Turn off the pumpout condenser water, and turn on the pressure again reaches 30 psig (207 kPa), and then
pumpout compressor to push liquid out of the storage turn off the pumpout compressor. Repeat this process
tank. until the pressure no longer rises. Then, turn on the
pumpout compressor and pump until the pressure reaches
d. Close liquid line valve 7. 18 in. Hg. (40 kPa absolute).
e. Turn off the pumpout compressor. f. Close valves 1a, 1b, 3, 4, 6, 7, and 10.
f. Close valves 3 and 4.
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
g. Open valves 2 and 5.
CONDITION C C C C C C C C C C
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C C g. Turn off the pumpout condenser water and continue to
use the PIC II PUMPDOWN LOCKOUT screen func-
h. Turn on the pumpout condenser water. tions, which lock out the chiller compressor for
i. Run the pumpout compressor until the pumpout stor- operation.
age tank pressure reaches 5 psig (34 kPa) (18 in. Hg 4. Establish a vacuum for service.
[40 kPa absolute] if repairing the tank). To conserve refrigerant, operate the pumpout compressor
j. Turn off the pumpout compressor. until the chiller pressure is reduced to 18 in. Hg vac., ref
k. Close valves 1a, 1b, 2, 5, 6, and 10. 30 in. bar. (40 kPa abs.) following Step 3e.
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C C C C C C C C
63
Chillers with Isolation Valves 2. Evacuate the refrigerant gas from the chiller condenser
vessel.
TRANSFER ALL REFRIGERANT TO CHILLER CON- a. Access the PUMPDOWN LOCKOUT function ac-
DENSER VESSEL — For chillers with isolation valves, cessed from the CVC CONTROL TEST table to turn
refrigerant can be stored in one chiller vessel or the other on the chiller water pumps. Turn the chiller water pumps
without the need for an external storage tank. on manually if they are not controlled by the PIC II.
1. Push refrigerant into the chiller condenser. b. Close pumpout unit valves 3 and 4; open valves 2
a. Valve positions: and 5.
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 VALVE 1a 1b 2 3 4 5 8 11 12 13 14
CONDITION C C C C C C CONDITION C C C C C C C
b. Using the PIC II controls, turn off the chiller water c. Turn on the pumpout condenser water.
pumps and pumpout condenser water. If the chiller d. Run the pumpout compressor until the chiller con-
water pumps are not controlled through the PIC II, turn denser pressure reaches 18 in. Hg vac (40 kPa abs.).
them off manually. Monitor pressure at the CVC and at refrigerant gages.
c. Turn on the pumpout compressor to push the liquid e. Close valve 1b.
refrigerant out of the chiller cooler vessel.
f. Turn off the pumpout compressor.
d. When all liquid refrigerant has been pushed into
the chiller condenser vessel, close chiller isolation g. Close valves 1a, 2, and 5.
valve 11. VALVE 1a 1b 2 3 4 5 8 11 12 13 14
e. Access the PUMPDOWN LOCKOUT screen on the CONDITION C C C C C C C C C C C
PIC II CONTROL TEST table to turn on the chiller
water pumps. If the chiller water pumps are not con- h. Turn off the pumpout condenser water.
trolled by the PIC II, turn them on manually. i. Proceed to the PUMPDOWN LOCKOUT test from
f. Turn off the pumpout compressor. the CVC CONTROL TEST table to turn off the chill-
er water pumps and lock out the chiller compressor.
2. Evacuate the refrigerant gas from chiller cooler vessel. Turn off the chiller water pumps manually if they are
a. Close pumpout compressor valves 2 and 5, and open not controlled by the PIC II.
valves 3 and 4.
RETURN CHILLER TO NORMAL OPERATING
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITIONS
CONDITION C C C C C C C
1. Ensure vessel that was opened has been evacuated.
b. Turn on the pumpout condenser water. 2. Access the TERMINATE LOCKOUT function CVC from
c. Run the pumpout compressor until the chiller cooler the CONTROL TEST table to view vessel pressures and
vessel pressure reaches 18 in. Hg vac (40 kPa abs.). turn on chiller water pumps. If the chiller water pumps
Monitor pressures on the CVC and on refrigerant gages. are not controlled by the PIC II, turn them on manually.
d. Close valve 1a. 3. Open valves 1a, 1b, and 3.
e. Turn off the pumpout compressor. VALVE 1a 1b 2 3 4 5 8 11 12 13 14
f. Close valves 1b, 3, and 4. CONDITION C C C C C C C C
64
GENERAL MAINTENANCE
Refrigerant Properties — The standard refrigerant for
the 19XR chiller is HFC-134a. At normal atmospheric pres- HFC-134a should not be mixed with air or oxygen and
sure, HFC-134a will boil at –14 F (–25 C) and must, there- pressurized for leak testing. In general, this refrigerant
fore, be kept in pressurized containers or storage tanks. The should not be present with high concentrations of air or
refrigerant is practically odorless when mixed with air oxygen above atmospheric pressures, because the mix-
and is noncombustible at atmospheric pressure. Read the ture can undergo combustion.
Material Safety Data Sheet and the latest ASHRAE Safety
Guide for Mechanical Refrigeration to learn more about safe REFRIGERANT TRACER — Use an environmentally
handling of this refrigerant. acceptable refrigerant as a tracer for leak test procedures.
TO PRESSURIZE WITH DRY NITROGEN — Another
method of leak testing is to pressurize with nitrogen only
HFC-134a will dissolve oil and some nonmetallic ma- and to use a soap bubble solution or an ultrasonic leak
terials, dry the skin, and, in heavy concentrations, may detector to determine if leaks are present.
displace enough oxygen to cause asphyxiation. When NOTE: Pressurizing with dry nitrogen for leak testing should
handling this refrigerant, protect the hands and eyes and only be done if all refrigerant has been evacuated from the
avoid breathing fumes. vessel.
1. Connect a copper tube from the pressure regulator on the
Adding Refrigerant — Follow the procedures de- cylinder to the refrigerant charging valve. Never apply
scribed in Trim Refrigerant Charge section, this page. full cylinder pressure to the pressurizing line. Follow the
listed sequence.
2. Open the charging valve fully.
Always use the compressor pumpdown function in the 3. Slowly open the cylinder regulating valve.
Control Test table to turn on the cooler pump and lock 4. Observe the pressure gage on the chiller and close the
out the compressor when transferring refrigerant. Liq- regulating valve when the pressure reaches test level. Do
uid refrigerant may flash into a gas and cause possible not exceed 140 psig (965 kPa).
freeze-up when the chiller pressure is below
30 psig (207 kPa) for HFC-134a. 5. Close the charging valve on the chiller. Remove the cop-
per tube if it is no longer required.
Removing Refrigerant — If the optional pumpout sys- Repair the Leak, Retest, and Apply Standing
tem is used, the 19XR refrigerant charge may be transferred Vacuum Test — After pressurizing the chiller, test for
to a pumpout storage tank or to the chiller condenser or cooler leaks with an electronic halide leak detector, soap bubble
vessels. Follow the procedures in the Pumpout and Refrig- solution, or an ultrasonic leak detector. Bring the chiller back
erant Transfer Procedures section when transferring refrig- to atmospheric pressure, repair any leaks found, and retest.
erant from one vessel to another. After retesting and finding no leaks, apply a standing vacuum
Adjusting the Refrigerant Charge — If the addi- test. Then dehydrate the chiller. Refer to the Standing Vacuum
tion or removal of refrigerant is required to improve chiller Test and Chiller Dehydration section (pages 48 and 51) in
performance, follow the procedures given under the Trim the Before Initial Start-Up section.
Refrigerant Charge section, this page. Checking Guide Vane Linkage — When the
Refrigerant Leak Testing — Because HFC-134a is chiller is off, the guide vanes are closed and the actuator
above atmospheric pressure at room temperature, leak test- mechanism is in the position shown in Fig. 33. If slack de-
ing can be performed with refrigerant in the chiller. Use an velops in the drive chain, do the following to eliminate
electronic halide leak detector, soap bubble solution, or ultra- backlash:
sonic leak detector. Ensure that the room is well ventilated 1. With the chiller shut down and the actuator fully closed,
and free from concentration of refrigerant to keep false read- remove the chain guard and loosen the actuator bracket
ings to a minimum. Before making any necessary repairs to holddown bolts.
a leak, transfer all refrigerant from the leaking vessel. 2. Loosen guide vane sprocket adjusting bolts.
Leak Rate — It is recommended byASHRAE that chill- 3. Pry bracket upwards to remove slack, then retighten the
ers be taken off line immediately and repaired if the refrig- bracket holddown bolts.
erant leak rate for the entire chiller is more than 10% of the 4. Retighten the guide vane sprocket adjusting bolts. En-
operating refrigerant charge per year. sure that the guide vane shaft is rotated fully in the clock-
In addition, Carrier recommends that leaks totalling less wise direction in order close it fully.
than the above rate but more than a rate of 0.1% of the total Trim Refrigerant Charge — If, to obtain optimal chiller
charge per year should be repaired during annual mainte- performance, it becomes necessary to adjust the refrigerant
nance or whenever the refrigerant is transferred for other serv- charge, operate the chiller at design load and then add or
ice work. remove refrigerant slowly until the difference between the
Test After Service, Repair, or Major Leak — If leaving chilled water temperature and the cooler refrigerant
all the refrigerant has been lost or if the chiller has been opened temperature reaches design conditions or becomes a mini-
for service, the chiller or the affected vessels must be pres- mum. Do not overcharge.
sure tested and leak tested. Refer to the Leak Test Chiller Refrigerant may be added either through the storage tank
section to perform a leak test. or directly into the chiller as described in the Charge
Refrigerant into Chiller section.
To remove any excess refrigerant, follow the procedure in
Transfer Refrigerant from Chiller to Pumpout Storage Tank
section, Steps 1a and b, page 63.
65
Service Ontime — The CVC will display a SERVICE
ONTIME value on the MAINSTAT screen. This value should
be reset to zero by the service person or the operator each
time major service work is completed so that the time be-
tween service can be viewed and tracked.
Inspect the Control Panel — Maintenance consists
of general cleaning and tightening of connections. Vacuum
the cabinet to eliminate dust build-up. If the chiller control
malfunctions, refer to the Troubleshooting Guide section for
control checks and adjustments.
66
Oil Specification — If oil is added, it must meet the 3. Clean the chamber and valve assembly thoroughly. Be
following Carrier specifications: sure the valve moves freely. Ensure that all openings are
free of obstructions.
Oil Type for units using R-134a . . . . . . . . . . . . . . Inhibited
polyolester-based synthetic 4. Examine the cover gasket and replace if necessary.
compressor oil formatted for See Fig. 34 for a view of the float valve design. For linear
use with HFC, gear-driven, float valve designs, inspect the orientation of the float slide
hermetic compressors. pin. It must be pointed toward the bubbler tube for proper
ISO Viscosity Grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 operation.
68
2. Close the suction service valve and open the discharge • The CONTROL ALGORITHM STATUS screens (which
line to the storage tank or the chiller. include the CAPACITY, OVERRIDE, LL_MAINT,
3. Operate the compressor until the crankcase pressure drops ISM_HIST, LOADSHED, WSMDEFME, and OCCDEFCM
to 2 psig (13 kPa). screens) display information that helps to diagnose prob-
lems with chilled water temperature control, chilled water
4. Stop the compressor and isolate the system by closing temperature control overrides, hot gas bypass, surge al-
the discharge service valve. gorithm status, and time schedule operation.
5. Slowly remove the oil return line connection (Fig. 32). • The control test feature facilitates the proper operation and
Add oil as required. test of temperature sensors, pressure transducers, the guide
6. Replace the connection and reopen the compressor serv- vane actuator, oil pump, water pumps, tower control, and
ice valves. other on/off outputs while the compressor is stopped. It
OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS also has the ability to lock off the compressor and turn on
(Fig. 35) — The optional pumpout system high-pressure switch water pumps for pumpout operation. The CVC shows the
opens at 161 psig (1110 kPa) and closes at 130 psig temperatures and pressures required during these
(896 kPa). Check the switch setting by operating the pump- operations.
out compressor and slowly throttling the pumpout con- • From other SERVICE tables, the operator/technician can
denser water. access configured items, such as chilled water resets, over-
ride set points, etc.
• If an operating fault is detected, an alarm message is gen-
erated and displayed on the CVC default screen. A more
detailed message — along with a diagnostic message —
is also stored into the ALARM HISTORY table.
Checking Display Messages — The first area to check
when troubleshooting the 19XR is the CVC display. If the
alarm light is flashing, check the primary and secondary mes-
sage lines on the CVC default screen (Fig. 12). These mes-
sages will indicate where the fault is occurring. These mes-
sages contain the alarm message with a specified code. This
code or state appears with each alarm and alert message. The
ALARM HISTORY table on the CVC SERVICE menu also
contains an alarm message to further expand on the alarm.
For a complete list of possible alarm messages, see Table 8.
If the alarm light starts to flash while accessing a menu screen,
press the EXIT softkey to return to the default screen to
read the alarm message. The STATUS screen can also be
accessed to determine where an alarm exists.
Checking Temperature Sensors — All tempera-
ture sensors are thermistor-type sensors. This means that the
resistance of the sensor varies with temperature. All sensors
Fig. 35 — Optional Pumpout System Controls have the same resistance characteristics. If the controls are
on, determine sensor temperature by measuring voltage drop;
if the controls are powered off, determine sensor tempera-
Ordering Replacement Chiller Parts — When ture by measuring resistance. Compare the readings to the
ordering Carrier specified parts, the following information values listed in Table 9A or 9B.
must accompany an order: RESISTANCE CHECK — Turn off the control power and,
• chiller model number and serial number from the module, disconnect the terminal plug of the sensor
• name, quantity, and part number of the part required in question. With a digital ohmmeter, measure sensor resis-
tance between receptacles as designated by the wiring dia-
• delivery address and method of shipment. gram. The resistance and corresponding temperature are listed
in Table 9A or 9B. Check the resistance of both wires to
ground. This resistance should be infinite.
TROUBLESHOOTING GUIDE VOLTAGE DROP — The voltage drop across any ener-
Overview — The PIC II has many features to help the gized sensor can be measured with a digital voltmeter while
operator and technician troubleshoot a 19XR chiller. the control is energized. Table 9A or 9B lists the relation-
ship between temperature and sensor voltage drop (volts dc
• The CVC shows the chiller’s actual operating conditions measured across the energized sensor). Exercise care when
and can be viewed while the unit is running. measuring voltage to prevent damage to the sensor leads,
• The CVC default screen freezes when an alarm occurs. connector plugs, and modules. Sensors should also be checked
The freeze enables the operator to view the chiller con- at the sensor plugs. Check the sensor wire at the sensor for
ditions at the time of alarm. The STATUS screens con- 5 vdc if the control is powered on.
tinue to show current information. Once all alarms have
been cleared (by correcting the problems and pressing the
RESET softkey), the CVC default screen returns to nor- Relieve all refrigerant pressure or drain the water be-
mal operation. fore replacing the temperature sensors.
69
CHECK SENSOR ACCURACY — Place the sensor in a CONDENSER PRESSURE parameter on the HEAT_EX
medium of known temperature and compare that temper- screen). To calibrate oil pressure or waterside flow de-
ature to the measured reading. The thermometer used to vice, view the particular reading (CHILLED WATER DELTA
determine the temperature of the medium should be of P and CONDENSER WATER DELTA P on the HEAT_EX
laboratory quality with 0.5° F (.25° C) graduations. The sen- screen, and OIL PUMP DELTA P on the COMPRESS
sor in question should be accurate to within 2° F (1.2° C). screen). It should read 0 psi (0 kPa). If the reading is not
See Fig. 7 for sensor locations. The sensors are immersed 0 psi
directly in the refrigerant or water circuits. The wiring at each (0 kPa), but within ± 5 psi (35 kPa), the value may be set
sensor is easily disconnected by unlatching the connector. to zero by pressing the SELECT softkey while the ap-
These connectors allow only one-way connection to the sen- propriate transducer parameter is highlighted on the CVC
sor. When installing a new sensor, apply a pipe sealant or
thread sealant to the sensor threads. screen. Then press the ENTER softkey. The value will
now go to zero. No high end calibration is necessary for
DUAL TEMPERATURE SENSORS — For servicing con- OIL PUMP DELTA P or flow devices.
venience, there are 2 sensors each on the bearing and motor
temperature sensors. If one of the sensors is damaged, the If the transducer value is not within the calibration range,
other can be used by simply moving a wire. The number 2 the transducer returns to the original reading. If the pres-
terminal in the sensor terminal box is the common line. To sure is within the allowed range (noted above), check the
use the second sensor, move the wire from the number 1 voltage ratio of the transducer. To obtain the voltage ra-
position to the number 3 position. tio, divide the voltage (dc) input from the transducer by
the supply voltage signal (displayed in CONTROL TEST
Checking Pressure Transducers — There are menu in the CCM PRESSURE TRANSDUCERS screen)
8 pressure transducers on 19XR chillers. They determine or measure across the positive (+ red) and negative
cooler, condenser, oil pressure, and cooler and condenser flow. (− black) leads of the transducer. For example, the con-
The cooler and condenser transducers are also used by the denser transducer voltage input is measured at CCM ter-
PIC II to determine the refrigerant temperatures. The oil sup- minals J2-4 and J2-5. The voltage ratio must be between
ply pressure transducer value and the oil transmission sump 0.80 and 0.11 for the software to allow calibration. Pres-
pressure transducer value difference is calculated by the CCM. surize the transducer until the ratio is within range. Then
The CCM module then displays the differential pressure. In attempt calibration again.
effect, the CCM reads only one input for oil pressure for a 4. A high pressure point can also be calibrated between 25
total of 5 pressure inputs: cooler pressure, condenser pres- and 250 psig (172.4 and 1723.7 kPa) by attaching a regu-
sure, oil differential pressure, cooler waterside differential lated 250 psig (1724 kPa) pressure (usually from
pressure, and condenser waterside differential pressure. See a nitrogen cylinder). The high pressure point can be cali-
the Check Pressure Transducers section (page 68) under Sched- brated by accessing the appropriate transducer parameter
uled Maintenance. on the HEAT_EX screen, highlighting the parameter, press-
These 5 pressure transducers can be calibrated if neces- ing the SELECT softkey, and then using the
sary. It is not usually necessary to calibrate at initial start-up.
However, at high altitude locations, it is necessary to cali- INCREASE or DECREASE softkeys to adjust the
brate the transducers to ensure the proper refrigerant value to the exact pressure on the refrigerant gage. Press
temperature/pressure relationship. Each transducer is sup- the ENTER softkey to finish the calibration. Pressures
plied with 5 vdc power from the CCM. If the power supply
fails, a transducer voltage reference alarm occurs. If the trans- at high altitude locations must be compensated for, so the
ducer reading is suspected of being faulty, check the supply chiller temperature/pressure relationship is correct.
voltage. It should be 5 vdc ± .5 v displayed in CONTROL The PIC II does not allow calibration if the transducer is
TEST under CCM Pressure Transducers. If the supply too far out of calibration. In this case, a new transducer must
voltage is correct, the transducer should be recalibrated or be installed and re-calibrated.
replaced. TRANSDUCER REPLACEMENT — Since the trans-
COOLER CONDENSER PRESSURE TRANSDUCER AND ducers are mounted on Schrader-type fittings, there is no
WATERSIDE FLOW DEVICE CALIBRATION — Cali- need to remove refrigerant from the vessel when replacing
bration can be checked by comparing the pressure readings the transducers. Disconnect the transducer wiring by pulling
from the transducer to an accurate refrigeration gage read- up on the locking tab while pulling up on the weather-tight
ing. These readings can be viewed or calibrated from the connecting plug from the end of the transducer. Do not pull
HEAT_EX screen on the CVC. The transducer can be checked on the transducer wires. Unscrew the transducer from the
and calibrated at 2 pressure points. These calibration points Schrader fitting. When installing a new transducer, do not
are 0 psig (0 kPa) and between 25 and 250 psig (173 and use pipe sealer (which can plug the sensor). Put the plug
1724 kPa). To calibrate these transducers: connector back on the sensor and snap into place. Check for
1. Shut down the compressor, cooler, and condenser pumps. refrigerant leaks.
NOTE: There should be no flow through the heat
exchangers.
2. Disconnect the transducer in question from its Schrader Be sure to use a back-up wrench on the Schrader fitting
fitting for cooler or condenser transducer calibration. For whenever removing a transducer, since the Schrader fit-
oil pressure or flow device calibration keep transducer in ting may back out with the transducer, causing a large
place. leak and possible injury to personnel.
NOTE: If the cooler or condenser vessels are at 0 psig
(0 kPa) or are open to atmospheric pressure, the trans- Control Algorithms Checkout Procedure — One
ducers can be calibrated for zero without removing the of the tables on the CVC SERVICE menu is CONTROL
transducer from the vessel. ALGORITHM STATUS. The maintenance screens may
3. Access the HEAT_EX screen and view the particular be viewed from the CONTROL ALGORITHM STATUS
transducer reading (the EVAPORATOR PRESSURE or table to see how a particular control algorithm is operating.
70
These maintenance screens are very useful in helping to Control Test — The Control Test feature can check all
determine how the control temperature is calculated and guide the thermistor temperature sensors, pressure transducers, pumps
vane positioned and for observing the reactions from load and their associated flow devices, the guide vane actuator,
changes, control point overrides, hot gas bypass, surge pre- and other control outputs such as hot gas bypass. The tests
vention, etc. The tables are: can help to determine whether a switch is defective or a pump
relay is not operating, as well as other useful troubleshoot-
CAPACITY Capacity This table shows all values ing issues. During pumpdown operations, the pumps are en-
Control used to calculate the chilled ergized to prevent freeze-up and the vessel pressures and
water/brine control point. temperatures are displayed. The Pumpdown/Lockout fea-
OVERRIDE Override Details of all chilled water con- ture prevents compressor start-up when there is no refrig-
Status trol override values.
erant in the chiller or if the vessels are isolated. The Termi-
HEAT_EX Surge/ The surge and hot gas bypass nate Lockout feature ends the Pumpdown/Lockout after the
HGBP control algorithm status is
Status viewed from this screen. All pumpdown procedure is reversed and refrigerant is added.
values dealing with this control
are displayed.
LL_MAINT LEAD/LAG Indicates LEAD/LAG operation
Status status.
OCCDEFCM Time The Local and CCN occupied
Schedules schedules are displayed here
Status to help the operator quickly de-
termine whether the schedule LEGEND TO TABLES 8A - 8J
is in the 9occupied9 mode or
not. CCM — Chiller Control Module
CVC — Chiller Visual Control
WSMDEFME Water The water system manager is a CHW — Chilled Water
System CCN module that can turn on ISM — Integrated Starter Module
Manager the chiller and change the PIC II — Product Integrated Control II
Status chilled water control point. This VFD — Variable Frequency Drive
screen indicates the status of
this system.
B. READY TO START
71
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING OCCUPIED MODE Unit in recycle mode, chilled water temperature is not sufficiently above
set point to start.
RECYCLE RESTART PENDING REMOTE CONTACT CLOSED Unit in recycle mode, chilled water temperature is not sufficiently above
set point to start.
RECYCLE RESTART PENDING START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start, chilled
water temperature is not sufficiently above set point to start.
RECYCLE RESTART PENDING ICE BUILD MODE Chiller in ICE BUILD mode. Chilled fluid temperature is satisfied for ICE
BUILD conditions.
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
E. START-UP IN PROGRESS
PRIMARY MESSAGE SECONDARY MESSAGE
CAUSE/REMEDY
STARTUP IN PROGRESS OCCUPIED MODEChiller is starting. Time schedule is occupied.
STARTUP IN PROGRESS REMOTE CONTACT CLOSED
Chiller is starting. Remote contacts are enabled and closed.
STARTUP IN PROGRESS START COMMAND IN EFFECT
Chiller is starting. Chiller START/STOP in MAINSTAT manually
forced to start.
AUTORESTART IN PROGRESS OCCUPIED MODE Chiller is starting after power failure. Time schedule is occupied.
AUTORESTART IN PROGRESS REMOTE CONTACT CLOSED Chiller is starting after power failure. Remote contacts are enabled
and closed.
AUTORESTART IN PROGRESS START COMMAND IN EFFECT Chiller is starting after power failure. Chiller START/STOP on MAINSTAT
manually forced to start.
72
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
F. NORMAL RUN
73
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
74
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
I. CHILLER PROTECT LIMIT FAULTS (cont)
75
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
I. CHILLER PROTECT LIMIT FAULTS (cont)
J. CHILLER ALERTS
76
Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
J. CHILLER ALERTS (cont)
77
Table 9A — Thermistor Temperature (F) vs Resistance/Voltage Drop
TEMPERATURE VOLTAGE RESISTANCE TEMPERATURE VOLTAGE RESISTANCE TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (Ohms) (F) DROP (V) (Ohms) (F) DROP (V) (Ohms)
−25 4.821 98,010 60 3.409 7,665 145 1.211 1,141
−24 4.818 94,707 61 3.382 7,468 146 1.192 1,118
−23 4.814 91,522 62 3.353 7,277 147 1.173 1,095
−22 4.806 88,449 63 3.323 7,091 148 1.155 1,072
−21 4.800 85,486 64 3.295 6,911 149 1.136 1,050
−20 4.793 82,627 65 3.267 6,735 150 1.118 1,029
−19 4.786 79,871 66 3.238 6,564 151 1.100 1,007
−18 4.779 77,212 67 3.210 6,399 152 1.082 986
−17 4.772 74,648 68 3.181 6,238 153 1.064 965
−16 4.764 72,175 69 3.152 6,081 154 1.047 945
−15 4.757 69,790 70 3.123 5,929 155 1.029 925
−14 4.749 67,490 71 3.093 5,781 156 1.012 906
−13 4.740 65,272 72 3.064 5,637 157 0.995 887
−12 4.734 63,133 73 3.034 5,497 158 0.978 868
−11 4.724 61,070 74 3.005 5,361 159 0.962 850
−10 4.715 59,081 75 2.977 5,229 160 0.945 832
−9 4.705 57,162 76 2.947 5,101 161 0.929 815
−8 4.696 55,311 77 2.917 4,976 162 0.914 798
−7 4.688 53,526 78 2.884 4,855 163 0.898 782
−6 4.676 51,804 79 2.857 4,737 164 0.883 765
−5 4.666 50,143 80 2.827 4,622 165 0.868 750
−4 4.657 48,541 81 2.797 4,511 166 0.853 734
−3 4.648 46,996 82 2.766 4,403 167 0.838 719
−2 4.636 45,505 83 2.738 4,298 168 0.824 705
−1 4.624 44,066 84 2.708 4,196 169 0.810 690
0 4.613 42,679 85 2.679 4,096 170 0.797 677
1 4.602 41,339 86 2.650 4,000 171 0.783 663
2 4.592 40,047 87 2.622 3,906 172 0.770 650
3 4.579 38,800 88 2.593 3,814 173 0.758 638
4 4.567 37,596 89 2.563 3,726 174 0.745 626
5 4.554 36,435 90 2.533 3,640 175 0.734 614
6 4.540 35,313 91 2.505 3,556 176 0.722 602
7 4.527 34,231 92 2.476 3,474 177 0.710 591
8 4.514 33,185 93 2.447 3,395 178 0.700 581
9 4.501 32,176 94 2.417 3,318 179 0.689 570
10 4.487 31,202 95 2.388 3,243 180 0.678 561
11 4.472 30,260 96 2.360 3,170 181 0.668 551
12 4.457 29,351 97 2.332 3,099 182 0.659 542
13 4.442 28,473 98 2.305 3,031 183 0.649 533
14 4.427 27,624 99 2.277 2,964 184 0.640 524
15 4.413 26,804 100 2.251 2,898 185 0.632 516
16 4.397 26,011 101 2.217 2,835 186 0.623 508
17 4.381 25,245 102 2.189 2,773 187 0.615 501
18 4.366 24,505 103 2.162 2,713 188 0.607 494
19 4.348 23,789 104 2.136 2,655 189 0.600 487
20 4.330 23,096 105 2.107 2,597 190 0.592 480
21 4.313 22,427 106 2.080 2,542 191 0.585 473
22 4.295 21,779 107 2.053 2,488 192 0.579 467
23 4.278 21,153 108 2.028 2,436 193 0.572 461
24 4.258 20,547 109 2.001 2,385 194 0.566 456
25 4.241 19,960 110 1.973 2,335 195 0.560 450
26 4.223 19,393 111 1.946 2,286 196 0.554 445
27 4.202 18,843 112 1.919 2,239 197 0.548 439
28 4.184 18,311 113 1.897 2,192 198 0.542 434
29 4.165 17,796 114 1.870 2,147 199 0.537 429
30 4.145 17,297 115 1.846 2,103 200 0.531 424
31 4.125 16,814 116 1.822 2,060 201 0.526 419
32 4.103 16,346 117 1.792 2,018 202 0.520 415
33 4.082 15,892 118 1.771 1,977 203 0.515 410
34 4.059 15,453 119 1.748 1,937 204 0.510 405
35 4.037 15,027 120 1.724 1,898 205 0.505 401
36 4.017 14,614 121 1.702 1,860 206 0.499 396
37 3.994 14,214 122 1.676 1,822 207 0.494 391
38 3.968 13,826 123 1.653 1,786 208 0.488 386
39 3.948 13,449 124 1.630 1,750 209 0.483 382
40 3.927 13,084 125 1.607 1,715 210 0.477 377
41 3.902 12,730 126 1.585 1,680 211 0.471 372
42 3.878 12,387 127 1.562 1,647 212 0.465 367
43 3.854 12,053 128 1.538 1,614 213 0.459 361
44 3.828 11,730 129 1.517 1,582 214 0.453 356
45 3.805 11,416 130 1.496 1,550 215 0.446 350
46 3.781 11,112 131 1.474 1,519 216 0.439 344
47 3.757 10,816 132 1.453 1,489 217 0.432 338
48 3.729 10,529 133 1.431 1,459 218 0.425 332
49 3.705 10,250 134 1.408 1,430 219 0.417 325
50 3.679 9,979 135 1.389 1,401 220 0.409 318
51 3.653 9,717 136 1.369 1,373 221 0.401 311
52 3.627 9,461 137 1.348 1,345 222 0.393 304
53 3.600 9,213 138 1.327 1,318 223 0.384 297
54 3.575 8,973 139 1.308 1,291 224 0.375 289
55 3.547 8,739 140 1.291 1,265 225 0.366 282
56 3.520 8,511 141 1.289 1,240
57 3.493 8,291 142 1.269 1,214
58 3.464 8,076 143 1.250 1,190
59 3.437 7,868 144 1.230 1,165
78
Table 9B — Thermistor Temperature (C) vs Resistance/Voltage Drop
TEMPERATURE VOLTAGE RESISTANCE TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms) (C) DROP (V) (Ohms)
−40 4.896 168 230 45 1.898 2 184
−39 4.889 157 440 46 1.852 2 101
−38 4.882 147 410 47 1.807 2 021
−37 4.874 138 090 48 1.763 1 944
−36 4.866 129 410 49 1.719 1 871
−35 4.857 121 330 50 1.677 1 801
−34 4.848 113 810 51 1.635 1 734
−33 4.838 106 880 52 1.594 1 670
−32 4.828 100 260 53 1.553 1 609
−31 4.817 94 165 54 1.513 1 550
−30 4.806 88 480 55 1.474 1 493
−29 4.794 83 170 56 1.436 1 439
−28 4.782 78 125 57 1.399 1 387
−27 4.769 73 580 58 1.363 1 337
−26 4.755 69 250 59 1.327 1 290
−25 4.740 65 205 60 1.291 1 244
−24 4.725 61 420 61 1.258 1 200
−23 4.710 57 875 62 1.225 1 158
−22 4.693 54 555 63 1.192 1 118
−21 4.676 51 450 64 1.160 1 079
−20 4.657 48 536 65 1.129 1 041
−19 4.639 45 807 66 1.099 1 006
−18 4.619 43 247 67 1.069 971
−17 4.598 40 845 68 1.040 938
−16 4.577 38 592 69 1.012 906
−15 4.554 38 476 70 0.984 876
−14 4.531 34 489 71 0.949 836
−13 4.507 32 621 72 0.920 805
−12 4.482 30 866 73 0.892 775
−11 4.456 29 216 74 0.865 747
−10 4.428 27 633 75 0.838 719
−9 4.400 26 202 76 0.813 693
−8 4.371 24 827 77 0.789 669
−7 4.341 23 532 78 0.765 645
−6 4.310 22 313 79 0.743 623
−5 4.278 21 163 80 0.722 602
−4 4.245 20 079 81 0.702 583
−3 4.211 19 058 82 0.683 564
−2 4.176 18 094 83 0.665 547
−1 4.140 17 184 84 0.648 531
0 4.103 16 325 85 0.632 516
1 4.065 15 515 86 0.617 502
2 4.026 14 749 87 0.603 489
3 3.986 14 026 88 0.590 477
4 3.945 13 342 89 0.577 466
5 3.903 12 696 90 0.566 456
6 3.860 12 085 91 0.555 446
7 3.816 11 506 92 0.545 436
8 3.771 10 959 93 0.535 427
9 3.726 10 441 94 0.525 419
10 3.680 9 949 95 0.515 410
11 3.633 9 485 96 0.506 402
12 3.585 9 044 97 0.496 393
13 3.537 8 627 98 0.486 385
14 3.487 8 231 99 0.476 376
15 3.438 7 855 100 0.466 367
16 3.387 7 499 101 0.454 357
17 3.337 7 161 102 0.442 346
18 3.285 6 840 103 0.429 335
19 3.234 6 536 104 0.416 324
20 3.181 6 246 105 0.401 312
21 3.129 5 971 106 0.386 299
22 3.076 5 710 107 0.370 285
23 3.023 5 461
24 2.970 5 225
25 2.917 5 000
26 2.864 4 786
27 2.810 4 583
28 2.757 4 389
29 2.704 4 204
30 2.651 4 028
31 2.598 3 861
32 2.545 3 701
33 2.493 3 549
34 2.441 3 404
35 2.389 3 266
36 2.337 3 134
37 2.286 3 008
38 2.236 2 888
39 2.186 2 773
40 2.137 2 663
41 2.087 2 559
42 2.039 2 459
43 1.991 2 363
44 1.944 2 272
79
Control Modules Notes on Module Operation
1. The chiller operator monitors and modifies configura-
tions in the microprocessor by using the 4 softkeys and
Turn controller power off before servicing controls. This the CVC. Communications between the CVC and the CCM
ensures safety and prevents damage to the controller. is accomplished through the SIO (Sensor Input/Output)
bus, which is a phone cable. The communication be-
The CVC, CCM, and ISM modules perform continuous tween the CCM and ISM is accomplished through the sen-
diagnostic evaluations of the hardware to determine its con- sor bus, which is a 3-wire cable.
dition. Proper operation of all modules is indicated by LEDs 2. If a green LED is on continuously, check the communi-
(light-emitting diodes) located on the circuit board of the CVC, cation wiring. If a green LED is off, check the red LED
CCM, and ISM. operation. If the red LED is normal, check the module
There is one green LED located on the CCM and ISM address switches (Fig. 36-38).
boards respectively, and one red LED located on the CVC, All system operating intelligence resides in the CVC. Some
CCM, and ISM boards respectively. safety shutdown logic resides in the ISM in case com-
RED LED (Labeled as STAT) — If the red LED: munications are lost between the ISM and CVC. Outputs
• blinks continuously at a 2-second interval, the module is are controlled by the CCM and ISM as well.
operating properly 3. Power is supplied to the modules within the control panel
• is lit continuously, there is a problem that requires replac- via 24-vac power sources.
ing the module The transformers are located within the power panel, with
• is off continuously, the power should be checked the exception of the ISM, which operates from a 115-vac
• blinks 3 times per second, a software error has been dis- power source and has its own 24-vac transformer located
covered and the module must be replaced in the module.
If there is no input power, check the fuses and circuit breaker. In the power panel, T1 supplies power to the compressor
If the fuse is good, check for a shorted secondary of the oil heater, oil pump, and optional hot gas bypass, and T2
transformer or, if power is present to the module, replace the supplies power to both the CVC and CCM.
module.
Power is connected to Plug J1 on each module.
GREED LED (Labeled as COM) — These LEDs indicate
the communication status between different parts of the con-
troller and the network modules and should blink continu-
ously.
J5 J1 J7 MODULE PART #
KEYPAD POWER/CCN SIO SOFTWARE PART #
STAT
80
Chiller Control Module (CCM) (Fig. 37) 8. Access the MAINSTAT table and highlight the TOTAL
COMPRESSOR STARTS parameter. Press the
INPUTS — Each input channel has 2 or 3 terminals. Refer
to individual chiller wiring diagrams for the correct terminal SELECT softkey. Increase or decrease the value to
numbers for your application. match the starts value recorded in Step 3. Press the
OUTPUTS — Output is 24 vac. There are 2 terminals per ENTER softkey when you reach the correct value. Now,
output. Refer to the chiller wiring diagram for your specific move the highlight bar to the COMPRESSOR ONTIME
application for the correct terminal numbers. parameter. Press the SELECT softkey. Increase or de-
crease the run hours value to match the value recorded
Integrated Starter Module (Fig. 38)
in Step 2. Press the ENTER softkey when the correct
INPUTS — Inputs on strips J3-5 and J3 are analog and dis- value is reached.
crete (on/off) inputs. The specific application of the chiller
determines which terminals are used. Refer to the individual 9. Complete the CVC installation. Following the instruc-
chiller wiring diagram for the correct terminal numbers for tions in the Input Service Configurations section,
your application. page 53, input all the proper configurations such as the
time, date, etc. Check the pressure transducer calibra-
OUTPUTS — Outputs are 24 vac and wired to strip J9. There tions. PSIO installation is now complete.
are 2 terminals per output.
Solid-State Starters — Troubleshooting information
Replacing Defective Processor Modules — The pertaining to the Benshaw, Inc., solid-state starter may be
module replacement part number is printed on a small label found in the following paragraphs and in the Carrier RE-
on the rear of the CVC module. The chiller model and DISTART MICRO Instruction Manual supplied by the starter
serial numbers are printed on the chiller nameplate located vendor.
on an exterior corner post. The proper software is factory- Attempt to solve the problem by using the following pre-
installed by Carrier in the replacement module. When liminary checks before consulting the troubleshooting tables
ordering a replacement chiller visual control (CVC) module, found in the Benshaw manual.
specify the complete replacement part number, full chiller
model number, and chiller serial number. The installer must
configure the new module to the original chiller data. Fol-
low the procedures described in the Software Configuration 1. Motor terminals or starter output lugs or wire should
section on page 53. not be touched without disconnecting the incoming
power supply. The silicon control rectifiers (SCRs)
although technically turned off still have AC mains
potential on the output of the starter.
Electrical shock can cause personal injury. Disconnect
all electrical power before servicing. 2. Power is present on all yellow wiring throughout the
system even though the main circuit breaker in the
unit is off.
INSTALLATION
1. Verify the existing CVC module is defective by using With power off:
the procedure described in the Troubleshooting Guide • Inspect for physical damage and signs of arcing, overheat-
section, page 69, and the Control Modules section, ing, etc.
page 80. Do not select the ATTACH TO NETWORK • Verify the wiring to the starter is correct.
DEVICE table if the CVC indicates a communication • Verify all connections in the starter are tight.
failure. • Check the control transformer fuses.
2. Data regarding the CVC configuration should have been TESTING SILICON CONTROL RECTIFIERS IN THE
recorded and saved. This data must be reconfigured into BENSHAW, INC., SOLID-STATE STARTERS — If an SCR
the new CVC. If this data is not available, follow the is suspected of being defective, use the following pro-
procedures described in the Software Configuration cedure as part of a general troubleshooting guide.
section.
1. Verify power is applied.
If a CCN Building Supervisor or Service Tool is avail-
able, the module configuration should have already been 2. Verify the state of each SCR light-emitting diode (LED)
uploaded into memory. When the new module is in- on the micropower card.
stalled, the configuration can be downloaded from the NOTE: All LEDs should be lit. If any red or green side
computer. of these LEDs is not lit, the line voltage is not present
Any communication wires from other chillers or CCN or one or more SCRs has failed.
modules should be disconnected to prevent the new CVC 3. Check incoming power. If voltage is not present check
module from uploading incorrect run hours into memory. the incoming line. If voltage is present, proceed to
3. To install this module, record values for the TOTAL COM- Steps 4 through 11.
PRESSOR STARTS and the COMPRESSOR ONTIME NOTE: If after completing Steps 4 - 11 all mea-
from the MAINSTAT screen on the CVC. surements are within specified limits, the SCRs are
4. Power off the controls. functioning normally. If after completing Steps 4 - 11
resistance measurements are outside the specified
5. Remove the old CVC. limits, the motor leads on the starter power lugs T1 through
6. Install the new CVC module. Turn the control power T6 should be removed and the steps repeated. This will
back on. identify if abnormal resistance measurements are being
7. The CVC now automatically attaches to the local net- influenced by the motor windings.
work device. 4. Remove power from the starter unit.
81
J11 J12
DISCRETE DISCRETE J1
OUTPUTS OUTPUTS 24 VAC
ANALOG OUT
J8
SIO
J7
SIO
J6
SW2
V/I INPUTS
J5
J9 J8 J7 COM STAT
82
5. Using an ohmmeter, perform the following resistance
measurements and record the results:
SCR PAIRS
Care must be taken to prevent nut rotation while tight-
MEASURE BEING RECORDED ening the bolts. If the nut rotates while tighting the
BETWEEN CHECKED VALUE bolt, SCR replacement must be started over.
T1 and T6 3 and 6
T2 and T4 2 and 5 6. Reconnect the red (cathode) wire from the SCR and the
T3 and T5 1 and 4 white (anode-gate) wire to the appropriate location on
the firing card (i.e., SCR1 wires to firing card terminal
If all measured values are greater than 5K ohms, pro- G1-white wire, and K1-red wire).
ceed to Step 10. If any values are less than 5K ohms, 7. Reconnect all other wiring and bus work.
one or more of the SCRs in that pair is shorted. 8. Return starter to normal operation.
6. Remove both SCRs in the pair (See SCR Removal/
Installation).
7. Using an ohmmeter, measure the resistance (anode to
cathode) of each SCR to determine which device has
failed.
NOTE: Both SCRs may be defective, but typically, only NUT
LOOSEN
one is shorted. If both SCRs provide acceptable resis- AND
CLAMPING
tance measurements, proceed to Step 10. BOLT TIGHTEN
A BOLTS
8. Replace the defective SCR(s). ALUMINUM FROM
HEATSINK THIS END
9. Retest the ‘‘pair’’ for resistance values indicated above.
10. On the right side of the firing card, measure the resis- ROLL PIN
tance between the red and white gate/cathode leads for
each SCR (1 through 6). A measurement between 5 and SCR
50 ohms is normal. Abnormally high values may indi-
cate a failed gate for that SCR.
If any red or white SCR gate leads are removed SCR PART CLAMP A NO OF BOLT
NUMBER SIZE DIMENSION TURNS LENGTH
from the firing card or an SCR, care must be taken BISCR (in.) (in.)
to ensure the leads are replaced EXACTLY as they 2.75 3.0
were (white wires to gates, and red wires to cath- 6601218 1030 ( 70 mm) 1 ⁄2
1
( 76 mm)
odes on both the firing card and SCR), or damage 2.75 3.0
to the starter and/or motor may result. 6601818 1030 11⁄2
( 70 mm) ( 76 mm)
2.75 3.5
8801230 1035 ( 70 mm) 13⁄4
( 89 mm)
11. Replace the SCRs and retest the pair. 2.75 3.0
8801830 1035 ( 70 mm) 13⁄4
( 89 mm)
SCR REMOVAL/INSTALLATION — Refer to Fig. 39. 4.00 4.0
15001850 2040 23⁄4
1. Remove the SCR by loosening the clamping bolts on each (102 mm) (102 mm)
side of the SCR, 4.00 5.0
15001850 2050 (102 mm) 23⁄4
(127 mm)
2. After the SCR has been removed and the bus work is loose, 220012100 Consult Benshaw Representative
apply a thin coat of either silicon based thermal joint com- 330018500 Consult Benshaw Representative
pound or a joint compound for aluminum or copper wire
connections to the contact surfaces of the replacement SCR. Fig. 39 — SCR Installation
This allows for improved heat dissipation and electrical
conductivity.
3. Place the SCR between the roll pins on the heatsink as-
semblies so the roll pins fit into the small holes in each
side of the SCR.
NOTE: Ensure the SCR is installed so the cathode side is
the side from which the red wire extends. The heatsink is
labeled to show the correct orientation.
4. Hand tighten the bolts until the SCR contacts the
heatsink.
5. Using quarter-turn increments, alternating between clamp-
ing bolts, apply the appropriate number of whole turns
referencing the table in Fig. 39.
83
Physical Data — Tables 10A-17 and Fig. 40-47 pro- and wiring schematics for the operator’s convenience during
vide additional information on component weights, com- troubleshooting.
pressor fits and clearances, physical and electrical data,
ENGLISH
NUMBER OF
TUBES Dry (Rigging) Weight Chiller Charge
(lb)
CODE
Refrigerant Water Volume
Cooler Condenser Cooler Condenser Weight (gal)
Only Only
Cooler Condenser Cooler Condenser
10 142 180 2,742 2,704 290 200 34 42
11 161 200 2,812 2,772 310 200 37 45
12 180 225 2,883 2,857 330 200 40 49
15 142 180 3,003 2,984 320 250 39 48
16 161 200 3,089 3,068 340 250 43 52
17 180 225 3,176 3,173 370 250 47 57
20 200 218 3,442 3,523 345 225 48 48
21 240 266 3,590 3,690 385 225 55 55
22 282 315 3,746 3,854 435 225 62 63
30 200 218 4,137 3,694 350 260 55 55
31 240 267 4,319 3,899 420 260 64 65
32 280 315 4,511 4,100 490 260 72 74
35 200 218 4,409 4,606 400 310 61 62
36 240 267 4,617 4,840 480 310 70 72
37 280 315 4,835 5,069 550 310 80 83
40 324 370 5,898 6,054 560 280 89 96
41 364 417 6,080 6,259 630 280 97 106
42 400 463 6,244 6,465 690 280 105 114
45 324 370 6,353 6,617 640 330 98 106
46 364 417 6,561 6,851 720 330 108 117
47 400 463 6,748 7,085 790 330 116 127
50 431 509 7,015 7,285 750 400 115 128
51 485 556 7,262 7,490 840 400 126 137
52 519 602 7,417 7,683 900 400 133 136
55 431 509 7,559 7,980 870 490 127 142
56 485 556 7,839 8,214 940 490 139 152
57 519 602 8,016 8,434 980 490 147 162
60 557 648 8,270 8,286 940 420 144 159
61 599 695 8,462 8,483 980 420 153 168
62 633 741 8,617 8,676 1020 420 160 177
65 557 648 8,943 9,204 1020 510 160 176
66 599 695 9,161 9,428 1060 510 169 187
67 633 741 9,338 9,648 1090 510 177 197
70 644 781 12,395 13,139 1220 780 224 209
71 726 870 12,821 13,568 1340 780 243 229
72 790 956 13,153 13,969 1440 780 257 248
75 644 781 13,293 14,211 1365 925 245 234
76 726 870 13,780 14,702 1505 925 266 257
77 790 956 14,159 15,160 1625 925 283 278
80 829 990 16,156 15,746 1500 720 285 264
81 901 1080 16,530 16,176 1620 720 302 284
82 976 1170 16,919 16,606 1730 720 319 304
85 829 990 17,296 17,001 1690 860 313 295
86 901 1080 17,723 17,492 1820 860 331 318
87 976 1170 18,169 17,984 1940 860 351 341
NOTES: 2. Condenser data: based on a condenser with standard wall tubing,
1. Cooler data: based on a cooler with standard wall tubing, 2-pass, 2-pass, 150 psig, nozzle-in-head waterbox with victaulic grooves.
