CT COSTA

NORTE S/E CRISTOBAL


13.8 Δ /230Y KV
B A
1G4
G4 T4
CH EL ALTO 79MW 23T4
96/96MVA
G1 G2 G3 CE 13.8 Δ /230Y KV 23B12 23M12 23A12 23LB10
CE CE 1.6 KM ACCC DRAKE 1026 2.03 km X2 XLPE 2C 2000
24.06MW 24.06MW 24.06MW CE NUEVO ROSA DE 1G3 T3
NVO. CE G3
S/E CHANGUINOLA 1G1 1G2 1G3
CHAGRES
62.5MW
MARAÑON
17.5MW
PORTOBELO
32.5MW
CHAGRES 1 LOS VIENTOS
55MW 52.5MW 3x 9.3 MVAR
79MW
96/96 MVA
13.8 Δ /230Y KV
23T3 23A22

230/13.8 KV T1 230/13.8 KV T2 230/13.8 KV T3 G61-G66 G49-G53 G18-G28 23B22 23M22


26MVA G42-G48 G11-G17 T2
A S/E CAHUITA 23T1 26MVA 23T2 26MVA 23T3 S/E DOMINICAL G54-G71 G54-G60 G72-G80 G1-G10 C1 C2 C3
G2 23LA30
1.6 KM ACCC DRAKE 1026 2.03 km X2 XLPE 2C 2000

9MVAR

2MVAR

9MVAR
9MVAR
9MVAR
M M M G81-G88 BUR 2 A R.BUR 1 159MW 23T2
(ICE)

9MVAR
9MVAR
23A32

9MVAR
230-21 23A1 23A2 23A3 B A 34.5/0.69 kV CONGO A 19-3 3C1 2C2 3C3 218/218 MVA
230-30 34.5/0.69 kV

13.84 km ACCC DRAKE 1026

13.84 km ACCC DRAKE 1026


13.8 Δ /230Y KV
13.51 km 230-34

1LA12

1LA22
23LB20 23LA20 78.38 km 23B32 23M32
ACAR 750 18/19 ACAR 750 18/19 23LA42 S/E PAREDONES 23B43 M 23LA40 11.7 km G1 1G1 T1

1T2

A LAGUNA ALTA
B 79MW 23T1
A 3C1 3R1 3C5 3C6 3C7
23M42 23A42 S/E EL ALTO 3C2 3C3 3C4 C6 23C6 23C5

ARRAIJAN
C5

ARRAIJAN
230-35 230-33 A 96/96 MVA 30MVAR

A A. REV
23A22 M M 30MVAR
23B22 23M22 7.2 km 750 ACAR 23LA30 17.5 km

A WLM
23LB30 23M32 23LA42 3AC2 3AD2 3BH2 3A12 3BF2 3BG2 3BH2 3B12
S/E CAÑA BLANCA

A JDA
230Y / 13.8Y KV 23LB80 23LA80

A S/E

A S/E
23T1 23LA10 12.5/14MVA 23LA11 C4 23C4 23C2 T2
23B32 23A32 ETESA C2 34-157
G1
4.95 MW
1G1 T1
23LA10
M S/E PRIMAVERA 23A1 23A2 23A3
230+8x1.25%34.5 kV 3T92
3AB2
3T91 SSAA SSAA SSAA S/E BURUNGA 30MVAR 30MVAR
3T2 10.7 km 13.2Δ /13.8 Y/34.5ΔkV
23B12 23M12 23A12 CH 1T1A 23T1A 23LB51 23LB53 23T1 23T2 23T3 230/13.8 KV 230+8x1.25%%%34.5
KV 160 kVA 400 kVA 400 kVA 20/26.7/33 MVA
230-45 120/140 MVA 34.5/13.8 kV 34-128 34-8B 34-130 34-129 34-8A 34-1C 477AAC
SAN ANDRES 23B12 23M12 23A12 T1 T2 T3 20/20MVA 120/140 MVA 16 MVA 3TT1 C3 23C3 23C1 C1
23T1 636 ACSR 2.8 km 23LB52 30MVAR
230Y/115Y/34.5 Δ kV G2 1G2 3T2 3T3 3T4 3T5 3A22 3LA32 3LA42 3LA52 3LA62 3LA72 3LA82 3T1 30MVAR
4.95 MW 23LA10 T92 T91 3A12
50/50/50MVA 230-25B 230/34.5KV
A S/E RIO CLARO 1 1G1 1G2 1G3 N.C. TT1
23LB10 S/E GEEHAN
T1 3T1A ACAR 18/19 31 km M 23T1 CH PANDO CH B
100MVA T1 10 MVA
A
MONTE LIRIO S/E EL COCO 23L12 13.8 /13.8YKV

