You are on page 1of 1

RELATED TO SYSTEM;

PROBLEM REASON SOLUTION


a. Uncontrolled salt tank a. Remove refill, clear the ball.
filling rate. b. Check the salt line connection.
Salt tank overflows. b. There is air in the Salt c. Clear Drainage lines
suction line.
c. Drainage line is clogged.
After the regeneration there There is dirt at flapper. Clean the surface of Flapper.
is a leakage to drainage.
a. Faulty regeneration. a. After checking salt rate
There is a hard water b. By-pass line has leaks. regenerate again.
leakage after regeneration. c. O-ring around the diffuser b. Change By-pass valve.
pipe damaged. c. Change O-ring.
d. Incorrect capacity. d. Enter the real capacity.
a. Low water pressure. a. Input pressure must be
b. Drainage line is clogged. Minimum 2.5 bar.
c. Ejector clogged. b. Resolve obstructive.
d. Ejector damaged. c. Clean Ejector.
e. The valve disc 2 or 3 does d. Change Ejector.
No salt water suction.
not close. e. Clear the substance on the
f. Air control unit closes fast. valve disc. If it is necessary
replace the disk.
f. Check refill. If necessary change
the air control unit.
a. Adapter or motor not a. Connect the power.
Unit does not do automatic
connected. b. Change Engine.
regeneration.
b. Motor defective.
Units regenerate at wrong Time of the day in the Correct the time program.
time. program is incorrect.
a. Low water pressure. a. Input pressure must be
Wild absorption of salt
b. Ejector damaged. minimum 2.5 bars.
water.
b. Change Ejector.
a. There is dirt at the Valve a. Open and close the valve disc
disk number 1. manually to remove pollution
b. Valve disc 2 is not closing away.
during the salt water suction. b. Check all the connection points
Salt tank overflowing.
c. Salt water suction line on the salt water suction line.
takes air line. c. There is a larger or smaller
d. Faulty drainage control. drainage flow then should be.
Make checks

15