You are on page 1of 4

Conference on Diagnostics in Electrical Engineering CDEE 2016

Continuous condition monitoring of high


voltage transformers by direct sensor
monitoring of oil aging for a stable power
network
Manfred Mauntz1) and Jörn Peuser2)

cmc Instruments GmbH, Hauptstr. 388, Germany, www.cmc-instruments.de


1)
tel: +49 6173 32 0078, email: mrm@cmc-instruments.de,
2)
tel: +49 6173 32 0078, email: jp@cmc-instruments.de

Abstract— The new online oil sensor system, OilQSens®, transformer system. Once the oil condition monitoring
enables continuous condition monitoring and power grid sensors are installed on the High Voltage Transformers or
protection of high voltage transformers by sensor monitoring other components like the oil regeneration system, the
of oil aging. The requirements for transformers in the measuring data can be displayed and evaluated elsewhere.
renewable energy rise. Ever more flexibility at a maximum
operational reliability and a long life are required of them at
The signals are transmitted to a web-based condition
the same time, so the requirements for the transformer oil monitoring system via LAN, WLAN or serial interfaces of
grow correspondingly. The new online oil sensor system the sensor unit. Monitoring of the damage mechanisms
OilQSens® measures the components conductivity kappa, during operation below the tolerance limits of the
dielectric constant epsilon r and temperature T independently components enables specific preventive and condition-
and calculates the breakdown-voltage, loss angle tan delta, oriented maintenance independent of rigid inspection
acidification, and it looks promising to calculate also the intervals. With this sensor system, components of the
humidity. The new approach utilizes sensor detection of complex impedance, X, of oils, in particular the specific
chemical aging of the insulating oil and its inhibitors. Based
electrical conductivity, κ, and the relative permittivity, εr,
on a very sensitive measurement method with high accuracy
even small changes in the conductivity and dielectric constant are measured as well as the oil temperature T [1-3]. The
of the transformer oil composition can be detected reliably. values κ and εr are determined independently of each other.
The new sensor system effectively controls the proper Fig. 1 shows the basic sensor with its triple plate design.
operation conditions of High Voltage Transformers, oil-filled
circuit breakers and oil regeneration systems.

Keywords— high voltage transformer, electrical


conductivity, loss factor tan, sensor system, relative permittivity,
oil regeneration system, dielectric constant, breakdown voltage,
condition monitoring, oil transformer system, oil regeneration
plant, oil aging, oil regeneration, oil quality, condition
monitoring system, online oil sensor system, formed acid, web
based condition monitoring, oil filled circuit breaker.

I. PRINCIPLE OF OPERATION
The online diagnostics system measures components of the
specific complex impedance of oils. For instance,
contamination during the assembly, formed acids, Fig. 1. Basic sensor with triple plate design.
aldehydes and peroxides, result in an increase of the
electrical conductivity, which directly correlates with the Oils are electrical non-conductors. The electrical
degree of contamination of the oil. This leads to the conductivity of pure oils is in the range below 0.5 pS/m.
formation of sludge, which in turn attacks the cellulose The process of degradation and the products of
insulation, inhibits oil flow, traps heat inside the contamination in the oil changes the conductivity of
transformer, and finally results in the destruction of the insulating oils. Contamination during production or
transformer. The determination of impurities or reduction assembly, formed acids, aldehydes and peroxides all bind
in the quality of the oil and the quasi-continuous evaluation together to form sludge. Sludge attacks the cellulose
of chemical aging follow the holistic approach of a real- insulation, inhibits oil flow and traps heat inside the
time monitoring of an alteration in the condition of the oil- transformer. It rises with increasing ion concentration and
978-1-5090-6179-2/16/$31.00 ©2016 IEEE
Conference on Diagnostics in Electrical Engineering CDEE 2016