150 psig, nozzle-in-head waterbox with victaulic grooves. Weight Weight includes the float valve, discharge elbow, and distribution
includes suction elbow, control panel, and distribution piping. Weight piping. Weight does not include unit-mounted starter, isolation valves,
does not include compressor. and pumpout unit.
84
Table 10B — Heat Exchanger Data (SI)
SI
NUMBER OF
TUBES Dry (Rigging) Weight Chiller Charge
(kg)
CODE
Refrigerant Water Volume
Cooler Condenser Cooler Condenser Weight (L)
Only Only
Cooler Condenser Cooler Condenser
10 142 180 1244 1226 132 91 129 158
11 161 200 1275 1257 141 91 140 170
12 180 225 1307 1296 150 91 152 185
15 142 180 1362 1353 145 113 149 183
16 161 200 1401 1391 154 113 163 198
17 180 225 1440 1439 168 113 178 216
20 200 218 1561 1598 157 102 183 181
21 240 266 1628 1673 175 102 207 210
22 282 315 1699 1748 197 102 234 239
30 200 218 1876 1675 159 118 208 210
31 240 267 1958 1768 190 118 242 246
32 280 315 2046 1859 222 118 271 282
35 200 218 2000 2089 181 141 232 233
36 240 267 2094 2195 218 141 266 273
37 280 315 2193 2300 249 141 301 314
40 324 370 2675 2745 254 127 338 365
41 364 417 2757 2839 286 127 368 400
42 400 463 2832 2932 313 127 396 433
45 324 370 2881 3001 290 150 372 403
46 364 417 2976 3107 327 150 407 442
47 400 463 3060 3213 358 150 438 481
50 431 509 3181 3304 340 181 435 483
51 485 556 3293 3397 381 181 477 518
52 519 602 3364 3484 408 181 502 552
55 431 509 3428 3619 395 222 481 536
56 485 556 3555 3725 426 222 527 575
57 519 602 3635 3825 446 222 557 613
60 557 648 3751 3758 426 190 546 601
61 599 695 3838 3847 444 190 578 636
62 633 741 3908 3935 462 190 604 669
65 557 648 4056 4174 462 231 605 668
66 599 695 4155 4276 481 231 641 707
67 633 741 4235 4376 494 231 671 745
70 644 781 5622 5959 553 354 848 791
71 726 870 5814 6153 608 354 919 867
72 790 956 5965 6335 653 354 974 937
75 644 781 6028 6445 619 420 927 885
76 726 870 6259 6667 683 420 1009 971
77 790 956 6421 6875 737 420 1072 1052
80 829 990 7326 7141 680 327 1080 1000
81 901 1080 7496 7336 735 327 1143 1075
82 976 1170 7673 7531 785 327 1208 1150
85 829 990 7844 7710 766 390 1183 1118
86 901 1080 8037 7933 825 390 1254 1205
87 976 1170 8240 8156 880 390 1329 1291
NOTES: 2. Condenser data: based on a condenser with standard wall tubing,
1. Cooler data: based on a cooler with standard wall tubing, 2-pass, 2-pass, 1034 kPa, nozzle-in-head waterbox with victaulic grooves.
150 psig, nozzle-in-head waterbox with victaulic grooves. Weight Weight includes the float valve, discharge elbow, and distribution
includes suction elbow, control panel, and distribution piping. Weight piping. Weight does not include unit-mounted starter, isolation valves,
does not include compressor. and pumpout unit.
85
Table 11 — 19XR Additional Data for Marine Waterboxes*
ENGLISH SI
HEAT EXCHANGER
FRAME, PASS Psig Rigging Weight Water Volume kPa Rigging Weight Water Volume
(lb) (gal) (kg) (L)
FRAME 2, 1 AND 2 PASS 150 730 84 1034 331 318
FRAME 2, 2 PASS 150 365 42 1034 166 159
FRAME 3, 1 AND 2 PASS 150 730 84 1034 331 317
FRAME 3, 2 PASS 150 365 42 1034 166 159
FRAME 4, 1 AND 3 PASS 150 1060 123 1034 481 465
FRAME 4, 2 PASS 150 530 61 1034 240 231
FRAME 5, 1 AND 3 PASS 150 1240 139 1034 562 526
FRAME 5, 2 PASS 150 620 69 1034 281 263
FRAME 6, 1 AND 3 PASS 150 1500 162 1034 680 612
FRAME 6, 2 PASS 150 750 81 1034 340 306
FRAME 7, 1 AND 3 PASS 150 2010 326 1034 912 1234
FRAME 7, 2 PASS 150 740 163 1034 336 617
FRAME 8, 1 AND 3 PASS 150 1855 406 1034 841 1537
FRAME 8, 2 PASS 150 585 203 1034 265 768
FRAME 2, 1 AND 3 PASS 300 860 84 2068 390 318
FRAME 2, 2 PASS 300 430 42 2068 195 159
FRAME 3, 1 AND 3 PASS 300 860 84 2068 390 317
FRAME 3, 2 PASS 300 430 42 2068 195 159
FRAME 4, 1 AND 3 PASS 300 1210 123 2068 549 465
FRAME 4, 2 PASS 300 600 61 2068 272 231
FRAME 5, 1 AND 3 PASS 300 1380 139 2068 626 526
FRAME 5, 2 PASS 300 690 69 2068 313 263
FRAME 6, 1 AND 3 PASS 300 1650 162 2068 748 612
FRAME 6, 2 PASS 300 825 81 2068 374 306
FRAME 7, 1 AND 3 PASS 300 3100 326 2068 1406 1234
FRAME 7, 2 PASS 300 1830 163 2068 830 617
FRAME 8, 1 AND 3 PASS 300 2745 405 2068 1245 1533
FRAME 8, 2 PASS 300 1475 203 2068 766 768
*Add to heat exchanger data for total weights or volumes.
NOTES:
1. Weight adder shown is the same for cooler and condenser of equal frame size.
2. For the total weight of a vessel with a marine waterbox, add these values to the heat
exchanger weights (or volumes).
86
Table 13 — 19XR Motor Weights Standard and High Efficiency Motors
ENGLISH SI
MOTOR Stator Weight* Rotor Weight† End Bell Stator Weight* Rotor Weight† End Bell
SIZE (lb) (lb) Cover (kg) (kg) Cover
60 Hz 50 Hz 60 Hz 50 Hz (lb) 60 Hz 50 Hz 60 Hz 50 Hz (kg)
BD 1030 1030 240 240 185 467 467 109 109 84
BE 1070 1070 250 250 185 485 485 113 113 84
BF 1120 1120 265 265 185 508 508 120 120 84
BG 1175 1175 290 290 185 533 533 132 132 84
BH 1175 1175 290 290 185 533 533 132 132 84
CD 1286 1358 258 273 274 583 616 117 124 125
CE 1305 1377 265 281 274 592 625 120 127 125
CL 1324 1435 280 296 274 600 651 127 134 125
CM 1347 1455 303 303 274 611 660 137 137 125
CN 1358 1467 316 316 274 616 665 143 143 125
CP 1401 1479 329 316 274 635 671 149 143 125
CQ 1455 1479 329 316 274 660 671 149 152 125
DB 1665 1725 361 391 236 755 782 164 177 107
DC 1681 1737 391 404 236 762 788 177 183 107
DD 1977 2069 536 596 318 897 938 243 248 144
DE 2018 2089 550 550 318 915 948 249 248 144
DF 2100 2139 575 567 318 952 970 261 257 144
DG 2187 2153 599 599 318 992 977 272 272 144
DH 2203 2207 604 604 318 999 1001 274 274 144
DJ 2228 2305 614 614 318 1011 1046 279 279 144
EH 3060 3120 701 751 414 1388 1415 318 341 188
EJ 3105 3250 716 751 414 1408 1474 325 341 188
EK 3180 3250 716 768 414 1442 1474 325 348 188
EL 3180 3370 737 801 414 1442 1529 334 363 188
EM 3270 3370 737 801 414 1483 1529 334 363 188
EN 3270 3520 801 851 414 1483 1597 363 386 188
EP 3340 3520 830 851 414 1515 1597 376 386 188
*Stator weight includes stator and shell.
†Rotor weight includes rotor and shaft.
NOTE: When different voltage motors have different weights the largest weight is given.
87
Table 14A — 19XR Waterbox Cover Weights — English (lb)
FRAME 1 FRAME 2 FRAME 3
HEAT WATERBOX
EXCHANGER DESCRIPTION Standard Flanged Standard Flanged Standard Flanged
Nozzles Nozzles Nozzles
NIH, 1 Pass Cover, 150 psig 177 204 320 350 320 350
NIH, 2 Pass Cover, 150 psig 185 218 320 350 320 350
NIH, 3 Pass Cover, 150 psig 180 196 310 340 310 340
COOLER/ NIH/MWB End Cover, 150 psig 136 136 300 300 300 300
CONDENSER NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 486
NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518
NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468
NIH/MWB End Cover, 300 psig 175 175 400 400 400 400
88
Table 14B — 19XR Waterbox Cover Weights — SI (kg)
FRAME 1 FRAME 2 FRAME 3
HEAT WATERBOX
EXCHANGER DESCRIPTION Standard Flanged Standard Flanged Standard Flanged
Nozzles Nozzles Nozzles
NIH, 1 Pass Cover, 1034 kPa 80 93 145 159 145 159
NIH, 2 Pass Cover, 1034 kPa 84 99 145 159 145 159
NIH, 3 Pass Cover, 1034 kPa 82 89 141 154 141 154
COOLER/ NIH/MWB End Cover, 1034 kPa 62 62 136 136 136 136
CONDENSER NIH, 1 Pass Cover, 2068 kPa 112 137 186 220 186 220
NIH, 2 Pass Cover, 2068 kPa 116 147 186 235 186 235
NIH, 3 Pass Cover, 2068 kPa 115 131 196 212 196 212
NIH/MWB End Cover, 2068 kPa 79 79 181 181 181 181
89
Table 15 — Optional Pumpout System Table 17 — Motor Voltage Code
Electrical Data
MOTOR VOLTAGE CODE
MOTOR CONDENSER MAX Code Volts Frequency
CODE UNIT VOLTS-PH-Hz RLA LRA
60 200 60
1 19EA47-748 575-3-60 3.8 23.0 61 230 60
4 19EA42-748 200/208-3-60 10.9 63.5 62 380 60
5 19EA44-748 230-3-60 9.5 57.5 63 416 60
6 19EA46-748 400/460-3-50/60 4.7 28.8 64 460 60
LEGEND 65 575 60
LRA — Locked Rotor Amps 66 2400 60
RLA — Rated Load Amps 67 3300 60
68 4160 60
69 6900 60
50 230 50
Table 16 — Additional Miscellaneous Weights 51 346 50
52 400 50
ITEM Lb Kg
53 3000 50
CONTROL CABINET 30 14
54 3300 50
UNIT-MOUNTED STARTER 500 227
55 6300 50
OPTIONAL ISOLATION VALVES 115 52
90
COMPRESSOR, TRANSMISSION AREA
VIEW A
LOW SPEED SHAFT THRUST DISK
Fig. 40 — Compressor Fits and Clearances
91
VIEW B − HIGH SPEED SHAFT
92
93
LEGEND (cont)
FR — Frame
GV — Guide Vane
HGBP — Hot Gas Bypass
HT EXCHD — Heat Exchanger
ISM — Integrated Starter Module
L — Main Supply Power
LVG — Leaving
N.O. — Normally Open
PRESS — Pressure
LEGEND REQM’T — Requirement
TB — Terminal Board
AUX — Auxiliary
BRG — Bearing Denotes Oil Pump Terminal
C — Contactor
CB — Circuit Breaker Denotes Power Panel Terminal
CCM — Chiller Control Module
CCN — Carrier Comfort Network ** Denotes Motor Starter Panel Conn
COMP’R — Compressor
COND — Condenser Denotes Component Terminal
CVC — Chiller Visual Controller
DISCH — Discharge Wire Splice
ENT — Entering
EVAP — Evaporator Denotes Conductor Male/Female Connector
EXT — External Option Wiring
LEGEND (cont)
FR — Frame
GV — Guide Vane
HGBP — Hot Gas Bypass
HT EXCHD — Heat Exchanger
ISM — Integrated Starter Module
L — Main Supply Power
LVG — Leaving
N.O. — Normally Open
PRESS — Pressure
REQM’T — Requirement
LEGEND TB — Terminal Board
AUX — Auxiliary Denotes Oil Pump Terminal
BRG — Bearing
C — Contactor
CB — Circuit Breaker Denotes Power Panel Terminal
CCM — Chiller Control Module
CCN — Carrier Comfort Network ** Denotes Motor Starter Panel Conn
COMP’R — Compressor Denotes Component Terminal
COND — Condenser
CVC — Chiller Visual Controller Wire Splice
DISCH — Discharge
ENT — Entering Denotes Conductor Male/Female Connector
EVAP — Evaporator
EXT — External Option Wiring
LEGEND
LEGEND
AUX — Auxiliary HPR — Horsepower
C — Contactor ISM — Integrated Starter Module
CB — Circuit Breaker L — Main Supply Power
CR — Control Relay LL — Control Power Supply
CT — Current Transformer M — Contactor
DS — Disconnect Switch RES — Resistor
FU — Fuse S — Contactor
G — Ground TB — Terminal Block
CAUTION: Yellow wires remain energized when unit main disconnect is off.
Optional features are indicated by bold dashed lines.
Dry Contact
Field Connection
For connection diagram refer to 261143 D4.
Fig. 44 — Cutler-Hammer Wye Delta Unit Mounted Starter Wiring Schematic (Low Voltage)
96
97
NOTES: LEGEND
LED status with power applied and prior to run command. AUX — Auxiliary G — Ground Wire Node Symbol
‘‘ON’’ BR — Bridge Rectifier L — Main Supply Power PC Board Terminals
1 may have terminal block
CB — Circuit Breaker LL — Control Power Supply
‘‘OFF’’ COMM — Communication M — Contactor Benshaw supplied Twisted Pair
COND — Condenser O/L — Overload Reset terminal block
Transformer T1 primary fuses FU1/FU2 value dependent on system voltage and model, per Chart 1. CPU — Central Processing Unit S — Contactor Twisted Shielded Pair
2 Transformer connections per transformer nameplate connection diagram. CVC — Chiler Visual Controller SCR — Silicone Controller Rectifier Terminal Strip
CT — Current Transformer ST — Shunt Trip
MOVs are used on power stack assemblies for system voltages of 200 thru 460 vac (as shown). Resistor/ EVAP — Evaporator TB — Terminal Block Shield Wire
3 capacitor networks (DVDTs) are used on power stack assemblies in place of MOVs for a system voltage FU — Fuse Power Connection Field Wiring
of 575 vac (not shown).
K3 relay shown in deenergized state. K3 contact will close when power is applied. K3 contact will open
4 on stop command or system fault.
Fig. 45 — Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic (Low Voltage)
LEGEND
98
AUX — Auxiliary
C — Contactor
CB — Circuit Breaker
COMM — Communication
COND — Condenser
CPT — Control Power Transformer
CR — Control Relay
CT — Current Transformer
DS — Disconnect Switch
EVAP — Evaporator
FU — Fuse
G — Ground
GFCT — Ground Fault Current Transformer
HPR — Horsepower
ISM — Intergrated Starter Module
L — Main Power Supply
LL — Control Power Supply
LVG — Leaving
M — Contactor
MTR — Motor
PRESS — Pressure
PT — Power Transformer
ST — Shunt Trip
STAT — Status
TB — Terminal Block
TRANS — Transition
VFD — Variable Frequency Drive
VL — Wire Label
Starter Vendor Power Wiring
Starter Vendor Control Wiring
Field Installed Power Wiring
(supplied by others)
Field Installed Control Wiring
(supplied by others)
Option — Starter Vendor Wiring
Twisted Pair Wiring by Starter Vendor
AUX — Auxiliary
C — Contactor
CB — Circuit Breaker
COMM — Communication
COND — Condenser
CPT — Control Power Transformer
CR — Control Relay
CT — Current Transformer
DS — Disconnect Switch
EVAP — Evaporator
FU — Fuse
G — Ground
GFCT — Ground Fault Current Transformer
HPR — Horsepower
ISM — Intergrated Starter Module
L — Main Power Supply
LL — Control Power Supply
LVG — Leaving
M — Contactor
MTR — Motor
PRESS — Pressure
PT — Power Transformer
ST — Shunt Trip
STAT — Status
TB — Terminal Block
TRANS — Transition
VFD — Variable Frequency Drive
VL — Wire Label
Starter Vendor Power Wiring
Starter Vendor Control Wiring
Field Installed Power Wiring
(supplied by others)
Field Installed Control Wiring
(supplied by others)
Option — Starter Vendor Wiring
Twisted Pair Wiring by Starter Vendor
100
INDEX (cont)
Storage Vessel, 7 Unit Mounted Solid-State Starter, 9
Summary (Lubrication Cycle), 8 Unit Mounted Wye-Delta Starter, 10
Surge Prevention Algorithm, 38 Using the Optional Storage Tank and Pumpout
Surge Protection, 39 System, 46
System Components, 5 Water/Brine Reset, 37
Temperature Sensors (Check), 69 Water Leaks, 68
Test After Service, Repair, or Major Leak, 65 Water Piping (Inspect), 51
Tighten All Gasketed Joints and Guide Vane Packing, 46 Water Treatment, 68
Tower Fan Relay Low and High, 37 Weekly Maintenance, 66
Trim Refrigerant Charge, 65 Wiring (Inspect), 51
Troubleshooting Guide, 69
101
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 211 Catalog No. 531-974 Printed in U.S.A. Form 19XR-3SS Pg 104 6-98 Replaces: New
Tab 5a
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
INITIAL START-UP CHECKLIST FOR
19XR HERMETIC CENTRIFUGAL LIQUID CHILLER
(Remove and use for job file.)
MACHINE INFORMATION:
ADDRESS MODEL
DESIGN CONDITIONS:
COOLER ******
CONDENSER ******
YES NO
Was Machine Tight?
If Not, Were Leaks Corrected?
Was Machine Dehydrated After Repairs?
Amount:
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 211 Catalog No. 531-974 Printed in U.S.A. Form 19XR-3SS Pg CL-1 6-98 Replaces: New
Tab 5a
INSPECT WIRING AND RECORD ELECTRICAL DATA:
RATINGS:
Motor Voltage Motor(s) Amps Oil Pump Voltage Starter LRA Rating
INITIAL START:
Line Up All Valves in Accordance With Instruction Manual: Start Water Pumps and Establish Water Flow
Oil Level OK and Oil Temperature OK Check Oil Pump Rotation-Pressure
Check Compressor Motor Rotation (Motor End Sight Glass) and Record: Clockwise
Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? Yes* M No M
*If yes, determine cause.
SIGNATURES:
CARRIER CUSTOMER
TECHNICIAN REPRESENTATIVE
DATE DATE
CL-2
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-3
19XR PIC II TIME SCHEDULE CONFIGURATION SHEET OCCPC01S
Day Flag Occupied Unoccupied
M T W T F S S H Time Time
Period 1:
Period 2:
Period 3:
Period 4:
Period 5:
Period 6:
Period 7:
Period 8:
NOTE: Default setting is OCCUPIED 24 hours/day.
Period 1:
Period 2:
Period 3:
Period 4:
Period 5:
Period 6:
Period 7:
Period 8:
NOTE: Default setting is OCCUPIED 24 hours/day.
CL-4
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Undervoltage Threshold 85 to 95 % 85
Over/Under Volt Time 1 to 10 SEC 5
Voltage % Imbalance 1 to 10 % 5
Voltage Imbalance Time 1 to 10 SEC 5
Motor Rated Load Amps 10 to 5000 AMPS 200
Motor Locked Rotor Trip 100 to 60000 AMPS 1000
Locked Rotor Start Delay 1 to 10 cycles 5
Starter LRA Rating 100 to 60000 AMPS 2000
Motor Current CT Ratio: 1 10 to 1000 100
Current % Imbalance 5 to 40 % 15
Current Imbalance Time 1 to 10 SEC 5
3 Grnd Fault CT’s? (1=No) 0/1 NO/YES YES
Ground Fault CT Ratio: 1 150 150
Ground Fault Current 1 to 25 AMPS 15
Ground Fault Start Delay 1 to 20 cycles 10
Ground Fault Persistence 1 to 10 cycles 5
Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE
Frequency-60 Hz? (No=50) 0/1 NO/YES YES
CUT ALONG DOTTED LINE
CL-5
19XR PIC II OPTIONS TABLE CONFIGURATION SHEET
Surge Protection
Surge Delta % Amps 5 to 15 % 10
Surge Time Period 7 to 10 MIN 8
CL-6
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-7
19XR PIC II SETUP2 TABLE CONFIGURATION SHEET
Diffuser Control
Diffuser Option 0 to 1 DSABLE/ENABLE DSABLE
Guide Vane 25% Load Pt 0 to 78 % 25
Diffuser 25% Load Pt 0 to 100 % 0
Guide Vane 50% Load Pt 0 to 78 % 50
Diffuser 50% Load Pt 0 to 100 % 0
Guide Vane 75% Load Pt 0 to 78 % 75
Diffuser 75% Load Pt 0 to 100 % 0
Diffuser Full Span mA 15 to 22 mA 18
CL-8
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-9
19XR PIC II RAMP_DEM TABLE CONFIGURATION SHEET
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA −30 to 30 ^F 10
RESET TYPE 2
Remote Temp (No Reset) −40 to 245 DEG F 85
Remote Temp (Full Reset) −40 to 245 DEG F 65
Degrees Reset −30 to 30 ^F 10
RESET TYPE 3
CHW Delta T (No Reset) 0 to 15 ^F 10
CHW Delta T (Full Reset) 0 to 15 ^F 0
Degrees Reset −30 to 30 ^F 5
CL-10
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-11
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 211 Catalog No. 531-974 Printed in U.S.A. Form 19XR-3SS Pg CL-12 6-98 Replaces: New
Tab 5a
30GX and 30HXC series
PRO-DIALOG Control
50 Hz
GLOBAL CHILLER
The cover illustrations are solely for illustration, and form no part of any offer for sale or any sale contract. The manufacturer
reserves the right to change the design at any time without notice.
2
Table of contents
3
1 - SAFETY CONSIDERATIONS 2 - GENERAL DESCRIPTION
Installation, start-up and servicing of equipment can be hazard- PRO-DIALOG Plus is a system for controlling units which use
ous if factors particular to the installation are not considered: screw compressors:
operating pressures, electrical components, voltages and the • Single or dual circuit
installation site itself (elevated plinths, rooftops and built-up • Air or water-cooled condensers
structures). • Non-reversible heat pumps
Only highly trained and qualified installation engineers and PRO-DIALOG Plus controls compressor start-up and demand
technicians, who are fully trained on the product, are limits needed to maintain the desired entering or leaving tem-
authorised to install and start up this equipment. perature setpoint for water. It automatically sets the position of
the electronic expansion valve (if used) to optimise the evapo-
During all servicing operations, it is important to read, under- rator charge. It controls operation of the fans (on air-cooled
stand and follow all the recommendations and instructions units) or water valves (on water-cooled units) to maintain the
given in the installation and service instructions for the correct head pressure in each circuit.
product, including the tags and labels affixed to the equipment,
compo-nents and any parts supplied separately, and to comply Safety circuits are constantly monitored by PRO-DIALOG
with all other relevant safety regulations. Plus to ensure safe operation of the unit. PRO-DIALOG Plus
also gives access to a Quick Test program covering all inputs
• Apply all safety codes and practices. and outputs.
• Wear safety glasses and gloves.
• Use the proper tools to move heavy objects. Move units All PRO-DIALOG Plus controls can work in accordance with
carefully and set them down gently. three independent modes:
• Local mode: the machine is controlled by commands from
1.2 - Avoiding electrocution the user interface.
• Remote mode: the machine is controlled by remote
Only personnel qualified in accordance with the recommenda- contacts (volt-free contacts, analogue signals).
tions of the IEC (International Electrotechnical Commission) • CCN mode: the machine is controlled by commands from
may be permitted access to electrical components. It is the Carrier Comfort Network (CCN). In this case a data
particularly recommended that all sources of electricity to the communication cable is used to connect the unit to the
unit be shut off before any work is begun. Shut off the main CCN communication bus.
power supply at the main circuit breaker or isolator. The operating mode must be chosen with the Operating Type
selection button described in section 4.2.1.
IMPORTANT:
Risk of electrocution: Even when the main power isolator or When the PRO-DIALOG Plus system operates autonomously
circuit breaker is off, it is still possible for certain components (Local or Remote mode) it retains all of its own control capa-
such as crankcase heaters and trace heaters to be energised, bilities but does not offer any of the features of the CCN
since they are connected to a separate power source. network.
Risk of burns: Electrical currents cause components to get
hot either temporarily or permanently. Handle power cables, 2.2 - Abbreviations used
electrical cables and conduits, terminal box covers and motor
frames with very great care. In this manual the circuits are called circuit A and circuit B.
The compressors in circuit A are labelled A1 and A2. Those in
IMPORTANT: Even when the unit is switched off, the power circuit B are labelled B1 and B2.
circuit remains energized as long as the unit or circuit dis-
connect is not open. Refer to the wiring diagram for details. The following abbreviations are frequently used:
Use the adapted safety guidelines. AI - Analogue Input
AO - Analogue Output
IMPORTANT: This equipment uses and emits electromag- CCn - Operating type: CCN
netic signals. The tests carried out on this product have CCN - Carrier Comfort Network
shown that it complies with all applicable codes regarding DI - Discrete Input
electromagnetic compatibility. DO - Discrete Output
EXV - Electronic Expansion Device
IMPORTANT : If the boards need to be handled wear anti- LED - Light Emitting Diode
static gloves to avoid exposing the electronic components to a Loader - Compressor capacity step
destructive voltage. Only unpack the boards from their anti- LOFF - Operating type: Local off
static bag when they need to be installed. rEM - Operating type: by remote control contacts
SCPM - Compressor Protection Module
SCT - Saturated disCharge Temperature
SIO - Standard Input/Output - internal communication
bus linking the basic board to the slave boards
SST - Saturated Suction Temperature
4
3 - HARDWARE DESCRIPTION The various control components are arranged in modules
within the control cabinet:
3.1 - General
• Control module: This comprises the basic board, the user
Control board interface, the EXV control board and option boards, as
well as the customer’s terminal block.
2 • Start-up module: This consists of the start-up boards,
9
1
3 compressor protection boards, as well as the compressor
circuit breakers and contactors.
• Fan module (air-cooled unit): Consists of one or two
8xDO boards together with the fan circuit breakers and
contactors.
8 4
Control box
1 2 3 4 5
5
3.2.3 - The user interface 3.2.7 - Light emitting diodes on boards
The user interface is in two parts: All boards continuously check and indicate the proper
• The main interface: This gives access to all of the operation of their electronic circuits. A light emitting diode
control parameters for the unit. It consists of a 2-digit (LED) lights on each board when it is operating properly.
primary display block and a secondary 4-digit display
block with 10 LEDs and 5 buttons. Red LED
• The summary interface: This gives quick access to just
the main control parameters for the unit. It comprises 12 • The MAIN red LED flashes at about 2 second intervals to
buttons and 16 LEDs, and includes a schematic diagram show that the module is working properly.
of the unit. • Irregular flashing or no flashing is a sign of a defective
board.
3.2.4 - Connections between boards
The basic board and slave boards communicate with each Green LED
other over an internal three-wire RS485 communication bus (item SIO on the board)
(SIO bus). These three wires link all the boards in parallel.
• This LED flashes continuously to show that the board is
Terminals 1, 2 and 3 on connector J9 (A, B, C are connected communicating correctly over its internal bus.
internally) of the basic board are connected to terminals 1, 2 • If this LED is not flashing, check the wiring of the SIO
and 3 of connector J12 of the SCPM boards, terminal J4 of the bus and the address of the board (slave board only). If the
PD4-EXV board, and terminal J9 of auxiliary boards type 1 or basic board is not linked to any slave boards, this LED
2 respectively. should not flash.
• If all slave boards indicate a communication fault, check
Incorrect connection will render the system inoperative. the SIO bus connection on the basic board. If this
connection is correct and the fault persists, replace the
3.2.5 - Slave board addresses basic board.
Every slave board has a unique address controlled by 8 DIP
switches. The switch is disabled when it is in the open position Orange LED - CCN/clock board
(OPEN or OFF). On SCPM boards SIO address switch is
labelled 'ADDR'. • This LED flashes to show that the basic board is commu-
nicating via the CCN bus.
NOTE: Any incorrect address will prevent the unit from
starting. Turn off the power before amending the address of 3.3 - The controls
any auxiliary board.
3.3.1 - Electronic expansion valve (EXV)
Board addresses The EXV is used to adjust the refrigerant flow to changes in
the operating conditions of the machine. For this purpose, a
Board DIP switch (0 = open) series of calibrated orifices are machined into the wall of the
1 2 3 4 5 6 7 8 refrigerant inlet port. As the refrigerant passes through these
PD4-EXV 1 0 1 1 1 0 0 0 orifices, it expands and becomes a bi-phase mixture (liquid and
Auxiliary board type 1 or 2 - # 1 1 0 0 0 1 1 0 0 gas).
Auxiliary board type 1 or 2 - # 1 0 0 0 1 1 1 0 0
SCPM # 1 (compressor A1) 0 0 1 0 1 0 1 0 To adjust the refrigerant flow to changes in operating conditions,
SCPM # 2 (compressor A2) 1 1 1 1 1 0 1 0
a piston moves constantly up or down to vary the cross-section
SCPM # 3 (compressor B1) 0 1 0 1 0 1 1 0
of the refrigerant path. This piston is driven by an electronically
SCPM # 4 (compressor B2) 1 0 1 0 1 1 1 0
controlled linear stepper motor. The high degree of accuracy
with which the piston is positioned ensures that the flow of
3.2.6 - Power supply to the boards refrigerant is precisely controlled.
All boards are supplied by a 24 V source, referred to earth. In
the event of a power supply interrupt, the unit restarts automa- NOTE: The external connector of the EXV must be cleaned
tically without the need for an external command. However, and coated with silicone grease (Part No. 397 EE) to keep out
any faults active when the supply is interrupted are saved and condensation and prevent corrosion.
may in certain cases prevent a circuit or unit from restarting.
3.3.2 - The head pressure controls
NOTE: When connecting the power supply for the boards, The controller can deal with the following:
maintain polarity. • in the case of air-cooled units, for each circuit, fan stages
together with, if necessary, a variable speed fan (controlled
by an auxiliary board type 1)
• in the case of water-cooled units, a water valve. This valve
is controlled by an auxiliary board type 1 which supplies a
0-10 V d.c. signal.
6
3.3.3 - The evaporator pump 3.3.7 - Thermistors
In appropriate cases the controller can also regulate an evapo- These all have similar characteristics.
rator pump. This facility does not require an additional board.
Evaporator entering and leaving water temperature sensor
3.3.4 - The condenser pump The evaporator entering water temperature sensor and the
In appropriate cases the controller can also regulate a condenser leaving water temperature sensor are installed in the entering
pump (for water-cooled units). This control does not require an and leaving side water box.
additional board.
Discharge gas sensor
3.3.5 - The evaporator heater This sensor is used to measure the discharge gas temperature,
The evaporator heater can be regulated by the unit control on and permits control of the discharge temperature superheat. It
air-cooled units to protect the evaporator against frost. This is located in the discharge line of each compressor.
control requires an additional board.
Motor sensor
3.3.6 - Pressure sensors This is used to control the motor temperature of each compressor.
These are used to measure the following pressures in each The terminals of this sensor are situated on the compressor
circuit: terminal board.
• Discharge gas pressure (high pressure type)
• Suction pressure (low pressure type) Condenser entering and leaving water temperature sensors
• Oil pressure (high pressure type, except for the low These are used to control the heating capacity on heat pumps.
ambient temperature option when the sensor used is a In cooling only units they have no control function. They are
wide-band sensor) installed in the common condenser entering and leaving line.
• Economizer pressure (high pressure type)
Heat reclaim condenser entering/leaving water temperatures
These electronic sensors deliver 0 to 5 V d.c. The economizer These sensors measure the entering and leaving water tempera-
and oil pressure sensors are connected to the SCPM board and, tures of heat reclaim condensers and are used on air-cooled
as the others, are measured by the basic board. units. They may be fitted as options.
7
3.4 - User connections
CONNECTION TERMINALS
DESCRIPTION CONNECTOR/ TERMINAL DESCRIPTION REMARKS
CHANNEL
Alarm relay output, circuit A J3 / CH24 30A - 31A Indicates alarms in circuit A Volt-free contacts 24 V a.c. 48 V d.c.
max, 20 V a.c. or V d.c., 3 A max, 80
mA min, external power supply.
Alarm relay output, circuit B J3 / CH25 30B - 31B Indicates alarms in circuit B Connector: 6 pin WAGO 231-306/
026000 pitch 5.08.
Critical fault relay output J3 / CH26 37-38 Indicates that the compressor control contactor is stuck
closed
User safety loop and chilled J4 / CH15a 34 - 35 This contact is mounted in series with the water flow 24 V a.c., 20 mA
water pump interlock control contact. It can be used for any user safety loop that Connector: 10 pin WAGO 734-110,
requires that the unit is shut down, if it is open. The chilled pitch 3.5
water pump operation auxiliary contact is connected
between these two terminals.
Remote start/stop J4 / CH11 32 - 33 The remote start/stop command is only used if the unit is
under remote operation control (rEM). See section 4.2.1.
Remote cooling setpoint J4 / CH12 65 - 66 The remote cooling setpoint selection command is only
selection used if the unit is under remote operation control (rEM).
See section 4.2.1.
Remote heating/cooling J4 / CH13 63 - 64 The remote heating/cooling control command is only used
control if the unit is under remote operation control (rEM). See
section 4.2.1.
or J4 / CH13 63 - 64 The command allows selection of the second condensing
remote heat reclaim control setpoint or of the heat reclaim mode. It is only used if the
unit is under remote operation control (rEM). See section
4.2.1.
Demand limit command J4 / CH14 73 - 74 This contact permits activating the unit demand limit
function. See section 5.8. This contact is active, whatever
the operating type.
0-10 V d.c. setpoint reset or J8 / CH10 71 - 72 This 0-10 V d.c. input is used for setpoint reset or unit Connector: 2 pin WAGO 231-302/
demand limit entry demand limit. It is active, whatever the unit operating type. 026000 pitch 5.08
This 0-10 V signal can be supplied by a user command or a
0-10 V temperature sensor.
Connection to CCN J12 1-2-3 A RS-485 bus is used for connection to the CCN. Use of a shieled cable (max. length:
The CCN connector is located on the CCN/clock board 1000m).
(inserted on the PD4 BASIC board) Shielding: braiding on 95%-100% of
- Pin 1: signal + the cable surface.
- Pin 2: ground Shielding connection at the two cable
- Pin 3: signal - ends.
AVAILABLE TERMINALS
DESCRIPTION CONNECTOR/ TERMINAL DESCRIPTION REMARKS
CHANNEL
Condenser water flow switch J5/CH17 This contact is used to detect lack of condenser water flow 24 V a.c - 20mA
input and shuts down the unit.
Evaporator 1 and 2 pump J5/CH18 This contact is used to detect an evaporator pump operation
operation input fault and switches over to the other evaporator pump*.
Evaporator 1 control J2/CH19 This contact permits control of evaporator 1 pump by the 24 V a.c. internal supply.
unit*. Max. consumption
Evaporator 2 control J2/CH20 This contact permits control of evaporator 2 pump by the - each output: 20 VA/10W
unit*. - for all 3: 40 VA/20 W if all are used
Condenser pump control J2/CH21 This contact permits control of condenser pump by the unit*.
Legend
* Associated functions, if selected: automatic changeover, pump 1 and 2; manual or CCN selection; periodical; by default.
8
4 - SETTING UP PRO-DIALOG PLUS CONTROL
Up arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises
increase of the value of any parameter.
Down arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises
decrease of the value of any parameter.
Enter Gives access to the modification mode, validates a modification or displays expanded item description.
Start/stop Authorises start or stop of the chiller in local mode or modification of its operating type.
SETPOINTS menu Displays the unit setpoints and enables them to be modified.
INPUTS menu Displays the status of the unit digital and analogue inputs.
OUTPUTS/TESTS menu Displays the status of the unit outputs and enables them to be tested.
OPERATING LOG menu Displays the operating times and number of starts for the unit and the compressors.
9
The summary interface (right hand section) includes a mimic The following operating types can be selected using the
diagram of the unit, together with push-buttons and LEDs. It Start/Stop button:
gives quick access to the main operating parameters of the unit.
OPERATING TYPES
SUMMARY INTERFACE LEDS 4-DIGIT DISPLAY DESCRIPTION
LED INDICATION WHEN LIT LOFF Local Off. The unit is halted in local mode.
Green LED: L-On Local On. The unit is in local control mode and is authorised
The unit is authorised to start or is already running to start.
Red LED: L-Sc* Local On - timer control. The unit is in local control mode. It
- Lit: circuit A or unit shut down by alarm is authorised to start if the period is occupied. If the timer
- Flashing: circuit A or unit running with alarm present program for unit operation is unoccupied, the unit remains shut
Red LED: down until the period next becomes occupied.
- Lit: circuit B or unit shut down by alarm CCN* CCN. The unit is controlled by CCN commands.
- Flashing: circuit B or unit running with alarm present
rEM* Remote. The unit is controlled by remote control contacts.
Red LED:
Water flow switch default or user safety lock open. MAST* Master Unit. The unit runs as a master in a two unit lead/lag
arrangement. This is displayed if the unit is configured for
Green LED: master/slave control. See section 5.21.
The evaporator pump is running.
Legend
Yellow LEDs: * Displayed if the configuration requires it.
From top to bottom - start/stop status of compressor A1 and A2 Section 5.1 gives a more detailed description of the commands to start/stop
or B1 and B2. Flashing LED indicates that the circuit is in the the unit, analysed by operating type.
protection or defrost mode (A or B).
Green LED: 4.2.2 - Stopping the unit in local mode
The unit operates in heating mode.
The unit can be stopped in local mode at any time by
Green LED:
The unit operates in cooling mode. pressing the Start/Stop button.
10
4.3 - Menus NOTE: The access to a sub-menu may require entering a
password. This is automatically requested. See section 4.5.7.2.
4.3.1 - Selecting a menu
The MENU button authorises you to select a menu from the The example below shows how to modify the value of item 1
10 main menus that are available. Each time you press this in the Setpoint menu.
button one of the 10 LEDs lights up in turn alongside each
of the icons representing a main menu. The active menu is MODIFYING THE VALUE OF A PARAMETER
the one against which the LED is lit. If a menu is empty then OPERATION PRESS MENU LED ITEM ITEM
button NUMBER NUMBER
its LED is not lit. To scroll quickly through the menus, hold 2-DIGIT 4-DIGIT
the MENU button down. DISPLAY DISPLAY
Hold on the MENU button until the 0
LED for SETPOINT lights.
4.3.2 - Selecting a menu item
The up and down Arrow buttons let you scroll through the 0
menu items. Menu item numbers are displayed in the two-digit
Press one of the Arrow buttons until 1
display. The item number increases or decreases every time you the two-digit display shows 1 (item
number 1- cooling setpoint 2).
press the up or down Arrow button. The menu items that are The value for setpoint 2 is displayed
not in use or incompatible with the configuration are not in the four-digit display (6.0°C in 1 6.0
this example).
displayed. The value or status associated with the active item is
displayed in the four-digit display. To scroll quickly through Press the Enter button for more
than 2 seconds to enable the value
the items, hold the up or down Arrow button down. associated with item 1 to be modified. 1 6.0
The Setpoint menu LED flashes
indicating that modification mode
The following example shows how to access item 3 in the is active.
11
4.4 - General menu structure
MAIN MENUS
12
STATUS TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION ALARMS ALARMS HISTORY RUNTIME
SUB-MENUS
USER SERVICE FACTORY RUNTIME 1 MAINTE-
[USEr] [SErviCE] [FACtorY] [RuntiME 1] NANCE
SUB-SUB-MENUS
OUTPUT 1 OUTPUT 2 USER 1 USER 2 SCHEDULE 1 SCHEDULE 2 HOLIDAYS HOUR + DATE BROADCAST SERVICE 1 SERVICE 2 SERVICE 3 MASTER/SLAVE FACTORY 1 FACTORY 2
[OUTPUT 1] [OUTPUT 2] [USEr 1] [USEr 2] [SCHEduLE 1] [SCHEduLE 2] [HoLidAy] [dAtE] [brodCASt] [SErviCE 1] [SErviCE 2] [SErviCE 3] [FACTORY 1] [FACTORY 2]
[MAStEr SLAvE]
---
---
---
HOLIDAYS 15
[HoLidAy15]
in % temperature, circuit A circuit B for zero reset and phase reversal code 9
Not in use
interlock control
9 Present demand Discharge superheat, Suction pressure, circuit Cooling - threshold Oil level, circuit A - - - Historic alarm -
limit in % circuit A B for max. reset code 10
10 Present lag limit in Temperature motor Oil pressure, Cooling - max. Oil level, circuit B - - - - -
% A1 compressor B1 reset value
11 Setpoint in local Temperature motor Oil pressure, Heating - threshold External 0-10 V d.c. - - - - -
control A2 compressor B2 for zero reset signal
12 Setpoint occupied/ Saturated discharge Oil differential pressure, Heating - threshold Compressor current A1 - - - - -
unoccupied mode temperature, circuit B compressor B1 for max. reset
13 Active setpoint Saturated suction Oil differential pressure, Heating - max. Compressor current A2 - - - - -
temperature, circuit B compressor B2 reset value
14 Control point Gas discharge Economizer B1 pressure - Compressor current B1 - - - - -
temperature, circuit B
15 Controlled water Discharge superheat, Economizer B2 - Compressor current B2 - - - - -
temperature circuit B pressure
16 Condensing point Temperature motor Remote discharge - Total compressor - - - - -
B1 pressure, circuit A operating current
17 Heat reclaim Temperature motor Remote discharge - - - - - - -
indicator, circuit A B2 pressure, circuit B
18 Heat reclaim Outdoor temperature Heat reclaim pressure, - - - - - - -
indicator, circuit B circuit A
19 - Water loop Heat reclaim pressure, - - - - - - -
13
±nn.n °C 1: Controlled water temperature: temperature of the water that the unit tries to maintain at the control point.
2: Unit operating type
LOFF - Local Off
L-On - Local On
L-Sc - Local On - based on unit clock.
CCn - CCN Control.
rEM - Remote Control
MASt - Master unit
3: Unit status
OFF - Off: Unit is stopped and not authorised to start.
rEADY - Ready: Unit is authorised to start
dELAY - Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can be
configured in the User Configuration menu.
StOPPing - Stopping: Unit is currently stopping.
running - On: Unit is running or authorised to start.
triPout - Fault shutdown.
OvErridE - Limit: The operating conditions do not allow total unit operation.
4. Unit occupied/unoccupied status
OCCUPIEd - Occupied: Unit in occupied mode
UNOCCUPIEd - Unoccupied: Unit in unoccupied mode
5. Heating/cooling operating mode
COOL - Cooling: Unit operates in cooling mode
HEAT - Heating: Unit operates in heating mode
rECLAIM - Cooling: Unit is in auto cooling and heat reclaim demand is active
6. Alarm mode
ALArM - Alarm: Unit is totally stopped because of failure.
ALErt - Alert: Unit is in failure but not completely stopped.
7. Master/Slave status
MAStEr - Master: The master/slave control is active and the unit is the master
SLAvE - Slave: The master/slave control is active and the unit is the slave
1 [1] nn - Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode
code is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the following
table
14
DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)
MODE # MODE NAME DESCRIPTION
7 Delay at start-up active The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.
The delay is configured in the User1 configuration menu.
8 2nd cooling setpoint active The second cooling setpoint is active. See section 5.7.1
9 Setpoint reset active In this mode, the unit uses the reset function to adjust the leaving or entering water temperature setpoint. See section
5.7.2.
10 Demand limit active In this mode, the capacity at which the unit is allowed to operate is limited. See section 5.8.
11 Ramp loading active Ramp loading is active. In this mode, the controlled high or low water temperature value (in °C/min) in heating mode is
limited to a preset value in order to prevent compressor overload. The ramp function must be configured (see User1
configuration menu). The ramp values can be modified (see setpoint menu).
12 Low entering water temperature The unit is in heating mode and the temperature of the evaporator leaving water is lower than the lesser of the two
protection in heating mode cooling setpoints. A capacity stage is removed. This mode only applies to heat pumps.
13,14 Low suction temperature protection 13 = circuit A & 14 = circuit B. Protection for evaporator suction low temperature circuit is active. In this mode, circuit
capacity is not authorised to rise if the unit is in cooling mode, and saturated suction temperature in the circuit is lower
than the frost protection threshold.
15,16 Low discharge superheat protection 15 = circuit A & 16 = circuit B.
In this mode the circuit capacity is not authorised to rise.
17,18 High pressure protection 17 = circuit A & 18 = circuit B. The circuit is in high pressure protection mode because the HP protection threshold
has been exceeded. The circuit capacity is not authorised to rise and any slave compressor can be stopped in order
to prevent a high pressure break.
19,20 High current protection 19 = circuit A & 20 = circuit B. Circuit capacity is not allowed to rise, as the compressor has reached the high current
protection threshold and could be shut down.
21 Heat reclaim active Circuit A or circuit B operates in heat reclaim mode and not in standard cooling mode (pumpdown phase is activated).
22 Evaporator heater active Mode active if risk of frost exists.
23 Evaporator pump reversal active Two evaporator water pumps installed on the unit and pump reversal is active. See section 5.3
24 Periodic evaporator pump start-up The unit is shut down and is started every day at 14:00 hours for 2 seconds. This function must be configured in the
User1 menu. See sections 5.3 and 4.5.7.3.
25 Low night-time capacity Unit capacity is limited. The period when this mode starts, as well as the limited capacity in night-time mode are
controlled in Costomer 1 menu.
26 Unit under SM control Unit is under control of a System Manager (FSM or CSM III).
27 Master/slave link active Unit is connected to a secondary unit by a master slave link and either:
- the unit is configured as a master and this master is operating, or
- the unit is configured as a slave and this slave is operating.
4.5.2 - Description of the Temperatures menu 4.5.3 - Description of the Pressures menu
TEMPERATURES MENU [2] PRESSURES MENU [2]
ITEM FORMAT UNITS COMMENTS
ITEM FORMAT UNITS COMMENTS
0 ±nn.n °C Evaporator entering water temperature
0 nnnn kPa Discharge pressure circuit A
1 ±nn.n °C Evaporator leaving water temperature
1 nnnn kPa Suction pressure circuit A
2[1] ±nn.n °C Condenser entering water temperature
2 nnnn kPa Oil pressure compressor A1
3[1] ±nn.n °C Condenser leaving water temperature
3[1] nnnn kPa Oil pressure compressor A2
4[1] ±nn.n °C Reclaim condenser entering water temperature
4 nnnn kPa Differential oil pressure compressor A1
5[1] ±nn.n °C Reclaim condenser leaving water temperature
5[1] nnnn kPa Differential oil pressure compressor A2
6 ±nn.n °C Saturated discharge temperature circuit A
6 nnnn kPa Economizer pressure A1
7 ±nn.n °C Saturated suction temperature circuit A
7[1] nnnn kPa Economizer pressure A2
8 ±nn.n °C Discharge gas temperature circuit A
8 nnnn kPa Discharge pressure circuit B
9 ±nn.n °C Discharge superheat temperature circuit A
9 nnnn kPa Suction pressure circuit B
10 ±nn.n °C Motor temperature A1
10 nnnn kPa Oil pressure compressor B1
11[1] ±nn.n °C Motor temperature A2
11[1] nnnn kPa Oil pressure compressor B2
12 ±nn.n °C Saturated discharge temperature circuit B
12 nnnn kPa Differential oil pressure compressor B1
13 ±nn.n °C Saturated suction temperature circuit B
13[1] nnnn kPa Differential oil pressure compressor B2
14 ±nn.n °C Discharge gas temperature circuit B
14 nnnn kPa Economizer pressure B1
15 ±nn.n °C Discharge superheat temperature circuit B
15[1] nnnn kPa Economizer pressure B2
16 ±nn.n °C Motor temperature B1
16[1] nnnn kPa Remote discharge pressure, circuit A
17[1] ±nn.n °C Motor temperature B2
17[1] nnnn kPa Remote discharge pressure, circuit B
18 ±nn.n °C Outdoor temperature
18[1] nnnn kPa Pumpdown pressure, heat reclaim, circuit A
19[1] ±nn.n °C Water loop temperature, master/slave assembly
19[1] nnnn kPa Pumpdown pressure, heat reclaim, circuit B
Legend
Legend
1 This item is displayed in certain unit configurations only
1 This item is displayed in certain unit configurations only.
2 Access to this menu is read-only.
2 Access to this menu is read-only
15
4.5.4 - Description of the Setpoints menu
Legend
1 This item is displayed in certain unit configurations only.
2 All points contained in this table can be modified.
* Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.
Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.
** These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.5.7.3.
Note:
Three setpoint reset configuration modes can be selected in the Customer 1
menu:
1 Reset using an external 0-10 V d.c. signal
2 Reset using Delta T
3 Reset by external temperature sensor (air-cooled units only)
The items with zero reset or maximum reset are based on these three modes.
* MCT = Maximum Condensing Temperature (depending on the application)
16
4.5.5 - Description of the Inputs menu
Legend
1 This item is displayed in certain unit configurations only
2 Access to this menu is read-only
* Active in all operating types
See section 3.4
17
4.5.6 - Description of the Outputs/Tests menu
4.5.6.1 - General
This menu displays the status of the controller outputs. More-
over, when the machine is fully stopped (LOFF) the outputs
can be activated for manual or automatic tests (the access to
the tests is password controlled).
18
OUTPUTS STATUS 2 AND TESTS MENU [2] [3]
ITEM FORMAT UNITS DESCRIPTION
0 This item returns you to the previous menu.
1 [1] tESt 0-8 Fan contactor status/test, circuit A
This item permits display of the number of fan stages. It also permits them to be tested in a sequentially. In test mode the
direction arrows permit successive display from 0 to 8, so as to authorise the forcing the outputs.
2 [1] tESt 0-8 Fan contactor status/test, circuit B
This item permits display of the number of fan stages. It also permits them to be tested in a sequentially. In test mode the
direction arrows permit successive display from 0 to 8, so as to authorise the forcing the outputs.
3 tESt Alarm command status/test
- b1 = alarm circuit A
- b2 = alarm circuit B
In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each alarm
output.
4 tESt % EXV position, circuit A
In the test mode the direction arrows permit forcing the valve to its fully open position.
5 tESt % EXV position, circuit B
In the test mode the direction arrows permit forcing the valve to its fully open position.
6 [1] tESt % Variable speed fan, circuit A or condenser water valve position in %
7 [1] tESt % Variable speed fan, circuit B or condenser water valve position in %
8 On - Evaporator water pump No. 1 command status. Not displayed if unit does not control a pump.
Stop - On: the pump operates
tESt - Stop: the pump has stopped
FAIL - Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump without
Good - delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is then
Forc - immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its status is
forced by CCN.
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
appears:
- Fail: displayed if the test has failed, because the pump is not started
- Good: displayed if the test succeeds
9 On - Evaporator water pump No. 2 command status. Not displayed if unit does not control a pump.
OFF - On: the pump operates
tESt - Stop: the pump has stopped
FAIL - Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump without
Good - delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is then
Forc - immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its status is
forced by CCN.
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
appears:
- Fail: displayed if the test has failed, because the pump is not started
- Good: displayed if the test succeeds
10 On - Condenser pump status/test
OFF - On: the pump operates
tESt Stop: the pump has stopped
FAIL Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump without
Good delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is then
Forc immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its status is
- forced by CCN.
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
appears:
- Fail: displayed if the test has failed, because the pump is not started
- Good: displayed if the test succeeds
11[1] nn Evaporator heater and heat reclaim condenser status
- b1 = evaporator heater
- b2 = heat reclaim condenser heater
12[1] tESt % Condenser water valve position in heat reclaim mode
13[1] Solenoid valve status/test, heat reclaim function
- b1 = heat reclaim coil shutoff solenoid valve, circuit A
- b2 = heat reclaim coil drain solenoid valve, circuit A
- b3 = heat reclaim coil shutoff solenoid valve, circuit B
- b4 = heat reclaim coil drain solenoid valve, circuit B
In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation
of each output.
14 YES Used only for local interface
no Cause all diodes and blocks to light up or flash, to verify that they are operating correctly
tESt
Legend
1 This item is displayed in certain unit configurations only
2 A test is only possible if the units are in local off mode and if all compressors have stopped
3 The password is only valid for the test. 'Test' is displayed during the test, alternating with the item number
19
4.5.6.3 - Manual tests The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-
This function allows the user to test the outputs individually, if word-protected. The other menus are directly accessible,
the machine is completely shut down (LOFF). To carry out a except if item 6 of the User 1 menu (password for all
manual test use the arrow keys to access the output to be tested configurations) has been validated.
and press the Enter key (longer than 2 seconds) to activate the
modification mode. The password is automatically requested, if 4.5.7.2 - Password
it has not previously been verified. The Outputs/Test LED on A password must be entered in order to access the test function
the user interface begins to flash. Enter the desired test value or to modify a configuration. It is automatically requested, if
and again press Enter to start the test. 'TESt' is displayed on the necessary: 'EntEr PASS' is displayed on the 4-digit display and
4-digit display alternately with the value tested. The Outputs/ the configuration menu LED flashes, indicating that the
Test LED stops flashing. Press the Enter key or an arrow key to modifi-cation mode is active. Press the arrow keys until the
stop the test. value '11' is displayed on the 4-digit display. Press Enter to
validate this. The configuration menu LED stops flashing. If
4.5.7 - Description of the Configuration menu the password is correct, 'Good' is displayed. If the password is
incorrect, 'PASS incorrEct' is displayed. The User password has
4.5.7.1- General a default value of 11.
This menu can be used to display and modify all configura-
tions: Factory, Service and User. Only the User Configuration This value can be modified through the Service configuration.
can be modified by the end-user. The Factory, Service and The password can be entered if the unit is fully stopped, other-
master/slave configurations are not described in this docu- wise 'ACCES dEniEd' (access denied) will be displayed on the
ment. A configuration can only be modified if the unit is fully 4-digit display. The controller automatically deactivates the
stopped (LOFF). password after 5 minutes without activity (i.e. no buttons
pressed) or after powering up.
20
CONFIGURATION
USER
[USEr]
PERIOD 3 PERIOD 3
HOLIDAY 3
PERIOD 4 PERIOD 4
HOLIDAY 4
PERIOD 5 PERIOD 5
HOLIDAY 5
PERIOD 6 PERIOD 6
HOLIDAY 6
PERIOD 7 PERIOD 7
HOLIDAY 7
PERIOD 8 PERIOD 8
HOLIDAY 8
...
...
...
HOLIDAY 15
HOLIDAY 16
21
4.5.7.3 - Description of the User 1 Configuration sub-menu
USER 1 CONFIGURATION SUB-MENU [2]
ITEM FORMAT UNITS DEFAULT COMMENTS
0 USEr MEnu - - When selected this item authorises return to the previous menu.
1 [1] 0/1/2 0 Lead circuit selection
0 = automatic based on the number of start-ups and the operating hours of each circuit
1 = lead circuit A
2 = lead circuit B
2 [1] 0/1 - 0 Circuit capacity increase sequence
0 = equal charge for both circuits
1 = priority charge on one circuit
3 [1] YES/no - no Ramp loading select. For units with more than one compressor per circuit.
Yes = ramp enabled
No = ramp disabled
This configuration enables the ramp to be activated for heating or cooling (depending on configuration): the
maximum rate (in °C/min) of temperature drop or rise for the heat exchanger water (leaving or entering, upon
configuration). Ramp setting value can be configured in the Setpoint menu.
4 1 to 15 min 1 Delay at start-up. This value is reinitialised after power-up or when both circuits are halted by local, remote or
CCN command. No compressor will be started up until this pause has expired. However, the evaporator pump
command will be activated immediately. The safety lockout loop will not be checked until the pause has expired.
5 0/1/2/3/4 - 0 Pump sequence select
0 = no pump
1 = one pump only
2 = two pumps with auto rotation
3 = pump #1 manual select
4 = pump #2 manual select
If the auto sequence is selected, the pump change-over occurs when the rotation delay is elapsed. If the
manual sequence is selected then, the selected pump is used in priority. Change-over occurs if one pump fails.
6 [1] 24 to 3000 hours 48 Pump changeover delay. Displayed if auto pump sequence is selected. This parameter is used for pump
auto-rotation: the control tries to limit the pump run time difference to the pump changeover delay value.
Change-over between pumps occurs when this difference becomes greater than the configured pump
changeover delay.
7 0/1/2/3 - 0 Automatic reset selection. Permits activation of automatic reset type
0 = none
1 = 0-10 V d.c. reference voltage
2 = temperature difference
3 = outdoor temperature
8 0/1/2 - 0 Demand limit selection
0 = demand limit not selected
1 = demand limit by contact
2 = demand limit by external signal 0-10 V d.c.
9 [1] 0 to 10 Volts 0 Voltage corresponding to 100% of the demand limit
10 [1] 0 to 10 Volts 0 Voltage corresponding to 0% of the demand limit
11 «YES/no» - yes Extended menu select
Yes = menu description available
No = menu description not available
This item authorises activating or inhibiting the menu item expanded display.
12 «YES/no» - no Password for all User Configurations
Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)
No = password require for User menu only
When this item is validated, the User Password will be required for all configurations accessible by the User.
13 nn.n - - Software version number
This item shows the number of the software version used by this controller. Access is read only.
14 nnnn Amp 1500 Total compressor current limit
This item is used to set the maximum limit for the total compressor running current (see paragraph “Pro-
Dialog Plus control operations/Limiting the unit running current”)
Legend
1 This item is masked when not used.
2 Access to menu is read/write.
22
4.5.7.4 - Description of the User 2 Configuration sub-menu
4.5.7.5 - Description of Date and Time configuration sub- 4.5.7.6 - Description of the Time Schedules sub-menus
menu The control provides two timer programs. If the CCN/clock
board is not installed, the two schedules are permanently in
DATE & TIME CONFIGURATION SUB-MENU occupied mode.
ITEM FORMAT COMMENTS
0 dAtE MEnu When selected this item authorises return to the
previous menu.
The first timer program (schedule #1) provides a means to
1 n 1n 2n 3n 4 Current time setting.
automatically switch the unit from an occupied mode to an
00:00 to 23:59 n1n2: hours (00 to 23). The first time the Enter button is unoccupied mode: the unit is started during occupied periods.
continuously pressed, the first two characters in the 4-
digit display flash so that hours can be adjusted.
n3n4: minutes (00 to 59). Continuous pressing of the The second timer program (schedule #2) provides a means to
Enter key again causes the last two characters to flash automatically switch (when auto mode is selected) the active
and minutes can be adjusted.
setpoint from an occupied setpoint to an unoccupied setpoint.
2 Current day of week setting.
«Mon» Monday Cooling or heating setpoint 1 is used during occupied periods.
«tUe» Tuesday Cooling setpoint 2 is used during unoccupied periods. For
«uEd» Wednesday
«tHu» Thursday additional information on setpoint activation see section 5.7.1.
«FrI» Friday
«SAt» Saturday
«Sun» Sunday
Each schedule consists of eight time periods set by the
3 n 1n 2n 3n 4 Current day and month setting. operator. These time periods can be flagged to be in effect or
01:01 to 31:12 n1n2:day (01 to 31). The first time the Enter button is not in effect on each day of the week plus a holiday period (see
continuously pressed, the first two characters in the 4-
digit display flash so that day can be adjusted.
section 4.5.7.7 on public holidays). The day begins at 00.00
n3n4:month (01 to 12). Continuous pressing of the Enter hours and ends at 24.00 hours.
key again causes the last two characters to flash so
that month can be adjusted.
Program is in unoccupied mode unless a schedule time period
4 nnnn Current year setting.
is in effect. If two periods overlap and are both active on the
same day, the occupied mode takes priority over the
unoccupied period.
23
PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 8) 4.5.7.7 - Description of the Holidays sub-menus
ITEM # FORMAT COMMENTS This function is used to define 16 public holiday periods. Each
0 Period X Menu Indicates the period (X) you are going to configure.
When selected this item authorises a return to the
period is defined with the aid of three parameters: the month,
main menu. starting day and duration of the public holiday period. During
1 n1n2n3n4 Occupied period - Start time*. these public holidays the controller will be in occupied or
00:00 to 24:00 Authorises entering the time of day at which the unoccupied mode, depending on the programmed periods
occupied period starts.
2 n1n2n3n4 Occupied period - End time*.
validated for public holidays (see section 4.5.7.8).
00:00 to 24:00 Authorises entering the time of day at which the
occupied period ends. Each of these public holiday periods can be displayed and
3 Mo- 0 or Mo- 1 1 = the period is in effect on Monday.
0 = period not in effect on Monday
changed with the aid of a sub-menu.
4 tu- 0 or tu- 1 1 = the period is in effect on Tuesday.
0 = period not in effect on Tuesday. ATTENTION: The broadcast function must be activated to
5 UE-0 or UE- 1 1 = the period is in effect on Wednesday. utilise the holiday schedule, even if the unit is running in
0 = period not in effect on Wednesday.
stand-alone mode (not connected to CCN). See section
6 tH- 0 or tH- 1 1 = the period is in effect on Thursday.
0 = period not in effect on Thursday.
4.5.7.6.
7 Fr-0 or Fr- 1 1 = the period is in effect on Friday. HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 16)
0 = period not in effect on Friday.
ITEM # FORMAT COMMENTS
8 SA- 0 or SA- 1 1 = the period is in effect on Saturday.
0 = period not in effect on Saturday. 0 HoLidAy X Sub-menu When selected this item authorises a return to
the configuration menu.
9 Su- 0 or Su- 1 1 = the period is in effect on Sunday.
0 = period not in effect on Sunday. 1 0 to 12 Start month of public holiday period
0 = period not in use
10 Ho- 0 or Ho- 1 1 = the period is in effect on public holidays. 1 = January, 2 = February, etc.
0 = period not in effect on public holidays.
2 0 to 31 Start day of public holiday period. 0 period
Legend not in use.
* n1n2: hours (00 to 24). The first time the Enter button is continuously pressed,
the first two characters in the 4-digit display flash so that hours can be 3 0 to 99 days Duration of the public holiday period in
adjusted. days.
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes
the last two characters to flash so that minutes can be adjusted. Typical programming for public holidays:
A public holiday period lasting 1 day on 20th May, for instance, is configured as
Typical timer program: follows: start month = 5, start day = 20, duration = 1
A public holiday period lasting 2 day on 25th May, for instance, is configured as
follows: start month = 5, start day = 25, duration = 2
Time MON TUE WES THU FRI SAT SUN HOL
20 P3 P6
21
22
23 Occupied
Unoccupied
24
24
BROADCAST CONFIGURATION SUB-MENU
ITEM # FORMAT COMMENTS
0 broAdCASt MEnu When selected this item authorises a return to the main menu.
1 YES/no Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be only
one broadcast acknowledger in a CCN.
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used
(see section 4.5.7.8) or if you want to configure the daylight saving time function.
2 YES/no This item authorises enabling or disabling the Broadcast function. When it is set to Yes, the control will make a periodic broadcast
on the CCN. When it is set to No, the control is not the broadcaster and there is no need to configure the other choice in this table.
There must be only one broadcaster in a CCN and this item should not be configured if any other system element is acting as
broadcaster.
Warning: if the unit operates in standalone (not CCN connected) this choice must be set to Yes if the holiday function is used (see
section 4.5.7.8) or if you want to configure the daylight saving time function.
3 nnn OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.
0 to 239 Used for CCN network function only.
4 nnn OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor
0 to 239 connected to it. Used for CCN network function only.
5 nn Daylight saving start month. In this mode you enter the month in which the broadcaster will adjust its time for the start of
1 to 12 daylight saving time.
6 nn Daylight saving start day. In this mode you enter the day on which the broadcaster will adjust its time for the start of daylight
1 to 31 saving time.
7 n 1n 2n 3n 4 Authorises entering the hours and minutes for saving start. In this mode you enter the time of day when the broadcaster will
00:00 to 24:00 adjust its time for the start of daylight saving time.
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that
hours can be adjusted.
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be
adjusted.
8 nnnn Daylight saving start minutes to add: number of minutes by which the broadcaster will adjust its time for the start of daylight
1 to 1440 minutes saving time.
9 nn Daylight saving stop month. In this mode you enter the month in which the broadcaster will adjust its time for the end of
1 to 12 daylight saving time.
10 nn Daylight saving stop day. In this mode you enter the day on which the broadcaster will adjust its time for the end of daylight
1 to 31 saving time.
11 n 1n 2n 3n 4 Authorises entering the hours and minutes for saving stop. In this mode you enter the time of day when the broadcaster
00:00 to 24:00 will adjust its time for the end of daylight saving time.
12 nnnn Daylight saving start minutes to subtract: number of minutes by which the broadcaster will adjust its time for the end of
1 to 1440 minutes daylight saving time.
Legend
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.
4.5.8 - Description of the Alarms menu 4.5.9 - Description of the Alarms History menu
This menu is used to display and reset up to 5 active alarms. It
ALARMS HISTORY MENU
also permits alarm reset. If no alarm is active this menu is not
ITEM # FORMAT COMMENTS
accessible. See section 6 for a complete description of the 1 [1] nn Alarm history code 1*
alarm codes and alarm reset. 2 [1] nn Alarm history code 2*
3 [1] nn Alarm history code 3*
ALARMS MENU
4 [1] nn Alarm history code 4*
ITEM # FORMAT DESCRIPTION
5 [1] nn Alarm history code 5*
0 [1] X ALArM X alarms are active
6 [1] nn Alarm history code 6*
rESEt ALArM Reset of alarms is requested
7 [1] nn Alarm history code 7*
To reset all active alarms, continuously press the Enter 8 [1] nn Alarm history code 8*
key. ‘rESET ALArM’ is then displayed. Press the select
9 [1] nn Alarm history code 9*
key again: all alarms are reset.
10 [1] nn Alarm history code 10*
1 [1] nn Current alarm code 1*
Legend
2 [1] nn Current alarm code 2*
1 This item is masked when nil
3 [1] nn Current alarm code 3* * Pressing the Enter key when alarm code is displayed causes the following
4 [1] nn Current alarm code 4* message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
5 [1] nn Current alarm code 5*
- “time of alarm”: hh-mm
Legend - “date”: dd-mm
1 This item is masked when nil - “full CCN alarm message”: up to 64 characters
* Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
- “time of alarm”: hh-mm
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters
25
4.5.10 - Runtime menu description 4.5.10.2 - Maintenance menu description
To be active, the maintenance function must be preset in the
RUNTIMES
Service configuration.
26
5 - PRO-DIALOG PLUS CONTROL OPERATION - Start/Stop schedule: occupied or unoccupied status of
the unit as determined by the chiller start/stop program
5.1 - Start/stop control (Schedule #1). Used when the unit is equipped with an
optional CCN/clock board, otherwise the chiller occupied
The table below summarises the unit control type and stop or mode is forced to occupied all the time.
go status with regard to the following parameters. - Master control type. This parameter is used when the
- Operating type: this is selected using the start/stop unit is the master unit in a two chiller lead/lag arrange-
button on the front of the user interface. ment. The master control type determines whether the
- Remote start/stop contacts: these contacts are used unit is to be controlled locally, remotely or through CCN
when the unit is in remote operating type (rEM). See (this parameter is a Service configuration).
sections 3.6.2 and 3.6.3. - CCN emergency shutdown: if this CCN command is
- CHIL_S_S: this network command relates to the chiller activated, it shuts the unit down whatever the active
start/stop when the unit is in CCN control (CCn). Vari- operating type.
able forced to disable: the unit is halted. Variable forced to - General alarm: the unit is totally stopped due to failure.
Enable: the unit runs in accordance with schedule 1.
5.2 - Heating/cooling selection The current heat/cool operating mode on the unit is indicated
by item 4 in the Information menu and by the heat/cool LEDs
On heat pumps, heating/cooling selection can be controlled on the summary interface.
differently depending on the active operating type:
• Locally on the unit, using operating types L-C1, L-C2,
LC1r and LC2r (for cooling) and L-H (for heating).
• Remotely using the heat/cool selection volt-free contact
when the unit is in Remote operating type (rEM).
• Via a CCN command when the unit is in CCN operating
type (CCn).
PARAMETER STATUS
ON/OFF CONTROL HEATING/COOLING SELECTION REMOTE HEATING/COOLING HC_SEL OPERATING MODE
STATUS TYPE IN LOCAL MODE CONTACTS
Off - - - - Cooling
On Local Cooling - - Cooling
On Local Heating - - Heating
On Remote - Cooling mode - Cooling
On Remote - Heating mode - Heating
On CCN - - Cooling Cooling
On CCN - - Heating Heating
27
5.3 - Evaporator water pump control 5.5 - Control interlock contact
The unit can control one or two evaporator water pumps. The This contact can prevent unit start-up if it is open and if the
evaporator water pump is turned on when this option is confi- start-up delay has passed. Furthermore, this contact must
gured (see User configuration) and when the unit is in one of remain closed when the unit is not in local off, remote or CCN
the on modes described above or in delay mode. Since the control mode. Opening this contact for more than 8 seconds
minimum value for the delay at start-up is 1 minute (configurable while the unit is operating, will cause immediate shut-down of
between 1 and 15 minutes), the pump will run for at least one the faulty unit.
minute before the first compressor starts.
5.6 - Evaporator heater control
The pump is kept running for 20 seconds after the unit goes to
stop mode. The pump keeps working when the unit switches The evaporator heater can be activated to protect an evaporator
from heating to cooling mode or vice-versa. It is turned off if that may be damaged by ice, if the unit is shut down for a long
the unit is shut down due to an alarm unless the fault is a frost period at low outdoor air temperature. If the heater is not
protection error. sufficient to increase the water temperature, the evaporator
pump can be started.
The pump can be started in particular operating conditions
when the evaporator heater is active. See section 5.21 for the NOTE: The evaporator heater control parameters may be
particular evaporator pump control for the follower unit (master/ modified using the Service Configuration menu.
slave assembly). If two pumps are controlled and the reversing
function has been selected (see User 1 configuration), the 5.7 - Control point
control tries to limit the pump run time delta to the configured
pump change-over delay. If this delay has elapsed, the pump Control point represents the leaving water temperature that the
reversing function is activated, when the unit is running. unit must produce.
During the reversing function both pumps run together for two • In cooling mode: control point = active setpoint + reset
seconds. If a pump has failed and a secondary pump is • In heating mode: control point = active setpoint - reset
available, the unit is stopped and started again with this pump.
5.7.1 - Active setpoint
The control provides a means to automatically start the pump Two setpoints can be selected as active in cooling mode.
each day at 14.00 hours for 2 seconds when the unit is off. If Usually, the second setpoint is used for unoccupied periods or
the unit is fitted with two pumps, the first pump is started on for ice storage (medium or low brine unit). A single setpoint is
odd days and the second pump is started on even days. Starting available in heating mode.
the pump periodically for few seconds increases the life-time
of the pump bearings and the tightness of the pump seal. Depending on the current operating mode, the active setpoint
can be selected with the operating type selector button, or with
NOTE: If this function is used, there should not be any the user’s volt-free contacts, or with network commands (see
chilled water pump interlock between terminals 34 and 35 section 3.4).
(see section 3.4).
5.7.2 - Reset
5.4 - Condenser water pump control Reset means that the active setpoint is modified so that less
machine capacity is required (in cooling mode, the setpoint is
Only available on water-cooled units. increased, in heating mode it is decreased). This modification is
in general a reaction to a drop in the load. For the Pro-Dialog
The condenser pump can be controlled by two modes, depend- Plus control system, the source of the reset can be configured
ing on the configuration (only accessible by Carrier Service). in the User 1 configuration: it can be based on an external 0-10 V
1 - Control based on unit start/stop control. In this case it is signal, provided either by the outdoor temperature (that gives a
controlled in the same way as the evaporator pump. measure of the load trends for the building) or by the return
2 - Control based on compressor status. In this case the pump water temperature (delta T that gives an average building load).
is activated at the same time as the first compressor. It In response to a drop in the outdoor temperature or to a drop in
only switches off when no compressor is activated. delta T, the cooling setpoint is normally reset upwards in order
to optimise unit performance:
In both cases the reset parameters, i.e. slope, source and maxi-
mum value, are configurable in the Setpoints menu (see section
4.5.4). Reset is a linear function based on three parameters.
• A reference at which reset is zero (outdoor temperature or
delta T - no reset value).
• A reference at which reset is maximum (outdoor
temperature or delta T - full reset value).
• The maximum reset value.
28
5.8 - Demand limit The control system continuously takes account of the tempera-
ture error with respect to the setpoint, as well as the rate of
Generally, demand limit is used by an energy management change in this error and the difference between entering and
system in order to restrict the unit electricity consumption. leaving water temperatures, in order to determine the optimum
moment at which to add or withdraw a capacity stage.
The PRO-DIALOG Plus control system for 30GX & 30HX
provides two methods of demand limit: NOTE: If the same compressor undergoes too many starts
• By reference to a limiting signal from a user-controlled (per hour) this automatically brings about reduction of
volt-free contact: the capacity of the unit cannot exceed compressor starts, which makes leaving water temperature
the demand limit setpoint (which can be modified in the control less precise.
Setpoints menu) when the limit contact is closed.
• By reference to an external 0-10 V d.c. signal: the capacity 5.11 - Determining the lead circuit
of the unit cannot exceed the demand limit imposed by
this external signal. It is a linear function and its para- This function commands the start/stop sequence of the two
meters are configurable in the User1 menu (voltages at 0% refrigerant circuits called A and B. The circuit authorised to
limitation and 100% of limitation). This function is not start first is the lead circuit. Three methods can be configured
available if reset by reference to an external 0-10 V d.c. by the user in the Configuration menu:
signal has already been selected. • Auto mode: the control system determines the lead
circuit so as to equalise the number of starts on each
Whatever the method used, demand limit is active in all circuit (value weighted by the operating times of each
operating types: Local, Remote or CCN. However, in circuit). Thus, the circuit with the least number of starts is
Local operating type, demand limit can be disabled with always given precedence to start. The lead circuit is
keypad commands (see section 4.3.3) and in CCN stopped last.
operating type, demand limit can be controlled directly • Circuit A as leader: Circuit A is always the lead circuit.
with the aid of CCN commands. It is the first to start and the last to stop.
• Circuit B as leader: Circuit B is always the lead circuit.
NOTE: A limitation value of 100% means that the unit may It is the first to start and the last to stop.
call upon the full array of its capacity stages.
5.12 - Circuit loading sequence
Here is an example of demand limit by an external 0-10 V d.c.
signal. This example assumes that the limitation parameters are Two circuit loading sequences are available. The choice of
such that at 0 volt the authorised capacity shall be maximum sequence can be configured by the user in the Configuration
capacity, and at 10 volts the authorised capacity shall be zero menu (see section 4.5.7.3).
(this is the default configuration). • Balanced circuit loading: If this sequence is selected,
the control system tries to keep the capacity of circuits A
Demand limit by 0-10 V d.c. signal and B equal as the total load on the unit increases or
decreases.
No demand limit • Loading with priority given to one circuit: If this
sequence is selected, the control system loads the lead
Maximum permitted capacity
Total demand limit NOTE: 30HX and 30GX units use 06N twin screw compres-
sors. The screw compressor efficiency is better at full load
than at part load. By default the 'close control'* configuration
is not validated, and the control will always try to optimise
0-10 V dc demand limit unit efficiency.
*
temperature precision has priority over compressor capacity. This parameter
is only accessible to Carrier Service.
5.9 - Limiting the unit running current
5.13 - Compressor start-up sequence in one circuit
This feature is used to avoid tripping the circuit breaker by:
• prohibiting an increase in compressor capacity when the The first compressor to start is the one with the least number of
current reaches a first threshold. start-ups and operating hours. If both compressors are operat-
• unloading one or more capacity stages when a second ing and the load decreases, the compressor that started first
protection threshold is reached. shuts down. This avoids cycling of ther same compressor.
See chapter: Description of the user 1 configuration sub-menu.
5.14 - EXV control
5.10 - Capacity control
The electronic expansion valves (EXVs) control charging and the
This function adjusts the number of active compressors and refrigerant flow in the evaporator, maintaining the optimum
loaders to keep the leaving water temperature at its setpoint. The evaporator throttle and a correct discharge superheat. Opening the
precision with which this is achieved depends on the capacity valve permits reduction of the throttle, and thus improves the
of the water loop, the flow rate, the load, and the number of heat exchange in the evaporator. This opening can be limited to
stages available on the unit. maintain the condenser subcooling and correct superheat,
29
avoiding liquid slugging at the compressors and ensuring In the event of capacity stages being shed, no capacity increase
operating stability. will be authorised on the circuit concerned for a period of 5
minutes.
5.15 - Motor cooling valve control
NOTE: The last capacity stage cannot be shed by this protec-
The temperature of the motor windings is controlled to a set- tion function. An alarm is activated, if the high pressure is
point of 82°C. This is achieved by cycling of the motor cooling still too high.
valves to allow the liquid refrigerant to flow across the motor
windings, if necessary. On units equipped with economizers 5.20 - High current load shedding function
with plate heat exchangers, a thermostatic valve controls the
necessary refrigerant flow entering this heat exchanger and This function does not require an additional board. It prevents
continuously flowing over the motor windings. All refrigerant high current breaks on each compressor by the following
used for motor cooling returns to the rotors through an orifice means:
situated mid-way along the compression cycle and is • Preventing any capacity increase on the compressor once
compressed to the discharge pressure. the high current value has reached an initial threshold
• Shedding one or more capacity stages once a second
5.16 - Head pressure control on air-cooled units protection threshold has been reached.
The saturated condensing temperature is controlled by reference In the event of capacity stages being shed, no capacity increase
to a fixed setpoint (user-definable in the Setpoints menu). This will be authorised on the circuit concerned for a period of 5
temperature is maintained by cycling fans on and off, as well as minutes.
by varying the speed of a fan.
5.21 - Start-up procedure - prelubrication
NOTE: Certain units can have up to 8 fan stages, of which
one per circuit is a variable speed fan, depending on their This procedure describes the necessary procedures to ensure
configuration and wiring. the lubrication of the compressor before start-up.
5.17 - Head pressure control on water-cooled units The control follows the sequence below:
The saturated condensing temperature is controlled by reference For the lead compressor (the first compressor in the circuit to
to a user-definable fixed setpoint. start):
1. Start the oil pump and measure the initial oil pressure.
This temperature is maintained by using the valve to control 2. Wait approximately 30 seconds.
the flow of water in each condenser circuit. 3. Verify the oil solenoid valve tightness, i.e.: if oil pressure
increases and the solenoid valve is not open, the oil
5.18 - Head pressure setpoint selection solenoid valve failure alarm is activated and prelubrica-
tion is stopped. The procedure is aborted.
There are two head pressure setpoints available: the first is called 4. If not, the oil solenoid valve is activated.
“head pressure setpoint” and the second “reclaim setpoint”. 5. Wait approximately 15 seconds.
These setpoints only have an effect when the control system is 6. If oil pressure increases, prelubrication is assured and the
controlling head pressure: air or water-cooled units operating in compressor can start.
cooling mode (only when they are fitted with condenser water 7. If not, a further prelubrication cycle is started. Return to
valves). point 1.
The active setpoint can be selected in one of the following NOTE: After three cycles, the low oil pressure alarm at pre
ways: start-up is acctivated, and prelubrication is also stopped.
• With item 5 of the information menu.
• With a volt-free selection contact connected to the customer For the lag compressor (one compressor in the circuit is already
terminal block when the unit is in Remote operating type in operation).
(rEM). See section 3.4, description of the control contacts. 1. Activate the oil solenoid valve.
• With a network command when the unit is in CCN opera- 2. Wait approximately 15 seconds.
ting type (CCn). 3. If oil pressure increases, prelubrication is assured and the
compressor can now start.
5.19 - High pressure load shedding function 4. If not, the low oil pressure at start-up alarm is activated
and the prelubrication is also stopped.
This function does not require an additional board. It prevents
high pressure breaks on a circuit by the following means: 5.22 - Master/slave assembly
• Preventing any capacity increase on the circuit once the
high pressure value has reached an initial threshold. Two PRO-DIALOG Plus units can be linked to produce a master/
• Shedding one or more capacity stages once a second slave assembly. The two machines are interconnected over the
protection threshold has been reached. CCN bus. All parameters required for the master/slave function
must be configured through the Service configuration menu.
30
Master/slave operation requires the connection of a temperature 5.24 - Optional heat reclaim module
probe at the common manifold on each machine, if the heat
exchanger leaving water temperature is controlled. This option only applies to air-cooled units, equipped with a
water-cooled heat reclaim condenser. An additional 4 x DO
The master/slave assembly can operate with constant or variable board must be installed. This board permits control of:
flow. In the case of variable flow each machine must control its • two solenoid shutoff valves for the heat reclaim coil, one
own water pump and automatically shut down the pump, if the per circuit.
cooling capacity is zero. For constant flow operation the pumps • two drain solenoid valves, one per circuit. These permit
for each unit are continuously operating, if the system is opera- draining the refrigerant from the inactive coil, when the
ting. The master unit can control a common pump that will be unit changes over from the cooling mode to the heat
activated, when the system is started. In this case the slave unit reclaim mode.
pump is not used.
Selecting the heat reclaim mode can be done with either the
All control commands to the master/slave assembly (start/stop, local interface or remotely with the (recl_sw) contact or by CCN.
setpoint, heating/cooling operation, load shedding, etc.) are
handled by the unit which is configured as the master, and must The heat reclaim function is active when: the heat reclaim
therefore only be applied to the master unit. They will be trans- entering water temperature is lower than the heat reclaim
mitted automatically to the slave unit. The master unit can be setpoint, minus half of the heat reclaim dead band.
controlled locally, remotely or by CCN commands. Therefore
to start up the assembly, simply validate the Master operating The heat reclaim function is not active when: the heat reclaim
type (MASt) on the master unit. If the Master has been confi- entering water temperature is higher than the heat reclaim
gured for remote control then use the remote volt-free contacts setpoint, plus half of the heat reclaim dead band.
for unit start/stop. The slave unit must stay in CCN operating
type continuously. To stop the master/slave assembly, select In the dead band the function remains in its active mode. The
Local Off (LOFF) on the master unit or use the remote volt- default value of the dead band is 4.4°C. This value can be
free contacts if the unit has been configured for remote control. modified by Carrier Service.
One of the functions of the master unit (depending on its con- Change-over procedure from cooling mode to heat reclaim
figuration) may be the designation, whether the master or slave mode:
is to be the lead machine or the follower. The roles of lead • Start-up of the condenser pump
machine and follower will be reversed when the difference in • Verification of the condenser flow switch control contact.
running hours between the two units exceeds a configurable If this remains open after one minute of condenser pump
value, ensuring that the running times of the two units are operation, the circuit remains in cooling mode and alarm
automatically equalised. The changeover between lead machine 83 for circuit A (alarm 84 for circuit B) will be activated.
and follower may take place when the assembly is started up, • As soon as the saturated condensing temperature reaches
or even whilst running. The running time balancing function is 30°C and the superheat reaches 8.3 K, the pumpdown
not active if it has not been configured: in this case the lead sequence is activated.
machine is always the master unit. • Pumpdown: closing of the cooling mode coil shutoff
valve. Opening of the drain valve, closing of the EXV
The lead machine will always be started first. When the lead valve.
machine is at its full available capacity, start-up delay (confi- • When the pumpdown pressure reaches the end of the
gurable) is initialised on the follower. When this delay has pump-down threshold, the pumpdown valve is closed and
expired, and if the error on the control point is greater than 1.7°C, the heat reclaim function is effective.
the follower unit is authorised to start and the pump is activated.
The follower will automatically use the master unit active set- Item 17 and 18 of the INFORMATION menu permits consulting
point. The lead machine will be held at its full available capa- different heat reclaim function sequences:
city for as long as the active capacity on the follower is not 17 = sequence of circuit A
zero. When the follower unit receives a command to stop, its 18 = sequence of circuit B
evaporator water pump is turned off with 20 seconds delay. 0 = cooling mode
1 = heat reclaim mode selection
In the event of a communication fault between the two units, 2 = pumpdown sequence
each shall return to an autonomous operating mode until the 3 = effective heat reclaim mode
fault is cleared. If the master unit is halted due to an alarm, the 4 = pumpdown fault*
slave unit is authorised to start without prior conditions. 5 = water flow switch fault*
5.23 - Controlling Pro-Dialog Plus units with a System * Alarm 83 for circuit A or 84 for circuit B is activated. Consulting the items 17
and 18 gives cause as (4) or (5). Resetting of the alarms re-initialises the
Manager information.
31
6 - DIAGNOSTICS - TROUBLESHOOTING RESET OF ACTIVE ALARMS
OPERATION ITEM NUMBER ITEM VALUE PRESS MENU
2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED
6.1 - General Hold down the MENU
button until the LED 0
The PRO-DIALOG Plus control system has many fault tracing for alarms lights. The
4-digit display shows 0 2 ALArM
aid functions. The local interface and its various menus give the number of active
access to all unit operating conditions. The test function makes alarms (2 in this
example).
it possible to run a quick test of all devices on the unit. If an
Press the Enter button 0 rESEt ALArM
operating fault is detected, an alarm is activated and an alarm until "rESEt ALARrM"
code is stored in the Alarm menu. is shown in the 4-digit
display.
Press the Enter button 0 Good
6.2 - Displaying alarms again to validate the then, 2 AL
reset. "Good" is dis- then, no ALArM
played for 2 seconds
The alarm LEDs on the summary interface (see section 4.1) then, "2 ALArM" and
give a quick display of the status of each circuit and the unit as then, "no ALArM".
a whole.
• A flashing LED shows that the circuit is operating but
there is an alarm.
• A steady LED shows that the circuit has been shut down
due to a fault.
When the cause of the alarm has been corrected the alarm can
be reset, depending on the type, either automatically on return
to normal, or manually when action has been taken on the unit.
Alarms can be reset even if the unit is running.
A manual reset must be run from the main interface using the
following procedure:
32
6.4 - Alarm codes
The following list gives a complete description of each alarm
code and its possible cause.
ALARM DESCRIPTION WHY WAS THIS ACTION TAKEN BY RESET TYPE PROBABLE
CODE ALARM GENERATED? THE CONTROL CAUSE
1 Evaporator entering fluid thermistor failure Thermistor outside range -40 to Unit shut down Auto, if the temperature Thermistor or
118°C measured by the sensor wiring fault or
becomes normal again cable/wire
damaged
2 Evaporator leaving fluid thermistor failure Ditto Unit shut down Ditto Ditto
3 Condenser entering fluid thermistor failure Ditto None, simple message Ditto Ditto
4 Condenser leaving fluid thermistor failure Ditto None in cooling mode Ditto Ditto
Unit shut down in heating mode
5 Condenser entering fluid thermistor failure Ditto None, simple message Ditto Ditto
6 Condenser leaving fluid thermistor failure Ditto None Ditto Ditto
7 Outdoor temperature sensor fault Ditto Reset based on deactivated outdoor Ditto Ditto
sensor
8 CHWS (master/slave) fluid thermistor fault Ditto Master/slave function deactivated Ditto Ditto
9 Compressor A1, discharge gas sensor Ditto Compressor A1 shut down Ditto Thermistor,
solenoid, motor
cooling or wiring
fault
10 Compressor A2, discharge gas sensor Ditto Compressor A2 shut down Ditto Ditto
11 Compressor B1, discharge gas sensor Ditto Compressor B1 shut down Ditto Ditto
12 Compressor B2, discharge gas sensor Ditto Compressor B2 shut down Ditto Ditto
13 External 0-10 V dc signal fault Signal outside range 1- Loadshed: not used Ditto Defective input or
2- Demand limit: deactivated wiring fault
14 Discharge pressure transducer failure,circuit A Measured signal = 0V dc Circuit A shut down Ditto Defective
transducer, wiring
fault
15 Discharge pressure transducer failure, circuit Ditto Circuit B shut down Ditto Ditto
B
16 Suction pressure transducer failure, crt A Ditto Circuit A shut down Ditto Ditto
17 Suction pressure transducer failure, crt B Ditto Circuit B shut down Ditto Ditto
18 Oil pressure transducer failure, compr A1 Ditto Compressor A1 shut down Ditto Ditto
19 Oil pressure transducer failure, compr A2 Ditto Compressor A2 shut down Ditto Ditto
20 Oil pressure transducer failure, compr B1 Ditto Compressor B1 shut down Ditto Ditto
21 Oil pressure transducer failure, compr B2 Ditto Compressor B2 shut down Ditto Ditto
22 Economizer A1 transducer failure Ditto Circuit A shut down for unit with Ditto Ditto
economizer. Otherwise compressor
A1 shut down.
23 Economizer A2 transducer failure Ditto Compressor A2 shut down Ditto Ditto
24 Economizer B1 transducer failure Ditto Circuit B shut down for unit with Ditto Ditto
economizer. Otherwise compressor
B1 shut down.
25 Economizer B2 transducer failure Ditto Compressor B2 shut down Ditto Ditto
26 Pressure sensor failure - coil pump down Ditto Circuit A remains in cooling mode Ditto Ditto
circuit A
27 Pressure sensor failure - coil pump down Ditto Circuit B remains in cooling mode Ditto Ditto
circuit B
28 Fault in the motor cooling valve position Ditto None Ditto Ditto
sensor, circuit A
29 Fault in the motor cooling valve position Ditto None Ditto Ditto
sensor, circuit B
30 Loss of communication with SCPM A1 board SCPM A1 board does not respond Compressor A1 shut down Ditto Wiring fault,
incorrect address
or defective board
31 Loss of communication with SCPM A2 board SCPM A2 board does not respond Compressor A2 shut down Ditto Ditto
32 Loss of communication with SCPM B1 board SCPM B1 board does not respond Compressor B1 shut down Ditto Ditto
33 Loss of communication with SCPM B2 board SCPM B2 board does not respond Compressor B2 shut down Ditto Ditto
34 Loss of communication with EXV board 4xDO board associated with the Unit shut down Ditto Ditto
EXV does not respond
35 Loss of communication with fan board #1 4xDO board controlling the first four Unit shut down if number of fan Ditto Ditto
fan stages does not respond stages by circuit is lower than three.
Otherwise circuit A shut down.
36 Loss of communication with fan board # 2 4xDO board controlling the fan Circuit B shut down Ditto Ditto
stages of circuit B does not
respond
37 Loss of communication with auxiliary board Board does not respond Unit shut down if heating mode has Automatic Bus wiring fault,
type 1 been selected. incorrect address
or defective board
38 Loss of communication with heat reclaim or Analogue board does not respond Unit shut down if heat reclaim mode is Automatic if board is again Auxiliary board
evaporator heater board selected. detected faulty
Faulty connection
39 'CCN/clock board' fault CCN/clock board is no longer Unit shut down Ditto Defective CCN/
detected clock board
40** Control box thermostat fault or phase reversal Sensor overheated Unit shut down Auto if the same alarm has Badly ventilated
not tripped the same day control box
33
ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE GENERATED? THE CONTROL TYPE
41 Unit emergency stop CCN command to stop the unit received Unit shut down CCN/ Control network
Automatic
42 Initial factory configuration All factory parameters are 0 Unit cannot start Auto No factory configuration
required
43-n Illegal initial factory configuration Bad factory configuration Ditto Ditto Factory configuration error
43-1 Compr A capacity too high
43-2 Compr B2 configured and
compressor B1 absent
43-3 Fan configured for a water-cooled
condenser
43-4 Fans not configured
43-5 Heat reclaim option configured
and reclaim sensors configured
44 Discharge pressure circuit A too SCT>loadshed threshold. Max. satur. condensing Circuit A shut down Auto in the Transducer/high pressure switch or fan
high pressure (mct_sp) if only one capacity stage remains 10mn that circuit defective, water flow obstructed in
in operation. follow the condenser, water entering
temperature or condenser air too high
45 Discharge pressure circuit B too SCT>loadshed threshold. Max. satur. condensing Circuit B shut down Ditto Ditto
high pressure (mct_sp) if only one capacity stage
remains in operation.
46 Oil solenoid failure, compressor Oil pressure differential >17kPa during the period Compressor A1 not Auto if the Oil valve defective
A1 following pump start-up and before opening of the oil authorised to start same alarm
solenoid (see prelubrication) has not
tripped the
same day
47 Oil solenoid failure, compressor Ditto Compressor A2 not Ditto Ditto
A2 authorised to start
48 Oil solenoid failure, compressor Ditto Compressor B1 not Ditto Ditto
B1 authorised to start
49 Oil solenoid failure, compressor Ditto Compressor B2 not Ditto Ditto
B2 authorised to start
50 Pre-start oil pressure, Oil pump does not sufficiently increase the pressure Compressor A1cannot start Ditto Low oil level, oil pump, oil solenoid or oil
compressor A1 during several prelubrication cycles transducer failure
51 Pre-start oil pressure, Oil pump does not sufficiently increase the pressure Compressor A2 cannot start Ditto Ditto
compressor A2 during several prelubrication cycles
52 Pre-start oil pressure, Oil pump does not sufficiently increase the pressure Compressor B1 cannot start Ditto Ditto
compressor B1 during several prelubrication cycles
53 Pre-start oil pressure, Oil pump does not sufficiently increase the pressure Compressor B2 cannot start Ditto Ditto
compressor B2 during several prelubrication cycles
54 Oil level circuit A low Oil level control contact open during operation Circuit A shut down Manual Oil level detector defective, oil quantity
insufficient
55 Oil level circuit B low Oil level control contact open during operation Circuit B shut down Manual Ditto
56 Low saturated suction temp, crt A SST under defrost theshold* for 3 minutes Circuit A shut down Auto if the Low refrigerant charge, filter drier
same alarm obstructed, expansion valve and
has not transducer defective, low water flow, low
tripped the evaporator water temperature
same day
57 Low saturated suction temp, SST under defrost threshold* for 3 minutes Circuit B shut down Ditto Ditto
circuit B
58 High saturated suction temp, After 90 seconds of operation if SST > 12,8°C & EXVCircuit A shut down Manual Expansion valve, liquid level sensor or
circuit A < 1% transducer defective, high evaporator
temp.