mobility. The electrical conductivity of almost all stays nearly constant. The implemented adaptive algorithm
impurities is high compared to the extremely low can now work in the background of the measurement
conductivity of the original pure oil. A direct correlation procedure autonomously, it has to be reset only after an oil
between the electrical conductivity and the degree of exchange to adapt to the new lubricant [4, 5].
contamination of oils has been found. Thus contamination
of the lubricant can be identified by an increase of the
electrical conductivity of the oil in operation. The III. APPLICATION EXAMPLE: MONITORING OF
hypothesis is to find changes in moisture as a linear trend AN OIL REGENERATION PLANT
from the changes in the dielectric constant. The loss factor The oil sensor unit has been installed on the inlet of an oil
tan δ is calculated from the electrical conductivity and regeneration plant for online monitoring of oil quality
permittivity , with the dielectric constant , and the during the cleaning process (see Fig. 3).
angular frequency = 2πf

tan
is the dielectric constant and ω is the angular frequency.
For temperature-independent representation, directly
measured values are converted to temperature-
compensated values TC:
Fig. 3. Oil sensor attached to the inlet of the oil regeneration plant.

tan The data shown in Figure 4 and 5 has been recorded


continuously over a time period of about 9 days at an
average oil temperature of 41°C. Figure 4 shows the loss
II. MEASUREMENT ACCURACY AND TEMPERATURE factor tan δ calculated from the measured conductivities κ
COMPENSATION and dielectric constants εr of the oil by OilQSens®.
Ion mobility and thus, electrical conductivity κ are
dependent on the internal friction of the oil and therefore,
also on its temperature. The conductivity κ of the oil
increases with temperature. The type of contamination and
its temperature dependence cannot be assumed to be
known. For proper comparability of measurements, a self-
learning adaptive temperature compensation algorithm has
been developed. Now changes of oil quality can be
accurately assessed by the temperature compensated
conductivity value, even though the specific contamination
is not determinable. The relative permittivity is measured
independently with the same sensor arrangement as used
for the electrical conductivity. Figure 2 shows the effect of
temperature compensation.
Fig. 4. Loss factor tan delta over time during a regeneration process.

The dielectric losses in insulating oil are proportional to the


loss factor. In the application of the oil regeneration plant
the signal of the loss factor tan δ can be used to control the
oil cleaning process: once the loss factor tan δ have reached
its minimum, further filtration will not improve the overall
oil quality. The cleaning process is either finished or the
filters are depleted. Figure 5 shows the compensated values
for optimal comparison with the laboratory results at 90°C.
There is a good agreement of the OilQSens® online data
with the offline laboratory measurements.

Fig. 2. Effect of the temperature compensation algorithm.

The algorithm needs about 10 initial measurements to start


the compensation and gets more precise after a short time.
While the conductivity κ changes significantly with
temperature, the temperature compensated conductivity κ40
Conference on Diagnostics in Electrical Engineering CDEE 2016

Fig. 5. OilQSens® loss factor tan delta calculated at 90°C in comparison


to laboratory measurements. Fig. 7. Breakdown voltage and measured humidity over time.

In conclusion, installed on high voltage transformers, the


OilQSens® sensor system can provide warnings when the
maximum allowable gradient of the temperature-
compensated conductivity curve is exceeded and can be
used to limit power accordingly. In addition, when a
maximum allowable conductivity is exceeded, a warning
signal for the implementation of oil maintenance measures,
such as an oil filtering in the secondary flow can be
generated.