59 High saturated suction temp, After 90 seconds of operation if SST > 12,8°C & Circuit B shut down Manual Ditto
crt B EXV < 1%
60 Low discharge superheat, Superheat <2,8 K for 10 minutes Circuit A shut down Auto if the Thermistor, transducer, EXV or
circuit A same alarm economizer defective
has not
tripped the
same day
61 Low discharge superheat, crt B Superheat <2,8 K for 10 minutes Circuit B shut down Ditto Ditto
62 Max. oil pressure difference, (Discharge pressure - oil pressure) >340 kPa for Compressor A1 shut down Manual Obstructed oil filter, oil solenoid or shut-
compressor A1 more than 6 seconds off valve blocked, or manual oil valve
closed
63 Max. oil pressure difference, (Discharge pressure - oil pressure) >340 kPa for Compressor A2 shut down Manual Ditto
compressor A2 more than 6 seconds
64 Max. oil pressure difference, (Discharge pressure - oil pressure) >340 kPa for Compressor B1 shut down Manual Ditto
compressor B1 more than 6 seconds
65 Max. oil pressure difference, (Discharge pressure - oil pressure) >340 kPa for Compr B2 shut down Manual Ditto
compressor B2 more than 6 seconds
66 Loss of commuincation with The unit is controlled by a System Manager Unit returns to autonomous Auto Defective CCN BUS wiring or system
System Manager (Flotronic or Chiller) and communication with this operating mode module failure
module is lost for more than two minutes
67 Loss of communication with The master/slave link is broken due to a loss of Unit returns to autonomous Auto Defective CCN BUS wiring or loss of
master or slave unit communication between the two units for more than operating mode supply
2 minutes
68 Low oil pressure compr A1 Oil pressure differential below the setpoint Compressor A1 shut down Auto if the Low condenser air or water
(dynamically calculated) for 15 seconds same alarm temperature, oil filters obstructed, oil
has not valve blocked, oil solenoid and oil
tripped the pressure transducer defective
same day
69 Low oil pressure compr A2 Oil pressure differential below the setpoint Compressor A2 shut down Ditto Ditto
(dynamically calculated) for 15 seconds
70 Low oil pressure compr B1 Oil pressure differential below oil setpoints 1 or 2 Compressor B1 shut down Ditto Ditto
(see alert criteria for low oil pressure and setpoint)
34
ALARM CODE DESCRIPTION (CONT.)
ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE GENERATED? THE CONTROL TYPE
71 Low oil pressure compr B2 Oil pressure differential below the setpoint Compressor B2 shut down Auto if the Ditto
(dynamically calculated) for 15 se same alarm
conds has not
tripped the
same day
72 Evaporator frost protection 1 - Evaporator EWT or LWT below defrost Unit shut down. Evaporator Ditto Defective thermistor, low water flow
setpoint pump and if applicable heater
2 - On units equipped with an evaporator start-up, if unit has shut down
heater, heater operates for more than 15 air-cooled units)
minutes but does ot heat the evaporator
73 Condenser frost protection, circuit For water-cooled units and fluid type = Unit shut down. Condenser Automatic Discharge pressure
A water, if SCT<1,1°C pump start-up, if unit has transducer defective,
shut down refrigerant leak or low
condenser water temperature
74 Condenser frost protection, circuit For water-cooled units and fluid type = Unit shut down. Condenser Automatic Ditto
B water, if SCT<1,1°C pump start-up, if unit has shut
down
75 Evaporator water flow control 1 - Control not closed, before end of the Unit shut down. Pump shut Manual Evaporator pump control or
failure start-up delay or open during operation down water flow switch failure
2 - Pump shut down for 2 mins and water
flow contact closed
76 Condenser water flow loss Water flow switch (water-cooled units) not Unit shut down Manual Condenser pump, low water
closed during the minute after start-up flow, water flow switch
77 High current, compressor A1 Current higher than threshold value detected Compressor A1 shut down Auto after Operation above the compressor
10 mn capacity
delay
78 High current, compressor A2 Ditto Compressor A2 shut down Ditto Ditto
79 High current, compressor B1 Ditto Compressor B1 shut down Ditto Ditto
80 High current, compressor B2 Ditto Compressor B2 shut down Ditto Ditto
81 Pump 1 fault Evaporator water pump contact open, when Unit shut down Manual Pump overheat or bad pump
the pump has received a command to run connection
82 Pump 2 fault Ditto Ditto Manual Ditto
83 Heat reclaim mode fault, circuit A 1. Interlock not closed 1 minute after Circuit A remains in cooling Manual 1. Water flow switch defective.
condenser pump start-up or open during mode 2. Leak or heat reclaim shutoff or
heat reclaim operation drain solenoid valve open.
2. More than two consecutive pumpdown
sequences not successful.
84 Heat reclaim mode fault, circuit B Ditto Circuit B remains in cooling Manual Ditto
mode
85 Water flow fault, heat reclaim Water flow detector (water-cooled units) not Unit remains in cooling mode Manual Ditto
condenser closed for one minute
86-nn Master/slave configuration fault Bad master/slave configuration Master/slave control not Auto/ Master/slave configuration error
allowed manual for
heating/
cooling
mode fault
87-n Maintenance alert A maintenance alert is active None Manual
87-1 Charge too low
87-2 Water loop too low
87-3 Air filter maintenance delay elapsed
87-4 Pump 1 maintenance delay elapsed
87-5 Pump 2 maintenance delay elapsed
87-6 Water filter maintenance delay
elapsed
35
ALARM FUNCTION DESCRIPTION ACTION RESET NOTE
1xx Defect compressor A1 See SCPM subcodes below See SCPM subcodes below Manual
2xx Defect compressor A2 See SCPM subcodes below See SCPM subcodes below Manual
3xx Defect compressor B1 See SCPM subcodes below See SCPM subcodes below Manual
4xx Defect compressor B2 See SCPM subcodes below See SCPM subcodes below Manual
Legend:
* Defrost threshold = 1,1°C for water or for the lowest cooling setpoint less 4,4°C for brine or low brine.
** This safety circuit is controlled by two contacts, 16A and 16B, which are connected in series internally. If there is only a single control box there is a jumper on
16B, otherwise 16B controls the control box safety of the circuit. If one of the two contacts 16A and 16B is open, the whole unit is in fault status.
SCPM: Compressor protection module
FSM: Flotronic System ManagerTM
CSM: Chiller System Manager
MTA: Compressor Must Trip Amperes
Order No. 13054-76 (Phase 3 ), 04.2002. Supersedes order No.: 13054-76, 04.2000 Manufactured by: Carrier S.A., Montluel, France.
Manufacturer reserves the right to change any product specifications without.notice. Printed in the Netherlands on totally chlorine-free paper.
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.2
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
AIR HANDLING UNIT
INSTALLATION, START-UP AND
Carrier
International SERVICE INSTRUCTIONS
Sdn. Bhd.
® Malaysia CENTRAL STATION AIR HANDLING UNITS
INTRODUCTION
These instructions apply to the
Carrier 39G Galaxy Air Handling Unit.
1.0 Safety Consideration 1 Air handling units are designed to provide safe and
reliable service, when operated within design
specifications. To avoid injury to personnel and damage
2.0 Pre-Installation 2
to equipment or property when operating this
equipment, use good judgement and follow safe
3.0 Rigging 2
practices as out lined below.
4.0 Installation 3
WARNING
5.0 Unit Identification 5 a) Check the assembly and component weights to
be sure that the rigging equipment can handle
6.0 Section Joining Instruction 6 them safely.
b) Check for adequate ventilation so that fumes will
7.0 Fan Motor & Drives 7 not migrate through ductwork to occupy space
when welding or cutting inside air handling unit.
8.0 Installation Of Variable Inlet Vane Actuator 8 c) Do not remove access panel or door until fan is
completely stopped.
9.0 Refrigerant Piping, Direct Expansion Coils 8 d) Do not work on dampers until their operators are
disconnected.
10.0 Guide To Starting Up 11 e) Be sure that the fan motors are properly grounded
before working on them.
11.0 Guide To Servicing 12 f) Never enter an enclosed fan cabinet or reach into
the unit while the fan is running.
g) Disconnect power to the fan motor (Lock open and
tag) before working on the fan.
h) Disconnect power to electric heaters (Lock open
and tag) before working on or near heaters.
i) Never pressurise equipment in excess of specified
test pressure.
j) Protect adjacent flammable material when welding
or flame cutting. Use sheet metal or asbestos cloth
to contain sparks. Have a fire extinguisher at hand
and ready for immediate use.
2.1 Check items received against packing list. Notify 3.1 All 39G units are equipped with rigging hole. As
Carrier of any discrepancies. such, the units can be rigged by means of the rigging
2.2 Examine for damage incurred during shipment. File rod.
claim with transit company if any damage is found.
2.3 Refer to rigging details as shown in (Fig.1) to transfer
unit from truck to storage site.
2.4 If unit is to be stored for more than 2 weeks prior Shipping Bracket Picture shown typical shipping bracket for
standard offering of rubber isolator. It applies
to installation, please exercise the following also to spring isolator configuration.
precautions :-
a) Choose a dry storage site that is reasonably level
and sturdy to prevent undue stress and damage
to the unit structure or components. Do not store
on vibrating surface - damage to stationary bearing
can occur.
b) Remove all fasteners and other small parts - tag
and store these items in a safe place until needed.
c) Unit are shipped from the factory wrapped in protective
plastic sheet. The plastic sheets may be damaged
during transit or after inspection. Cover entire unit
with tarpaulin or plastic coverall. Extend cover under
unit if stored on ground. Secure cover with adequate
tie downs.
d) When unit is stored over an extended period we Fig. 2 Shipping Bracket
recommend a monthly procedure as follows -:
Remove the tarpaulin from the unit, enter fan through
access door or fan section inlet, remove the belt CAUTION
ties (if any) and rotate fan and motor (if any) slowly
by hand. This helps to re-distribute bearing grease If a fork lift truck is used, lift only from the heavy end.
and to prevent bearing corrosion.
3.2 Units are shipped fully assembled or in sections,
depending on size and application. The 39G Galaxy
central station air handling unit are built up in "Modules"
(Refer to Fig. 3). Any unit which is 22M (module)
or longer in length will be shipped in shorter sections.
3.3 Do not remove skids or protective covering until
unit or section is ready for final replacement.
IMPORTANT:
a) Do not lift unit by coil connections or headers.
b) Do not remove protective caps from coil piping
connections until ready to connect piping.
c) Do not remove protective cover on grease from fan
shaft until ready to install sheave.
d) When fan and motor drives are supplied from the
factory, the pulleys are installed but the belts are
supplied loose to avoid shipping damage. These
belts should be tag and stored at a safe place until
needed. This will help to minimise theft at job site.
e) Do not remove the shipping bracket (Refer to Fig. 2)
that are supplied to prevent the fan housing and
motor base from moving during transit. These
shipping bracket should only be removed after the
air handling unit is positioned and just immediately
after the fan motor and drive is installed.
f) Do not remove the shipping wood block, unless the
Fig. 1 Rigging Of Units fan motor and drive is going to operate.
2
DIMENSION OF FUNCTIONS (MODULES)
Note:-
Add 110mm for overall casing dimension which
includes the aluminium frames.
Fig. 4 Installation At Ground Level
4.0 INSTALLATION
3
FAN OFF
Fig. 6
4
4.3 Typical Assemblies, Dimensions And Service Areas
4.4 The 39G Air Handling Units are as standard fitted * Refer to your nearest Carrier representatives
with factory installed spring or rubber type anti-vibrations for the nomenclature.
mounts. Externally mounted anti-vibration mounts
in addition to the factory installed anti-vibration are
not recommended.
5
6.0 SECTION JOINING INSTRUCTION
6.1 25mm & 50mm
The installation procedure for joining bracket (Pre drilled holes) are as follows:
a. Identify the correct sections which need to be joined together.
b. Make sure all proper action are taken to level the two separate sections.
c. Affix the gasket (that is supplied with the unit) along the edges of the aluminium frame that is required to be joined
together. (refer figure 1)
d. Locate the pre-drilled holes along the horizontal and vertical frame.(refer figure 1)
e. To install the correct quantity of joining bracket, refer to SECTION JOINING INSTRUCTION sticker. Start by placing
the joining bracket between the frame and insert the bolt, nut and washer set.(refer figure 2)
f. Tighten the bolt and nut until it compress the gasket and make sure there is no leakage. The purpose of gasket is to prevent
any air leakage.
7
8.0 INSTALLATION OF VARIABLE INLET VANE 9.0 REFRIGERANT PIPING, DIRECT
ACTUATOR (OPTIONAL) EXPANSION COILS
8.1 Backward Curved Fans – Inlet vane linkage is factory Direct expansion coils are split into 2, 4 or 8 splits
installed on both inlets of fan. Install actuator and depending upon the unit size and coil circuiting. Each
checked linkage operation as follows:- split requires its own distributor nozzle, expansion
(a) Position Actuator – Locate inlet guide vane actuator valve and suction piping. Suction connections are
inside fan section. Actuator is to be mounted to any on the entering side connections for each coil split
suitable structural member (such as bearing support). are on the air leaving side in the same order from
Actual location will vary with unit size and fan discharge to bottom. Refer to example on (Fig. 12).
arrangement.
(b) Check Linkage - Align actuator and lever arm,
before connecting actuator to linkage for freedom of
movement from fully closed to fully open position. CAUTION
Then connect actuator and recheck linkage for proper
operation. Linkage adjustment must allow maximum Direct expansion coils are shipped pressurized with
travel actuator. dry air. Release pressure from each coil split through
valves in protective caps before removing caps. Do
not leave piping open to the atmosphere unnecessarily.
Water and water vapor are detrimental to the refrigerant
CAUTION system. Until the piping is complete, recap the system
and charge with nitrogen at the end of each work-day.
Improper adjustment of linkage for actuator travel Clean all piping connections before soldering joints.
may cause linkage to slip. The lower split of face split coils should be first on,
last off. Row split coils utilize special intertwined circuits:
either splits of these row split coils can be first on,
last off.
Fan Type
Backward curved Max Torque Force (Nm)
BCG 400 8.3
BCG 450 12.3
BCG 500 18.6
BCG 560 19.6
BCG 630 27.5
BCG 710 39.2
BCG 800 63.8
BCG 900 78.5
BCG 1000 98.1
Fig. 11 Inlet Vane Operator Data
CAUTION
8
9.1 Suction Piping
Connect suction piping as shown in (Fig.13) for face
split coil or (Fig 14) for row split coil. Suction line from
coil connection to end of the 15-diameter-long riser
should be same tube size as coil connection to ensure
proper refrigerant velocity. Refer to Carrier System
Design Manual, Part 3, and size remaining suction
line header pressure drop equivalent to approximately
2.50F. Refer to Fig 16 for piping risers to the compressor.
Note:-
Factory supplied distributor nozzle sizes are
marked on coil cover label. Be sure that correct
nozzle is installed in each distributor before installing
expansion valve.
9
Fig. 15 Double-Circuited Face Split Coil Manifolding (Typical)
11
10.12 Chilled Water and Hot Water Coil. 11.4 To clean the coil, spray mild detergent solution
To vent the coils, proceed as follows :- on the coils with garden type sprayer. Rinse with
a) Close all coil water supply and return main fresh water. Check to ensure that the condensate
valves. line is not clogged up.
b) Open all vents but no more than 2 full turns.
c) If vent is clogged up with dirt it may be necessary 11.5 Winter shutdown for chilled water coil, proceed
to remove needle valves from vents and clean as follows :-
as necessary. 1) Anti freeze methods of coil protection.
d) Open coil water supply and return valves. Fill a) Close coil water supply and return valves.
coil with water until all air is expelled. This b) Drain coil as follows :
occurs when the hissing sound from the vent Method 1
stops and only water is oozing out from the vent. “Break” flange of coupling at each header location,
e) Close vent needle valves. separate flange or coupling connection to facilitate
coil drawing.
Method 2
CAUTION It is recommended that the auxillary drain be
added to coil piping if yearly “Winterizing” of coils
The venting procedure for hot water coil must be
is anticipated. This auxillary piping should be located
done when the water is not heated up.
at the highest and lowest point on the respective
header connection for each coil. Hence, to drain
the coil, open both valves to the auxillary drain
10.13 Direct Expansion Coil piping.
Charge refrigerant in accordance with the c) After coil is drained, Method 1, connect line
recommendation as shown in the Installation with a service valve and union from upper
Operating and Maintenance instructions for the nozzle to an anti freeze reservoir. Connect a
condensing unit. self priming reversible pump between the low
header connection and the reservoir. Method
11.0 GUIDE TO SERVICING 2, make connection to auxillary drain valves.
d) Fill reservoir with any inhibited anti-freeze
11.1 Review the safety considerations at the beginning
acceptable to local authority codes.
of these instructions. Good safety habits are
e) Open service valve and circulate solution for
important tools when performing servicing
15 minutes, then check its strength.
procedures.
f) If solution is too weak, add more anti-freeze
until desired strength is reached, then circulate
11.2 Use a strobe type tachometer or calculate as per
solution through coil for 15 minutes or until
item 10.9.
concentration is satisfactory.
g) Remove upper line from reservoir to reversible
11.3 To replace the fan motor, proceed as follows :-
pump. Drain coil to reservoir and close service
a) Shut off the power of the motor.
valve.
b) Disconnect the tag power wires at motor
h) Break union and remove reservoir and it lines.
terminals.
i) Leave coil flanges or coupling open and auxillary
c) Loosen motor brace-to-mounting rails attaching
drain valves open until spring.
bolts. Loosen belt tensioning bolts to adjust
the motor position so V-Belts can be removed
11.6 Coil Removal
without stretching over grooves.
a) (Refer to Fig. 6 and 7) for service clearance area.
d) Mark belts as to position. Remove and set aside
b) For chilled water coil, shut off the valves.
belts, tag as necessary.
c) Disconnect the chilled water and condensate
e) Remove motor to motor bracket hold down bolts.
piping.
f) Remove motor pulley and set aside.
d) Remove coil section panel (all screws are located
g) Remove the motor.
on the inside of the unit).
h) Install the new motor. Re-assemble by reversing
e) On header end, remove screws holding the
steps a to f. Be sure to re-install multiple belts
block off and the coil casing.
in their original position. Use a new set if
f) Slide coil and baffles out of unit.
required. Do not stretch belts over the pulleys.
g) Lift coil using hooks at the coil casing. Do not
Align belts as per item 7.3.
lift by header or center of coil.
i) Re-connect motor leads and restore power.
h) Reinsert coil by reversing order of procedures
Check fan proper rotation as described in
listed.
item 10.10 Start-Up procedure.
i) Apply sealant as necessary to edges to ensure
air tightness.
12
11.7 Fan Shaft and Bearing 11.9 Lubrication
a) Disconnect power supply to fan motor. Fan bearings are not permanently lubricated.
b) Use wooden blocks to prevent the fan and Advisable to top-up grease every 3 months.
motor assembly from free floating over the
anti-vibration mounts. 11.10 Filters
c) Loosen motor frame adjustment to release The 39G unit can be supplied with or without filters
belt tension. Remove belts. from the factory. There are 3 types of standard
Caution: Do not stretch belts over the pulley. filters available.
Damage to belt can result. a) High velocity panel filters (Side withdrawal
d) Loosen bolts on bushing of pulley and remove type).
bushing, then the pulley. b) Low velocity panel filters (Side withdrawal
e) Loosen bearing set screw and locking collar. type).
Drive eccentric type collar in direction opposite c) Bag filters (Side withdrawal type).
to shaft rotation. d) HEPA filter EU13 particle board frame.
f) Remove bearing while observing the following
precaution. (Refer 11.8). Notes:-
The high velocity filter frame are design to accept
11.8 Blower Wheel Replacements filter media cells with aluminium or steel frame.
a) There are two type of DIDW centrifugal fans * HVF & LVF Media-these filters shall be of the
used with the 39G unit. washable /disposable 48mm deep plated panel
i) Backward Curved. type, gravimetric efficiency 85% to 93% to ASHRAE
ii) Forward Curved. 52-76.
b) All blower wheel and fan shaft are designed to BF Media-these bag filters shall be of the disposable
be removed through fan housing inlet. Generally, dry media type, deep bed, fixed panel type, 600mm,
there should be no need to disconnect the average gravimetric efficiency 85% to ASHRAE
flexible connection and duct work. 52-76.
For other types of filters, please contact your
nearest Carrier representatives.
CAUTION
13
14
Item Description
1 Belt Tensioner
2 Bolt, HEX HD M10-30L(S)
3 Bolt, HEX HD M12-30L
4 Bolt, HEX HD M12-40L
APPENDIX 1 : ASSEMBLY FAN AND MOTOR BASE (PHASE 1)
15
16
FILTER TYPE, DIMENSION AND QUANTITY FOR EACH AHU SIZE.
MODEL
PART NAME PART NO.
0508A 0508B 0511 0612 0713 0813 0914 0916 1018 1118 1319 1422 1522 1722 1724 1725 1926 2127 2230 2234 2434 2636
a) HEPA Filter EU13 Particle Board Frame (Media Thickness 292mm)
(H305 x W305)mm 39GA509-320 - - 1 - - - - - - - - - - - - - - - - - - -
(H305 x W610)mm 39GA509-321 1 1 1 - - - - - 2 2 - - - 3 - - - - - - 5 -
(H508 x W508)mm 39GA509-322 - - - 2 2 2 - - - - 6 - - - 12 12 12 - 20 24 - -
(H610 x W610)mm 39GA509-323 - - - - - - 2 2 2 2 - 6 6 6 - - - 9 - - 15 20
b) 1” Bag Filter 402mm L
(H289 x W391)mm 39GA509-388 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-384 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-381 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-386 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
c) 1” Bag Filter 450mm L
(H289 x W391)mm 39GA509-396 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-392 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-389 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-394 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
d) 1” Bag Filter 529mm L
(H289 x W391)mm 39GA509-380 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-376 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-373 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-378 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
e) 1” HVF Filter Washable
(H289 x W391)mm 39GA509-130 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-035 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-032 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-037 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
f) 2” HVF Filter Washable
(H289 x W391)mm 39GA509-131 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-041 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-038 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-043 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
g) 1” HVF Filter Disposable
(H289 x W391)mm 39GA509-128 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-023 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-020 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-025 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
h) 2” HVF Filter Disposable
(H289 x W391)mm 39GA509-129 - - 1 - - - - - - - - - - - - - - - - - - -
(H391 x W595)mm 39GA509-029 - 1 1 - - 2 - - - - - - - - - - - - - - - -
(H289 x W595)mm 39GA509-026 1 - - 4 - 2 2 3 3 3 - 2 5 5 5 4 - 4 7 8 4 4
(H595 x W595)mm 39GA509-031 - - - - 2 - 2 2 3 3 6 6 6 6 6 8 12 12 12 15 20 20
Note: Dimension in mm
INTERNAL SPRING ISOLATOR ARRANGEMENT
SPRING SELECTION (UBF/DBF) (For UBR/DBR, A<->B; C<->D)
MOTOR FAN SIDE A/B FREE SIDE C MOTOR SIDE D
UNIT (39G) FAN SIZE HP WGT(kg) A B C D
FCG02-160 (7kg) 1 15 514 513 513 515
1.5 20 514 513 513 516
0508A
1.5 20 515 514 513 516
FCG02-180 (9kg)
2 22 515 514 513 516
1.5 20 514 515 513 516
0508B FCG02-180 (9kg)
2 22 515 515 513 516
1.5 20 515 514 513 516
0511 FCG02-200 (10kg) 2 22 515 514 513 516
3 30 515 514 513 516
2 22 515 514 513 516
3 30 515 514 513 516
FCG02-225 (12kg)
4 30 515 514 513 516
5 42 515 514 513 516/524
0612
2 22 515 514 514 516
3 30 515 514 514 516
BCG12-225 (15kg)
4 30 515 514 514 516
5 42 515 514 514 516/524
3 30 515 515 514 516
4 30 515 515 515 516
FCG02-280 (20kg) 5 42 516 515 515 516/524
5.5 42 516 515 515 516/524
7.5 65 516 515 515 517
0713
3 30 516 515 514 516
4 30 516 515 515 516
BCG12-280 (23kg) 5 42 516 515 515 516/524
5.5 42 516 515 515 516/524
7.5 65 516 515 515 517
4 30 516 515 515 516/524
5 42 516 515 515 516/524
FCG02-315 (23kg)
5.5 42 516 515 515 516/524
7.5 65 516 515 515 517
0813
4 30 516 515 515 516
5 42 516 515 515 516/524
BCG12-315 (27kg)
5.5 42 516 515 515 516/524
7.5 65 516 515 515 517
4 30 516 516 516 516/524
5 42 516 516 516 516/524
FCG02-355 (30kg) 5.5 42 516 516 516 516/524
7.5 65 516 516 516 517
10 76 516 516 516 517/524
0914
4 30 516 516 516 516/524
5 42 516 516 516 516/524
BCG12-355 (36kg) 5.5 42 516 516 516 516/524
7.5 65 516 516 516 517/524
10 76 516 516 516 517/524
4 30 516 516 515 516/524
5 42 516 516 515 516/524
FCG02-355 (30kg)
5.5 42 516 516 515 516/524
7.5 65 516 516 515 517/524
0916
4 30 516 516 515 516
5 42 516 516 515 516/524
5.5 42 516 516 515 516/524
BCG12-355 (36kg) 7.5 65 516 516 515 517/524
10 76 516 516 515 517/524
15 118 516/524 516 515 518/524
UBF/DBF UBR/DBR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
17
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (UBF/DBF) (For UBR/DBR, A<->B; C<->D)
MOTOR FAN SIDE A/B FREE SIDE C MOTOR SIDE D
UNIT (39G) FAN SIZE HP WGT(kg) A B C D
5 42 516 516 516 516/524
FCG02-400 (45kg) 5.5 42 516/524 516 516 516/524
7.5 65 516/524 516 516 517/524
10 76 516/524 516 516 517/524
5 42 516 516 516 517
FCG05-450 (65kg) 5.5 42 516 516 516 517
7.5 65 516/524 516 516 517/524
10 76 516/524 516 516 518
1018
5.5 42 516 516 516 517
BCG15-400 (61kg) 7.5 65 516/524 516 516 517/524
10 76 516/524 516 516 517/524
15 118 516/524 516 516 519
5.5 42 516 516/524 516 517
BCG15-450 (73kg) 7.5 65 516/524 516/524 516 517/524
10 76 516/524 516/524 516 518
15 118 516/524 516/524 516 519
UBF/DBF UBR/DBR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
18
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
UBF/DBF UBR/DBR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
19
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (UBF/DBF) (For UBR/DBR, A<->B; C<->D; E<->F)
MOTOR FAN SIDE A/B FREE SIDE C MOTOR SIDE C MIDDLE SIDE E/F
UNIT (39G) FAN SIZE HP WGT(kg) A B C D E F
20 139 517 517/524 516 517/524 517/524 519
25 189 517 517/524 516 518 517/524 519/524
2127 FCG05-710 (183kg) 30 203 517 517/524 516 518/524 517/524 519/524
40 290 517 517/524 516/524 519/524 518 521
50 320 517 517/524 516/524 520 518 521
20 139 517/524 518 516 517/524 517/524 519
25 189 517/524 518 516 518 517/524 519/524
2127 BCG15-710 (201kg) 30 203 517/524 518 516 518/524 517/524 519/524
40 290 517/524 518 516/524 519/524 518 521
50 320 517/524 518 516/524 520 518 521
2127 20 139 518 518/524 516 517/524 517/524 519
2230 25 189 518 518/524 516 518/524 517/524 519/524
2234 FCG05-800/GI (233kg) 30 203 518 518/524 516 518/524 517/524 520
40 290 518 518/524 516/524 520 518 521
50 320 518 518/524 516/524 520 518 521/524
60 355 518 518/524 516/524 520/524 518/524 522
2127 20 139 518 518/524 516 517/524 517/524 519
2230 25 189 518 518/524 516 518/524 518 520
2234 BCG15-800/GI (250kg) 30 203 518 518/524 516 518/524 518 520
40 290 518 519 516/524 519/524 518 521
50 320 518 519 517 520/524 518/524 521/524
60 355 518 519 517 520/524 518/524 522
2230 25 189 518/524 519/524 516 518/524 518/524 520/524
2234 30 203 518/524 519/524 516 518/524 518/524 520/524
2434 FCG05-900/GI (316kg) 40 290 518/524 519/524 516/524 520 518/524 521/524
2636 50 320 518/524 519/524 516/524 520 519 522
60 355 518/524 519/524 516/524 520/524 519 522/524
75 520 518/524 519/524 517 523 519 525/524
2230 25 189 519 520 516 518/524 518/524 520/524
2234 30 203 519 520 516 518/524 518/524 521
2434 BCG15-900/GI (358kg) 40 290 519 520 516/524 520 519 522
2636 50 320 519 520 516/524 520 519 522/524
60 355 519 520 516/524 520/524 519 523
75 520 519 520 517 523 519/524 525/524
2434 25 189 518/524 520 516 519 519 520/524
2636 30 203 518/524 520 516 519 519 521
FCG05-1000/GI (376kg) 40 290 518/524 520 516 520/524 519 522
50 320 518/524 520 516 521 519 522/524
60 355 518/524 520 516 521/524 519/524 523
75 520 518/524 520 516/524 525 519/524 525/524
2434 25 189 519 520/524 516 519 519/524 520/524
2636 30 203 519 520/524 516 519 519/524 521
BCG15-1000/GI (416kg) 40 290 519 520/524 516 520/524 519/524 522
50 320 519 520/524 516 521 519/524 522/524
60 355 519 520/524 516 521/524 519/524 523
75 520 519 520/524 516/524 525 520 525/524
UBF/DBF UBR/DBR
(6-SPRING POINTS) (6-SPRING POINTS)
A F D A F D
MOTOR
FAN FAN
MOTOR
B E C B E C
20
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (THF/BHF) (For THR/BHR, A<->B; C<->D)
MOTOR FAN SIDE A/B MOTOR SIDE C FREE SIDE D
UNIT (39G) FAN SIZE HP WGT(kg) A B C D
1 15 513 514 515 513
FCG02-160 (7kg)
1.5 20 513 514 516 513
0508A
1.5 20 513 515 516 513
FCG02-180 (9kg)
2 22 513 515 516 513
1.5 20 514 515 516 513
0508B FCG02-180 (9kg)
2 22 514 515 516 513
1.5 20 515 513 515 515
0511 FCG02-200 (10kg) 2 22 515 513 515 515
3 30 515 513 516 515
2 22 514 515 516 515
FCG02-225 (12kg) 3 30 514 516 516 515
4 30 514 516 516 515
0612 5 42 515 516 516/524 515
2 22 515 515 516 515
BCG12-225 (15kg) 3 30 515 515 516 515
4 30 515 515 516 515
5 42 515 515 516/524 515
3 30 515 515 516 514
4 30 515 516 516 515
FCG02-280 (20kg) 5 42 515 516 516/524 515
5.5 42 515 516 516/524 515
7.5 65 515 516 517 515
0713
3 30 515 516 516 514
4 30 515 516 516 515
BCG12-280 (23kg) 5 42 515 516 516 515
5.5 42 515 516 516 515
7.5 65 515 516 517 515
4 30 515 516 516/524 515
FCG02-315 (23kg) 5 42 515 516 516/524 515
5.5 42 515 516 516/524 515
7.5 65 515 516/524 517 515
0813
4 30 515 516 516 515
BCG12-315 (27kg) 5 42 515 516 516/524 515
5.5 42 515 516 516/524 515
7.5 65 515 516 517 515
4 30 515 516 516/524 515
5 42 515 516 516/524 515
FCG02-355 (30kg) 5.5 42 515 516 516/524 515
7.5 65 515 516 517/524 515
10 76 515 516 517/524 515
0914
4 30 515 516 516/524 515
5 42 515 516 516/524 515
BCG12-355 (36kg) 5.5 42 515 516 516/524 515
7.5 65 516 516 517/524 515
10 76 516 516 517/524 515
4 30 515 516 516/524 515
FCG02-355 (30kg) 5 42 515 516 516/524 515
5.5 42 515 516 516/524 515
7.5 65 515 516 517 515
0916 4 30 516 516 516 515
5 42 516 516 516/524 515
5.5 42 516 516 516/524 515
BCG12-355 (36kg)
7.5 65 516 516 517 515
10 76 516 516/524 517/524 515
15 118 516 516/524 518/524 515
THF/BHF THR/BHR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
21
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (THF/BHF) (For THR/BHR, A<->B; C<->D)
MOTOR FAN SIDE A/B MOTOR SIDE C FREE SIDE D
UNIT (39G) FAN SIZE HP WGT(kg) A B C D
5 42 516 516 516/524 516
FCG02-400 (45kg) 5.5 42 516 516 516/524 516
7.5 65 516 516 517/524 516
10 76 516 516 517/524 516
5 42 516 516 517 516
FCG05-450 (65kg) 5.5 42 516 516 517 516
7.5 65 516 516 518 516
1018 10 76 516 516 518 516
5.5 42 516 516 517 516
BCG15-400 (61kg) 7.5 65 516 516/524 517/524 516
10 76 516 516/524 517/524 516
15 118 516 516/524 519 516
5.5 42 516 516 517 516
BCG15-450 (73kg) 7.5 65 516 516/524 517/524 516
10 76 516 516/524 518 516
15 118 516 516/524 519 516
THF/BHF THR/BHR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
22
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (THF/BHF) (For THR/BHR, A<->B; C<->D)
MOTOR FAN SIDE A/B MOTOR SIDE C FREE SIDE D
UNIT (39G) FAN SIZE HP WGT (kg) A B C D
15 118 517/524 517 518 517
1725 BCG15-630 (149kg) 20 139 518 517/524 518/524 517
25 189 518 517/524 519/524 517/524
30 203 518 517/524 520 517/524
1722 20 139 518 517/524 518/524 517
1724 FCG02-710 (175kg) 25 189 518 517/524 519/524 517/524
1725 30 203 518 517/524 520 517/524
1926 40 290 518/524 518 521/524 518/524
1722 20 139 518/524 518/524 518/524 517/524
1724 25 189 518/524 518/524 519/524 517/524
1725 BCG15-710 (201kg) 30 203 518/524 518/524 520 518
1926 40 290 519 518/524 521/524 518/524
50 320 519 518/524 523 518/524
15 118 518 517 518/524 517
1725 FCG05-630 (137kg) 20 139 518 517 518/524 517
25 189 518 517/524 519/524 517/524
30 203 518 517/524 520 517/524
20 139 519 518 519 517
25 189 519 518/524 520 517/524
30 203 519 518/524 520/524 517/524
1926 FCG05-800/GI (233kg)
40 290 519/524 518/524 522 518
50 320 519/524 519 522/524 518/524
60 355 519/524 519 523/524 518/524
20 139 519/524 518 519 517/524
25 189 519/524 518/524 520 517/524
30 203 519/524 518/524 520/524 517/524
1926 BCG15-800/GI (250kg)
40 290 519/524 519 522 518
50 320 519/524 519 522/524 518/524
60 355 519/524 519 523/524 518/524
THF/BHF THR/BHR
(4-SPRING POINTS) (4-SPRING POINTS)
A D A D
MOTOR
FAN FAN
MOTOR
B C B C
23
INTERNAL SPRING ISOLATOR ARRANGEMENT (Con’t)
SPRING SELECTION (THF/BHF) (For THR/BHR, A<->B; C<->D; E<->F)
MOTOR FAN SIDE A/B FREE SIDE C MOTOR SIDE C MIDDLE SIDE E/F
UNIT (39G) FAN SIZE HP WGT(kg) A B C D E F
20 139 517/524 517 518 516 519 518
25 189 517/524 517 518/524 516 519 518
2127 FCG05-710 (183kg) 30 203 517/524 517 518/524 516 519/524 518
40 290 517/524 517 520 516/524 520/524 518
50 320 517/524 517 520 516/524 521 518/524
20 139 518 517 517/524 516 518/524 517/524
25 189 518 517 518 516/524 519 518
2127 BCG15-710 (201kg) 30 203 518 517 518 516/524 519 518
40 290 518 517 519/524 516/524 520 518/524
50 320 518 517 519/524 517 520/524 518/524
2127 20 139 518/524 517/524 517/524 516 518/524 518
2230 25 189 518/524 517/524 518 516/524 519 518
2234 30 203 519 518 518/524 516/524 519/524 518
FCG05-800/GI (233kg)
40 290 519 518 519/524 516/524 520/524 518/524
50 320 519 518 519/524 517 521 518/524
60 355 519 518 520 517 521 519
2127 20 139 519 517/524 517/524 516 518/524 518
2230 25 189 519 517/524 518 516 519/524 518/524
2234 30 203 519 517/524 518/524 516/524 519/524 518/524
BCG15-800/GI (250kg)
40 290 519 517/524 519/524 516/524 520/524 518/524
50 320 519 517/524 519/524 517 521 519
60 355 519 517/524 520 517 521/524 519
2230 25 189 519/524 518 518/524 516 519/524 519
2234 30 203 519/524 518 518/524 516/524 520 519
2434 40 290 519/524 518 519/524 516/524 521 519
FCG05-900/GI (316kg)
2636 50 320 519/524 518 520 517 521/524 519/524
60 355 519/524 518 520/524 517 522 519/524
75 520 519/524 518 523 517/524 525 520
2230 25 189 521 519 518/524 516 520 519
2234 30 203 521 519 519 516/524 520 520
2434 40 290 521 519 519/524 516/524 521 520
BCG15-900/GI (358kg)
2636 50 320 521 519 520 516/524 521/524 520
60 355 521 519 520/524 517 522 520
75 520 521 519 523 517/524 525 520/524
2434 25 189 520 518/524 519 516 520/524 519
2636 30 203 520 518/524 519 516 520/524 519
40 290 520 518/524 520/524 516 522 519/524
FCG05-1000/GI (376kg)
50 320 520 518/524 521 516 522/524 519/524
60 355 520 518/524 521/524 516 523 519/524
75 520 520 518/524 525 516/524 525/524 520
2434 25 189 520/524 519 519 516 520/524 519/524
2636 30 203 520/524 519 519 516 521 519/524
40 290 520/524 519 520/524 516 522 519/524
BCG15-1000/GI (416kg)
50 320 520/524 519 521 516 522/524 519/524
60 355 520/524 519 521/524 516/524 523 520
75 520 520/524 519 525 516/524 525/524 520
THF/BHF THR/BHR
(6-SPRING POINTS) (6-SPRING POINTS)
A F D A F D
MOTOR
FAN FAN
MOTOR
B E C B E C
24
DIMENSION
25
1) External AHU Length = (Section Length + K) mm
K = 110mm for 25mm casing thickness
160mm for 50mm casing thickness
4) If the External AHU Length is > 1900mm, section will be split into several casing for shipping purposes.
G F E D C B A
A
C
C
HH
E
S
S
HV
26
MEMO
27
Carrier
International
Sdn. Bhd.
® Malaysia
39G Rev. 4
05 2003
3.3
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
FAN COIL UNIT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.4
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
AIR-COOL SPLIT UNIT
Before using your air conditioner, please read
this manual carefully and keep it for future reference.
SPLIT-TYPE
ROOM AIR CONDITIONER
The design and specifications are subject to change without prior notice for
Read This Manual
product improvement. Consult with the sales agency or manufacturer for details.
Keep this manual where the operator can easily
find them.Inside you will find many helpful hints
on how to use and maintain your air conditioner
properly. Just a little preventative care on your
part can save you a great deal of time and money
CS152U-11D1(L) over the life of your air conditioner. You'll find many
answers to common problems in the chart of
202000192449 troubleshooting tips. If you review the chart of
20130906 Troubleshooting Tips first, you may not need
to call for service.
CONTENTS When using this air conditioner in the European countries, please read the
following information:
SAFETY PRECAUTIONS
Warning .....................................................................................................................................3 This appliance is can be used by children aged from 8 years and above and persons with
Caution ......................................................................................................................................4 reduced physical, sensory or mental capabilities, or lack of experience and knowledge if they
. have been given supervision or instruction concerning use of the appliance in a safe way and
understand the hazards involved. Children shall not play with the appliance. Cleaning and user
NAMES OF PARTS
maintenance shall not be made by children without supervision.
Indoor unit ........... .....................................................................................................................5
outdoor unit ...............................................................................................................................5 DISPOSAL: Do not dispose of this product as unsorted municipal waste. Collection of such waste
Indication lamp...........................................................................................................................5 separately for special treatment is necessary.
It is prohibited to dispose of this appliance in domestic household waste. For disposal, there are
OPERATING INSTRUCTIONS several possibilities:
Special functions .......................................................................................................................6 A) The municipality has established collection systems, where electronic waste can
Operating temperature................................................................................................................7 be disposed of at least free of charge to the user.
Manual operation ......................................................................................................................7 B) When buying a new product, the retailer will take back the old product at least
Airflow direction control ............................................................................................................8
How the air conditioner works ..................................................................................................9 free of charge.
C) The manufacturer will take back the old appliance for disposal at least free of
charge to the user.
CARE AND MAINTENANCE D) As old products contain valuable resources, they can be sold to scrap metal
Before maintenance...... ...........................................................................................................10 dealers.
Cleaning the unit.......................................................................................................................10
Cleaning the air filter and air freshening filter ..........................................................................10 Wild disposal of waste in forests and landscapes endangers your health when hazardous
Replacement of the air filter and air freshening filter ...............................................................11 substances leak into the ground-water and find their way into the food chain.
Preparation for extended non-operation....................................................................................11
Pre-season inspection...............................................................................................................11
TROUBLESHOOTING TIPS
Normal function of the air conditioner.......................................................................................12
Troubleshooting guide .............................................................................................................14
1 2
SAFETY PRECAUTIONS SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following instructions
CAUTION
must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage.
The seriousness is classified by the following indications.
3 4
NAMES OF PARTS OPERATING INSTRUCTIONS
2 1 3 7 Special functions
Names of parts
Refrigerant Leakage Detection , ,
Indoor unit With this new technology, the dipsplay area will appear EC and the indication lamps
continue flashing when the outdoor unit detects refrigerant leakage.
1. Front panel
4 2. Air inlet
5 6 Louver Angle Memory Function(optional):
3. Air filter
8 Within the scope of safety angle, it will memorize the open angle of horizontal louver.
4. Air outlet
If it exceeds, it will memorize the boundry of safety angle. In the following circumstances,
5. Horizontal air flow grille
it will return to standard angle: 1) pressing the turbo or manual control button, 2)unplug
6. Vertical air flow louver(inside)
and then plug in the machine. So we strongly suggest that the open angle of the horizontal
7. Display panel louver should not be set too small, in case the condensed water forms and drops from the
Air inlet(side) Air inlet(rear) horizontal louver.
Outdoor unit
8. Connecting pipe SELF CLEAN function Optional
9. Connecting cable Function used after the shut down of cooling operation to clean the Evaporator
9 10. Stop valve ,it keeps the air fresh for the next operation.
Air outlet For cooling models, the unit will operate under FAN ONLY mode
10 NOTE:
at LOW fan speed for half an hour, and then turn off automatically.
All the pictures in this manual are for For cooling & heating models, the unit will operate as in the below sequence :
explanation purposes only. The actual shape FAN ONLY mode at Low fan speed--Heating operation with LOW fan speed
of the indoor unit you purchased may be slight ---FAN ONLY operation--Stop Operation---Turn off.
Signal receiver different on front panel and display window.The Note:
actual shape shall prevail. This function is only available under COOL(AUTO COOL, FORCED COOL) and
DRY mode.
Before selecting the function, it is recommended to run the air conditioner under
Indication lamp cooling operation for about half an hour. Once the Self Clean function is activated,
all TIMER setting will be cancelled.
A OPERATION indication lamp During SELF CLEAN operation, when pressing the SELF CLEAN button on the remote
This lamp illuminates when the air controller again,the unit will stop the operation and turn off the unit automatically.
Signal receiver conditioner is in operation.
TIMER indication lamp CLEAN AIR function(on some models)
Lights up during Timer operation. Improving the quality of indoor air is one of the purposes of an air conditioner. Thisair
DEFROST indication lamp conditioner is equipped with ionizer or Plasma Dust Collector(Depending on specific
B configuration of the model). With the anions generated by Ionizer, the air circulation
(Enabled on cooling & heating models only):
Lights up when the air conditioner starts of the air conditioner fills the room with refreshing, natural and healthy air. The Plasma
defrosting automatically or when the warm Dust Collector generates a high voltage ionization zone, through which the air is
air control feature is activated in heating converted to plasma. Inside the air most of the dust, smoke, and pollen particles are
operation. captured by the electrostatic filter.
Temperature indicator
Displays the temperature settings when the Anti-mildew function Optional
air conditioner is operational.
Displays the malfunction code. When turns off the unit on COOL, DRY, AUTO (Cool) mode, the air conditioner will continue
operating for about 10 minutes (depending on models) with soft wind.This will help to
dry up the condensed water inside the evaporator, and prevent the breeding of mildew.
Under Anti-mildew operation, do not restart the air conditioner until the unit iscompletely off.
5 6
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS
NOTE: This manual does not include Remote Controller Operations, see the Airflow direction control
<<Remote Controller Instruction>> packed with the unit for details.
Adjust the air flow direction properly, otherwise it
Operating temperature might cause discomfort or cause uneven room
temperatures.
Mode Adjust the horizontal louver using the remote controller.
Cooling operation Heating operation Drying operation
Temperature Adjust the vertical louver manually.
Room temperature
17 32 0 30 10 32 50 90 To set the vertical air flow(Up--Down) direction
62 90 32 86 Perform this function while the unit is in operation.
Range
Use the remote controller to adjust the air flow
Outdoor temperature 18 43 11 43 52 109 direction. The horizontal louver can be moved at
64 109 a range of 6O for each press, or swing up and down
-7 43 20 109
,,
automatically. Please refer to the REMOTE
( For the models with low
-7
20
24
76
,,
temperature cooling system 18 52 64 126
CONTROLLER OPERATION MANUAL for details.
(For special tropical models)
18 52 64 126 To set the horizontal air flow direction (left - right)
(For special tropical models)
Move the deflector rod manually to adjust the air flow
NOTE: in the direction you prefer.
1. Optimum performance will be achieved within these operating temperatures.If air IMPORTANT:Do not put your fingers into the panel of
conditioner is used outside of the above conditions, certain safety protection features blower and suction side.The high-speed fan inside may
might come into operation and cause the unit to function abnormally. cause danger.
Deflector rod
2. If the air conditioner runs for a long time in cooling mode and the humidity is high(over (two places) NOTE:
80%) , condensed water may drip out of the unit. Please sets the vertical air flow louver to Best working conditions(the energy efficiency can be
its maximum angle (vertically to the floor), and set HIGH fan mode. affected if not set under these conditions):
The best angle of louvers is the default angle of cooling
Manual operation mode
The best way of setting the angle of louvers at heating
Units are equipped with a switch to run emergency operation mode. It can be accessed by mode is: run the unit for 5 minutes and then use the
opening the front panel. This switch is used for manual operation in case the remote controller remote controller to set the louvers at the default angle
fails to work or maintenance necessary. of cooling mode.
1 Hold the panel sides and lift the front panel CAUTION
up to an angle until it remains fixed with a Range Do not operate the air conditioner for long periods with
clicking sound. For some models, please the air flow direction set downward in cooling or
use suspension bars to prop up the panel. dehumidifying mode. Otherwise, condensation may
AUTO/COOL
2 Once you push the manual button, the occur on the surface of the horizontal louver causing
Manual switch moisture to drop on to the floor or on furnishings.
operation mode is shifted in an order as:
AUTO, COOL, OFF. The temperature will When the air conditioner is started immediately after it
1 was stopped, the horizontal louver might not move for
Suspension bars
be set at 24OC/76OF and the fan on Auto.
3 After operation, close the panel firmly to its approximately 10 seconds.
Open angle of the horizontal louver should not be set
original position.
too small, as COOLING or HEATING performance may
be impaired due to too restricted air flow area.
CAUTION:
This switch is used for testing purposes Do not move the horizontal louver manually, otherwise
only. You had better not choose it. the horizontal louver will be out of sync. Please cease
AUTO/COOL To restore the remote controller operation, operating, unplug power for a few seconds,then restart
Manual switch use the remote controller directly. the air conditioner.
2
7 8
OPERATING INSTRUCTIONS CARE AND MAINTENANCE
9 10
CARE AND MAINTENANCE TROUBLESHOOTING TIPS
5. Install the air freshening filter back into position. Normal function of the air conditioner
6. Insert the upper portion of air filter back into the
unit, taking care that the left and right edges line The following events may occur during normal operation.
up correctly and place filter into position. 1. Protection of the air conditioner.
Compressor protection
Replacement of air filter and air freshening filter The compressor can't restart for 3-4 minutes after it stops.
1. Remove the air filter. Anti-cold air (Cooling and heating models only)
2. Remove the air freshening filter. The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in
3. Install a new air freshening filter.
one of the following three situations and the set temperature has not been reached.
4. Reinstall the air filter and securely close the front
A) When heating has just started.
panel.
B) Defrosting.
C) Low temperature heating.
Preparation for extended non-operation The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).
Defrosting (Cooling and heating models only)
If you plan to idle the unit for a long time, perform
Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low
the following:
(1) Clean the indoor unit and filters. and humidity is high resulting in lower heating efficiency of the air conditioner.
(2) Operate the fan for about half a day to dry the During this condition air conditioner will stop heating operation and start defrosting automatically.
inside of the unit. The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and
(3) Stop the air conditioner and disconnect power. the amount of frost built up on the outdoor unit.
(4) Remove the batteries from the remote controller.
The outdoor unit requires periodic maintenance 2. A white mist coming out from the indoor unit
and cleaning. Do not attempt to do this yourself. A white mist may generate due to a large temperature difference between air inlet and air outlet
Contact your dealer or service provider. on COOL mode in an indoor environment that has a high relative humidity.
A white mist may generate due to moisture generated from defrosting process when the air
Pre-season inspection conditioner restarts in HEAT mode operation after defrosting.
Check that the wiring is not broken off or 3. Low noise of the air conditioner
disconnected. You may hear a low hissing sound when the compressor is running or has just stopped running.
Clean the indoor unit and filters.
It is the sound of the refrigerant flowing or coming to a stop.
Check that the air filter is installed.
You can also hear a low "squeak" sound when the compressor is running or has just stopped
Check if the air outlet or inlet is blocked after the
air conditioner has not been used for a long time. running. This is caused by heat expansion and cold contraction of the plastic parts in the unit
when the temperature is changing.
A noise may be heard due to louver restoring to its original position when power is turned on.
Caution
Do not touch the metal parts of the unit when 4. Dust is blown out from the indoor unit.
removing the filter. Injuries can occur when This is a normal condition when the air conditioner has not been used for a long time or during first
handling sharp metal edges. use of the unit.
Do not use water to clean inside the air conditioner.
Exposure to water can destroy the insulation, 5. A peculiar smell comes out from the indoor unit.
leading to possible electric shock. This is caused by the indoor unit giving off smells permeated from building material, from furniture,
When cleaning the unit, first make sure that the or smoke.
power and circuit breaker are turned off.
Do not wash air filter with hot water at more than 6. The air conditioner turns to FAN only mode from COOL or HEAT (For cooling and
40OC/104OF. Shake off moisture completely and dry heating models only) mode.
it in the shade. Do not expose it directly to the sun, When indoor temperature reaches the temperature setting on air conditioner, the compressor will
it may shrink. stop automatically, and the air conditioner turns to FAN only mode. The compressor will start again
when the indoor temperature rises on COOL mode or falls on HEAT mode (For cooling and heating
models only) to the set point.
11 12
TROUBLESHOOTING TIPS TROUBLESHOOTING TIPS
7.The air conditioner runs Anti-mildew function after turning off the unit. Troubleshooting guide
When turning off the unit under COOL(AUTO COOL, FORCED COOL) and DRY mode, the air
conditioner will run Anti-mildew function for 7-10 minutes, then stop the operation and turn The unit may stop operation or continue
OPERATION(RUN) indicator or other to run in a safety condition(depending
off the unit automatically. indicators continue flashing. on models). Waiting for about 10
minutes, the fault may be recovered
8. Dripping water may generate on the surface of the indoor unit when cooling in a high automatically, if not, disconnect the
relatively humidity (relative humidity higher than 80%). Adjust the horizontal louver to If one of the following code appears on the power and then connect it in again. If
the maximum air outlet position and select HIGH fan speed. Trouble display area : E0,E1,E2,E3.....or P0,P1,P2, the problem still exists, disconnect
P3..... the power and contact the nearest
9. Heating mode (For cooling and heating models only) customer service center.
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit Fuse blows frequently or circuit breaker trips
during heating operation. When the outdoor temperature falls, heat drawn in by the air
frequently . Stop the air conditioner immediately,
conditioner decreases accordingly. At the same time, heat loading of the air conditioner
disconnect the power and contact the
increases due to larger difference between indoor and outdoor temperature. If a Other objects or water fall into the air conditioner.
nearest customer service center.
comfortable temperature can't be achieved by the air conditioner, we suggest you use a
The remote controller won't work or works
supplementary heating device.
abnormally.
10. Auto-restart function
Malfunctions Cause What should be done?
Power failure during operation will stop the unit completely.
For the unit without Auto-restart feature, when the power restores, the OPERATION indicator Unit does not Power cut Wait for power to be restored.
on the indoor unit starts flashing. To restart the operation, push the ON/OFF button on the start
remote controller. For the unit with Auto-restart feature, when the power restores, the unit Unit may have become Unplugged. Check that plug is securely in wall
restarts automatically with all the previous settings preserved by the memory function. receptacle.
Fuse may have blown. Replace the fuse.
Battery in Remote controller may Replace the battery.
have been exhausted.
The time you have set with timer Wait or cancel timer setting.
is incorrect.
Unit not cooling Inappropriate temperature Set temperature correctly. For
or heating setting. detailed method please refer to
(Cooling/ heating "Using remote control" section.
models only)
Air filter is blocked. Clean the air filter.
room very well
while air flowing Doors or Windows are open. Close the doors or windows.
out from the air Air inlet or outlet of indoor or Clear obstructions away first, then
conditioner outdoor unit has been blocked. restart the unit.
If the trouble has not been corrected, please contact a local dealer or the nearest customer
service center. Be sure to inform them of the detailed malfunctions and unit model number.
13 14
OWNER'S MANUAL
4 2
AU
TO
6
CO
OL
DR TEM
Y
SE P
HE T
AT CLOC
FAN K
SET
HOU
FAN R
SPEE
MO D
DE
M
FAN
SPE
ED
SW
ING
SW AIR
DIRE
ING CTIO
N
RESE CLO
T LOCK OK CK
C/H
TIM
ECO E ON
TIM
E OFF
5
8 8
7
9
OUTDOOR UNIT
OR
9
7
8 7
8
8
8 8
Fig.1
INDOOR UNIT OUTDOOR UNIT
1 Air flow louver (at air outlet) 7 Connecting pipe
2 Air inlet (with air filter in it) 8 Air inlet
3 Installation part 9 Air outlet
4 Display panel
5 Remote controller
6 Drain pipe
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air
conditioner you purchased(depend on model). The actual shape shall prevail.
CONTENTS PAGE It is not good for your health to expose your body to the
air flow for a long time.
owner’s manual
1
Do not operate the air conditioner with a wet hand.
An electric shock may happen.
2. TEMPORARY OPERATIONS
The air conditioner consists of the indoor unit, the outdoor unit,
Do not touch the heat exchanger fins. the connecting pipe and the remote controller. (See Fig.1)
These fins are sharp and could result in cutting injuries.
Function indicators on indoor unit display panel
Do not place items which might be damaged by moisture
under the indoor unit. PRE-DEF indicator(cooling and heating type)
Condensation may form if the humidity is above 80%, the or fan only indicator(cooling only type)
drain outlet is blocked or the filter is polluted.
Infrared signal receiver
After a long use, check the unit stand and fitting for
damage.
If damaged, the unit may fall and result in injury.
MANUAL
Never touch the internal parts of the controller. Display panel Fig. 2-1
Do not remove the front panel. Some parts inside are
dangerous to touch, and a machine trouble may happen.
owner’s manual
2
3. AIR CONDITIONER OPERATIONS AND 4. HINTS FOR ECONOMICAL OPERATION
PERFORMANCE The following should be noticed to ensure an economical operation.
Use the system in the following temperature for safe and (Refer to corresponding chapterfor details)
effective operation. The Max operation temperature for
the air conditioner.(Cooling/Heating) Adjust the air flow direction properly to avoid winding toward
your body.
Table 3-1
Adjust the room temperature properly to get a comfortable
Temperature situation and to avoid supercooling and superheat.
Outdoor Room
Mode temperature temperature
In cooling, close the curtains to avoid direct sunlight.
Cooling operation 18°C~43°C 17°C~32°C
To keep cool or warm air in the room, never open doors or
windows more often than necessary.
Heating operating
(Cooling only -7°C~24°C 17°C~27°C Set the timer for the desired operating time.
type without)
Never put obstructions near the air outlet or the air inlet. Or it
Dry operation 18°C~43°C 17°C~32°C will cause lower efficiency, even a sudden stop.
If you don't plan to use the unit for a long time, please discon-
nect power and remove the batteries from the remote control-
ler. When the power switch is connected, some energy will be
NOTE consumed, even if the air conditioner isn't in operation. So
please disconnect the power to save energy. And please
1 If air conditioner is used outside the above conditions, it may switch the power on 12 hours before you restart the unit to
cause the unit to function abnormally. ensure a smooth operation.
2 The phenomenon is normal that the surface of air A clogged air filter will reduce cooling or heating efficiency,
conditioning may condense water when the relative larger please clean it once two weeks.
humidity in room, please close the door and window.
Power failure
Power failure during operation will stop the unit completely. Fig. 5-1
The OPERATION lamp on the indoor unit will start When cooling
flashing when power is restored. Adjust the louver horizontally.
Disconnect the unit with the power and then connect the unit
Fig. 5-2
with the power again. Push the ON/OFF button on the remote
controller to restart operation. When heating
Adjust the louver downwards. (vertically)
Fig. 5-3
owner’s manual
3
6. MAINTENANCE 1 3.2-10.5KW
Open the air intake.(Refer to Fig.6-1)
Take out the air filter.(Refer to Fig.6-2)
CAUTION Clean the air cleaning filter with water or vacuum cleaer,then
dry it in cool place.
Before you clean the air conditioner, be sure the power Re-install the air filter in the reverse order of Fig.6-2.
supply is off.
Let the indoor units run in fan only operation for about half
a day in order to dry the interior of the units.
owner’s manual
4
Symptom 3: White mist comes out of a unit
Symptom 3.1: Indoor unit
7. FOLLOWING SYMPTOMS ARE NOT AIR When the tone of operating noise changes.
CONDITIONER TROUBLES This noise is caused by the change of frequency.
Symptom 1: The system does not operate Symptom 5: Dust comes out of the unit
The air conditioner does not start immediately after the ON/OFF When the unit is used for the first time in a long time.
button on the romote controller is pressed. This is because dust has gotten into the unit.
If the operation lamp lights, the system is in normal condition.To
prevent overloading of the compressor motor, the air
conditioner starts 3 minutes after it is turned ON.
Symptom 6: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes,
If the operation lamp and the "PRE-DEF indicator(cooling and
etc., and then emit it again.
heating type) or fan only indicator(cooling only type)" light, it
means you choose the heating model, When just starting, if the
compressor has not started, the indoor unit appears "anti cold Symptom 7: The outdoor unit fan does not
wind" protection because of its overlow outlet temperature. spin.
Symptom 2: Change into the fan mode during During operation. The speed of the fan is controlled in order to
cooling mode optimize product operation.
owner’s manual
5
8. TROUBLESHOOTING
8.1 Troubles and causes of air conditioner
If one of the following malfunctions occur, stop operation, shut
off the power, and contact with your dealer.
Other malfunctions.
owner’s manual
6
Table 8-1
NO. Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp
LED
3 Water-level alarm malfunction
flash
LED
5 Outdoor unti malfunction
Slow flash
Table 8-2
Air flowing normally but Temperature is not set correctly. Set the temperature properly.
completely can't cooling Be in 3 minutes protection of Wait.
compressor.
Refrigerant is too little or too much. Check leakage, and rightly recharge
Air or no concretingc gas in the refrigerant.
refrigerating circuit. Vacuum and recharge refrigerant.
Units start or stop frequently Compressor is malfunction. Maintenance or change compressor.
Voltage is too high or too low. Install manostat.
System circuit is blocked. Find reasons and solution.
Outdoor unit and indoor unit heat Clean the heat exchanger.
exchanger is dirty. Clean the air filter.
The air filter is dirty. Eliminate all dirties and make air
Inlet/outlet of indoor/outdoor units is smooth.
blocked. Close doors and windows.
Doors and windows are open Make curtains in order to shelter from
Low cooling effect Sunlight directly shine. sunshine.
Too much heat resource. Reduce heat source.
Outdoor temp. is too high. AC cooling capacity reduces (normal).
Leakage of refrigerant or lack of Check leakage and rightly recharge
refrigerant. refrigerant.
owner’s manual
7
Table 8-3
The indication on the display Check whether the timer The air conditioner operation will
disappears after a lapse of operation has come to an stop up to the set time.
time. end when the TIMER OFF
is indicated on the display.
Check whether the timer Up to the set time, the air conditioner
The TIMER ON indicator operation is started when will automatically start and the
goes off after a lapse of the TIMER ON is indicated appropriate indicator will go off.
certain time. on the display.
owner’s manual
8
QSDLU-001AEN
The design and s pecifications are subject to change wi thout prior notic e for product
improvement. Cons ult with the s ales agency or manufa cturer for details.
OWNER'S MANUAL
3
INDOOR UNIT
4
6 7 8
5
AU
TO
CO
OL
DR TEM
Y
SE P
HE T
AT CLOC
FAN K
SET
10
HOU
FAN R
SPEE
MO D
DE
M
FAN
SPE
ED
SW
ING
SW AIR
DIRE
ING CTIO
9
N
RESE CLO
T LOCK OK CK
C/H
TIM
ECO E ON
TIM
E OFF
11
11
OUTDOOR UNIT
12
OR 12
10 11 10
11
12
11
11 11
Fig.1
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air
conditioner you purchased(depend on model).The actual shape shall prevail.
CONTENTS PAGE It is not good for your health to expose your body to the
air flow for a long time.
IMPORTANT SAFETY INFORMATION...........................................................1 Do not insert fingers, rods or other objects into the air
PARTS NAMES.........................................................................................2 inlet or outlet.
When the fan is rotating at high speed, it will cause injury.
AIR CONDITIONER OPENRATIONS AND PERFORMANCE...........................2
HINTS FOR ECONOMICAL OPERATION......................................................3 Never use a flammable spray such as hair spray, lacquer
or paint near the unit.
ADJUSTING AIR FLOW DIRECTION...........................................................3
It may cause a fire.
MAINTENANCE........................................................................................3
Never touch the air outlet or the horizontal blades while
FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES...........5
the swing flap is in operation.
TROUBLESHOOTING................................................................................5 Fingers may become caught or the unit may break down.
owner’s manual
1
Do not operate the air conditioner with a wet hand. Temporary button Infrared signal receiver
An electric shock may happen.
owner’s manual
2
5. ADJUSTING AIR FLOW DIRECTION
NOTE
While the unit is in operation, you can adjust the air flow louver
1 If air conditioner is used outside the above conditions, it to change the flow direction and naturalize the room
may cause the unit to function abnormally. temperature evenly. Thus you can enjoy it more comfortably.
Ventilate often. Extended use requires special attention to Use a dry cloth to wipe the indoor unit and remote
ventilation. controller.
Keep doors and windows closed. If the doors and windows A wet cloth may be used to clean the indoor unit if it is
remain open, air will flow out of your room causing a decrease very dirty.
in the cooling or heating effect.
Never use a damp cloth on the remote controller.
Never place objects near the air inlet or the air outlet of the unit.
It may cause deterioration in the effect or stop the operation. Do not use a chemically-treted duster for wiping or leave
such material on the unit for long.
Set the timer . it may damage or fade the surface of the unit.
If you don't plan to use the unit for a long time, please take the Do not use benzine, thinner, polishing powder, or similar
batteries from the remote controller. When the power is on, solvents for cleaning.
some energy will be consumed,even if the air conditioner isn't in These may cause the plastic surface to crack or deform.
operation. So please disconnect the power to save energy.
owner’s manual
3
Maintenance after a long stop period 5 Re-install the air filter.
(eg. at the beginning of the season)
6 Install and close the air-in grill in the reverse order of step 1
and 2 and connect the control box cables to the
Check and remove everything that might be blocking inlet
corresponding terminators of the main body .
and outlet vents of indoor units and outdoor units.
Let the indoor units run in fan only operation for about half a
day in order to dry the interior of the units.
2 Take out the air-in grill (together with the air filter shown in
Fig.6-1).
Pull the air-in grill down at 45 and lift it up to take out the
grill.
CAUTION
Do not dry out the air filter under direct sunshine or with
fire.
owner’s manual
4
A continuous low hissing sound is heard when the system is in
7. FOLLOWING SYMPTOMS ARE NOT AIR operation.
CONDITIONER TROUBLES This is the sound of refrigerant gas flowing through both indoor
and outdoor units.
Symptom 1: The system does not operate
A hissing sound which is heard at the start or immediately after
The air conditioner does not start immediately after the ON/OFF stopping operation or defrost operation.
button on the romote controller is pressed. This is the noise of refrigerant caused by flow stop or flow
If the operation lamp lights, the system is in normal condition.To change.
prevent overloading of the compressor motor, the air
conditioner starts 3 minutes after it is turned ON.
Symptom 3: White mist comes out of a unit During operation. The speed of the fan is controlled in order to
optimize product operation.
Symptom 3.1: Indoor unit
When humidity is high during cooling operation If the interior of
an indoor unit is extremely contaminated, the temperature
distribution inside a room becomes uneven. It is necessary to
clean the interior of the indoor unit. Ask your dealer for details
on cleaning the unit. This operation requires a qualified service
8. TROUBLESHOOTING
person
Symptom 3.2: Indoor unit, outdoor unit
8.1 Troubles and causes of air conditioner
When humidity is high during cooling operation If the interior of If one of the following malfunctions occur, stop operation, shut
an indoor unit is extremely contaminated, the temperature off the power, and contact with your dealer.
distribution inside a room becomes uneven. It is necessary to
clean the interior of the indoor unit. Ask your dealer for details The operation lamp is flashing rapidly (5Hz).
on cleaning the unit. This operation requires a qualified service This lamp is still flashing rapidly after turn off the power and turn
person. on again. (See in Table 8-1 and Table 8-2)
Symptom 4: Noise of air conditioners cooling Obstacles and water enter the unit.
owner’s manual
5
Table 8-1 (Applicable to inverter air conditioner only)
NO. Malfunction running lamp timer lamp defrosting lamp alarm lamp display (nixie tube)
Malfunction running lamp timer lamp defrosting lamp alarm lamp display
NO. (nixie tube)
owner’s manual
6
Table 8-3
Refrigerant is too little or too much. Check leakage, and rightly recharge
refrigerant.
Air or no concreting gas in the Vacuum and recharge refrigerant.
Units start or stop frequently refrigerating circuit.
Compressor is malfunction. Maintenance or change compressor.
Voltage is too high or too low. Install manostat.
System circuit is blocked. Find reasons and solution.
Outdoor unit and indoor unit heat Clean the heat exchanger.
exchanger is dirty.
The air filter is dirty. Clean the air filter.
Inlet/outlet of indoor/outdoor units is Eliminate all dirties and make air
blocked. smooth.
Doors and windows are open Close doors and windows.
Low cooling effect Sunlight directly shine. Make curtains in order to shelter from
sunshine.
Too much heat resource. Reduce heat source.
Outdoor temp. is too high. AC cooling capacity reduces (normal).
Leakage of refrigerant or lack of Check leakage and rightly recharge
refrigerant. refrigerant.
owner’s manual
7
Table 8-4
The indication on the display Check whether the timer The air conditioner operation will
disappears after a lapse of operation has come to an stop up to the set time.
time. end when the TIMER OFF
is indicated on the display.
Check whether the timer Up to the set time, the air conditioner
The TIMER ON indicator operation is started when will automatically start and the
goes off after a lapse of the TIMER ON is indicated appropriate indicator will go off.
certain time. on the display.
owner’s manual
8
QS01U-007AW
The d e sign a nd s pecif ica tio ns ar e subj ect t o cha ng e with o ut pr ior no tice f or p ro duct
improv emen t. C o nsul t w ith the s al es a gen cy or man u factu rer for d et ails.
202000171405
2012.12.25
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.5
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
COOLING TOWER
Operation & Maintenance
Manual
TXS SERIES
COOLING TOWER
CONTENTS PAGE
1.0 INTRODUCTION 1
2.0 CONSTRUCTION 1
2.1 GENERAL
2.2 TOWER BODY
2.3 FAN
2.4 INFILL
2.5 WATER DISTRIBUTION SYSTEM
4.0 OPERATION 54
4.1 PRECAUTION DURING OPERATION
4.1 CARES FOR LONG-TERM SHUT DOWN
7.0 TROUBLESHOOTING 10
12
Operation & Maintenance Manual - TXS Series
1.0 INTRODUCTION
Dear Customer,
You have chosen a Truwater TXS Series Cooling Towers for your plant, thank you for trusting
us. This instruction manual has been prepared to furnish the operator with detailed information to
ensure continued efficient and safe operation of cooling tower at all times. Therefore, the
operator is urged to thoroughly read this manual not only at the time of star-up, but also during
routine maintenance services to acquaint himself fully with the construction and operation of the
equipment.
2.0 CONSTRUCTION
2.1 GENERAL
The major sections of the cooling tower are shown in Figure 1. The functional key points
of the cooling tower are the fan and infill. The cooling tower, which cools recirculating
water based on the principles of heat exchange between water and air, is designed and
built to the highest standard of workmanship and efficiency, backed by the specialized
experience of the industry’s most competent engineering staff.
2.3 MOTOR
The AC induction, three phase squirrel cage motors are totally enclosed fan cooled (TEFC)
enclosure installed outside the hot moist discharged air-stream. The protective class of outside
frame is IP55. The normal ambient temperature limits are -20oC to + 40oC. The maximum
altitude is 1000m above sea level.
2.4 FAN
The specially designed low-noise axial fans are propeller-type, incorporating heavy-duty
blades of aluminum alloy. Blades are freely adjustable. The manufacturer must be
contacted for readjusting the blades to ensure proper fan balancing afterwards.
2.5 INFILL
The performance of the cooling tower depends very much upon the efficiency of the infill
used. The high-density film infill is fabricated from rigid, corrugated PVC sheets that are
conductive to cooling tower. The infill is resistance to rot, fungi, bacteria and acids and
alkalis as commonly found in cooling towers.
1
2
No. Parts
1 V-Belt & Pulley System
2 Fan Assembly
3 Motor
4 Infill
5 Louver
6 PVC Casing
7 Inspection Door
8 Ladder
9 Cold Water Basin
Phase Order A B C
Head U1 V1 W1
Tail U2 V2 W2
iii.) For motor horsepower 4HP and below, the wiring connection is Y Connection and
others is ∆ Connection as shown above.
Note: The above wiring connection is only applicable for single speed motor, FEM brand,
for others type / brands motor, please refer attached Motor Service Manual.
3.4 INSPECTION
It is imperative that all operating assemblies be inspected before they are placed in
operation. The following is a list of components to be checked before starting the tower:
iv.) Now start the fan intermittently and check if the motor is operating in the
proper direction of rotation. Also check if any abnormal noise is developing or
if vibration is occurring. The fan should never be exposed to a vibration level
of more than 7.1mm/sec rms measured at the drive shaft bearings,
Always shut off the electrical power to the tower fan motor prior to entering the
tower or performing any work on the tower. Any electrical switches should be
locked out and tagged out to prevent others from turning the power back on.
3.4.4 Check tightness of bolts that attach mechanical equipment support to the tower
framing. Check tightness of bolts in fan cylinder joints and fan cylinder anchorage.
Re-tighten if necessary.
3.4.5 Check tightness of bolts at diagonals and columns, and grits and columns in the
area between fan and cold water basin.
3.4.5 Check tightness of the following bolted joints in the fan and drive
assemblies:
i.) Fan hub clamp bolts.
ii.) Fan shaft lock nuts.
iii.) Motor mounting bolts.
4.0 OPERATION
i.) Start the cooling water circulation pump. Adjust the flow rate with the flow control valve.
Inspect the water distribution system via the inspection door to ensure even water
distribution.
ii.) Check to see if the water level of the cold-water basin is kept at the operating water level.
iii.) Make sure the cooling water is not dirty and contaminated. If it is dirty, drain the tower and
fill it with clean water.
iv.) The motor should bring the fan up to speed in less than 15 seconds. The motor should bring
the fan up to speed in less than 15 seconds. If it does not, check the connections, fuses,
overloads and voltage at motor terminals during start-up period.
v.) Do not cycle a motor on and off more than necessary. Generally, the total starting time
should not exceed 30 seconds each hour. Too frequent cycling may cause the windings to
burn out.
vi.) Run the fan to check the following points.
The fan turns in normal direction (clockwise as viewed from the air delivery side).
There is no unusual sound and vibration.
The fan motor is within the rated value; the excess of electric current may be caused by
low voltage.
The supply voltage to the motor is proper.
vii.) Normal operating temperatures of electric motors can be hot enough to cause burns.
Avoid any unprotected contact with the operated motor surface.
viii.) Always maintain good cooling water quality. See Table 1 and for recommended
cooling water quality criteria.
ix.) See if the casing, framework and louvers are dirty. Clean them up with fresh water, if
required.
vii.) For long-term storage (in excess of 6 months) it is necessary to check the fan
condition of the rust preventive coating on all machine surfaces in order to prevent
corrosion. Reapply or repair where necessary, using Esso Rust ban 397 or equivalent.
viii.) The motor should be run for three hours at least once a month. This serves to dry out
windings and re-lubricate bearing surfaces.
ix.) At start of new operating season, make sure bearings are adequately lubricated before
returning motor to service.
Belt tension
Center distance indicator applied to
mid center distance
16mm deflection
per 1 meter of span
Belt Deflection
Center distance (meter) x 16mm(deflection) = actual belt deflection
If Center Distance = 1000mm = 1meter
Deflection (l) = 16mm
Example:
SPA Belt, small pulley diameter = 150mm
Force value should be 36N (Referring to Table 2)
If F<36, too loose
F>36, too tight
Inspection item
General conditions
Bolt tightness
Cleaning
Recoating
Balance adjustment
Water level
Water leak
Abnormal vibrations
Fan M S R R D
Motor M S R R D D
Infill M M
Ball tap W
Water distribution W S Y Y
system
Valve S
Sump S M Q D
Strainer M M
Structural components S Y R Y
Casing Y
Louvers Y
6.3 BLOW-DOWN
The blow-down ( D ) is carried out in any of the following manners.
i.) The drain valve is kept slightly open during the operation.
ii.) The water level is set somewhat higher to allow constant overflow from the overflow
pipe.
iii.) The whole circulating water is frequently replaced with fresh water at the time of
cleaning the cooling tower.
The blow-down amount depends on the quality and concentration of the dissolved
components in the water. It usually ranges from 0.2 to 2% of the circulating water flow
rate.
Voltage too low at motor terminals Check transformer and setting if taps.
because of line drop Use higher voltage on transformer
terminals or reduce loads. Increase
wire size or reduce inertia.
Motor does Starting load too high Check load motor is supposed to carry
not come up at start.
to speed Broken rotor bars Look for cracks near the rings. A new
rotor may be required. Have motor
service man check motor.
Open primary circuit Locate fault with testing device and
repair
Wrong Wrong sequence of phases Change any two of the three motor
rotation leads.
(motor)
Motor misaligned Realign.
Weak support Strengthen coupling.
Coupling out of balance Balance coupling.
Driven equipment unbalanced Rebalance driven equipment.
Defective bearings Replace bearings.
Bearing not in line Line up properly.
Motor
Balancing weights shifted Rebalance motor.
vibrates
Contradiction between balancing of Rebalance coupling or motor.
rotor and coupling (half key – full
key)
Polyphases motor running single Check for open circuit.
phase
Excessive end play Adjust bearing or add shim.
Bent or sprung shaft Straighten or replace shaft.
Excessive belt pull Decrease belt tension.
Pulleys too far away Move pulley closer to motor bearing.
Pulley diameter too small Use larger pulleys.
Misalignment Correct by realignment of drive.
Insufficient grease Maintain proper quantity of grease in
bearing.
Hot bearings
Deterioration of grease or lubricant Remove old grease, wash bearings
ball
contaminated thoroughly in kerosene and replace
with new grease.
Excess lubricant Reduce quantity of grease; bearing
should not be more than ½ filled.
Overloaded bearing Check alignment, side and end thrust.
Broken ball or rough races Replace bearing, first clean housing
thoroughly.
Blade rubbing inside of fan Adjust cylinder to provide blade tip
cylinder clearance.
Fan noise
Loose bolts in blade clamps Check and tighten if necessary. Check
fan blade pitch.
3.6
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
PUMP
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
INSTALLATION, OPERATION
AND MAINTENANCE INSTRUCTIONS
Contents
Section Page
1. General Observations ……………………….2
2. Operation……………………………………….4
4. Trouble Shooting……………………………...6
5. Maintenance……………………………………7
Please read these Operating instructions before installation and operation of the pump.
Should the pump respectively pumping set suffer damages because these instructions
have not been followed the guarantee will become void.
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 1
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
1. GENERAL OBSERVATIONS
The installation location should provide enough room for inspection and maintenance
work. The room should be well aired. If the temperature of the pumped liquid is high
(80ºC to max 120ºC) the room temperature should not exceed 40ºC (otherwise use
special motors).
The pump-motor unit should be firmly fastened to its base in such a way that loosening
through vibration is avoided during operation.
Depending on the type of installation, horizontal and vertical installations are possible.
The appropriate type of electrical motor has to be selected. If vertically installed the
position of the motor underneath the pump should be avoided since leakage through
the mechanical seal may penetrate into the motor bearings.
The pipe work should be connected and supported in such a way that no stress is
introduced into the pump casing. After unfastening the flange bolts, both flanges
should spring apart by the thickness of the gasket and neither separate under an angle
nor stay together under force.
(b) suction and discharge pipes are independently supported near the pump;
(c) Flexible connections are used if the temperature of the pumping liquid is high.
Flange gaskets should not protrude into the bore, which should be clean of weld
splatter, burrs, rust and other impurities.
(a) be as short and straight as possible and made one or two sizes larger than the
pump suction, so that the flow velocity does not exceed 1.5 – 2.0 m/sec;
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 2
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
(c) be absolutely airtight and rise towards the pump or at least run horizontally;
(d) be equipped with a gate or foot value. These valves must not be used to control
the pump flow and must always remain fully open when the pump is running.
(a) have a diameter sufficiently large to limit the flow velocity to 2.5 – 3 m/sec;
(b) be fitted with a non-return valve between pump and discharge valve to prevent
reverse flow while the pump is stopped. This is particularly important when
pumps are operated in parallel. If reverse flow is allowed to occur, the pump will
‘turbine’ backwards and may be damaged when started under these conditions;
(c) be equipped with a discharge valve for start-up and flow regulation.
All bends should have large radii and their number should be limited to a minimum. If a
strainer is used in the suction line to prevent foreign matter from being drawn into the
pump the screen should have sufficient openings to keep the flow velocity through it
below 0.6 m/sec.
This pump is equipped with a mechanical seal standardized according to DIN 24960.
Check if the pump shaft can be rotate easily by hand.
Do not start or rotate the pump without liquid nor rotate in the wrong direction since this
will seriously damage the mechanical seal.
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 3
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
2. OPERATION
the motor protection has been adjusted to maximum load as indicated on the motor
identification plate;
If the pump operates under positive suction pressure, priming may be achieved by
venting the pump through the vent plug (057 in cross section).
If the pump operates in a suction mode with a foot valve, the pump may be primed
by filling pump and suction line through the vent plug.
If no foot valve is installed, the pump can be primed with a vacuum pump.
2.2 Start-up
Start the unit with closed discharge valve until pressure has built up in the discharge
line, then open discharge valve slowly. Do not operate unit for prolonged periods with
closed discharge valve to avoid over-heating of liquid and pump.
The pump set should be shut down at once and the trouble corrected if:
the pump set vibrates or makes excessive noise (watch for cavitation ‘crackle’).
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 4
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
shaft sealing
A new mechanical seal can leak after start-up. After approx. 60 min. of run-in,
leaking should not exceed 1-2 drops per minute.
the cleanliness of the suction strainer (a clogged strainer may cause cavitation!)
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 5
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
4. TROUBLE SHOOTING
DEFECTS
liquid delivered
Not enough
Cavitation
delivered
Vibration
pressure
No liquid
(Noise)
CAUSE
1 Pump not primed X
2 Speed too low X X X
3 Speed too high X X
4 Air leak on suction X X X X X
5 Air leak in seal X X
6 Air or gas in liquid X X X X
7 Discharge head too high (above rating) X X X X
8 Suction head too high X
9 Not enough suction head for hot liquid X
10 Inlet pipe not submerged enough X X X X X
11 Viscosity of liquid greater than rating X X X
12 Liquid heavier that rating X
13 Insufficient nett inlet head X X X X X
14 Impeller plugged up X X X
15 Wrong direction of rotation X X X
16 Excessive wear ring clearance X X
17 Damaged impeller X X X
18 Rotor binding X
19 Defects in motor X
20 Voltage and/or frequency lower than rating X
21 Foundation not rigid X
22 Misalignment of pump and driver X X
23 Bearing worn X
24 Rotor out of balance X
Pump shaft bent or improperly aligned with motor
25 X X
shaft
26 Impeller too small X X
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 6
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
5. MAINTENANCE
This pump does not need any special maintenance. However, it should be examined at
regular intervals for vibration-free funning, power absorption and leakages.
Do not ‘service’ a well-operating mechanical seal since the seal rings have run in
together in a given position. If the seal is disassembled and reassembled the rings will
not touch exactly in the same position and as a consequence, the seal may leak.
If the seal leaks more than 1 – 2 drops per minute and if this amount of leakage cannot
be tolerated in the respective installation, the seal will have to be exchanged for a new
one since an adjustment is not possible.
Unscrew motor from baseplate (if motor is fastened separately), remove bolts
between supporting frame, casing cover and casing and disengage motor including
supporting frame, casing cover, stub shaft and impeller from the casing.
Before and after disassembly determine the cause of the seal failure. Frequently
the cause does not lie in the mechanical seal itself but in the condition of the pump
or its surrounding (i.e. dirt, temperature, excessive axial play, etc.).
Examine the shaft sleeve and shaft (seat of sleeve gasket) for damage and replace
if necessary. Check proper running of shaft with dial gauge.
Check if the axial and radial play of the motor bearings is within the specified limits.
Permissible axial play of the standard IEC motors depends on the location of the fixed
bearing – shaft side or ventilator side. Most of the manufacturers locate the fixed
bearing on the ventilator side and as a consequence the axial play on the shaft side can
vary between 0.9 – 1.2 mm when the motor is cold. If motors of this design are used
care has to be taken that the movable ring will slide easily on the sleeve (moisten shaft
sleeve with vegetable oil or liquid soap).
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 7
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
Complete units which are assembled at the factory are preferentially equipped with
motors whose fixed bearing is located on the shaft side, thereby reducing the axial
play when cold to 0 – 0.2 mm.
If O-rings from PTFE are used, heat these rings in water bath before assembling to
80ºC.
Mount seal cover, which supports the stationary ring of standardized seals,
perpendicular to shaft.
Attention: When in doubt about the replacement seal or the elimination of the cause
of the defect, consult with a specialist.
After assembly, fill pump with water and connect to pressure network (max. 10 bar) to
check for leakage.
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 8
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
2 IMPELLER 1 - - 1
20 GASKET 1 1 2 5
8 SHAFT SLEEVE 1 - - 1
6 LANTERN RING 1 - 1 2
15 IMPELLER NUT 1 - - 1
16 IMPELLER KEY 1 - - 1
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 9
SINGLE STAGE CENTRIFUGAL END SUCTION PUMP
TO DIN 24255 DINFLOW
________________________________________________________________________________________________________________
Y:/regent/Instruction and products notes/Dinflow Instruction SS 06-Sept-07 Page 10
Megaflow
SINGLE STAGE DOUBLE SUCTION
SPLIT CASING CENTRIFUGAL PUMP
2
4.0 Commissioning, start -up/shutdown ................................................ 5
4.1 Commissioning ......................................................................................... 5
4.2 Shaft seal ................................................................................................. 5
4.3 Venting ..................................................................................................... 6
4.4 Commissioning ......................................................................................... 6
4.4.1 Checking the direction of rotation ............................................................... 6
4.4.2 Start-up .................................................................................................... 6
4.4.3 Pump operating range ............................................................................... 6
4.4.4 Shutdown .................................................................................................. 7
4. 5 Shutdown/storage/preservation ................................................................. 7
4.5.1 Storage of new pumps............................................................................... 7
4.5.2 Measures to be taken for prolonged shutdown ........................................... 7
4.6 Returning to service after storage .............................................................. 7
-1-
understood by the responsible person- 0.6 Safety Instructions for
nel. Maintenance, Inspection and
Installation Work
0.3 Non-compliance with Safety
Instructions The operator is responsible for ensuring
that all maintenance, inspection and
Non-compliance with safety instructions installation work be performed by
can jeopardize the safety of personnel, authorized, qualified specialist personnel
the environment and the machine who are thoroughly familiar with the
itself. Non-compliance with these manual.
safety instructions will also lead to
Work on the machine must be carried
forfeiture of any and all rights to
out only during standstill. The
claims for damages
shutdown procedure described in the
In particular, non - compliance can, for manual for taking the machine out of
example, result in: service must be adhered to without fail.
-failure of important machine/unit Pumps or pump units handling media
functions -failure of prescribed injurious to health must be
maintenance and servicing practices decontaminated. Immediately following
-hazard to persons by electrical, completion of the work, all safety -
mechanical and chemical effects relevant and protective devices must be
-hazard to the environment due to reinstalled and/or re - activated. Please
leakage of hazardous substances, observe all instructions set out in the
chapter on ―Commissioning" before
0. 4 Safety Awareness returning the machine to service.
It is imperative to comply with the 0.7 Unauthorized Modification and
safety instructions contained in this Manufacture of Spare Parts
manual, the relevant national health and
safety regulations and the operator's Modifications or alterations of the
own internal work, operation and machine are only permitted after
safety regulations. consultation with the manufacturer.
Original spare parts and accessories
0.5 Safety Instructions for the authorized by the manufacturer ensure
Operator/User safety. The use of other parts can
-Any hot or cold components that could invalidate any liability of the
pose a hazard must be equipped with a manufacturer for consequential damage.
guard by the operator, 0.8 Unauthorized Modes of
-Guards which are fitted to prevent Operation
accidental contact with moving parts
(e.g. coupling) must not be removed The warranty relating to the operating
whilst the machine is operating. reliability and safety of the pump/unit
supplied is only valid if the machine is
-Leakages (e.g. at the shaft seal) of
used in accordance with its designated
hazardous media handled (e.g.
use and if all operating instructions
explosive, toxic, hot) must be contained
described in chapter 1 have been
so as to avoid any danger to persons
followed. The limits stated in the data
and the environment. Pertinent legal
sheet must not be exceeded under any
provisions must be adhered to.
circumstances.
-Electrical hazards must be eliminated.
(In this respect refer to the relevant 1.0 Transport and interim storage
safety regulation applicable to different 1.1 Safety instructions
countries and/or the local energy
supply companies.) Transport of the unit requires
proper preparation and handling.
Observe the following
explanations and safety instructions.
-2-
1.2 Transport When lifting the unit by crane, observe the
directions of pull. Angles greater than 90°
Transport in horizontal position is are forbidden.
recommended in all cases, since this
Use separate belts on each side! The
ensures stable positioning of the unit
drawings opposite show correct lifting by
without any risk of accident, whatever the
crane.
method of transport, e. g., road, rail or
ship etc.
For transport purpose the unit should the
secured on suitable pallets or sleds. All
loose and movable parts must be
secured.
1.2.1 Lifting the pump unit by crane
The motor lifting lugs must
only be used for lifting the
motor alone and never for
lifting the complete unit.
-3-
2.0 Description of the product and and operating data. The fixed bearing at the
accessories internal bearing end is located on a bush to
permit rapid changing without removing the
2.1 Technical specification rotor or upper half.
The pump of the REGENT PUMPS series 2.4 Type of installation
is a horizontally installed, single-stage,
axially split volute casing pump with The pump is installed in horizontal position.
double - entry radial impeller. Connection See "Installation" operating instructions.
flanges are manufactured according to DIN,
ISO. BS of ANSI, as preferred. 2.5 Attachment
In waterworks, irrigation and drainage The accessories supplied with the pump
pumping plants, power stations, for are specified in the relevant individual
industrial water supply, in air conditioning operating instructions.
systems, dock installations, fire ex-
tinguishing systems and many other areas. 2.6 Dimensions and weights
2.2 Designation For dimensions and weights please refer to
the pump installation drawing.
T XXX–XXX–XXX
3.0 Installation at site
Type series
Suction DN in mm 3.1 Safety regulations
Discharge DN in mm
Electrical equipment operated
Nominal impeller dia. in mm
in hazardous locations must
2.3 Design details comply with the explosion
protection regulations. This is indicated on
2.3.1 Pump casing the motor rating plate. If the equipment is
Axially split volute casing with replaceable installed in hazardous locations. The
wear rings. Suction and discharge nozzles applicable local explosion protection
in lower half of casing are at the same regulations and the regulations of the test
level (inline version). certificate supplied with the equipment and
issued by the responsible approval
2.3.2 Impeller authorities must be observed and complied
with.
The double-entry radial impeller is
manufactured for the operating data The test certificate must be kept close to the
provided in each case. Also with wear location of operation for easy access (e.g.
rings, if requested. In double -entry radial foreman's office).
impellers the axial thrust is largely
balanced. 3.2 Checks to be carried out prior to
installation
2.3.3 Pump shaft
All structural work required must have
The shaft is fully sealed against the liquid been prepared in accordance with the
being pumped. Shaft - protecting sleeves dimensions stated in the dimension
are fitted in the seal area. table/installation plan. The concrete
foundations shall have sufficient strength
2.3.4 Shaft seal (min. BN 150) lo ensure safe and
functional installation in accordance with
The shaft seal at the drive end of internal
DIN 1045 or equivalent standards. Make
bearing end is designed as described in
sure that the concrete foundation has
the "Shaft seal" operating instructions.
set firmly before placing the unit on it. Its
2.3.5 Bearings and lubrication surface should be truly horizontal and
The pump is fitted with the bearing and even.
lubrication system stated in the design
-4-
3.3 Installing the pump/unit The flange covers on the pump suction and
discharge nozzles must be removed prior
See Operating Instructions ―installation". to installation in the piping.
Before setting up the pump,
check the operating data. 3.4.1 Auxiliary connections
Ensure that the data on the maker's plate The dimensions and locations of the
agrees with the data in the order and the auxiliary connections (cooling, heating,
system data, e. g. operating voltage, fre- sealing liquid, flushing liquid, etc.) are
quency, pumped liquid temperature etc. indicated on the installation plan or piping
layout.
3.3.1 Removal of pump rotor securing
device More detailed installation instructions are
given in the respective operating
This is not necessary for a horizontally instructions.
installed pump, since no securing device
is fitted. These connections are
required for proper functioning
3.3.2 Aligning the pump/drive of the pump and are therefore
To align the unit, refer to the sections, of vital importance!
"Coupling" and "Installation". 3.4.2 Coupling guard
Improper alignment of the unit In compliance with the accident
can cause damage to both the prevention regulations the pump
coupling and the unit itself! must not be operated without a
3.4 Connecting the piping coupling guard. If the customer specifically
Never use the pump itself as requests not to include a coupling guard in
an anchorage point for the our delivery, then the operator must supply
piping. Suction lift lines one.
should be laid with a rising slope towards 3.5 Final check
the pump and suction head lines with a Re - check the alignment as described in
downward slope towards the pump. The section 3.3.2.
pipelines should be anchored in close It must be easy to rotate the shaft by hand
proximity to the pump and should be at the coupling.
connected without transmitting any
Check the integrity and proper
stresses or strains. Their weight must not
functioning of all connections.
exert any load on the pump. With short
pipelines, the nominal diameters should be 4.0 Commissioning, start-up/
at least equal to the nominal diameters of shutdown
the pump nozzles. For long pipelines the
Compliance with the following
most economical nominal diameter has to
requirements is of paramount
be determined from case to case.
importance. Damage resulting
Any additional loads on the discharge and from non -compliance shall not be covered
suction nozzles, e.g. caused by: by the scope of warranty.
Weight of the water-filled pipes, changes
in the length of pipes owing to temperature 4.1 Commissioning
fluctuations, reactive forces due to Before starting up the pump make sure that
unbraced compensators must not exceed the following requirements have been
the stated values. checked and fulfilled.
An excessive, impermissible Has the pump been firmly bolted to the
increase in the pipeline forces base/foundation?
may cause leaks on the pump
where the medium handled can
escape into the atmosphere. Danger to life
when hot media are handled!