IV. CORRELATION BETWEEN BREAKDOWN


VOLTAGE, HUMIDITY AND RELATIVE
PERMITTIVITY
In a laboratory experiment, transformer oil was moisturized
and dried afterwards: the moisture was removed by Fig. 8. Relative permittivity and humidity over time: cycles with
cellulose. During this whole process the breakdown increasing and decreasing water content in oil
voltage, humidity and the relative permittivity were
measured over time. The temperature was kept constant at
40°C ± 1°C. The corresponding experimental setup is
shown in figure 6. According to normative standards, the V. CONCLUSION
breakdown voltage was measured six times with an oil The online diagnostics system measures components of the
tester BA 75 [6]. The humidity in the oil was determined specific complex impedance of oils. For instance, formed
by a moisture sensor [7]. The relative permittivity εr was acids, aldehydes and peroxides cause an increase in
measured by the OilQSens® sensor. electrical conductivity that directly correlates with the
degree of pollution of the oil. Indication of damage and
wear is measured as an integral factor of the degree of oil
contamination, oil aging and acidification. It provides
informative data on oil aging and the formed acids,
aldehydes and peroxides which result in an increase of the
electrical conductivity. These directly correlate with the
degree of contamination of the oil as proven by infrared
spectroscopy of used lubricants. For asset protection,
efficient machine utilization and targeted damage
prevention, the new OilQSens® online condition
monitoring system offers the opportunity to carry out
Fig. 6. Experimental setup.
timely preventative maintenance on demand instead of
rigid inspection intervals. The determination of impurities,
With the variation of the moisture in the oil the breakdown
reduction in quality of the insulated oil, oil aging and the
voltage changes correspondingly [8]: an increase in the
continuous evaluation of operating conditions of high
humidity in the oil leads to a decrease in the breakdown
voltage transformers (see figure 9), oil-filled circuit
voltage as shown as in figure 7. The correlation of the
breakers and oil regeneration systems meets the holistic
humidity and the relative permittivity εr is shown in figure approach of a real-time monitoring of a change in the
8. Based on these results it appears that the relative condition of the oil-transformer system. The signals from
permittivity εr correlates with the measured moisture in oil.
Conference on Diagnostics in Electrical Engineering CDEE 2016

the sensor are transmitted to a web-based condition [1] Gegner, J., Kuipers, U. and Mauntz, M.: Ölsensorsystem zur
monitoring system via LAN, WLAN or serial interface. Echtzeit-Zustandsüberwachung von technischen Anlagen und
Maschinen, Technisches Messen 77, 2010, pp. 283-292
The monitoring of the wear mechanisms during proper
[2] Kuipers, U., Mauntz, M.: Ölsensorsystem – Sensorsystem zur
operation, below the tolerance limits of the insulated oil Messung von Komponenten der komplexen Impedanz elektrisch
then allows preventive, condition-oriented maintenance to gering leitender und nichtleitender Fluide, dessen Realisierung und
be carried out on demand. This can prevent outages caused Anwendung, Patentanmeldung Nr. 10 2008 047 366.9, Anmelder:
by wear and aged oil problems while simultaneously cmc Instruments GmbH, Deutsches Patentamt, München,
Anmeldetag: 15. 9. 2008
increasing the overall lifetime of the oil-transformer
[3] Kuipers, U.; Mauntz, M.: Verfahren, Schaltungsanordnung, Sensor
system. Asset protection is assured. zur Messung physikalischer Größen in Fluiden sowie deren
Verwendung. Europäische Patentanmeldung Nr. EP 09000244,
Europäisches Patentamt, München, Anmeldetag: 09.01.2009
[4] Mauntz, M., Kuipers, U., Peuser, J.: Renewable energy power grid
protection by continuous, online condition monitoring of oil aging
in high voltage transformers and oil regeneration systems. The
Eighth International Conference on Material and Modeling MMT-
2014, July 28 -August 01, 2014 Center of Samaria Ariel, Israel,
ISBN: 978-965-91944-2-1, S. 86-94
[5] Gegner, J., Kuipers U. and Mauntz, M.: High-precision online
sensor condition monitoring of industrial oils in service for the early
detection of contamination and chemical aging, Sensor+Test
Conferences 7.-9.6.2011, Nürnberg, AMA Service GmbH,
Wunstorf, 2011, pp. 702-709
[6] Operation manual breakdown analyser BA 75, DHV0025 Rev05, b2
electronic GmbH, Austria
[7] User’s guide Vaisala HUMICAP® Moisture and temperature
Transmitter Series for Oil MMT310, M210474EN-B, Vaisala,
Fig. 9. : Installation of the OilQSens® sensor system at a high voltage Finland, 2008
transformer. [8] Tenbohlen, S., Seibold, R., Koch, M.: Das Alterungsverhalten
verschiedener Ester-flüssigkeiten für Leistungstransformatoren, FB
112 Grenzflächen in elektrischen Isoliersystemen -
Beanspruchungen, Design, Prüfverfahren, Lebensdauer, Vorträge
REFERENCES der 3. ETG-Fachtagung vom 16. bis 17. September 2008, Würzburg,
Kapitel 21, VDE-Verlag ISBN 978-3-8007-3116-9

You might also like