-5-
Have the coupling and pump unit been The direction of rotation must correspond to
aligned as specified? the direction indicated by the arrow on the
Are the pipes properly fitted? Has the pump. This can be verified by switching the
motor been installed according to its oper- pump on and then off again immediately.
ating instructions? Before checking the direction of
Can the unit be easily rotated by hand at rotation make sure that there is no
the coupling? (Carry out at least one full foreign matter in the pump casing.
rotation) Has the coupling guard been Never put your hands or any other objects
fitted? Have shaft been informed about into the pump!
sources of danger and measures taken to 4.4.2 Start - up
comply with the accident prevention
regulations? Dry-running will result in
increased wear and must be
Is the unit protected against overload
avoided
(appropriate safety valve)?
If a non - return valve is not fitted at the
Have the seals been fitted according to
discharge end, close the delivery gate
their operating instructions?
valve.
Have any additional devices been
If a shut - off valve is fitted at the suction
prepared and fitted according to their
end, open it fully.
operating instructions? Has lubrication
been provided for oil-lubricated bearings? All additional connections for cooling,
heating, lubrication, irrigation or sealing
Has the pump been vented as specified in
liquid etc, if fitted, must be opened fully or
section 4.3?
switched on and the flow must be checked.
4.2 Shaft seal Switch on the motor.
For putting the shaft into operation, refer As soon as the pump starts to deliver this
to Operating instruction "Shaft seal". If the can be recognized by the rising gauge
pump has been out of operation for a pro- pressure slowly open the delivery gate
longed period, the measures specified in valve fully.
section 4.6 must be carried out. The pump may operate against
4.3 Venting the closed gate valve only
during start – up and shutdown,
Before the pump is started up, it and the as otherwise inadmissible temperature rise
pipes must be vented and filled with the occurs resulting in damage.
liquid to be pumped. In the case of both
gravity feed and suction operation venting 4.4.3 Pump operating range
must be carried out via the hole on the up- The flow rate "Q" adjusts itself
per suction elbow. In the case of suction automatically to the delivery head
operation the pump must additionally be according to the Q - H characteristic. The
evacuated (a vacuum must be created). pumps permitted operating range is subject
4.4 Commissioning to limits, which have separate causes.
1. Partial load operating limit with low flow
4.4.1 Checking the direction of rate.
rotation This limit is indicated in the Q - H
For trouble-free operation of characteristic by Qmin or by the continuation
the pump, the correct of the characteristic which is
direction of rotation of the not depicted.
impeller is of paramount importance. If It is not permissible to operate
running in the wrong direction of rotation, the pump in the range from Q =0 t0 Qmin,
the pump cannot reach its duty point; prolonged operation in this range causes
vibrations and overheating will be the greatly increased mechanical loads which
consequence. The unit or the shaft seal the components cannot withstand. Brief
might be damaged. passage through the critical range is
Correct direction of rotation: permissible, e.g. during start - up.
-6-
2. NPSH -related limits in the partial load applicable the cooling chambers must be
and overload ranges drained or otherwise protected against
These two limits are determined by the freezing.
ratio of NPSHr to NPSHa. They are 4.5 Shutdown/storage/preservation
calculated as follows: The intersections of
NPSHr and NPSHa are projected onto the Each Regent Pumps pump leaves the
Q-H characteristic, where they give the factory carefully assembled. If
operating limits (refer to the diagram be- commissioning is to take place some time
low). Checking of the NPSHr operating after delivery, we recommend that the
limit is not necessary for operating the following measures be taken for pump
pump under design conditions. If system- storage.
related changes occur, an NPSH check 4.5.1 Storage of new pumps
must be carried out. If necessary, consult
New pumps are supplied by our factory duly
the nearest Regent Pumps after sales
prepared for storage.
service centre.
Maximum protection for up to 12 months,
if the pump is properly stored indoors.
Store the pump in a dry location.
Qmin 4.5.2 Measures to be taken for
prolonged shut down
NPSHr
1. The pump remains installed; periodic
check of operation.
NPSHa In order to make sure that the pump is
always ready for instant start-up and to
prevent the formation of deposits within the
pump and the pump intake area, start up the
pump set regularly once a month or once
4.4.4 Shutdown every 3 month for a short time (approx. 5
minutes) during prolonged shutdown
Close the shut-off element in the discharge periods. Prior to an operation check run
line. If the discharge line is equipped with a ensure that there is sufficient liquid available
check valve, the shut-off element may for operating the pump.
remain open, provided there is back 2. The pump is removed from the pipe and
pressure in the line. stored before putting the pump into storage
The shut-off element in the carry out all checks specified in sections
suction line must not be closed 5.1 to 5. 4: Spray - coat the inside wall of the
when switching off the pump, pump casing, and in particular the impeller
Switch off the motor, making clearance areas, with a preservative.
sure that the unit runs smoothly down to Spray the preservative through the suction
a standstill. Depending on- the system the and discharge nozzles. It is advisable to
pump should have an adequate after run close the nozzles (for ex. with plastic caps
period with the heat source switched off to or similar).
allow the medium handled to cool down
sufficiently to avoid any heat build-up within 4.6 Returning to service after
the pump. storage
In the case of prolonged shutdown, the Before returning the pump to service
shut-off element in the suction line has to carry out all checks and maintenance
be closed. Close the auxiliary connections. work specified in sections 5.1 and 5.2.
The shaft seal in pumps where the liquid is In addition, the instructions
fed in under vacuum must also be laid down in section 4.1
lubricated with sealing liquid during "Commissioning" and section
standstill. In the event of frost and/or 4.4.3 Operating limits must be
prolonged shutdowns, the pump and if observed.
-7-
Upon completion of the higher room temperatures, the bearing
work, all safety -related and temperature should be below 100°C
protective equipment must (212°F). If the pump features oil -
be properly refitted and/or lubricated bearings, the correct oil level
reactivated before starting the pump must be verified at regular,
set. intervals.
5.0 Maintenance/repair During pump operation the
shut-off element in the inlet line must not
5.1 General Instructions be closed. Any stand-by pumps installed
The operator is responsible for should be switched on and then
ensuring that all maintenance, immediately off again once a
inspection and installation work is week to keep them operational.
carried out by authorized, duly Attention should be paid to the
qualified staff that are thoroughly correct functioning of the
familiar with these operating in- auxiliary connections.
structions. If the flexible coupling elements begin to
show signs of wear, they should be
A regular maintenance schedule will
replaced in due time. See Operating
help avoid expensive repairs and
Instructions "Coupling".
contribute to trouble-free reliable
operation of the pump with a If the liquid for sealing, cooling and
minimum of maintenance expenditure lubricating is taken from an external
and work. source, the pressure must be 1.0 to 2.0
bar higher than at the suction nozzle.
Work on the unit must only
The gland packing (if the pump is fitted
be carried out with the
with one) should drip slightly during
electrical connections
operation. The gland should only be
disconnected. Make sure that the
gently tightened. See Operating In-
pump set cannot be switched on
structions "Shaft seal".
accidentally (danger to life!).
Pumps handling liquids 5.2.2 Maintenance of the shaft seal
posing health hazards must Maintenance is affected as described in
be decontaminated. When the "Shaft seal" Operating Instructions.
draining the medium, see to it that
there is no risk to persons or the 5.2.3 Maintenance of the bearings
environment. All relevant laws must The bearings are maintenance-free
be adhered to (danger to life!). and are greased for life. No lubrication
is required. Maintenance of oil -
5.2 Maintenance/inspection
lubricated bearings is to be effected as
5.2.1 Supervision of operation described in the "Oil -lubricated bear-
ings" Operating instructions.
The pump should run
quietly and free from 5.3 Dismantling
vibrations at all times. Before dismantling, secure the
The pump must never be allowed to pump so as to make sure it cannot be
run dry. switched on accidentally. The shut-off
Prolonged operation elements in the suction and discharge
against a closed shut -off lines must be closed. The pump must
element is not permitted in have cooled down to ambient temper-
order to prevent the medium ature, it must be drained and its pressure
handled from heating up. must be released.
At room temperatures of up to 30°C Dismantling and reassembly must
(86°F) the bearing temperature always be carried out in accordance with the
should not exceed 90°C (194°F). At relevant sectional drawing.
-8-
5.3.1 Fundamental instructions and bearing housing out of the recesses and lift
recommendations the rotor upwards out of the lower casing
Repair and maintenance work to the pump half. For further disassembly, place securely
must only be carried out by specially in horizontal position.
trained personnel, using original spare Pull of the bearing housing of the fixed
parts. bearing (opposite the drive end).
Observe the safety regulations laid down. Undo and twist off the grooved nut. Remove
And work on the motor shall be governed the deep groove ball bearing with bush from
by the specifications and regulations of the the shaft.
respective motor supplier. Remove bearing cover.
Dismantling and reassembly must always Remove V-Ring from shaft-protecting sleeve.
be carried out in accordance with the Remove shaft seal housing.
relevant general drawing. The general Pull off shaft protecting sleeve.
drawing and other relevant documents are The impeller is located with sliding fit on the
found in the annex. The dismantling se- shaft and can normally be removed easily.
quence can be derived from the general In case of difficulty, it can be loosened by
drawing. In case of damage you can gently tapping with a plastic hammer.
always contact our service departments.
Remove second shaft protection sleeve
5.3.2 Preparations for dismantling complete with the shaft seal housing, if fitted.
Remove coupling half.
Please observe the "Coupling" Operating
Instructions. Pull off bearing housing.
The pump is designed so that the Remove cir-clip and pull off deep groove ball
complete rotor can be removed in the bearing.
sequence described below without 5.4 Reassembly
removing the suction or discharge pipe or
disturbing the alignment of the pump unit: Reassembly is effected in reverse order to
Close the suction and delivery gate valves dismantling. For all work on the pump unit the
and drain the pump by opening the drain general diagram, in conjunction with the
plug and vent plug. individual parts list, serves as a guide.
Remove any pipes between additional The customary rules of mechanical
equipment and the pump. engineering and also the installation
Remove coupling guard. instructions for removal and installation of
shaft seal, bearing, impeller wear rings and
Detach the pump-side coupling half as
casing wear rings sections must be
described in the Operating instructions
observed. In the case of oil - lubricated
"Coupling". Loosen and push back the seal
cover. Undo flange screws and release the bearings, the Operating Instructions "Oil -
lubricated bearings" must be observed.
upper casing half from the lower casing
half with the aid of the forcing screws, For the required tightening torques please
remove with lifting gear and store in a safe refer to works standard ZN 192 unless
place. The interior of the pump is then free otherwise specified. It is essential to use the
(impeller with casing wear rings, shaft correct tightening torques and the required
seals) for inspection and further screw locking devices. The relevant parts are
disassembly. specially indicated in the general drawing.
In case of oil - lubricated pumps drain off The symbols for screw locking devices and
the oil. Remove the screw connection sealing elements are explained in BN 433. 0-
between bearing housing and bearing rings and V-rings must be replaced and
brackets. Also undo the nuts and bolts their seats on the shaft must be cleaned.
which secure the bearing cover. Press the
-9-
In addition, all the sealing elements must at the interior bearing end, proceed as
be fitted into the components provided for described above for the drive for the drive
this purpose before installation. motor side. Heat the deep groove ball bearing
For assembling the rotor, position the and fit it onto the sleeve.
pump shaft securely. All fits, threads and Push the sleeve with deep groove ball
sliding fits of the shaft must be cleaned bearing onto the pump shaft with key
and coated with assembly paste. inserted.
Insert the keys required for assembly into Tension the rotor parts elastically with groove
the pump shaft. nut and disc spring. For this purpose tension
Mount the impeller, which has a sliding fit. the disc spring to blocking point and then
When fitting the impeller, observe the undo the grooved nut again by half a turn.
direction of rotation (see diagram below). This measure is essential to
compensate for differences in
thermal expansion between pump shaft and
the components fitted on it.
Fitting of the rotor is then complete.
Insert the rotor into is the pump casing.
Apply liquid sealant (refer to the appended
list) to the surfaces of the casing wear
rings and the sealing faces of the casing.
Insert the rotor, observing the direction of
rotation. The diagram on the previous page
shows the correct method of installation.
Align the rotor and ensure that the fixing
pins are correctly seated in the casing.
The pins must be positioned as shown in the
For assembling the casing wear rings, diagram opposite.
observe item 7.4. 2 "Changing the casing The bearing housings must be fastened to
wear rings". the bearing brackets by means of the screw
Put the casing wear rings onto the running connections with the sealing cap inserted at
surfaces of the rotor. Ensure that the the interior bearing end. The seating
bezels of the rings are on the outside positions are determined by the recesses.
(towards the bearing). Insert the pins Fitting the bearing covers.
required for fixing the casing wear rings. Before fitting the casing cover, apply liquid
The remaining components are fitted first sealant to the joint surface of the lower
on the movable bearing side (i.e. the casing half (refer the appended list).
drive motor side) of the pump shaft. Tighten the flange screws diagonally from the
Push the shaft protecting sleeve onto the inside towards the outside.
pump shaft. Ensure that the groove Insert the keys for fitting the coupling into the
provided engages in the key of the pump shaft.
impeller. When fitting the coupling and accessories,
Push the complete housing shaft seal see refer to the individual operating instructions.
Operating Instructions "Shaft seals", V-
Ring over the pump shaft.
Push the bearing cover over the shaft.
Heat the deep grooved ball bearing and
fit it onto the pump shaft. It is essential to
avoid one sided pressure, e.g. hammer
blows, on the outer rings. The bearing is
secured by the disc and the securing ring.
To fit the shaft protecting sleeve, shaft
seal housing, V-Ring and bearing cover
- 10 -
5.5.1 Note concerning replacement of by split flows), the impeller neck must be
assemblies/parts. turned off on a lathe and the impeller wear
5.5.2 Replacing the shaft seal. ring fitted in addition (available as spare
parts).
Refer to Operating Instruction ―Shaft Alternatively, a new impeller can be supplied
seals‖. at short notice.
5.5.3 Replacing casing wear rings
and/or impeller wear rings.
The impeller clearance is given in the data
sheets ―Design and operating data‖.
To remove the impeller, proceed as
described in section 5.4 ―Reassembly‖.
After reassembly section 5.3.2, the casing
wear rings can be removed. When fitting
the rings, ensure that their bezels are on
the outside (towards the bearing).
The pins must be positioned as shown in
the following diagram.
If the impeller has not been fitted with a
wear ring at the factory, and changing the
casing wear ring alone does not achieve
anything close to the required impeller
clearance (the impeller neck is badly worn
- 11 -
5.6 Spare parts
5.6.1 Purchasing of spares
The following information is required for ordering (see manufacturers
nameplate of refer to the information given in the design and operating
data sheets):
Design series; serial number of pump: year of manufacture
The required parts should be specified as follows<see general drawing and
spares list).
Example:
2 3 4 5 6 8 10 and
more
Number of spare parts
117 impeller 1 1 1 2 2 3 30%
118 Casing wear ring 4 4 4 6 6 8 50%
117. 1 Impeller wear ring 4 4 4 6 G 8 50%
Shaft with keys and shaft nuts 1 1 2 2 2 3 30%
121 Anti — friction bearing 2 2 4 4 6 8 100%
119 Shaft protecting sleeve 4 4 4 6 6 8 50%
128 A Packing ring 32 32 48 46 48 64 40%
Set of seals 4 6 8 8 9 12 150%
Mechanical Rotating seal ring 4 6 8 8 8 12 90%
seal: 4 6 8 8 8 12 90%
Stationary seal ring 4 6 12 16 16 20 150%
0 – rings 4 6 12 16 16 20 150%
128B Seals on stationary seal rings 1 2 2 2 2 4 20%
Set of springs
These figures already include those components required twice for replacement
6.0 Trouble -shooting
- 12 -
NPSH
6.1 General
The diagram below is to facilitate
understanding of the causes of faults and
their remedies.
The cause of many operating faults on
pumps is often hydraulic. The hydraulic
behavior of a pump is illustrated by its
characteristic curves H, P, Eta and NPSH in
combination with the plant characteristic
curves HA and the pump curve H intersects.
The duty point B is where the system curves
HA and the pump curve H intersect. The duty
point B is where the system curves HA and
the characteristic curve H intersect. If it is not
possible to determine the cause of the
trouble, contact the Regent sole agent.
NPSH
Hgeo
Capacity
13
6.2 Causes of faults and their remedies Faults
Pump pressure too low
Pump pressure too high
Flow capacity too high
Flow capacity too low
Power consumption too high
Pump fails to pump liquid after being switched on
Pump ceases to pump liquid
Pump does not run smoothly (noise, vibrations)
Inadmissible temperature increase at pump/seal casing
Bearing temperature too high
Excessive leakage at the shaft seal
Drive machine overload
Leakage at pump
Cause Remedy
Duty point B does not lie at The
X X X X X X X X X calculated intersections of Q and - Re - adjust duty point
H
Pump or piping incompletely
X - Vent
vented or not primed
- Reduce speed
X X X X X Speed too high
- If there is constant overloading possibly machine impeller 1)
- Check
- Tighten lie bolts
X Tie bolts/seals - Renew gaskets
- Check pipe connections and pump mounting, if necessary
improve mounting of piping
- Check flushing/sealing liquid pressure
- Check sealing liquid line, possibly introduce sealing liquid from an
X Shall seal worn external source or increase pressure
- Renew shaft seal
- Renew worn components
- Alter piping
Unfavorable flow to suction to - If necessary, alter suction/intake pipe if resistances are too high
X X X X
suction noz2le of pump - Check whether pipe route has a twisted or irregular flow profile (e.
g. downstream of an elbow)
- 14 -
1) Consult Regent Pumps
Faults
Pump pressure too low
Pump pressure too high
Flow capacity too high
Flow capacity too low
Power consumption too high
Pump fails to pump liquid after being switched on
Pump ceases to pump liquid
Pump does not run smoothly (noise, vibrations)
Inadmissible temperature increase at pump/seal casing
Bearing temperature too high
Excessive leakage at the shaft seal
Drive machine overload
Leakage at pump
Cause Remedy
- Alter
Gland follower, seal cover (mech. - Renew
X X Seal) wrongly fitted, incorrect - Correct
packing material - Renew gland packing
- Renew worn components
- Check flushing / sealing liquid pressure
- Clean sealing liquid line, possibly introduce sealing liquid from an
Lack of cooling liquid or cooling external source or increase its pressure
X X liquid chamber contaminated
- Increase flow cooling liquid
- Clean cooling liquid
- Re-align pump / drive machines
Pump mis-aligned or there are - Check piping connections and pump mounting, if necessary
X X
resonance vibrations in the piping improve mounting of piping
- Apply vibration – damping measures
- Check duty point / layout
X Excessive axial thrust - Check mode of operation
- Check suction flow
- Clean bearing
Too little, too much or unsuitable
X - Renew lubricant
lubricant
- Top up reduce or change lubricant
- 15 -
1) Consult Regent Pumps
Number of
Interval personnel Time (h) Maintenance job
required
- 16 -
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
3.7
SYSTEM OPERATING PROCEDURE/INSTRUCTION:
EXHAUST FAN
INSTALLATION & MAINTENANCE GUIDEBOOK
Fan Series: CD / Direct Drive CABINET FAN
The safety recommendations contained herein aim to support the installer, maintenance engineers and
other technicians who operate the ventilation equipment as listed above. These recommendations cannot
represent totally the methods or procedures required for safe operation. Care should always be taken
when working in close proximity to equipment or moving parts. Total safety depends on acquired skill,
experience and reasonable care in all operations
The CD fan series construction consists of a Direct Drive Fan installed inside the fan cabinet. The cabinet
comes with a detachable access door at the base of the cabinet. This access door provides an access to the
direct driven fan (DD fan) for maintenance and troubleshoots purpose. The DD fan can also be
dismounted from the cabinet by removing the screw that secure the fan to the cabinet; if necessary.
The DD fan is suitable for handling non-toxic, non-flammable, non-corrosive air, without liquid, solid or
abrasive particles. Air temperature should not exceed 40°C. The fan should only be connected to an
electrical supply having the characteristics indicated on the label.
3. Installation
4. Maintenance
Disconnect the electrical power supply before working on the fan unit.
Periodically check (at least once a year or more frequently if the characteristics of the air stream required)
that there are no obstructions and, if necessary, clean the passages and blades of the fan blower wheel.
Any dust particular/ foreign body deposits on the fan blower wheel can cause wheel imbalance and may
subsequent has negative effect on the fan motor bearing life and on vibration and noise levels.
In addition check that the fan does not show any sign of deformation or breakage and that the screws of
fixing nuts protection are tightly screwed.
The cleaning of the fan blower wheel can be done by access through the inspection door. If the
maintenance work is performed from a ladder or other support, ensure a firm footing. If the fan is
connected to duct, precautions should be taken to avoid duct from fallout.
BK-01/CD01-1
INSTALLATION & MAINTENANCE GUIDEBOOK
Fan Series: CD / Direct Drive CABINET FAN
5. Trouble Shooting
Use the following table to solve possible problems that you may encounter when using the fan. If further
assistance is necessary, refer to Nicotra for information on technical service.
The fan does not work 1) Make sure that the wiring connection has been followed correctly,
all the wires are connected and that the circuit is live.
2) Make sure that the applied voltage is correct for the wiring
configuration of the motor.
3) Make sure that the power wiring is not earthed nor that any wire is
cut (in this case, replace motor or accessory wiring).
The fan rotates backwards 1) Make sure that the wiring diagram has been followed correctly.
2) Check that the rotation of the motor is the same as indicated on the
fan (if not, replace motor).
The fan draws more than the 1) Make sure that the wiring diagram has been followed correctly
rated current 2) Check that the pressure loss of the fan is not less than the design
value (if so, modify pressure loss).
The fan vibrates excessively 1) Make sure that all mechanical connections are tight and that the
or is too noisy blower wheel is mounted securely on the motor shaft, and is
positioned in the center of the fan housing (if not, tighten the
mechanical elements).
2) Check that the blower wheel is not deformed (if so, replace the
wheel).
3) Make sure that there is no accumulation of dust or grease on
impeller blades (if so, clean and rebalance the wheel).
4) Check whether the noise is due to fan vibrations or from the motor
(in the second case, replace the motor).
The fan does not give the 1) Make sure that the applied voltage is correct for the wiring
required performance configuration of the motor.
2) Make sure that the wheel orientation is correct (if not, replace the
wheel).
3) Verify that the fan is connected to the correct rotational speed
specified, for multi-speed motors.
4) Verify that the pressure loss of the fan is not greater than the design
value (if it is, modify the pressure loss).
NICOTRA reserves the right to improve or modify details/accessories without any obligation to update previous
production and manuals.
BK-01/CD01-2
I NSTALLATI ON, OPERATION
& M AINTENANGE M ANUAL
o
(J
?
6 ( gU I E ;< g3
= (L)
E ag l !v-
"i; A H .g | ti -X
E
=+ ts; F
00
i' : Er E;
-xF
.f;
E: E= ;
:5F .9I -r Fi E.E
+rl -'- E b
q ni
vd ,v F
E: Y._pA
=b ?
EFF
.Er
L, j-
EE
=.
=€
AVO'9
,t=zL o
-'5
-*t'-r G > G El :q i E ;,4
rF
==co5-
a .r
frY
E= €
tw = .i
o
o
+,
o
o
bo. E g-€
iE o=
u ., 0)
€l E ; +: . F Et
:l .tr EY3 : =E
i
aE
E-
e 5E
bo-U
;
= tr bO >-
q)o
E;}
. -; = 8 l H ;;E ;e $ H
ii.p
.^q
:XEE €.
iuH
^
P IJ
o 6t
g E.t:
'r- E E I E H g T E €; ;
T l i EY5*?
P l s *0gc* HE
F ''
tr=
€; g
)' ' ! E 9? G
g9
H; : E
E
H o E '=
!vq- c- o |
e€p
=SEg? Esfr
F: c_V 0J
|
EE :; E = E I ":*a'{F, Ef;E
.Y=
z8
XF
tr
.=
z n| <E ita- eir ; iloo< tr.Ez
-
Ktr
: '!.i-
!=
g
F
E .=-o = iEs
*
;
9\ ai
a+ P
=
E =r+ 5 * E irg
= F E;g
:.. fr r Z o-
+:-
==
.i:S
,or d
E=
-=
Iu
_oq
-- 6
>- E < :E = 2
g.>E
9 "or : :_i ! (!
;; Eg € - .E EH E F3 E i=*Y == -\
c
.9 r ;
T; ni :
^ d
; ai
: u
*9
.,
E
Pfi ;5
_O*
E b
-€
Ec
c
t Y + : , --J J
?E o
o-* cJ ^^i l S
o
-q
6.
'-
!o= -:z
ot cJcu I ..1
Gv
vu o-E
-A
E3 fg e E8 _
HE
. re
d4
crc= tsq -
6
o
T -c) .:*/ cJ d)
-9.6 r ^,
YY.= >oc
9= e( Jbo (E
!+ (u
.t)
o- h
= .P
U q rU
cil- .O) p.b
-L
H a;
-u
g,: CJ Y
oleL9
O- = .- tvL
P .: () t!
:.= ii e h !=
!q n - E= . c * XO J P
- d:
.=
ei #F S E: bn
H .!
F
v
e-
90
=f;
._ J E
rg =Y
E cj
.H=
.E
;c.=€
YA.P
=
rt O s ;E 6 G
L
o
E E
>E
3 E
E: x :=
E EE
€ .q.9 eG kU>
i E
E p +
E s.g f = h
i
.-
?.i '=
'E;i x .= I
b g".E
CL
o nQ 6; f. 0 Fs.ebBe,
. = .= = F (E
to E f i= f
o; o f,
P cJ
*
bOIi" tr *
E >-
: n, E i E '= F * E' ::€
-
t" o-
t r: ?
( i C Y/
-
G g .T g - .= ;_;+-
- xE .o OO
E5 = L = :.= o g ! E ;E H
.{ PEEb b PU.=
c:! F S '=; ,r i;>'lEr" F e or n,9 *.=6i@*
5
ralG
ar >.s
3 E8_EEf.=
giseF
9-c
8
Y -O
3I to- =
I
-E 9 0-:
i€ 9 -- ;l - I I 'v u.=
\ 2-*E
-
#'i-E rf v \Jt
:: E ? gc Jr. 5 €. .E
l!= .
N l JL g a )d -Pbou.)
--9
\tr.9o.-9tr;;'
E o-O = i i =.q
5 s +
I
^ 'F
c r ! 9"piH
9^ i5
vco
e c- p nUO - f
e-.- I a t s r= u g
6 , ., i Ft6f
; g*g ES Fg;P
:O-
Qi c6
=
'- FE 3:':F g ;- E
E
=: A
= .= Fii -,x:9EEil
x = >. '=
; E ;; -
-:=.d ;t ai
sO
+p
-
gr
:
8: = €
^- =- ^^
E9 E E€; "-
tt
' !{- Fn E
€
iEg :9 . + ,:g f- *
-
9 f f 8 " ' E . !r
P E +UE .oEJi 3b €5-F3
d
ii.:Q
-:
#F"F :.=
d r-L
o v Ea E g {\o
;.> u 0r.o E
bO,Q
-^- $.,1- G.= C c ^X.G
\- ,Yl H I: -FL
-g+
v7
-'
rg
cP E " E
-
., I Eo c
3EF €g{3
:: =
T i Ei >
Y o pQ:Y
=c ( !
- '=
^!
a n
cr=P
.y; i #p es t F t F € g H ; \f
( Y:
+ E R' -E
=. . .
9 F F
F C O'.E
'6 o6
o
E
Fp gs nc 6
a.o o
z
o I
o
-
= o
f
e= | l- l *e
!:el I l:A
ttl c
Eq
:c
l_1-]
-N
.E
.E
@ ';
lEgMfE
c _9
E ao
-f F ; o
o
o c
F c
c c oc '=
.tt s '6 \t==t €€ o6
€s
LJ
o
z
z
o
't
c) F
o
E
Fsr
o_q f5
(
;;l
-/)l 6e
c;i
.:fi
tro
o-.
-
f .g
o
'5
^r 6-
rf 69
E6 ;9
= .st :!o oE OE
o =
,6
F
!o
(oo
Ec
;^
ot
t! v)> @= >:
x G
o
o
c
o
6 @
o
o l
tll o o c o !
o
(J ,--W'-:3 c
G
G f
D ll-l I c
C) E
o
c
o
.E c
l_rl
a
o e _l lP ! .E o
> tE::- o f
a s C)
4 F/ - t
o a o
q o
o
tL
at
rll
FITIH
E l-r-l :
o
o
c
6
E
o
3
= =
I
c
o
f
'-
-g
o
.E
z =
@
tr
_!
9 \: * o c
- \f==::1 € = E @
Y
o
lrl | | oc o .= E o E
e
f
|
\,O
| qL
E6 o
6
E
-E
o =
G
E
Po
(9 vo ; 6 E +.c
i= q
f
E -
.!!
6t o- q
=E
-*-)
o >- .t" | 6 V nl
te ' b o LLLLi!
AA
6qy
=9: f ; }E I
U
F 9=
-+ a- o q:
a-v
!,^-o
-C/'=
c A= o r !-
E s €= z d:
E- 6= T E# I+ ! :
€
bo
bo tr - ,, &e
c a2Ey
'==C'^ tr >E €-; E .e3
-b oD
i; >- .=
2 X T ..i
:9 .9 Eq T6 = 3
E.iE IJ 6- 9c, -o o
tt)
'=
€**u
9;"8;
E=f^
g '-
v- - FP
d, > F
.\
Y.1..1 CJ
O
v
tt)
#j:!:
G = 10 - _c cr
+r 3' E artE i P"
00 L^LV
(g-C:= o e* u> € -G
LU
l= c !u<gl p
v6
.,:o:tr I
= -d b c,
-C!
UCJ
rP P E
q ,) f= q +8 - b . = E-.€E. . 3 E
o-
(!:] \ !x pt ! .E i - r t
# pA E Elt
#9
E
Q
c ' u i F :q Kg
i
tr Et E:eu =?
.' ( !o9iir r
+t E ;' = il;f,;€3 00
qrlq-E;:p
E :q ;s+=f;e
-v
L h
L- F v.= tr
€= €€IH*;
G 8
Eo R{-s
-6 F ?0Ot!
-=.ed.!';=gn' .Y -; --L = ;.E -:eE -.
OJ}'i
a- o
o
E '5:e fi g: =
S C rs ) inF
-
g 9i = 9 ooE
3 :u :
€ k- 9 s p l L d)
' 5J X P
av-.:--L
ar \2* C
-
-
3 .f= Ha
I ; U"€sriE,
f rq € ; F
boo
NK
l-l
* Ei EE ;a gg= E_
OL7 II
c J r !=:1
.u =a b
>U N
A\ ._ q
-o h.: +
>O
'-dt6vCJ
(J-.cy{x!
cJ P: !{i;
F eE Xg
EgiiissitEigi;
v*
. o
- .d
U
3 .*
'- .\!
Ei
ii ;- ! g !?
u' 6s= u ^v
Q n i 3' >
-o p g*
iEE ig$IEEiI
i F=,E ,!o
",
nl
- vyxv 6) .
-; .2-- * .8
bo
gE,iEi
UoYv.3
'=.6=^.q
ff ggEi
=
-.r Y
:. f^xi.9
*;] j: (d
Yz t .'; d -
!2X'"':cl*rs
p' = =x P=9o
l;EI:
.
V)
(t) *Y :; t Yy?. =cl..d
!a;-c
= ":c9;a/c
tf!O =- !c J
v ! I O - =9 r 'E
U ^ g U :-
E\ 7.-" dh!^
.g Y ?r -y.i :c.)
fE-iFE;Eg;ligJF5i=
: -<!u-vL\o
U ,^ 5i .= 5 d' ' ,
Ur-cu
i6E oti .' R 2 e.z
-
F U cr= + 3=--z
\o \O.cg..E-.-
/1
@K
qP-
_>l :- c 0.)
(J
^
L'=
G!
^Y^ v^ -:-
7 x 6J
F
^v
c -' o 3
>C ->. C? U C
nY c o
v-
-v E i cr u
x 'v i-= .r9--
q
@ d) Ce
6
A,
-o
=t s 6- (!
F=O
-q :: C) u =
PUUI 9>
v;ua, oo
L* LO e
.E c -rF' : u' 93c
- Y! o
on y
L!G
'=
1o.
9 C '- -_ --
c
=-: ^!d) =.- o Q '=
..1_Y ;i .!!: c _c X" n
= ! ^-
.
; E.e s " 6-
-'l
v- .dm
L@-
-
#=E €9 9 Eq.r )
S *; f bo
e rt.f,
L .*Q ou8 E .= H=
O=
J.u cq y
F
:qr/ c -,
C.-
e F E
!e F
F -.^
E
y L!-
o
F--mp
tr.! -f, C =-
.=T 'r
Cr= !i
- .:
v : f l -A
ta tr l - * 1U U * !
S
I
'a F"oj
UsE o e p EF
(;; E € I € e)
E o >'o = ",
EE
'F - ft- :
S 3u
L- q O
\ - o-
\ f-
o i9 - U =. : O o oX
E j q -!
% r u + : ( l )9 c
8lE S
_EX ;o3
!- 9
S :E S t-
s tr fi E E.= :
E s:S
.=.^ F Oh ;o
., c)
o
E;E
ar ': E q E eB
a.Z
=e = rL .. L_ CJ + 6uJ
-.i .{
€f- Ei;."^ e IdJ E F Fl i oo cl ! o1 <-
X -f- .(U AA- L M ='TA ^t
.
tO.Y-.-Q
A\
q vi ro .-E E ro O€ ro . ]
E-6 C gi- .= E ' ai
"=g
J>
o-q
o
:s EE E
=a
--
f 5 g € E.;=-
,i E'E
;E,iE IE E f
:l
-a
n' C :
_o 'v
-!U-
f - H it ii**0 sE - ,* = 0
aE€!*i Eg9E; P +
-d
- 4,:v
*
S
=
lLHo
=-c
=v *
C, -O
-c
.E
EE*i; $€i;: iEi I o
Ei t E; , t F " i: E a s *, , q
,! *
. p. il= -
I
$
1'.=
E
X ci
Ocr ? r
i $€+ st = t *; i #; €Pg
"S
: .b€
;'> !p E E qJ
{ .S
\$
-9=
E; I
', -. ro ( )Y' :'--.'c=> -
\o L, o c
h
\0
*U
"v
F-o t\ *\si+++ +$:EE€;E"
E$t
ffiK
E F€i *tE* €: E e:*
, 4 ;€ +
s ,tE * f F'; g E.E: .g ;; {-i E ;l
pi.E+
E
aE! EFE€
*€ t P E€ sc$ E e
E: : # A E;+ * €€ ; E: : E
E g€t;; ;Ei
go ! [ i E l t E
€ *€ i .FlE t€
E -a b E
E fi ;
+ G:€: Ec *;E i !: E = $#E =*
! E - E; E E E i:P E :E ;€ F :;:+
cH i : =
g;€+EE€+
: *
ii€
j ; iE €$Eg iE;
;€ryrr rr s;E :
n $;5 rr EEt;€ F:f
#== + ; l ;H s#i EE !
E e ;i 8..
E i 5 rfiE!
;+ re E s
* s EE$ A €to s.EF;tn
<.v--d ->-a
Z. O-o.6O-.. F q ) ( ,{ : F-A
N E lg- iE
\O (r.=.: =.Y ", p;iE
\g U (!c=
tr K
==&
!4
3'/) AJ 0J
H;
L9
o- o
.- qr Pi 'E-- €
-o-
E€ ==
-&
E
: .=f : € EH
.= 6 ;:i E
-L
c-0iL
tso ..o", =qr =
e ;8 a .! - Xa tt^ 9
d r .- - - L - ti
-o YEo oo =?=( !C .r
o-
i a 'E* E =Q
= "'
oe
j= qr
..s*Gn
- r?
.E - O- 5
?= E= :
e 6E vg-.
E_ ;€
vg J
.l Jp s,E
A')
6
= E F v 5oA ae
!!F =
cr E e
c
=
P
3i;
XE : F a P & it rxo - 1
€ : ?Ees E
2
E"3 (a
.- p Fv
cgl
'-- -cJ
E F =.!
Ez
=7ar i
=. = : g g.e
S ; 9.4 = tsu "Ci
5 -:, .= i-E .jI F3 3= ilg
; E
- E
E>
E f =.F" E PE
|
iE
(g
8E
C\
s = "- ='i -
=
A
:. n,
--
B u3j r; g s: E
=
;:tr tt E - -oE
c,l l-
5 O
E E 9-o i- : E
;: E? Ei
or .Y = v
i = a: G
t
qJ
c
E 9:
a- = c
c.:
o
i e fl.E .Qp>- +- 3J
E ;t{= s g" c , ) *: HE o .E.0e
dE.!
':E
E*d
s=
=o
loE {.E lsg
M
(
i u '* : * :e EE- :€ E € € F ;E
7-6 = = i =r
Ut -gE ,{ 6& 2Z tE.E ,EEE- =3
4.0
LIST OF EQUIPMENT INSTALLATION & SPARES
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
4.1
LIST OF EQUIPMENT INSTALLED
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION, SARAWAK
Chiller No. 1 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Duty) 550 R134a
Chiller No. 2 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Duty) 550 R134a
Chiller No. 3 Carrier 19XR4647385KG52 Water Cooled Centrifugal Liquid Chiller (Standby) 550 R134a
Chiller No. 4 Carrier 30HXC260 Water Cooled Multiple Screw Compressor Liquid Chiller 250 R134a
Cooling Tower 1 Truwater TXS 800 – 4L Low Noise Type 800 TRS
Cooling Tower 2 Truwater TXS 800 – 4L Low Noise Type 800 TRS
Chilled Water Pump No. 1 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 2 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 3 Regent D150/38 Horizontal Split Casing Pump 98 L/s VS 38 meter head
Chilled Water Pump No. 4 Regent D100/38 Horizontal Split Casing Pump 38 L/s VS 38 meter head
Condenser Water Pump No. 1 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 2 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 3 Regent 200-320 End Suction Pump 158.9 L/s VS 20 meter head
Condenser Water Pump No. 4 Regent 150-260 End Suction Pump 79.45 L/s VS 20 meter head
SCHEDULE OF AIR HANDLING UNIT
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
Block 1 Pentadbiran
B1-L1-AHU-1 39G0912 30 1767 2.3 3 2 1/2" 2 1/2" 1" 1.28 1450 1250 1050 258
B1-L1-AHU-2 39G1621 86 5590 2.5 7.5 3" 3" 1" 3.69 1950 2150 1750 813
B1-L2-AHU-1 39G1621 96 5910 2.6 11 3" 3" 1" 4.14 1950 2150 1750 873
B1-L2-AHU-2 39G1621 114 6717 3.1 11 3" 3" 1" 4.89 1950 2150 1750 883
B1-L2-AHU-3 39G1621 115 6669 2.8 11 3" 3" 1" 4.94 1950 2150 1750 900
Block 2 Perpustakaan
B2-L1-AHU-1 39G1822 174 7942 2.4 11 3" 3" 1" 7.47 2100 2250 1950 1080
B2-L2-AHU-1 39G2230 286 13686 2.9 30 3" 3" 1" 12.28 2400 3050 2350 1831
B3-L1-AHU-1 39G1825 237 8870 2.7 15 3" 3" 1" 10.17 2100 2550 1950 1213
B3-L1-AHU-2 39G1825 237 8870 2.7 15 3" 3" 1" 10.17 2100 2550 1950 1213
B4a-L1-AHU-1 39G0914 237 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L1-AHU-2 39G0914 237 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L1-AHU-3 39G1015 54 2297 2.1 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L1-AHU-4 39G1015 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L2-AHU-1 39G0914 63 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L2-AHU-2 39G0914 63 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L2-AHU-3 39G1015 54 2297 2.1 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L2-AHU-4 39G1015 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.72 1550 1550 1150 412
B4a-L3-AHU-1 39G0914 63 2150 2.2 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
B4a-L3-AHU-2 39G0914 63 2150 2.3 4 2 1/2” 2 1/2” 1" 2.33 1450 1450 1050 288
Fan Total
Total Fan Fluid
Airflow Static Water Water Drain Length Width Height Weight
AHU Marking Model Cooling Motor Flow
(l/s) (Inch Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
Cap (kW) (kW) Rate, L/s
w.g)
B4a-L3-AHU-3 39G1015 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 406
B4a-L3-AHU-4 39G1015 54 2297 2.0 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 406
B4b-L1-AHU-1 39G1015 59 2,441 1.6 3 2 1/2” 2 1/2” 1" 2.56 1550 1550 1150 401
B4b-L1-AHU-2 39G0912 40 1,779 1.9 3 2 1/2” 2 1/2” 1" 1.72 1450 1250 1050 273
B4b-L1-AHU-3 39G0914 48 2,168 1.8 3 2 1/2” 2 1/2” 1" 2.06 1450 1450 1050 308
B4b-L1-AHU-4 39G0914 48 2,168 1.8 2.2 2 1/2” 2 1/2” 1" 2.06 1450 1450 1050 308
B4b-L2-AHU-1 39G0914 97 2,098 1.7 3 2 1/2” 2 1/2” 1" 4.17 1450 1450 1050 281
B4b-L2-AHU-2 3951015 58 2,266 1.5 2.2 2 1/2” 2 1/2” 1" 2.5 1550 1550 1150 401
B4b-L2-AHU-3 39G1015 67 2,450 1.8 3 2 1/2” 2 1/2” 1" 2.89 1550 1550 1150 417
B4b-L2-AHU-4 39G1015 65 2,282 1.7 3 2 1/2” 2 1/2” 1" 2.81 1550 1550 1150 417
B4b-L3-AHU-1 39G0914 55 2,139 2.0 4 2 1/2” 2 1/2” 1" 2.36 1450 1450 1050 288
B4b-L3-AHU-2 39G1015 55 2,421 1.8 3 2 1/2” 2 1/2” 1" 2.39 1550 1550 1150 406
B4b-L3-AHU-3 39G1015 68 2,519 2.1 4 2 1/2” 2 1/2” 1" 2.92 1550 1550 1150 424
B4b-L3-AHU-4 39G1015 61 2,207 1.8 3 2 1/2” 2 1/2” 1" 2.64 1550 1550 1150 412
B5-L1-AHU-1 39G1418 108 4,607 2.5 7.5 3" 3" 1" 4.67 1750 1850 1550 710
B5-L1-AHU-2 39G1621 139 5,627 2.4 7.5 3" 3" 1" 5.97 1950 2150 1750 862
B8-L1-AHU-1 39G1418 76 4,526 2.1 5.5 3" 3" 1" 3.25 1750 1850 1550 671
B9-L1-AHU-1 39G1317 68 3,856 2.2 5.5 3" 3" 1" 2.92 1750 1750 1450 615
SCHEDULE OF FAN COIL UNIT
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
Block 1 Pentadbiran
B1-L1-FCU-1 42CET003 3.07 140 0.015 32W 3/4”FPT 3/4”FPT 3/4”MPT 0.13 770 557 242 21.5
B1-L2-FCU-1 42CET006 4.79 282 0.015 72W 3/4”FPT 3/4”FPT 3/4”MPT 0.2 1170 557 242 30
Block 2 Perpustakaan
B2-L1-FCU-1 40LM070 21.6 900 0.6 0.9 1” 1” 3/4” 0.86 680 1200 480 95
B2-L2-FCU-1 42CET003 3.1 137 0.015 32W 3/4”FPT 3/4”FPT 3/4”MPT 0.13 770 557 242 21.5
B3-L1-FCU-1 42CET010 7.9 472 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B3-L1-FCU-2 42CET003 3.1 111 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4a-L1-FCU-1 42CET003 3.1 79 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4a-L1-FCU-2 40LM060 18.4 737 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-3 40LM060 18.4 565 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-4 40LM060 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L1-FCU-5 40LM070 21.6 957 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4a-L1-FCU-6 40LM070 21.6 957 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4a-L1-FCU-7 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-8 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-9 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L1-FCU-10 42CET004 4.0 190 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-1 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-2 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-3 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4a-L2-FCU-4 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-5 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L2-FCU-6 42CET010 7.9 371 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L2-FCU-7 42CET010 7.9 380 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L2-FCU-8 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-9 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-10 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-11 42CET008 7.3 310 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4a-L2-FCU-12 40LM050 14.2 428 0.5 0.55 1" 1" 3/4" 0.83 680 1000 480 70
B4a-L2-FCU-13 40LM060 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L2-FCU-14 40LM090 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L2-FCU-15 40LM090 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L2-FCU-16 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-17 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-18 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L2-FCU-19 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-1 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-2 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-3 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-4 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-5 42CET005 4.3 190 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4a-L3-FCU-6 42CET010 7.9 371 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4a-L3-FCU-7 42CET010 7.9 380 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4a-L3-FCU-8 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-9 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-10 42CET004 4.0 141 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-11 42CET008 7.3 310 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4a-L3-FCU-12 40LM050 14.2 428 0.5 0.55 1" 1" 3/4" 0.83 680 1000 480 70
B4a-L3-FCU-13 40LM060 18.4 677 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4a-L3-FCU-14 40LM090 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L3-FCU-15 40LM090 29.1 949 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4a-L3-FCU-16 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-17 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-18 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4a-L3-FCU-19 42CET004 4.0 152 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B4b-L1-FCU-1 40LM090 29.1 978 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4b-L1-FCU-2 40LM060 18.4 590 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L1-FCU-3 40LM090 29.1 1,140 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4b-L1-FCU-4 40LM060 18.4 873 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-1 42CET008 7.3 377 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L2-FCU-2 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-3 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-4 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-5 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L2-FCU-6 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4b-L2-FCU-7 42CET010 7.9 451 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4b-L2-FCU-8 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-9 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-10 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L2-FCU-11 42CET008 7.3 336 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L2-FCU-12 40LM060 18.4 780 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-13 40LM060 18.4 461 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L2-FCU-14 40LM070 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4b-L2-FCU-15 40LM070 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4b-L3-FCU-1 42CET008 7.3 377 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 410 557 242 41
B4b-L3-FCU-2 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-3 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-4 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-5 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-6 42CET005 4.3 212 0.015 70w 3/4"FPT 3/4"FPT 3/4"MPT 0.19 970 557 242 25.6
B4b-L3-FCU-7 42CET010 7.9 451 0.015 70wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.34 1530 557 242 45
B4b-L3-FCU-8 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-9 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-10 42CET003 3.1 137 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4b-L3-FCU-11 42CET008 7.3 336 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4b-L3-FCU-12 40LM060 18.4 780 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L3-FCU-13 40LM060 18.4 461 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4b-L3-FCU-14 40LM070 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4b-L3-FCU-15 40LM070 21.6 949 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B4c-L1-FCU-1 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-2 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-3 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-4 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-5 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-6 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-7 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-8 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-9 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-10 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-11 42CET008 7.3 800 0.015 55wx3 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-12 42CET008 7.3 800 0.015 55wx4 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-13 42CET008 7.3 800 0.015 55wx5 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L1-FCU-14 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-15 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-16 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-17 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-18 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L1-FCU-19 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-20 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-21 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4c-L1-FCU-22 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-23 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-24 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-25 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-26 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L1-FCU-27 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-28 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-29 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L1-FCU-30 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-1 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-2 42CET008 7.3 800 0.015 55wx3 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-3 42CET008 7.3 800 0.015 55wx4 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-4 42CET008 7.3 800 0.015 55wx5 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-5 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-6 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-7 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-8 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-9 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-10 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-11 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-12 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-13 42CET008 7.3 800 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B4c-L2-FCU-14 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
B4c-L2-FCU-15 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-16 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-17 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
B4c-L2-FCU-18 42CET003 3.1 300 0.015 32w 3/4"FPT 3/4"FPT 3/4"MPT 0.13 770 557 242 21.5
18.05NP
B4c-L2-FCU-19 40LM120 35.2 3,475 0.7 1.83 25.4 0.43 0.43 680 1600 480 120
T (MPT)
B4c-L2-FCU-20 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-21 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-22 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-23 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-24 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-25 40LM090 29.1 2,712 0.6 1.43 1" 1" 3/4" 0.43 680 1200 480 100
B4c-L2-FCU-26 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-27 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-28 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B4c-L2-FCU-29 40LM060 18.4 1,758 0.5 0.82 1" 1" 3/4" 1.1 680 1000 480 72
B7-L2-FCU-1 40LM070 21.6 923 0.6 0.9 1" 1" 3/4" 0.86 680 1200 480 95
B7-L2-FCU-2 42CET012 9.8 486 0.015 73wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.42 1770 557 242 51
B7-L2-FCU-3 42CET004 4.0 179 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
B7-L2-FCU-4 40LM040 11.6 603 0.4 0.57 1" 1" 3/4" 0.65 680 1000 480 68
B8-L1-FCU-1 42CET008 7.3 359 0.015 55wx2 3/4"FPT 3/4"FPT 3/4"MPT 0.31 1410 557 242 41
B9-L1-FCU-1 42CET006 4.8 256 0.015 72w 3/4"FPT 3/4"FPT 3/4"MPT 0.2 1170 557 242 30
B9-L1-FCU-2 42CET004 4.0 172 0.015 45w 3/4"FPT 3/4"FPT 3/4"MPT 0.17 890 557 242 25
Fan
Total
Total Fan Fluid
Cooling Airflow Water Water Drain Length Width Height Weight
FCU Marking Model Static Motor Flow
Cap (l/s) Inlet Outlet Pipe (mm) (mm) (mm) (Kg)
(Inch (kW) Rate, L/s
(kW)
w.g)
Block 20 Kafeteria
50.8 50.8 3/4"
B20-FCU-1 40LM200 58.3 7,203 0.8 3 2.25 784 1651 1541 230
MPT MPT MPT
50.8 50.8 3/4"
B20-FCU-2 40LM200 58.3 7,203 0.8 3 2.25 784 1651 1541 230
MPT MPT MPT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION, SARAWAK
Block 15 Surau
B15-L1-A/C-1 WALL MOUNT 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B15-L1-A/C-2 WALL MOUNT 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
Block 16 CITU
B16-L1-A/C-1 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-2 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-3 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L1-A/C-4 CASSETTE 38FN033/42TNC033 9.7 971 *3/8 *3/4 32mm
B16-L1-A/C-5 CEILING 38CSR018/42XQ025 6.4 780 *1/4 *1/2 21mm
B16-L1-A/C-6 WALL MOUNT 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B16-L1-A/C-7 WALL MOUNT 38KCV225/42KCV225 7.3 712 *3/8 *5/8 15.7mm
B16-L1-A/C-8 WALL MOUNT 38KCV209/42KCV209 2.6 295 *1/4 *3/8 15.7mm
B16-L2-A/C-1 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-2 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-3 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-4 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-5 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B16-L2-A/C-6 WALL MOUNT 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B16-L2-A/C-7 WALL MOUNT 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
Block 17 Rumah Tetamu
B17-L1-A/C-1 WALL MOUNT 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B17-L1-A/C-2 WALL MOUNT 38KCV212/42KCV212 3.5 360 *1/4 *1/2 15.7mm
B17-L1-A/C-3 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-1 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-2 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
B17-L2-A/C-3 WALL MOUNT 38KCV218/42KCV218 5.3 480 *1/4 *1/2 15.7mm
Pipe Size
A/C Split Unit Tag No. Type Model Cooling Capacity (kW) CFM
Liquid Gas Drain Pipe
4.2
SPARE PARTS
38KCD209
1 Rear net 1
2 Condenser assembly 1
3 Valve plate 1
14 Asynchronous motor 1
18 Capacitor clip 1
19 Capacitor of compressor 1
25 Compressor 1
38KCD212
序号 零部件名称 数量 备注
2 Condenser assembly 1
3 Valve plate 1
7 Water collector 1
14 Asynchronous motor 1
18 Capacitor clip 1
19 Capacitor of compressor 1
21 Supporting board 1
25 Compressor 1
42KCD212
1 Panel assembly 1
2 Air filter 2
9 Evaporator assembly 1
11 Asynchronous motor 1
12 Bearing holder 1
13 Bearing base 1
15 Horizontal louver 1
19.7 Transformer 1
21 Remote Controller 1
23 Drain joint 1
1 Panel assembly 1
2 Air filter 2
6 Drain hose 1
9 Evaporator assembly 1
11 Asynchronous motor 1
12 Bearing holder 1
13 Bearing base 1
15 Horizontal louver 1
16 Chassis assembly 1
19.7 Transformer 1
21 Remote Controller 1
22 Seal 1
23 Drain joint 1
INTRODUCTION
This catalogue presents the most commonly used replacement parts for the standard
42XQ (Wireless remote control) / 42XQA (Wired remote control)
Underceiling/Console Fan Coil Unit and is not applicable to special units.
The illustration are for reference only and the actual parts for a particular unit may
look different from that shown in the illustrations.
ORDERING INSTRUCTIONS
A. All orders and inquiries should include the complete model and serial number
of the unit on which the parts are to be used, and the part number and
description of each part.
B. Dealers should forward orders to their Carrier distributor.
C. Distributor should forward orders to:
GENERAL NOTES
1. Casing parts and panels are not normally stocked, but are available upon
request while in production. Requests for casing parts and panels for units
no longer in production must be cleared through Carrier International Sdn Bhd
for availability prior to submitting an order.
Certain parts are omitted in the interest of simplicity as orders for them are
infrequent that a simple description of parts, plus the model and serial
number of the unit will be acceptable.
2. The replacement parts listed in this catalogue are "Carrier Specified Parts"
and as a result of "standardization", may not be identical to the original part
furnished on the equipment.
SUPERCEDES
FORM: 42XQ-1-SPC FORM: 42XQ-2-SPC
DATE: 18 Aug 2006 DATE: 03 Mar 2009
PAGE: 1 of 5 PAGE : 1 of 5
Carrier
International
42XQ/XQA
SPECIFIED 020 to 060 (50Hz)
PARTS Sdn Bhd (3385-T) ---71125 SERIES
SUPERCEDES
FORM: 42XQ-1-SPC FORM: 42XQ-2-SPC
DATE: 18 Aug 2006 DATE: 03 Mar 2009
PAGE: 2 of 5 PAGE : 2 of 5
Carrier
International
42XQ/XQA
SPECIFIED 020 to 060 (50Hz)
Sdn Bhd (3385-T)
PARTS ---71125 SERIES
42XQ/XQA
Item Part Name Part No. 020 025 030 040 050 060
CASING GROUP - SHEET METAL PARTS
1 Fan Deck 38801392 1 1
38801394 1 1
38801395 1 1
2 Mounting Bracket 28801108 2 2 2 2 2 2
3 Panel Front 38801385 1 1
38801386 1 1
38801387 1 1
4 Panel Back 38801388 1 1
38801390 1 1
38801391 1 1
5 Structural Union 38801400 1 1 1 1 2 2
CASING GROUP - PLASTIC PARTS & FORM
6 Air Intake - Small 13704287 2 2 1 1
- Large 13704288 2 2 2 2
7 Air Filter - Small 13801115 2 2 1 1
- Large 13801116 2 2 2 2
8 Coil Insulation Right EPS 46618181 1 1 1 1 1 1
9 Coil Insulation Left EPS 46618190 1 1 1 1 1 1
10 Drain Hose 43170000 1 1 1 1 1 1
11 Drain Pan 06701074 1 1
06701075 1 1
06701076 1 1
12 End Cap Right 13704285 1 1 1 1 1 1
13 End Cap left 13704286 1 1 1 1 1 1
14 Horizontal Louver 09305061 1 1
09305062 1 1
15 Horizontal Louver Right 09305063 1 1
16 Horizontal Louver Left 09305064 1 1
17 Left Internal Side Assy 05859238 1 1 1 1 1 1
18 Right Internal Side Assy 05859239 1 1 1 1 1 1
19 Upper Closure Assy. 05821148 1 1
05821147 1 1
05821146 1 1
SUPERCEDES
FORM: 42XQ-1-SPC FORM: 42XQ-2-SPC
DATE: 18 Aug 2006 DATE: 03 Mar 2009
PAGE: 3 of 5 PAGE : 3 of 5
Carrier
International
42XQ/XQA
SPECIFIED 020 to 060 (50Hz)
Sdn Bhd (3385-T)
PARTS ---71125 SERIES
SPARE PARTS LIST (cont')
42XQ/XQA
Item Part Name Part No. 020 025 030 040 050 060
BLOWER WHEEL AND MOTOR GROUP
20 Blower Wheel 42819023 2 2 3 3 4 4
21 Fan Housing Top 08401052 2 2 3 3 4 4
22 Fan Housing Bottom 08401053 2 2 3 3 4 4
23 Motor HC020045W9550-25 1
HC020068W9650-25 1
HC020076W9850-25 1
HC020082W9950-25 1
HC020075W0250A25 1
HC020104W0350A25 1
24 Capacitor HC91CA030D006-25 1
HC91CA035D007-25 1
HC91CA040D008-25 1 1 1
HC91CA050D009-25 1
25 Shaft 43125002 1 1
26 Shaft (Left) 43125001 1 1
27 Shaft (Right) 43125000 1 1
28 Coupling 05801028 1 1 2 2
29 Bearing Assy. 05821132 (Inc item 30 to 32) 1 1 2 2
30 Bearing 05801029 1 1 2 2
31 Bearing Bracket 38801397 1 1 2 2
32 Bearing Housing 38801398 1 1 2 2
33 Motor Fastener 33702005 2 2 2 2 2 2
34 Motor Bracket 38801396 1 1 1 1 1 1
COIL AND TUBING GROUP
35 Assy, Complete Coil 42XQA420-007 1
(Inclusive item 36 to 41)
42XQA420-008 1
(Inclusive item 36 to 41)
42XQA420-009 1
(Inclusive item 36 to 38 & 42 to 44)
42XQA420-010 1
(Inclusive item 36 to 38 & 42 to 47)
42XQA420-011 1
(Inclusive item 36 to 38 & 42 to 47)
42XQA420-012 1
(Inclusive item 36 to 38 & 42 to 47)
36 Nut Flare 3/8" DD02CA101 1 1 1 2
37 Coupling 3/8" DD08DA101 1 1 1 1
38 Cap, Flare Seal 3/8" DD21FA101 1 1 1 1
39 Nut Flare 5/8" DD02CA301 1 1 1 1
40 Coupling 5/8" DE08DA301 1 1 1 1
41 Cap, Flare Seal 5/8" DD21FA301 1 1 1 1
42 Nut Flare 3/4" DD02CA401 1 1
43 Coupling 3/4" DE08DA401 1 1
44 Cap, Flare Seal 3/4" DD21FA401 1 1
45 Body, Coupling EA52PK001 1 1 1
46 Cap EA52PL001-A---25 1 1 1
47 Accurator EA52PJ076---A-25 1
EA52PJ080---A-25 1
EA52PJ090---A-25 1
SUPERCEDES
FORM: 42XQ-1-SPC FORM: 42XQ-2-SPC
DATE: 18 Aug 2006 DATE: 03 Mar 2009
PAGE: 4 of 5 PAGE : 4 of 5
Carrier
International
42XQ/XQA
SPECIFIED 020 to 060 (50Hz)
Sdn Bhd (3385-T)
PARTS ---71125 SERIES
42XQ/XQA
Item Part Name Part No. 020 025 030 040 050 060
CONTROL GROUP
48 Receiver 17701061 1 1 1 1 1 1
49 Receiver Label 11702388 1 1 1 1 1 1
52 Control Panel Assy. 42XQA440-008 1 1 1 1 1 1
(42XQ - wireless) (Inclusive item 54 to 61)
53 Control Panel Assy. 42XQA440-010 1 1 1 1 1 1
(42XQA - wired) (Inclusive item 54 to 61)
54 Control Panel Base 38801380 1 1 1 1 1 1
55 Control Panel Cover 42201070 1 1 1 1 1 1
56 PCB Assy with Harness HK42ARXQ-003A-25 1 1 1 1 1 1
(42XQ - wireless)
PCB Assy with Harness HK42AWXQA004A-25 1 1 1 1 1 1
(42XQA - wired)
- Main control unit (IR cool) 42XQA440-012 1 1 1 1 1 1
with 6+3 core cable
- LED display receiver board 42XQA440-013 1 1 1 1 1 1
- Receiver + LED display cable 42XQA440-014 1 1 1 1 1 1
(960mm)
- Room air sensor (500mm) 42XQA440-015 1 1 1 1 1 1
- Freeze up sensor (500mm) 42XQA440-016 1 1 1 1 1 1
- IR remote controller (wireless) 42XQA440-017 1 1 1 1 1 1
- Wired remote controller 42XQA440-018 1 1 1 1 1 1
57 Transformer 42XQA440-009 1 1 1 1 1 1
58 Terminal Block 42731210 1 1 1 1 1 1
59 Terminal Block Cover 42XQA504-001 1 1 1 1 1 1
60 Wire for Control Box 42XQA440-007 1 1 1 1 1 1
61 Stepper Motor 25904100 1 1 1 1 1 1
62 Stepper Motor Joint 38801381 1 1 1 1 1 1
SUPERCEDES
FORM: 42XQ-1-SPC FORM: 42XQ-2-SPC
DATE: 18 Aug 2006 DATE: 03 Mar 2009
PAGE: 5 of 5 PAGE : 5 of 5
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
5.0
SERVICE & MAINTENANCE
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
5.1
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE FOR AIR CONDITIONING AND VENTILATION SYSTEMS (ACMV)
ITEM TASK DESCRIPTION FREQUENCY M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12
4 VENTILATION FAN
5 CHILLER
5.2
SERVICE REPORT AND RECORDS
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
5.3
BREAKDOWN & MAINTENANCE CALL
Contact Information
6.0
MANUFACTURER LITERATURE & CATALOGUES
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
6.1
MANUFACTURER LITERATURE & CATALOGUES:
CHILLER PLANT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
6.2
MANUFACTURER LITERATURE & CATALOGUES:
AIR HANDLING UNIT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
6.3
MANUFACTURER LITERATURE & CATALOGUES:
FAN COIL UNIT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
6.4
MANUFACTURER LITERATURE & CATALOGUES:
AIR-COOL SPLIT UNIT
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
6.5
MANUFACTURER LITERATURE & CATALOGUES:
COOLING TOWER
SERIES COOLING TOWER
TX-S MULTI-CELL 100-2000 HRT COOLING CAPACITY
Modular Design Crossflow Type
LOW NOISE • SUPER LOW NOISE • ENERGY SAVING SUPER LOW NOISE
TX-S Series is an induced draft cross-flow, film
filled, FRP multi-cell rectangular cooling
tower designed for the equipment cooling,
industrial process cooling and air
conditioning applications.
• Energy Saving
The low speed, high efficiency fan and low
pressure drop fill design optimize the energy
consumption. :: Fuji Electric, Kulim, 6000HRT
• Low Noise level
The noise level is lowered by the specifically
designed low noise fan.
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated
Output Rated Current Power Diameter Fan No of Drive
TXS - 1 L W H h kW (A 50/60Hz) Type Source (mm) Speed blades System
100-1L 3170 1680 2350 750 2.2 4.66 / 4.17 1400 450 4
100-1S 3170 1680 2350 750 2.2 4.66 / 4.17 1400 400 4
100-1E 3170 1680 2750 750 1.5 3.35 / 3.06 1400 397 4
125-1L 3370 1880 2350 750 3.7 7.35 / 6.95 1600 425 6
125-1S 3370 1880 2350 750 3.7 7.35 / 6.95 1600 380 4
TEFC, outdoor, 3 phase, induction motor, 4 pole
125-1E 3370 1880 2750 750 2.2 4.66 / 4.17 1600 360 6
3ph / 380V / 50Hz or 3ph / 415V / 50Hz
150-1L 3370 1880 2750 750 3.7 7.35 / 6.95 1600 425 6
150-1S 3370 1880 2750 750 3.7 7.35 / 6.95 1600 380 4
150-1E 3570 2080 2750 750 2.2 4.66 / 4.17 1830 360 6
175-1L 3370 1880 2750 750 5.5 11.0 / 9.93 1600 475 6
V Belt and Pulley
175-1S 3370 1880 2750 750 5.5 11.0 / 9.93 1600 430 4
175-1E 3770 2280 2750 750 3.7 7.35 / 6.95 2000 320 6
200-1L 3570 2080 2750 750 5.5 11.0 / 9.93 1830 450 5
200-1S 3570 2080 2750 750 5.5 11.0 / 9.93 1830 355 4
225-1L 3770 2280 2750 750 5.5 11.0 / 9.93 2000 450 6
225-1S 3770 2280 2750 750 5.5 11.0 / 9.93 2000 315 4
250-1L 3770 2280 2750 750 7.5 13.9 / 12.44 2000 450 6
250-1S 3770 2280 2750 750 7.5 13.9 / 12.44 2000 345 4
300-1L 3770 2280 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 450 6
300-1S 3770 2280 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 380 4
350-1L 4770 3030 3400 1000 11.0 20.1 / 18.56 2135 406 4
400-1L 4770 3030 3400 1000 15.0 26.8 / 24.05 2135 428 4
450-1L 5170 3430 3400 1000 11.0 20.1 / 18.56 2745 344 5
500-1L 5170 3430 3400 1000 15.0 26.8 / 24.05 2745 345 5
* We reserve the right to change data and specification without prior notice.
Outline And Foundation Drawing (Single Cell)
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
FOUNDATION DIMENSION PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
External Internal Water Auto & Dry Oper.
TXS - 1 B C D E1 E2 F G J Piping Piping Outlet Overflow Drain Manual Weight Weight
100-1L 1580 3050 1680 1250 900 1135 840 - 100 x 2 100 x 1 100 x 1 50 x 1 50 x 1 25 x 1 790 1880
100-1S 1580 3050 1680 1250 900 1135 840 - 100 x 2 100 x 1 100 x 1 50 x 1 50 x 1 25 x 1 790 1880
100-1E 1580 3050 1680 1250 900 1135 840 - 100 x 2 100 x 1 100 x 1 50 x 1 50 x 1 25 x 1 900 1970
125-1L 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 900 2110
125-1S 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 900 2110
125-1E 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 1010 2210
150-1L 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 980 2370
150-1S 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 980 2370
150-1E 1980 3450 2080 1450 1000 1335 1040 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 1010 2490
175-1L 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 990 2500
175-1S 1780 3250 1880 1450 900 1235 940 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 990 2500
175-1E 2180 3650 2280 1650 1000 1435 1140 - 100 x 2 125 x 1 125 x 1 50 x 1 50 x 1 25 x 1 1220 2790
200-1L 1980 3450 2080 1450 1000 1335 1040 - 100 x 2 125 x 1 150 x 1 50 x 1 50 x 1 25 x 1 1113 2880
200-1S 1980 3450 2080 1450 1000 1335 1040 - 100 x 2 125 x 1 150 x 1 50 x 1 50 x 1 25 x 1 1113 2880
225-1L 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 150 x 1 200 x 1 50 x 1 50 x 1 50 x 1 1180 3180
225-1S 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 150 x 1 200 x 1 50 x 1 50 x 1 50 x 1 1180 3180
250-1L 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 150 x 1 200 x 1 50 x 1 50 x 1 50 x 1 1190 3200
250-1S 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 150 x 1 200 x 1 50 x 1 50 x 1 50 x 1 1190 3200
300-1L 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 200 x 1 250 x 1 50 x 1 50 x 1 50 x 1 1785 3900
300-1S 2180 3650 2280 1650 1000 1435 1140 - 125 x 2 200 x 1 250 x 1 50 x 1 50 x 1 50 x 1 1785 3900
350-1L 2930 4650 3030 2090 1280 1790 1515 - 150 x 2 200 x 1 250 x 1 80 x 1 50 x 1 50 x 1 2150 5350
400-1L 2930 4650 3030 2090 1280 1790 1515 - 150 x 2 200 x 1 250 x 1 80 x 1 50 x 1 50 x 1 2280 5800
450-1L 3330 5050 3430 2490 1280 1990 1715 - 150 x 2 250 x 1 250 x 1 80 x 1 50 x 1 50 x 1 2970 6670
500-1L 3330 5050 3430 2490 1280 1990 1715 - 200 x 2 250 x 1 250 x 1 80 x 1 80 x 1 50 x 1 3130 7250
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Female Thread 4
Outline And Foundation Drawing (Two Cell)
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated
Rated Output Current Power Diameter Fan No of Drive
TXS - 2 L W H h kW (A 50/60Hz) Type Source (mm) Speed blades System
200-2L 3170 3360 2350 750 2.2 4.66 / 4.17 1400 450 4
200-2S 3170 3360 2350 750 2.2 4.66 / 4.17 1400 400 4
200-2E 3170 3360 2750 750 1.5 3.35 / 3.06 1400 397 4
250-2L 3370 3760 2350 750 3.7 7.35 / 6.95 1600 425 6
250-2S 3370 3760 2350 750 3.7 7.35 / 6.95 1600 380 4
TEFC, outdoor, 3 phase, induction motor, 4 pole
250-2E 3370 3760 2750 750 2.2 4.66 / 4.17 1600 360 6
3ph / 380V / 50Hz or 3ph / 415V / 50Hz
300-2L 3370 3760 2750 750 3.7 7.35 / 6.95 1600 425 6
300-2S 3370 3760 2750 750 3.7 7.35 / 6.95 1600 380 4
300-2E 3570 4160 2750 750 2.2 4.66 / 4.17 1830 360 6
350-2L 3370 3760 2750 750 5.5 11.0 / 9.93 1600 475 6
V Belt and Pulley
350-2S 3370 3760 2750 750 5.5 11.0 / 9.93 1600 430 4
350-2E 3770 4560 2750 750 3.7 7.35 / 6.95 2000 320 6
400-2L 3570 4160 2750 750 5.5 11.0 / 9.93 1830 450 5
400-2S 3570 4160 2750 750 5.5 11.0 / 9.93 1830 355 4
450-2L 3770 4560 2750 750 5.5 11.0 / 9.93 2000 450 6
450-2S 3770 4560 2750 750 5.5 11.0 / 9.93 2000 315 4
500-2L 3770 4560 2750 750 7.5 13.9 / 12.44 2000 450 6
500-2S 3770 4560 2750 750 7.5 13.9 / 12.44 2000 345 4
600-2L 3770 4560 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 450 6
600-2S 3770 4560 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 380 4
700-2L 4770 6060 3400 1000 11.0 20.1 / 18.56 2135 406 4
800-2L 4770 6060 3400 1000 15.0 26.8 / 24.05 2135 428 4
900-2L 5170 6860 3400 1000 11.0 20.1 / 18.56 2745 344 5
1000-2L 5170 6860 3400 1000 15.0 26.8 / 24.05 2745 345 5
* We reserve the right to change data and specification without prior notice.
5
Outline And Foundation Drawing (Two Cell)
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
FOUNDATION DIMENSION PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
External Internal Water Auto & Dry Oper.
TXS - 2 B C D E1 E2 F G J Piping Piping Outlet Overflow Drain Manual Weight Weight
200-2L 1580 3050 1680 1250 900 1135 840 1680 100 x 4 100 x 2 150 x 1 50 x 1 50 x 1 25 x 1 1580 3760
200-2S 1580 3050 1680 1250 900 1135 840 1680 100 x 4 100 x 2 150 x 1 50 x 1 50 x 1 25 x 1 1580 3760
200-2E 1580 3050 1680 1250 900 1135 840 1680 100 x 4 100 x 2 150 x 1 50 x 1 50 x 1 25 x 1 1800 3940
250-2L 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 200 x 1 50 x 1 50 x 1 50 x 1 1800 4220
250-2S 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 200 x 1 50 x 1 50 x 1 50 x 1 1800 4220
250-2E 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 200 x 1 50 x 1 50 x 1 50 x 1 2020 4420
300-2L 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 1960 4740
300-2S 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 1960 4740
300-2E 1980 3450 2080 1450 1000 1335 1040 2080 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2020 4980
350-2L 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 1980 5000
350-2S 1780 3250 1880 1450 900 1235 940 1880 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 1980 5000
350-2E 2180 3650 2280 1650 1000 1435 1140 2280 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2440 5580
400-2L 1980 3450 2080 1450 1000 1335 1040 2080 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2226 5760
400-2S 1980 3450 2080 1450 1000 1335 1040 2080 100 x 4 125 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2226 5760
450-2L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 150 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2360 6360
450-2S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 150 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2360 6360
500-2L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 150 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2380 6400
500-2S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 150 x 2 250 x 1 50 x 1 50 x 1 50 x 1 2380 6400
600-2L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 200 x 2 250 x 2 50 x 2 50 x 2 50 x 2 3570 7800
600-2S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 4 200 x 2 250 x 2 50 x 2 50 x 2 50 x 2 3570 7800
700-2L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 4 200 x 2 250 x 2 80 x 2 50 x 2 50 x 2 4300 10700
800-2L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 4 200 x 2 250 x 2 80 x 2 50 x 2 50 x 2 4560 11600
900-2L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 4 250 x 2 250 x 2 80 x 2 50 x 2 50 x 2 5940 13340
1000-2L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 4 250 x 2 250 x 2 80 x 2 80 x 2 50 x 2 6260 14500
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Female Thread 6
Outline And Foundation Drawing (Three Cell)
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated
Rated Output Current Power Diameter Fan No of Drive
TXS - 3 L W H h kW (A 50/60Hz) Type Source (mm) Speed blades System
300-3L 3170 5040 2350 750 2.2 4.66 / 4.17 1400 450 4
300-3S 3170 5040 2350 750 2.2 4.66 / 4.17 1400 400 4
300-3E 3170 5040 2750 750 1.5 3.35 / 3.06 1400 397 4
375-3L 3370 5640 2350 750 3.7 7.35 / 6.95 1600 425 6
375-3S 3370 5640 2350 750 3.7 7.35 / 6.95 1600 380 4
TEFC, outdoor, 3 phase, induction motor, 4 pole
375-3E 3370 5640 2750 750 2.2 4.66 / 4.17 1600 360 6
3ph / 380V / 50Hz or 3ph / 415V / 50Hz
450-3L 3370 5640 2750 750 3.7 7.35 / 6.95 1600 425 6
450-3S 3370 5640 2750 750 3.7 7.35 / 6.95 1600 380 4
450-3E 3570 6240 2750 750 2.2 4.66 / 4.17 1830 360 6
525-3L 3370 5640 2750 750 5.5 11.0 / 9.93 1600 475 6
V Belt and Pulley
525-3S 3370 5640 2750 750 5.5 11.0 / 9.93 1600 430 4
525-3E 3770 6840 2750 750 3.7 7.35 / 6.95 2000 320 6
600-3L 3570 6240 2750 750 5.5 11.0 / 9.93 1830 450 5
600-3S 3570 6240 2750 750 5.5 11.0 / 9.93 1830 355 4
700-3L 3770 6840 2750 750 7.5
5.5 11.0
13.9 / 9.93
/ 12.44 2000 450 6
700-3S 3770 6840 2750 750 5.5
7.5 11.0
13.9 / 9.93
/ 12.44 2000 315 4
750-3L 3770 6840 2750 750 7.5 13.9 / 12.44 2000 450 6
750-3S 3770 6840 2750 750 7.5 13.9 / 12.44 2000 345 4
900-3L 3770 6840 3460 750 7.5
11.0 20.1
13.9 / 18.56
/ 12.44 2000 450 6
900-3S 3770 6840 3460 750 7.5
11.0 20.1
13.9 / 18.56
/ 12.44 2000 380 4
1050-3L 4770 9090 3400 1000 11.0 20.1 / 18.56 2135 406 4
1200-3L 4770 9090 3400 1000 15.0 26.8 / 24.05 2135 428 4
1350-3L 5170 10290 3400 1000 11.0 20.1 / 18.56 2745 344 5
1500-3L 5170 10290 3400 1000 15.0 26.8 / 24.05 2745 345 5
* We reserve the right to change data and specification without prior notice.
7
Outline And Foundation Drawing (Three Cell)
TXS 900-3L
TXS 900-3S
TXS 1050-3L
TXS 1200-3L
TXS 1350-3L
TXS 1500-3L
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
FOUNDATION DIMENSION PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
External Internal Water Auto & Dry Oper.
TXS - 3 B C D E1 E2 F G J Piping Piping Outlet Overflow Drain Manual Weight Weight
300-3L 1580 3050 1680 1250 900 1135 840 1680 100 x 6 100 x 3 150 x 2 50 x 2 50 x 2 25 x 2 2370 5640
300-3S 1580 3050 1680 1250 900 1135 840 1680 100 x 6 100 x 3 150 x 2 50 x 2 50 x 2 25 x 2 2370 5640
300-3E 1580 3050 1680 1250 900 1135 840 1680 100 x 6 100 x 3 150 x 2 50 x 2 50 x 2 25 x 2 2700 5910
375-3L 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 150 x 2 50 x 2 50 x 2 25 x 2 2700 6330
375-3S 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 150 x 2 50 x 2 50 x 2 25 x 2 2700 6330
375-3E 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 150 x 2 50 x 2 50 x 2 25 x 2 3030 6630
450-3L 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 25 x 2 2940 7110
450-3S 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 25 x 2 2940 7110
450-3E 1980 3450 2080 1450 1000 1335 1040 2080 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 25 x 2 3030 7470
525-3L 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 50 x 2 2970 7500
525-3S 1780 3250 1880 1450 900 1235 940 1880 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 50 x 2 2970 7500
525-3E 2180 3650 2280 1650 1000 1435 1140 2280 100 x 6 125 x 3 200 x 2 50 x 2 50 x 2 50 x 2 3660 8370
600-3L 1980 3450 2080 1450 1000 1335 1040 2080 100 x 6 125 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3339 8640
600-3S 1980 3450 2080 1450 1000 1335 1040 2080 100 x 6 125 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3339 8640
700-3L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 150 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3540 9540
700-3S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 150 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3540 9540
750-3L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 150 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3570 9600
750-3S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 150 x 3 250 x 2 50 x 2 50 x 2 50 x 2 3570 9600
900-3L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 200 x 3 250 x 3 50 x 3 50 x 3 50 x 3 5355 11700
900-3S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 6 200 x 3 250 x 3 50 x 3 50 x 3 50 x 3 5355 11700
1050-3L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 6 200 x 3 250 x 3 80 x 3 50 x 3 50 x 3 6450 16050
1200-3L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 6 200 x 3 250 x 3 80 x 3 50 x 3 50 x 3 6840 17400
1350-3L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 6 250 x 3 250 x 3 80 x 3 50 x 3 50 x 3 8910 20010
1500-3L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 6 250 x 3 250 x 3 80 x 3 80 x 3 50 x 3 9390 21750
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Female Thread 8
Outline And Foundation Drawing (Four Cell)
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
OVERALL DIMENSION MOTOR AXIAL FLOW FAN
Model
Rated
Rated Output Current Power Diameter Fan No of Drive
TXS - 4 L W H h kW (A 50/60Hz) Type Source (mm) Speed blades System
400-4L 3170 6720 2350 750 2.2 4.66 / 4.17 1400 450 4
400-4S 3170 6720 2350 750 2.2 4.66 / 4.17 1400 400 4
400-4E 3170 6720 2750 750 1.5 3.35 / 3.06 1400 397 4
500-4L 3370 7520 2350 750 3.7 7.35 / 6.95 1600 425 6
500-4S 3370 7520 2350 750 3.7 7.35 / 6.95 1600 380 4
TEFC, outdoor, 3 phase, induction motor, 4 pole
500-4E 3370 7520 2750 750 2.2 4.66 / 4.17 1600 360 6
3ph / 380V / 50Hz or 3ph / 415V / 50Hz
600-4L 3370 7520 2750 750 3.7 7.35 / 6.95 1600 425 6
600-4S 3370 7520 2750 750 3.7 7.35 / 6.95 1600 380 4
600-4E 3570 8320 2750 750 2.2 4.66 / 4.17 1830 360 6
700-4L 3370 7520 2750 750 5.5 11.0 / 9.93 1600 475 6
V Belt and Pulley
700-4S 3370 7520 2750 750 5.5 11.0 / 9.93 1600 430 4
700-4E 3770 9120 2750 750 3.7 7.35 / 6.95 2000 320 6
800-4L 3570 8320 2750 750 5.5 11.0 / 9.93 1830 450 5
800-4S 3570 8320 2750 750 5.5 11.0 / 9.93 1830 355 4
900-4L 3770 9120 2750 750 5.5 11.0 / 9.93 2000 450 6
900-4S 3770 9120 2750 750 5.5 11.0 / 9.93 2000 315 4
1000-4L 3770 9120 2750 750 7.5 13.9 / 12.44 2000 450 6
1000-4S 3770 9120 2750 750 7.5 13.9 / 12.44 2000 345 4
1200-4L 3770 9120 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 450 6
1200-4S 3770 9120 3460 750 11.0
7.5 20.1
13.9 / 18.56
/ 12.44 2000 380 4
1400-4L 4770 12120 3400 1000 11.0 20.1 / 18.56 2135 406 4
1600-4L 4770 12120 3400 1000 15.0 26.8 / 24.05 2135 428 4
1800-4L 5170 13720 3400 1000 11.0 20.1 / 18.56 2745 344 5
2000-4L 5170 13720 3400 1000 15.0 26.8 / 24.05 2745 345 5
* We reserve the right to change data and specification without prior notice.
9
Outline And Foundation Drawing (Four Cell)
TXS 1200-4L
TXS 1200-4S
TXS 1400-4L
TXS 1600-4L
TXS 1800-4L
TXS 2000-4L
TX-S SERIES LOW NOISE, SUPER LOW NOISE & ENERGY SAVING SUPER LOW NOISE RANGE
Tower
FOUNDATION DIMENSION PIPING DATA PIPING SIZE WEIGHT (KG)
Model
Make Up
External Internal Water Auto & Dry Oper.
TXS - 4 B C D E1 E2 F G J Piping Piping Outlet Overflow Drain Manual Weight Weight
400-4L 1580 3050 1680 1250 900 1135 840 1680 100 x 8 100 x 4 150 x 2 50 x 2 50 x 2 25 x 2 3160 7520
400-4S 1580 3050 1680 1250 900 1135 840 1680 100 x 8 100 x 4 150 x 2 50 x 2 50 x 2 25 x 2 3160 7520
400-4E 1580 3050 1680 1250 900 1135 840 1680 100 x 8 100 x 4 150 x 2 50 x 2 50 x 2 25 x 2 3600 7880
500-4L 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 200 x 2 50 x 2 50 x 2 50 x 2 3600 8440
500-4S 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 200 x 2 50 x 2 50 x 2 50 x 2 3600 8440
500-4E 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 200 x 2 50 x 2 50 x 2 50 x 2 4040 8840
600-4L 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 3920 9480
600-4S 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 3920 9480
600-4E 1980 3450 2080 1450 1000 1335 1040 2080 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4040 9960
700-4L 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 3960 10000
700-4S 1780 3250 1880 1450 900 1235 940 1880 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 3960 10000
700-4E 2180 3650 2280 1650 1000 1435 1140 2280 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4880 11160
800-4L 1980 3450 2080 1450 1000 1335 1040 2080 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4452 11520
800-4S 1980 3450 2080 1450 1000 1335 1040 2080 100 x 8 125 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4452 11520
900-4L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 150 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4720 12720
900-4S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 150 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4720 12720
1000-4L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 150 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4760 12800
1000-4S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 150 x 4 250 x 2 50 x 2 50 x 2 50 x 2 4760 12800
1200-4L 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 200 x 4 250 x 4 50 x 4 50 x 4 50 x 4 7140 15600
1200-4S 2180 3650 2280 1650 1000 1435 1140 2280 125 x 8 200 x 4 250 x 4 50 x 4 50 x 4 50 x 4 7140 15600
1400-4L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 8 200 x 4 250 x 4 80 x 4 50 x 4 50 x 4 8600 21400
1600-4L 2930 4650 3030 2090 1280 1790 1515 3030 150 x 8 200 x 4 250 x 4 80 x 4 50 x 4 50 x 4 9120 23200
1800-4L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 8 250 x 4 250 x 4 80 x 4 50 x 4 50 x 4 11880 26680
2000-4L 3330 5050 3430 2490 1280 1990 1715 3430 200 x 8 250 x 4 250 x 4 80 x 4 80 x 4 50 x 4 12520 2900
* Note: 1.) For Internal Piping Detail, Please Contact Truwater's Engineer. 2.) Balancing Pipe Connection Is Available Upon Request.
3.) External Piping to Open End. Internal Piping & Water Outlet to JIS10K FF Flange. 4.) Overflow, Drain, Make Up Auto & Manual to BSP Female Thread 10
TX-S Series Quick Selection Table
The diagrams below show the common combinations of various cold water, hot water, wet bulb temperature.
However, if there is a difference in temperature combination, please contact the company for a selection
of the cooling tower by our computer software
Model Motor
TXS HRT kW m3/hr
11
SOUND LEVEL CHART (FROM 100~2000 TON)
The measuring point at 45 degrees is diagonally above the top edge of the fan stack, opposite of motor driver side. If
fan diameter is less than 1.5m, the measuring distance should be limited to 1.5m standard.
SOUND LEVEL dB(A) - SINGLE CELL (100~500 TON) SOUND LEVEL dB(A) - 2 CELLS (200~1000 TON)
Louver Panel Fan Louver Panel Fan
2m 10m 2m 10m 45 deg 2m 10m 2m 10m 45 deg
100-1L 63.5 55.0 57.5 53.0 68.0 200-2L 66.0 57.0 61.0 55.0 70.0
100-1S 58.5 51.0 55.0 49.5 66.0 200-2S 61.5 53.0 57.0 51.0 68.0
100-1E 56.0 49.0 53.0 46.0 63.0 200-2E 59.0 52.0 55.0 49.0 66.0
125-1L 65.0 57.0 61.0 54.5 70.0 250-2L 68.0 58.0 62.0 56.0 72.0
125-1S 60.5 52.5 57.0 51.0 68.0 250-2S 64.0 54.0 59.0 51.0 70.0
125-1E 57.0 50.0 54.0 47.0 65.0 250-2E 61.0 52.0 56.0 51.0 68.0
150-1L 66.0 57.0 62.0 54.5 70.0 300-2L 69.0 60.0 64.0 56.0 72.0
150-1S 60.5 52.5 57.0 50.5 68.0 300-2S 64.0 54.0 59.0 53.0 70.0
150-1E 59.0 51.0 56.0 49.0 65.0 300-2E 62.0 53.0 57.0 52.0 68.0
175-1L 67.0 58.0 63.0 56.0 71.5 350-2L 70.0 60.0 65.0 58.0 73.0
175-1S 62.0 53.0 58.5 52.0 69.0 350-2S 65.0 56.0 60.0 54.0 71.0
175-1E 61.0 52.0 58.0 51.0 68.0 350-2E 64.0 54.0 59.0 53.0 69.0
200-1L 67.0 58.0 62.0 55.5 71.0 400-2L 70.0 60.0 65.0 58.0 73.0
200-1S 62.0 53.0 58.0 52.0 69.0 400-2S 65.0 56.0 60.0 54.0 71.0
225-1L 67.0 58.0 62.0 54.0 71.0 450-2L 70.0 60.0 65.0 58.0 73.0
225-1S 63.0 54.0 57.5 52.0 69.0 450-2S 66.0 56.0 60.0 54.0 71.0
250-1L 68.0 59.0 62.5 56.5 72.0 500-2L 70.0 60.0 65.0 58.5 74.0
250-1S 63.0 54.0 60.0 53.5 70.0 500-2S 67.0 57.0 61.0 55.0 73.0
300-1L 68.0 59.0 64.0 57.0 72.0 600-2L 71.0 61.0 67.0 60.0 73.0
300-1S 65.0 56.0 60.0 54.0 71.0 600-2S 68.0 58.0 62.0 56.0 73.0
350-1L 69.0 60.0 65.0 58.0 73.0 700-2L 72.0 62.0 68.0 61.0 74.0
400-1L 71.0 62.0 67.0 59.0 73.5 800-2L 74.0 64.0 69.0 62.0 75.0
450-1L 69.0 60.0 65.0 58.0 73.0 900-2L 72.0 62.0 68.0 61.0 74.0
500-1L 71.0 62.0 67.0 59.0 73.5 1000-2L 74.0 62.0 69.0 62.0 75.0
SOUND LEVEL dB(A) - 3 CELLS (300~1500 TON) SOUND LEVEL dB(A) - 4 CELLS (400-2000 TON)
Louver Panel Fan Louver Panel Fan
2m 10m 2m 10m 45 deg 2m 10m 2m 10m 45 deg
300-3L 69.0 60.0 64.0 56.0 72.0 400-4L 70.0 61.0 65.0 58.0 73.0
300-3S 64.0 54.0 59.0 51.0 70.0 400-4S 65.0 56.0 60.0 54.0 71.0
300-3E 62.0 53.0 57.0 52.0 68.0 400-4E 63.0 54.0 58.0 53.0 69.0
375-3L 70.0 61.0 65.0 58.0 73.0 500-4L 70.0 61.0 65.0 58.0 73.0
375-3S 64.0 54.0 59.0 51.0 70.0 500-4S 65.0 56.0 60.0 54.0 71.0
375-3E 62.0 53.0 57.0 52.0 68.0 500-4E 63.0 54.0 58.0 53.0 69.0
450-3L 70.0 61.0 65.0 58.0 73.0 600-4L 71.0 62.0 66.0 59.0 73.5
450-3S 66.0 56.0 60.0 54.0 71.0 600-4S 67.0 57.0 61.0 55.0 73.0
450-3E 63.0 54.0 58.0 53.0 69.0 600-4E 65.0 55.0 60.0 54.0 71.0
525-3L 70.0 61.0 65.0 58.0 73.0 700-4L 71.0 62.0 66.0 59.0 73.5
525-3S 66.0 56.0 60.0 54.0 72.0 700-4S 67.0 57.0 61.0 55.0 73.0
525-3E 63.0 54.0 58.0 53.0 69.0 700-4E 65.0 55.0 60.0 54.0 71.0
600-3L 72.0 62.0 67.0 60.0 74.0 800-4L 72.0 62.0 66.0 59.0 74.0
600-3S 66.0 56.0 60.0 54.0 72.0 800-4S 68.0 58.0 62.0 56.0 73.0
700-3L 72.5 62.5 68.0 62.0 74.0 900-4L 72.0 62.0 67.0 60.0 75.0
700-3S 68.0 57.0 61.0 55.0 72.0 900-4S 69.0 59.0 66.0 59.0 73.0
750-3L 72.5 62.5 68.0 62.0 74.0 1000-4L 73.0 63.0 69.0 62.0 75.0
750-3S 68.0 57.0 61.0 55.0 72.0 1000-4S 71.0 61.0 67.0 60.0 74.0
900-3L 74.0 64.0 69.0 62.0 75.0 1200-4L 75.0 65.0 70.0 63.0 76.0
900-3S 71.0 61.0 67.0 60.0 73.0 1200-4S 73.0 63.0 69.0 62.0 74.0
1050-3L 75.0 65.0 70.0 63.0 76.0 1400-4L 76.0 67.0 72.0 64.0 77.0
1200-3L 76.0 67.0 72.0 64.0 78.0 1600-4L 77.0 69.0 73.0 66.0 79.0
1350-3L 75.0 65.0 70.0 63.0 76.0 1800-4L 76.0 67.0 72.0 64.0 77.0
1500-3L 76.0 67.0 72.0 64.0 78.0 2000-4L 77.0 69.0 73.0 66.0 79.0
12
RECOMMENDED UNIT LAYOUT
It is advisable to select and design the best layout or location to avoid air recirculation. Recirculation occurs when some of
the hot moist discharge air leaving the cooling tower flows back into the fresh air inlet.
The following guidelines will provide the best location or layout which will minimize recirculation, maximize fresh air flow and
allow adequate maintenance accessibility.
Ensure that the top of the cooling tower is higher than any adjacent walls, buildings or other structures.
Figure 1(a) and 1(b) are examples of incorrect installation. These conditions can be corrected by elevating the unit on
structural steel/concrete plinths so that the top is higher that the wall as shown in Figure 1(c).
INCORRECT : Wind effect with top of unit lower than top of wall CORRECT : Installation elevated so that top of unit is
higher than top of wall
13
B. MULTIPLE UNIT INSTALLATIONS
When more than one cooling tower is installed at the same TABLE 3
location, recirculation becomes a bigger problem.
Tower Model End Wall Minimum Dimension, mm
TXS Length, L mm D5 (End Wall Panel Side)
With the installations of two cooling towers, they should be
All models All sizes 1000
placed end to end with the narrows ends adjacent as
shown in Figure 3. Another method is to locate the units Tower Model Louver Width, Minimum Dimension, mm
TXS W mm D6 (Louver Side to Solid wall)
side-by-side with the longer sides parallel to each other as
shown in Figure 4. In either configuration, the distance 200-2L ~ 600-2L Below 4500 3500
between the units must provide adequate airflow as well
as room for piping to the unit and access for maintenance.
700-2L ~ 1000-2L Below 7000 4000
400-3E ~ 550-3E
600-3L ~ 700-3L
600-3S ~ 700-3S
14
TX-S SERIES CROSSFLOW COOLING TOWER SPECIFICATION
1.0 GENERAL 6.0 INFILL
The cooling tower shall be 6.1 Infill shall be Vacuum-formed
induced-draft, crossflow, rectangular, film-type, rigid, corrugated PVC sheets.
film filled, FRP Cooling Tower. Cooling The infill shall be bonded with specially
tower shall be Truwater TX-S Series or formulated glue in blocks. The infill
approved equivalent. modules shall be resistant to rot, fungi,
bacteria and organic/inorganic acids
and alkali as commonly found in
2.0 CAPACITY cooling towers. The design shall meet
Cooling Tower shall be capable of 0.02% drift loss of the circulation water
providing the thermal performance flow.
scheduled.
PVC Casing
7.0 HOT WATER DISTRIBUTION
3.0 PERFORMANCE WARRANTY SYSTEM
The cooling tower manufacturer shall The hot water distribution shall be of
guarantee that the tower supplied will open gravity type basin. It shall be
meet the specified performance made of FRP material. It shall be light
conditions when the tower is installed weight and non-corrosive to maintain
according to plans. stable water sprinkling effect.
5.2 The V-belts shall be of rubber with 9.0 ACCESS AND SAFETY
fabric impregnated able to withstand Ladder shall be provided for inspection
the adverse ambient conditions of 50°C & maintenance purposes. HDG steel
Mechanical Equipment
and 100% R.H. The pulleys shall be cast fan guard shall be provided over each
iron with the grooves of standard fan cylinder.
dimensions. The entire V-belt & pulley
set must be fully enclosed in a FRP
molded case to protect the v-belts from
in contact with the humid discharge air.
6.6
MANUFACTURER LITERATURE & CATALOGUES:
PUMP
D-Series
Design Featuresl
1'10 '130 180 650 850 11OO US.G.P,M Operating Temperatures
600 With standard packed gland - minus 10'C to 105"C.
500
Maximum with cooled stuffing box - 160 " C. With
mechanical seal - maximum depends upon seal fitted.
400
100
90 300
80
250
70
€oo 200 g
o F
u
s50 u
- 40
1so -
30 100
90
80
20 70
20 25 30 40 50 60 70 80 100 L/S
D-Series
180 240 350 500 650 9oO11oO 1750 2650 45OO US,G.PM
100
300
80
7o 250
60 200
'150
49
:30 100
;25
E soa
a,
<:::'
20 70:
U 60 $i
-.,15 so. '
40
10
:9 30,
, ,,' .8 25
, ,,7 .'
,.:,,:,,.6 20-, ,:
:..::,:...5
.,,,, .4
3':.:.4..:.::5::9.:7:8,,9:::1,fi:::::,:.15.:...?.c,..:25.3O:::40 50.60.,,]:30]'10{t 150 2O0 300 400
,11s,
',1:5:,,.,',24,,.25:39..,'r40r.'506017080 100,,.rr150 200250300:400.500.600,800:1000,.r.1500 mqn
Materialsl Megaflow Series
Standard Parts All Bronze
Casing No,8 Bronze
Casing Nuts Bronze
Casing Studs Stainless Steel
Casirtg.Wearing Rings No.5 Bronze .
45 60 90 120 150 180 240 300 450 600 900 1200 1500 1800 24oo 30oo 4000 o[ff/hl
9 12151A 24 3A 60 90 1io 50 r80 240 i00 i80 4?0 6b0 lbo 9b0td00r)00 .QIl/s]
Selection charts of Regent Megaflow'T'series pump (50H2)
Megaflow Series
Q IUS-ooml
l?000 15000 20000 '
Vertical lnstallation
Paft No. Paft Designation
116 Volute Casing
103
ffi 101
Cover
Foot
123 Pump Shaft
117 lmpeller
121 Bearing
102 Motot Stool
125 Bearing Housing
126 Bearing Cover
112 Spring
115 0-Ring
120 Radial Shaft Seal Ring
114 Shaft Seal Housing
107 Valve
1284 Gland Packing
131 Stufiing Box lnsert
127 Neck Ring
129 Lantern Ring
118 Casing Wear Ring
Vertical Split
119 Shaft Protecting Sleeve
Casing Pump 104 Spacer Sleeve
105 BEaring Bush
1'13 Washer
106 Flexible Tube
111 Nut
122 Circlip
Full Bronze Cast - Side Fire Pump - Bottom Fire Pump - Side
Suction Top discharge Suction Top discharge Suction Top discharge
Available From
R$encprtrrtps found since 7948
1-7 Redwood Drive
Dingley, Victoria 3172
Australia
Tel: +51 (0) 3 9551 5111
D i n f l o w
Bare
centrifugal
P u mshaft
p s
Bare
P u mshaft
ps
Dinflow
The Regent Dinflow is a single stage end
suction centrifugal pump. It provides high
performance at an economical cost and is
particularly suited to mechanical and fire
services as well as being suitable for use
in a variety of other applications.
Design Features:
150-260
32-200 50-160 65-200 40
40-200 80-200 100 200
10 -200 150-200
125-200 -260 30
8 50-160
32-160 65-160 80-160
6
40-160
20 Operating Temperatures
TOTAL HEAD
65 100
5 50-130 -130 -160
32-130
40-130 15 With standard packed gland - minus 10˚C
4
to 105˚C. Maximum with cooled stuffing
3 10
box - 160˚C. With mechanical seal -
2 3 4 5 6 8 10 20 30 40 50 60 80 100 150 200 300 450
maximum depends upon seal fitted.
FLOW RATE LITRES/SECOND
Operating Pressures
Maximum operating pressure 1600kPa.
Maximum test pressure up to 2100kPa.
(Maximum pressure will vary depending
on particular pump model - higher ratings
I.G.P.M.
available on application).
15 30 40 60 80 100 150 200 300 400 600 800 1200 1600 2200 3000 4000
160
100
40-320H 50-320H 65
-320H 80-320H
400 Maximum Speed
32-260
300 Maximum direct coupled speeds for
80 50-260
40-260 65-260 80-260 100-260 Dinflow pumps vary between 3600 RPM
60 200
50 32-200 and 1800 RPM, depending upon pump size.
40-200 50-200 65-200 150
40 80-200
100-200
50-160 125-200
30 32-160 40-160 100
METRES
65-160 80-160
Back Pull-Out Design
FEET
80
20 50 100-160 60
40-130
-130
65-130 50
The Dinflow pump is of “Back Pull-Out”
32-130
40 design, and when a suitable spacer
10
30 coupling is fitted to a direct coupled unit,
8
the casing and motor can remain in
6 20
TOTAL HEAD
5
position while all other pump parts can be
15
4
Refer to individual curves
for final selection
removed for simple and quick maintenance.
3 10
Casing ✔ ✔ ✔ ✔
Impeller ✔ ✔ ✔ ✔
Shaft 앶 앶 앶 ✔
Shaft Sleeve 앶 ✔ 앶 ✔
Wear Ring ✔ ✔ ✔ ✔
Applications:
* Airconditioning I.G.P.M.
* Heating and Ventilation 15 30 40 60 80 100 150 200 300 400 600 800 1200 1600 2200 3000 4000
160
* Refrigeration 400
* Fire Protection 100
300
* Plumbing 80
80-400
* Circulating 60
50
200
* Transfer 40 40-320
50-320
65
-320 80-320 100 150-320
150
-320 125-320
* Irrigation 30
50-260
100
METRES
32-260 40 65
* Drainage
FEET
-260 80-260 80
-260 100-260 125
20 -260
* Water Pressure Boosting 32-200 40 50
-200 65-200 60
-200 80-200 100-200 50
* Process Industry 50 40
40-160 -160 80
* Petroleum Products 10 32-160 65-160
-160
30
8 65
* General Industry 50 -130
-130
6 40-130 20
TOTAL HEAD
32-130
* Food and Drink Manufacture 5
15
* Water Treatment and Supply 4
Refer to individual curves
for final selection
* Cooling Towers 3 10
I.G.P.M.
15 30 40 60 80 100 150 200 300 400 600 800 1200 1600 2200 3000 4000
160
50-200
400
100
300
80 32-260 50
40-260 65-260 80-260 100-260
-260
60 200
50 32-200
40-200 65-200
80-200 100 150
40 50-160 -200
32-160
40-160 80-160
65-160
30 150 100
METRES
50-13 -400
50-130 0
FEET
125-260 40
10 1150 RPM
30
8
6 20
TOTAL HEAD
5 100-320
1150 RPM Refer to individual curves 15
4 for final selection
3 10
6.7
MANUFACTURER LITERATURE & CATALOGUES:
EXHAUST FAN
Wall Mounted Ventilating Fans
15AAQ1 15cm/6" Dimension
Excellent For Small Room G B
C
ØA
E sq.
C D
H F I 4 - Ø6 Hole
Dimensions (mm)
Model A B C D E F G H I
15AAQ1 155 240 195 254 170 75 55 54 52
30AQM8 30cm/12"
Suitable For General Indoor Ventilation
E
G sq.
F
C
D
40
17
10
H 90 I K
Specifications
Motor Motor W Motor Noise Nett
Motor
Model RPM CFM Level Weight
Rating Low High HP Type(dB) (kg)
20AQM8 1109 ~ 1301 318 14.9 ~ 18.3 0.02 37 2.30
240V 4 Pole
25AQM7 999 ~ 1221 530 50Hz 25.2 ~ 30.8 0.03 Condenser 39 2.60
30AQM8 925 ~ 1085 727 31.8 ~ 38.8 0.05 45 3.00
13
Ceiling Mounted Ventilating Fans
20CQT1 20cm/8" Dimension
Suitable For Home & Small Room A sq.
C
H D
B sq.
C
F dia.
E sq.
• Q-Blade design for perfect balance, Specifications
quiet operation Noise Nett
Model RPM CFM Motor Rating Motor W Motor Type
• High efficiency of air flow Level (dB) Weight (kg)
• Durable and long lasting operation 20CQT1 1207 265 220-240V 25.7 Condenser 41 1.80
50Hz
• Quiet and energy efficient
Dimensions (mm)
Model A B C D E F G H
20CQT1 315 305 286 128 260 223 200 18
Space
A F
Ø For
C B Locking
E H
12
AXIAL FAN SERIES
ADT O ADF O ADBO ARD
NICOTRAllGebhardt
NlcoTRAl\Gebh
1. AxialFanlntroduction
Gebhardt
Nicotra "'-"--"'
2. ADTSeries.",-",
3. A D FS e r i e s - , , - . - " I
4. ADTA Series t
- Air Performance
- SoundPowerLevel
5. -'
ADT,ADFGeneralDimension a
6. View
ADT,ADF ExPloded o
7. ADBSeries.--.-, o
8. --.
ADBGeneralDimensi.on. o
9. ADB Explo d.V,iew- o
10. A R DS e r i e s. - - " " I
--,
1 1 . ARDGeneralDimension I
12. ARD ExplodedView I
13. ProductsRange
14. -
Nomenclature
15. Appendix
NlCOTRAllGebhardt
lntroduction
The NicotraGebhardtaxialfan providewide rangeof air volumefrom 360 t3/hr to
216,000r3/hr, at staticpressureup to 10OOPa of completefan systemwith most
Remarkably
application.
diversified are the directresultof rigor-
highfan efficiencies
ouslydevelopedaerodynamicallyprofiled bladesandadvanced
impeller manufacturing
technique.
FEATURES
x l
'l ,
', 'i h ' ;
\
{
uh.,
\ \
. ' / .
1t \\ : ''-/'
F. r/
I\ 'l
I
\,
HighEfficiency
Blade
FullyAdjustable
Versatile
HighQualityMaterial
ComPonents
Interchangeable
ln Linel
. TheAxiallmpellerls Balanced G2.5
. Anti-static
GRN for Anti SparkApplic :
, T -
On BS7346part2#
. ThirdPartyCertification ForQmokeSpillAPP|ication
. SeriesADTAis AMCACertified
ForPe;formances
':,ji€ & $ounds
: j
NlCOTRAliGebhardt
Test Standard
to
The performances shownare for standardunits.Fansare testedin accordance
to
test resultsare corrected
Method1, BS 848 Part 1: 1980.Underthis standard,
standard of 1.2kglm3'
air densitY
dueto manufacturing
fan performance fallswith
variations
Anyvariationin individuar Perfor-
class B torerances of the Britishstandard.Fan soundlevelsare givenon
on in-ductmethodas
manceCurvestogetherwith OctaveBandspectrum,based
specifiedin BS 848 Parl2.
lmpeller
They are Glass Reinforced
Aerofoilbladesare availablein Threetypesof material.
Nylon(GRN),Aluminium GRN(ASrAr).
(AL)andAnti-static
GRN,GlassReinforcedNYlon
high temperaturecapability
GrassreinforcedNyron66 has greaterstrengthand for standard
heat).Higherspeedsare acceptable
(-40'Cto +150"Coi non-radiant
whenGRNbladesarefitted.i".ott"nded maximum Tip Speedfor GRNis
impeller
11Sm/sec.
AL
Aluminium,
in emergencysmokeand fume
Bladesare availablein AluminiumLM6.Provenfor use -40"c to
up to 400"c. rt is arso suitabrefor continuousoperation
extractapprications
+200"C.MaximumTipSpeedforALbladesislo0m/sec.
Anti-staticBlades
to provideanti-static properties The
are available.
GRN Bradesspeciailyformurated as "potentially
principle
application whichis categorised
forthesebladesis for installation
a
explosiveatmosphere" and wherethe riskof ignitionof gas or dustvapoursthrough
sparkincidentis a PossibilitY.
havea
Theseanti_static bradeswhichare madewith20% grassfilring(as standard)
percentage of carbonblackaddedto controlthe surfaceresistivity'
normalGRN
bladeshavea slightlylowertensilestrengththan the
The anti-static
however that
we are recommending
blades,thisshouldnotconcernmostapplications,
the maxcontinuous temperature
operating in limitedto -30degOto 110 degC'
NlGOTRAllcebhardt
Balancing
axialimpellers
All NicotraGebhardt to ISOStdNo 1940,Edi-
andfansarebalanced
Amplitude= 2'5 mm/s)in our
tion usingbalancinggradeof G2.5 (Displacement
factory.
HubSystem
6 hubssystems
bladesandtherearebasically
Ourrangeof axialfan is fullyadjustable
as shownbelow:
Hub Size Numberof Blades
110 5 Blades
160 5 & 10Blades
23O 3, 6 & 12 Blades
25O 3, 6 & 12 Blades
400 4 , 8 , 1 2& 1 6 B l a d e s
550 4,7 & 11Blades
for AxialFan
HubCombination
T h e c o mp l e teh u b syste mfo r i mpeller1400 and 1600 consistsof side plate m etal ,
c e n t e rh u b ,a l u m i n i u mb l a d e ,b l a d eh o l d e ra n d t a p e rl o c kb u s h .
O u r 2 5 0 a n d 4 0 0 h u b a re d e signedto be mountedwith taper - lockbush 25 17 of
4 2 m m , 48 mm,5 5 mm a n d 6 0 mm diameteras optionalfeatur e.
BladesDesign/TYPes
we havethe followingdesignof impellers:
Basically,
Casing
-
A l l s t a n da rd a xi a lfa n tu b e ca si ng' ssur facear e appliedwith paint RAL 7030 b y
p o w d e rc o a ti n g me th o d .C o a ti ngthicknessis 60pm'
T h u s ,b y th i s me th o d ,tu b e ca si ngsur faceappear edto be wr inkleand pr ovidebetter
a g a i n stch e mi ca al n d wear '
p r o c t e c ti o n
NICOTRA\\Gebhardt
Longcaseaxialcasingsare rolled.from 2.0 mm to 5'Omm mildsteel'The standard
{ootmountedsupportcan be provided
doubleflangedI Jractietmountingis provided,
Tube.uring comewitfrsianOard view port,and the accessdoor can be
as optional.
requestedas oPtion.
ElectricMotor
TEFC,foot mountedinsulationin
NicotraGebhardtuse standardthreephrasemotoll C|ass
insu|ation
1P55,
accordance EN ooog+or BS 4999,Enc|osure
withIECstandard
protectionclasses'two speedmotor(polesswitCh)
"F".Othermediumtemperatures,
and etc as oPtional.
ComPuterselection
model
softwareallowsyou to selectthe mostsuitable
fan selection
our user-friendly by the stateof art
dataand fan .u,ue wil| be generated
to yourneeds.Performance
software.
Trulyreversible
axialfan,everyotherblademustbe set in the oppositedirectionof
Fora trulyreversible
flow.The bladesmustbe the samehanding. The impacton performancein reverserota-
for up to maxpitchangleof 30 deg)'
(applicable
tionis approximately:
Airflow/ volume: -20%
Pressure reduction:-35%
Powerreduction: -30%
Contra-rotating
as optional'A two
Multi-stageaxial fans with contra-rotatingimpellerscan be supplied
the pressuredevel-
stage contra-rotatingassemblydevelopJapproximately2.5 times
fanandincreases
opiObya singlesta'ge soundlevelby8-10dB'
theoverall
N|COTRAllcebhardt
To selecta contra-rotating axial,dividethe staticpressureby 2.5 and selectAS
thoughit was a singlestageunit.The kW figureis for onestageonlyand shouldbe
multiplyby two to the system.
CasingOverviewDimension
0315-0560 0630-1
600(<FS200) 1120-1600(>FS200)
StandardArrangement
A = Fromthemotorto theimpeller
B = Fromtheimpeller
to themotor
AU= Fromthemotorto theimpeller,
up position.
NlCOTRAllGebhardt
ADT Series
APPLICATION
NicotraGebhardtADT are particularly suit-
of staleair,for general
ableforthe extraction
drying processand all those
ventilation,
applicationswhich require moving large
volumesof air.
CONSTRUCTION
The housingis madeof heavy-gauge mild
steel casing,seamlessdoubleflangesat
both end. Powder coated bake enamel
finishing(60 micron)or galvanizedsteel'
Highefficiency impellermadeof adjustable
pitchaerofoilblade;ALU type or GRN type'
Footmounting& Hot dip galvanized casing
as an oPtion.
is available
WORKING TEMPERATURE
- 4 0 ' Ct o 1 5 0 ' C: G R N
- 4 0 " Ct o 2 0 0 ' C: A L U
MOTOR
withtypeof "TotallyEnclosedFancooled'(TEFC),horizontalfootmounted
Three-phase
Cagelnduction
Squirrel Motor,featured systemwithClassB tem-
withclassF insulation
peraturerise (80"c).Voltagesupplyincludes400v/50H2,4O0Vl60Hz or 44OYl6OHz'
upon
Motorstandardsare comprywith lEc 60034or BS 4ggg.other requirements
demandbasis.
or steelflexible
Motorare wiredto an externalterminalboxwithcableandthroughPVC
Pleasereferto page17 Appendix
conduit. forwireconnectiondiagram'
NF T H EA I R
D I R E C T I OO
The standard to the motor(B),on demandthe fanscan be
air flowfromthe impeller
supplied withthe direction (A).
fromthe motorto the impeller
NlCOTRAIlGebhardt
ADI ADFGeneralDimension
ADT/FwithHanger
N x O
ADT/Fwith MountingFeet(optional)
ADT,ADF ExPlodedView
Part List, Specification,Arrangement
Part DescriPtion Specification
etc
1 Tube Casing Painted (RAL 7030), Hot Dipped, Stainless Steel'
Terminal Box PVC, Cast lron, etc
2
3 ViewPort Cover Depend on Vcasing material
4 Mouting Feet (OPtional) Depend on Vcasing material
5 Counter Flange (OPtional) Deoend on Vcasing material
6 Electrical Motor Soecification as Per requested
7 lmpeller ALU, GRN, GRN-antistatic
8 Fan Guard P a i n t e do r H o t D i P P e d
(OPTIONAL)
FLANGE
AXIALCOUNTER
MODEL @A 68 (PCD) @c D NxZ
315 3 15 355 395 40 BX 1 0
355 355 395 435 40 BX 1 0
400 400 440 480 40 1 2X 1 0
450 450 490 530 40 1 2X 1 0
500 500 540 580 40 12X10
560 560 605 660 40 1 2X 1 0
630 630 675 730 40 1 2X 1 0
710 710 755 810 40 18X12
800 800 845 900 40 1 Bx 1 2
900 900 945 1000 60 18X12
1000 1000 1045 11 0 0 60 24X12
1120 1120 1185 1250 60 24X12
1250 1250 1315 1380 60 24X12
1400 1400 1465 1530 60 32X14
1600 1600 1663 1730 60 32X14
NlCOTRAliGebhardt
ProductRange
Aerodynamic Performance
The Emergency withBS
Fumeand SmokeExtractFanrangeis testedin accordance
as a
undernormalambientconditions
848 Part1, andthe datashownis determined
standardbasisfor unitselection.
Pa
FanPerformanceCurves l n sw g
2000 80
60
400 - 1250@ 960 rpm 85848:ft'l:1980
TYPED lnstallation 0
1000 630-125O@72Orpm
800 3 0
600
20
400
u 1 0
) 08
3
u
2oo
06
I
< lnn 04
2 8 0 0,3
60
40
20
0 1 02 03 04 30 40 60 80 100m7s
VOLUIVlE {t3/mrn
025 0 5 6 8 12 16 20 80 I 20 160 (xl'ci00)
600
400
u 1 0
08
u
L 06
U
F
4
100
z 80 3
s 60
0 1 03 04 06 081 60 80'100m3/s
VOLUME
, ft3lmin
025 05 1 5 Z 6 8 12 16 20 80 t20 too lil(js[i
Dimensionsandperformance is
graphsdetailedin thisleafletareto be usedonlyas a guide.Certifiedinformation
our SalesOffice.Note:Dataabove1250mmshallbe providedon request.
on requestfrom
available
NlCOTRAilGebhardt
Nomenclature
in the
your requirements
when orderingNicotraGebhardtAxialfans,pleasespecify
sequenceto avoidconfusion'
followings
Data
1. FanTYPeand Performance
- FanTYPe: ADT,ADF,ADB or ARD
- CaPacitY
- StaticPressure
2. ElectricMotorDetails
50 Hz or 60 Hz type
- Power,mainsupply,voltage,frequency'
- MotorSPeed,PolaritY
(ClassF,ClassH, etc)
- Insulation
Material
3. lmPeller
- GlassReinforced GRN
NYlon,
- Aluminium A,L U
- AntiStaticGRN
No of Bladesand BladeT
(SamPle)
Description
I ALU- 18.5/4P
ADF1000/400/08c 120.0
ADT LongCaseDrive
1000 = 1000mm
FanDiameter
4007 H u bS i z e
8C BladetYPe"C",QtY= 3
20" BladeAngle20 Deg
ALU ALUMaterial
NlCOTRAllGebhardt
WiringDiagram
ForVarious
Application
LI L2
StarConnection L2r L22 L23
Star-Delta
Connection
n
Multi-speedmotoniin Dahlander
Connection(tappedwinding)
IU lw
t o.-
2U 2W
o +
LI L2
Low Speed
Multi-speedwith 2 separateWindingds
n
lu lv lw
t-H
9
012134567 7
61
012345689
969
!"#$%"&!
'"!($")*+
$,-./0+1.***"2./0++.*3
4$567$8999- : ! 7 % " - 7
;&",8999-
<!=::!!77%%""--:7!&
5KP60e6223F62435S
..1$&"d"::!T($ ;&",8<!=:!7%"-7
N7%"("(!:W6/
$,-.0BB+3**"2.0BB++
0123456F5602K8969
B31/$"6$($2 ;&",8:!7%"-<%":$=9""(!!-<%
+W$&($6c%$%6--&@,"$
$,-1013*"21013**
0123456X9P9H9Y9
A+///*Z%:WW$&0b:W$ ;&",8<!=:!7%"-($
4$66$<$,($%N7%-
$,-+303B3-"2+303B3*
0123456K8
6068969
;++*',,",5,,""(%( ;&",8<!=:!7%"-$6
7%"-,:","',,"%($,,&!Z&--+.
$,-3*0++B**"23*0++/3/
0123456HK0KIRa8969
#*
_$,,$6 ;&",8:!7%"=5U6&",-$7
U$($,̀(U67%$
$,-B10+++*"2B10*B/.
0123456R^I4L
#NBBQ]!7W$%W"&!%V6W%$ ;&",86",$6=:!7%"-:!-UV
T7A)M"%V"7$#U6$66M"%V
$,-*1301+1B"2*1301+1B
0123456F608GHI3JK58PFX8L0HYL
/ZU","[U&@U% ;&",8:!7%"=7&-$7-&\
[!7..)Q","/0.Z$@! (U67%",%$"
#"7UB )Z$@!
$,-.0B/1...B"2.0B/13..1
0123456P60RF624R510XC4Y61E239I4L
?**/#" V!V ;&",8&7W=:6:!&6-:!&
B03N!NUV6"9"(
NUV6"9"(!"()Q!&7W! )
$,-BB01B*+./B"2BB01B*+1
01234566R8456I16
4SI4L
TN"&@5$,,<$,()':7!%".B* ;&",8<!=:!7%"-:!&-"U
1Q$6:"!"(
$,-.03./11B"2.03./1+1
0123456C4160D10EF608GHI3JK58239I4L9
M."> ;&",86",$6=:!7%"7">-:!&
!!&.
!-/#"!( !"(
?$@ A67%:7
$,-+B0.*.3+*1"2+B0.*.3+1
012345610L16
51O64KI1P14KL
A*.*
!(" ;&",86",$6=:!7%"("-:!&
*)N$:7!%/3
$,-3*0*/+//."23*0*/+//1
?7@A61ABC
GHI
!"!#
$ %&'()*()"*+',
""*-.+././0.1(10 JK8LMNCK8MNO
2.**.(
3*4 54')1*#*
3((6(!
6"7((*4 54
0N8OPK?QLRMC?R8J
6!3800(4 546!3 SKOTCUR0VSRPWCK80MK8NWCUMRWNJ
900(76%**:!7
"*4 545"(+#;#7)
!*(3"!(6#<=>
89
012134567
DEDEFCC9CC
1234567839
29
!"#$"%$!%$
&$'%$(%)&%%*#+++
,'*'%"%%-
./$$&%%&01&%'&!
2""$"3453$$66*116789$+:
;0;-
&$""<2%$2%%
"'%!"#$"%$!%$-
""(%%)&"=
>%'&%&?;11&;@89-111&;@
%)'');A11B-
5'%<2"(8/&A11')?111&&
%$&-
CD/2!$$$')$2%%#
)%"''-
EFGHIJKLIMFGNOPJHMFGH
(%!%'3&;(2Q22R$R?2$3&?(2
$?2%%/=
STU
V
2W839 X23Y
W8Z
[3
W8Z
Q A11 A91
A11 9;1
R A11 ?111
R? A11 ?111
A11 ?111
? A11 ?111
0
123456785923
899859234
! "#$"$%& '($")*+,+-./
*$%#"$(&$0"1 2$3$("$"%#$4$10&2
5!$(&6!/7$%'((68$" $($(&5!#"$(&%/
9::;<=>?:@AB?:@?@:<>@BC>@A;:>
D(" "$($"%0"!0($(&5$"5! "$55('$(/
E!$FG,,0%+,,,H$"I% '%$'(050#$J+,#/
K=A>>
LDM$!% '++%$6I"$&("H1 2# "$($("1"/N0$5!
!$"H6#""H "("% $("#$$"$I!!!$($% $(LO
P,0,/
LDM$!%$6(""6( !$61 (""$(&QDR+S-,#$
&"T-/N&"(1%'$""(U0/
BC>@V;=>
O$&I(0$($"5!5L'$( ! "#$"I5!"H
& '($"WD("F$!$X6%)*+,+-./
M '6I"06$"5!5YHY+H7("7+'$(! "#$I"
$(%H#""(" "#$$"$I!!!$($% $(LO
P,0,/(%$(H6(1%"#$"$%& '($$(&/
<;V:
J (050"5!%$$(&0("HZ-G1(1 H0$(&%$$(
026# 6/
5 "H5!16H#$ 6"$$(&0$ 1H1$&
6#%$'% $(/
D$( 5(1%'$""(U0H#$(%%%$"0$(5
! 8$!0!%$(&%"/
D 5"$!"$'5655$$%"[+/.G
$& (! 8$!0!%$(&%"/
\>;B?]
E (5O ("L'$(0$(&#H"%&'H5I$&($(&1
1 $(&/D "("$501$"H62"( 5#$(($
$(&!%("0%%"H$($"$6("0$'011211H
(%$"1"($(^E$&/+_$(5(&I %""("$'
`abcde $"/
E (5'$(Y("70 "H$(&#H5I$&($(&1 1 $(&H
#$($!%H!0("$($"$(%$#12H#$& ($%%H
1"$"I5!^E$&/._/Y+'$(5(0H(6(! '$6I
""$'$"H$(&$(5"$(&I#1 1 $(&H2"( 5
#$($'("!0("$($"I$(%$#12H1"$"I
5!^E$&/0_/
7+'$(5( '#$"($1 $(&#$($'2$(&/
`abcdf 0
12345678
6 2 56
2 852
36 368 5 56
2
3672 342 8
42
6 3
8253
285762 432482 56852 3 8
4 56
2
2 5
8 32 742382 65
28
4 42232
4535
6 57
2 2345678 342 85!2
3522" 5 4238
63
2
2 53#2248 36 3 2
#3$5##
3
655
68" 36 %&
243567
52
&&&&
48 822 2 324
'(
2 82
25
6) *5 #
42
##
6
243567
655
68" 2 324372
243567
52 36 2 # 5724
368
2 52
52
6845
6 2485
68 335
3
2" 226
6724 28576
OPQRST
52 42+542#268 36 2 2385
#2
8 2
243567
52
2 742382
63562 56 2 2345678 2268
6 2
243567
655
68" 5 36 2 52426 4
# 2 %&
243567
52
2 2345678
2#82
28
34 4
# 2 324 ',52
5628
4
442 82)" 2 '-82 36 .35626362
.363
)
63568 5#
436 56
4#35
6
24567 4
24 5683
35
6" 82 36
#35626362
2 36 36 345
34
58 2345678
/01231245
OPQRSU
6253
247356
35678
345
8 28 36 56288 3
28 36 2
8
52
6 42+28
84213192:;<93=>3=?:@=<51925
A7655
6 4
22 2485
68 36 2 5
6 42+28" 5 56
2
628 #32
3
#565#"
24
4 5
24 4567 84528
6 2 272
2 56
2
628
(
2382"
63 2 #363424
4 82
25
6 36 235
8
B02:9<1=2303192
63634 368 342 8
52 5 2 83 452726
852
2 36 56
2 C2485
68 342 335
3
2 5
2524 DE
4 %, 4
35
6 8" 36 4
35
6 #8 2 4
24
82552 3
424567 5#2
2 2485
68 5 852 43#28 36 2 2385
462
5683
2# 56
62
2
4
452635
68 &F" G&F"
H&F 36 IJ&F 227#
62 % 2485
6 38
28 56 2 852
328 3 3
567 2 22 5 2 84
45262
&F" G&F
4 IJ&F 242 58 6
622
825 36
452635
6 26
424567 282 83634 368
K26 36 2485
68" 3
7 6
4#3
8
52 3882#
2
4 IJ&F
452635
6" 36 2 2385
427
3882#
2 5 3 52426
452635
6 56 LF
4 M&F 828
36
452635
6 #8 2 82552" 56823" 26
424567 368 52 5 3288
4528 5 #8 2
32
3
4567
2 84
452635
6"
52 4356
78
N24 3288
4528 #3 2 5683
2 56
2 83634
855
68" 526552
2248
4 6#248 (
2382"
2 2 235
8
6246567 23 345
34 3288
4
0
1234637839
3
4634
4934
364
48634
2344
23
4
6
236393!"# 34962
$%193&6
423'( 3493
$%%184
36)
93&6
4!
*2323+3634
49639244
2364+3!
, -3.
/"01223245#"678'9(/: ;<=>?@A>BCDECBF>BEGC>HIIF>JKL>MCDBENAF>OEPQ>IR>NDECAP@PENA
@AS>SD@EA>TUVW>EABP@UUCS>@B>BQNOA>EA>PQC>TEXPVDCY
0
12345367892
29
4
97
58
!"#$%&'!%(&)*#"(+!"%&*,!*'-!,-.(+*'%(%/#)0!+%1!-!!&,!1!,"#$!"#$%&'!(!*(*
$%,!2(+&*(%//%(#&(.!34562(+"!!&/!(%&,,0'(!,#0(/!(78+!*!(!*(*2!!'%!,#0(&(+!9'#(%
/%-#%(#.6&%''#,%&'!2(+(+!"#//#2&)*(%&,%,*:;<=>?@AABC)7>=D6E9F>?GH>BC)7H?'%&,
%7=A7="D%&,FIJGK?>BC)7LA'%&,%7H?7="D7
M%(&)*%!!"!!,(#(+!*(%&,%,%,!&*(.#">7=?N)O$H7
P.&%$'!**0!%&,#0(/!(%1!/#'(.6%**+#2&#&(+!*'%/!*-!/#2!%'+,%)%$6%!'%/'0/%(!,&
%''#,%&'!2(+(+!*%,*(%&,%,*60*&)(+!(#(%/#0(/!(%!%"#'%/'0/%(#&*7
QRSTUVUWU
X+!&# !%(&)&&*(%//%(#&(.!3562(+"!!&/!(%&,"!!#0(/!(6(+!%1%/%-/!*(%('!**0!#"(+!"%&6
6*/#2!(+%&2+!&(+!"%&*0*!,2(+,0'(!,#0(/!(6%&,'%&-!*%(*"%'(#/.'%/'0/%(!,*0-(%'(&)6
"I
#$(+!(#(%/ !**0!&(+!'%(%/#)0!6%&&'!%*!,,.&%$' !**0!6'%/'0/%(!,-.$0/(/.&)
'#&1!&(#&%/,.&%$'!**0!-.%"%'(#Y,*+#2&-!/#27
8+*,.&%$'!**0!&'!%*!! !*!&(*(+!!""!'(#"(+!%"/#2'#&(%'(#&#,0'!,-.(+!'0(@#""/%(!
%&,(+!%-*!&'!#"%�(/!(,0'(62+'+2#0/,%'(%*%,""0*!6%//#2&)%(/!%*(%(%/'#&1!*#&#"(+!
!Z'!**#",.&%$'!**0!&(#*(%('!**0!7
C%&!"#$%&'!*#'%/'0/%(!,*&#(;<['!&*!,7
\]
^
_`
abca
Rd
e#2!'01!**+#2&#&"%&!"#$%&'!,%)%$*%!$ !//!%-*#-!,#2!6X 7f!('%/*'%/!*(#(+!
)+(#"!%'+,%)%$*+#2(+!#2!'#&*0$ (#&#"(+!"%&-!%&)*"#!%'+"%&1!*#&6X-7
C%&*+%"(#2!6X 6*)1!&-.(+!%,,(#&#"$ !//!#2!%&,#2!0*!,-.(+!-!%&)*7
F&$#*('%*!*6-!%%&)#2!**$%//%&,#"(!&&!)/)-/!2+!&'#$ %!,(#$ !//!#2!6-0(-!'#$!*
!/%(1!/.$#!$ #(%&(2(+,!'!%*&)"%&*g!%&,*!!,6%&,$%.-!*)&"'%&(%((+!/#2!!&,#"(+!
*g!%&)!7
P1!/#**!*%!&#('%/'0/%(!,7
C%&$!'+%&'%/& 0(#2!*%"0&'(#&#""/#2%(!%&,*!!,6-0(,#!*&h('+%&)!-!(2!!&&*(%//%(#&
(.!*35B2(+"!!&/!(%&,"!!#0(/!(D%&,345B2(+"!!&/!(%&,,0'(!,#0(/!(D7
0
1223435647
899
99
9
!"#
$%&'()*+,
+
9
-
$99
9
9
.9
99
9
/
+/-
80
9
99
9/%1
-2
3
4
-
5
99
9
9
# "
+
,
+
9
96
#<; @#:;?7=:=>:=98
6
#
99
#
9
99
9
9
A
+
A+
+9
+
5
99
99
9
"
,
9-B
99
99
B!
-
C9
99
9
9
B#%B
+
9
96
0
123457289
99
!" !#$%"""!
!$&'(&)**+,-!!./01!""2!/)1 !
""2/
!3$4%$#"!"!5.!6*+60
$.!#&'(&!!)*6+,*/7$4 1&2 !#$%
89#:;.! ! /!!$! !/
<"&+$!4$%!.#! !34%14#1&22
%"5"!
2#!;
4#1&2=4$1&2+0*>6*1!2+66
52"#!;
4#1&2=4$1&2+0*>6*1!2+?
$!=!5$!"#"/
!#%%%5!# 9!! %"!
!5!"#%# #9.9%#$ !#%
$5"!%"/
!""5 !#$%.!#. !59
"!59!/
'%5@ !!%".!
%5@ "".9!$9#! !59.
9$$#A$!!@ /"
! !%59!595"!!"/
&A .5 #! !59 !.!!#
95!5!#".#9@ 9/
&."#!5!#@ 9#A5!59"9!5
##! # "!/
8".5!5!%.#! !595+.A#
$0!:/' "!"95#!#! !59"
%5/!#!9.5 ""9
"#15".".# 9!2.$5!#@ 9!#!
9 ##! 9"/
0
12345628935
25395
!!"#!$%&%%%!!!!
#%'
!$%!!%!!(!%)&!
!%%(!*%!)!%$*+("!!*!)'
,!%!!-!!$!!%!!&
&%%#&%!%#!!"!#%!'
,-%!+!!!%$*+!+%"%#
"&"+"!!%$#!%+!!#!(%
./012344!+"5!)'
!#+%!&%-+%"+&$+
+%"+"!!+!!%%#-"6$%'
,-%!$!!!!!!%%+%"+%%#7#!
+!!%#!&!%+!+!+
%%!%$8+#!&$$%%%!!%!"+!!!,*$!!!%%%&"+!
#"%##'+"%#!&%!%%!!+
-'
+!"9!+!!%!!!
$!!+"%!!#!!!*+!&"+!!!+"5!!
+!!#&%"+!%+!#!!!!'
:26935;9<
!-=>>+$+$%%&+
!!,?@,A>>*B4!&$!!!%%%$"#!./012344!
@%3'
C93
D9EF5
G<
0!HIJ%$?+!+(?%#)'J'!!!
!K&&L&L3&
3&$&%!"!,?@,
%'
!$"!!+
$!,?@,+"%!133,?@,+"%!A33&%#$!
!8+!!,?@,@!!M'
0
01234568609
3
59890
!""#$%&%'(")*'+,'-./!01%&0)%#2%!.34(#)*'+
5)&6"37"""38%9"(37:""7
;)</1!)=>>>6'1?!0%61!>>>6'1?!0%6?@A@%1&='1?!0%B!@6')!6@C
CADANGAN UNIVERSITI TEKNOLOGI MARA (UITM), KAMPUS MUKAH, DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK (O&M)
7.0
TEST CERTIFICATES
CADANGAN UNIVERSITI TEKNOLOGI MARA (UiTM) KAMPUS MUKAH DI ATAS
SEBAHAGIAN LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION,
SARAWAK.
CONCESSIONAIRE
8.0
AS BUILT DRAWING
CADANGAN UNIVERSITI TEKNOLOGI MARA (UiTM) KAMPUS MUKAH DI ATAS SEBAHAGIAN
LOT 35, BLOK 99, MUKAH LAND DISTRICT, MUKAH DIVISION, SARAWAK
UITM/TA/BP/ACV/01 BANGUNAN PENTADBIRAN - LEVEL 1 UITM/TA/DP/CW/01 DEWAN PEPERIKSAAN - LEVEL 1 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT CHILLED WATER PIPE LAYOUT
UITM/TA/BP/ACV/01a AIR-CONDITION AND VENTILATION SERVICES UITM/TA/FPA/ACV/01 FAKULTI PERLADANGAN & AGROTEKNOLOGI
LEVEL 1 PLAN
UITM/TA/BP/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES AIR-CONDITIONING AND VENTILATION LAYOUT
AIR-CONDITIONING CONTROL PANEL
UITM/TA/FPA/ACV/01a AIR-CONDITION AND VENTILATION SERVICES
UITM/TA/BP/ACV/01c AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL UITM/TA/FPA/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL
UITM/TA/BP/ACV/01d BANGUNAN PENTADBIRAN
FCU CONTROL PANEL UITM/TA/FPA/ACV/01c AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL
UITM/TA/BP/ACV/02 BANGUNAN PENTADBIRAN - LEVEL 2
AIR-CONDITION AND VENTILATION LAYOUT UITM/TA/FPA/ACV/01d AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL
UITM/TA/BP/ACV/03 BANGUNAN PENTADBIRAN - UPPER LEVEL 2
AIR-CONDITION AND VENTILATION LAYOUT UITM/TA/FPA/ACV/01e AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL
UITM/TA/BP/ACV/04 BANGUNAN PENTADBIRAN
AIR-CONDITION AND VENTILATION UITM/TA/FPA/ACV/02 FAKULTI PERLADANGAN & AGROTEKNOLOGI
SCHEDULE OF AHU, FCU AND EXHAUST FAN LEVEL 2 PLAN
AIR-CONDITIONING AND VENTILATION LAYOUT
UITM/TA/BP/CW/01 BANGUNAN PENTADBIRAN
LEVEL 1 FLOOR PLAN UITM/TA/FPA/ACV/03 FAKULTI PERLADANGAN & AGROTEKNOLOGI
CHILLED WATER PIPE LAYOUT LEVEL 3 PLAN
AIR-CONDITIONING AND VENTILATION LAYOUT
UITM/TA/BP/CW/02 BANGUNAN PENTADBIRAN
LEVEL 2 FLOOR PLAN UITM/TA/FPA/ACV/04 FAKULTI PERLADANGAN & AGROTEKNOLOGI
CHILLED WATER PIPE LAYOUT SCHEDULE OF AHU, FCU AND EXHAUST FAN
UITM/TA/P/ACV/01 PERPUSTAKAAN - LEVEL 1 FLOOR PLAN UITM/TA/FPA/CW/01 FAKULTI PERLADANGAN & AGROTEKNOLOGI
AIR-CONDITION AND VENTILATION LAYOUT LEVEL 1 FLOOR PLAN
CHILLED WATER PIPE LAYOUT
UITM/TA/P/ACV/01a AIR-CONDITION AND VENTILATION SERVICES
UITM/TA/FPA/CW/02 FAKULTI PERLADANGAN & AGROTEKNOLOGI
UITM/TA/P/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES LEVEL 2 FLOOR PLAN
AIR-CONDITIONING CONTROL PANEL CHILLED WATER PIPE LAYOUT
UITM/TA/P/ACV/02 PERPUSTAKAAN - LEVEL 2 FLOOR PLAN UITM/TA/FPA/CW/03 FAKULTI PERLADANGAN & AGROTEKNOLOGI
AIR-CONDITION AND VENTILATION LAYOUT LEVEL 3 FLOOR PLAN
CHILLED WATER PIPE LAYOUT
UITM/TA/BP/ACV/03 PERPUSTAKAAN
AIR-CONDITION AND VENTILATION UITM/TA/PPAUP/ACV/01 PEJABAT PUSAT AKUAKULTUR & UNIT PERLADANGAN
SCHEDULE OF AHU, FCU AND EXHAUST FAN GROUND FLOOR AND FIRST FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/P/CW/01 PERPUSTAKAAN - LEVEL 1 FLOOR PLAN
CHILLED WATER PIPE LAYOUT UITM/TA/PH/ACV/01 PUSAT HATCHERI - FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/P/CW/01 PERPUSTAKAAN - LEVEL 2 FLOOR PLAN
CHILLED WATER PIPE LAYOUT UITM/TA/PP/ACV/01 PUSAT PEMPROSESAN - GROUND FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/DP/ACV/01 DEWAN PEPERIKSAAN - LEVEL 1 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT UITM/TA/BKAD/ACV/01 BENGKEL KEJURUTERAAN AKUATIK DAN DEPO
GROUND FLOOR PLAN
UITM/TA/DP/ACV/01a AIR-CONDITION AND VENTILATION SERVICES AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/DP/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES UITM/TA/MD/ACV/01 MAKMAL DIAGNOSTIC - GROUND FLOOR PLAN
AIR-CONDITIONING CONTROL PANEL AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/KSAP/ACV/01 KEMUDAHAN SOKONGAN AKADEMIK / PENYELIDIKAN UITM/TA/DK/CW/01 DEWAN KULIAH - PELAN TINGKAT BAWAH
- PUSAT JUAL HASIL & STOR - GROUND FLOOR PLAN CHILLED WATER PIPE LAYOUT
AIR-COND AND VENTILATION LAYOUT
UITM/TA/KKPD/ACV/01 BANGUNAN UNIT KESELAMATAN / KESIHATAN /
UITM/TA/FSG/ACV/01 FAKULTI SAINS GUNAAN - LEVEL 1 PLAN PENYELENGGARAAN / DEPO KENDERAAN
AIR-CONDITION AND VENTILATION LAYOUT LEVEL 1 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/FSG/ACV/01a AIR-CONDITION AND VENTILATION SERVICES
UITM/TA/KKPD/ACV/01a AIR-CONDITION AND VENTILATION SERVICES
UITM/TA/FSG/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL UITM/TA/KKPD/ACV/01b AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL
UITM/TA/FSG/ACV/01c AIR-CONDITIONING AND VENTILATION SERVICES
AIR-CONDITIONING CONTROL PANEL UITM/TA/KKPD/ACV/01c BANGUNAN UNIT KESELAMATAN / KESIHATAN /
PENYELENGGARAAN / DEPO KENDERAAN
UITM/TA/FSG/ACV/01d AIR-CONDITIONING AND VENTILATION SERVICES FCU CONTROL PANEL
AIR-CONDITIONING CONTROL PANEL
UITM/TA/KKPD/ACV/02 BANGUNAN UNIT KESELAMATAN / KESIHATAN /
UITM/TA/FSG/ACV/01e AIR-CONDITIONING AND VENTILATION SERVICES PENYELENGGARAAN / DEPO KENDERAAN
AIR-CONDITIONING CONTROL PANEL LEVEL 2 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/FSG/ACV/02 FAKULTI SAINS GUNAAN - LEVEL 2 PLAN
AIR-CONDITION AND VENTILATION LAYOUT UITM/TA/KKPD/ACV/03 BANGUNAN UNIT KESELAMATAN / KESIHATAN /
PENYELENGGARAAN / DEPO KENDERAAN
UITM/TA/FSG/ACV/03 FAKULTI SAINS GUNAAN - LEVEL 3 PLAN AIR-CONDITION AND VENTILATION
AIR-CONDITION AND VENTILATION LAYOUT SCHEDULE OF AHU, FCU AND EXHAUST FAN
UITM/TA/FSG/CW/03 FAKULTI SAINS GUNAAN - LEVEL 3 FLOOR PLAN UITM/TA/MSB/ACV/01 MECHANICAL SERVICES
CHILLED WATER PIPE LAYOUT MSB ROOM SUBSTATION 2 AND 3
FLOOR PLAN VENTILATION LAYOUT
UITM/TA/FSG/CW/04 FAKULTI SAINS GUNAAN - LEVEL LOWER ROOF PLAN
CHILLED WATER PIPE LAYOUT UITM/TA/MSPP/ACV/01 MEDAN SELERA & PUSAT PELAJAR - LEVEL 1 PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/FPP/ACV/01 FAKULTI PENGURUSAN PERNIAGAAN
LEVEL 1 FLOOR PLAN UITM/TA/MSPP/ACV/01a MEDAN SELERA & PUSAT PELAJAR
AIR-CONDITION AND VENTILATION LAYOUT KITCHEN HOOD AND EXHAUST FAN CONTROL PANEL
UITM/TA/FPP/ACV/01a AIR-CONDITION AND VENTILATION SERVICES UITM/TA/MSPP/ACV/02 MEDAN SELERA & PUSAT PELAJAR - LEVEL 2 PLAN
AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/FPP/ACV/02 FAKULTI PENGURUSAN PERNIAGAAN
LEVEL 2 FLOOR PLAN UITM/TA/S/ACV/01 SURAU - LEVEL 1 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT AIR-CONDITION AND VENTILATION LAYOUT
UITM/TA/DK/ACV/01 DEWAN KULIAH - PELAN TINGKAT BAWAH UITM/TA/RT/ACV/03 RUMAH TETAMU - LEVEL 5 FLOOR PLAN
AIR-CONDITION AND VENTILATION LAYOUT AIR-CONDITION AND VENTILATION LAYOUT