ACAR 750 18/19


T1 CT COBRE PANAMÁ G1 G2 G3
A 50/50/50 MVA 16.65MW 16.65MW 16.65MW 1A2
150MW A

16.16 km
11T1

230-20B
A G2 G1 1T1
115-50 11A22 3T1 1G2 1G1 1T1 1T2
B A
9.7 km 1G1 1G2
T2
230/15.75 KV
150/190MVA T1 23T91
1200 ACSR
51m
T4 230Y/13.8 Δ kV
T1
A S/E ESTI

48.35 KM ACAR 1200 24/13

48.35 KM ACAR 1200 24/13


CH ESTI 23T92 65/65 MVA
34-54 3A12 G1 G2 LVAC
3LA10
M 3TT1
16.4MW 16.4MW
23B32 23B12
23AB2
23A32 23A12 System 23B52 23M52 23A52
B M 23T1 A
S/E BAYANO
11LA22
115Y/13.8 kV
M 3A22
TT1
A 13.8Δ/230Y kV
69/69MVA
A 23LB40 23LA40
230-12A T115 230-12A
23B11 23M13
S/E PACORA B
23A61
A
S/E IDAAN 23A1 T1 117.22 km 1200 ACAR

230-54
30/36 MVA T1 B 33.95 KM ACAR 1200 24/13

230-55
5MVA 1G1 60MW
S/E BONYIC G1 S/E PUNTA RINCON
1/0 ACSR 23T1
23LB22 23LA22
ST1
+/-60 MVAR
ST2
+/-60 MVAR
T14
22.2/0.208
23B42 23M42 23A42
23LA30
230-13A S/E PANAMÁ II 23B22
23LB20
23M22
23LA20
23A22 230-1A
50.88 KM M 23B51 23A62
CH
BAYANO
1G1 1G2 1G3 34-55 600 kVA 151.17 KM ACAR 1200 24/13 ACSR 636 42/7 ASERR. CAÑITAS
230-43 230-44 23LB30 B A
S/E BOFCO 477 ACSR 13.8Δ/230Y kV TT4 SE PENONOMÉ II 23B52
69/69MVA 22 km 22 km
22.2 kV 23B32 23M32 23A32 230 M M
1024 KCM ACAR 1024 KCM ACAR 34.5 kV 1G1 52-S1
1/0 ACSR 23A2 T2 1G2 25.4 kVA /34.5 kV /0.63 kV
CS SOLAR 23B41 T1
G1 G2 G3 6A11 6A21 6T141 6TT4
3X10MW G2 23LAB2 23LA62 PENONOMÉ II G1
1/0 ACSR RAVEN 23T2 23B82 23M82 23A82 M 23B42 87MW
CH 60MW S/E BOTIJA 23LA42 23LA22 A G1-G23
230Y/13.8 KV 13.8 /13.8 Δ YKV
BONYIC B 23LA23 23T24 3T241 120 MW 23LB70
23B22 23M22 23A22 23B31 109/109MVA 6250/6250KVA
T24 3X16.0MW 3X16.5MW 23B72

ACAR 1200 24/13


23AB2 3X16.0MW

ACAR 1200 24/13


M 1G2 52-S2
S/E CAÑAZAS A
0.267 km 0.267 km A 1G1 1G2 1G3 G4 G5 G6 G7 G8 G9
23B72 23M72 23LA72
23LB60 23B82
23B32
T2
G2 52-SE

44.65 KM
23T41A 52-SM

230-13B
44.65 KM
230-12B
S/E CAIMITO II S/E CAIMITO I B A 23T42 23T32 23T22 23LB20 23LA20 87MW
6T4 1G4 1G5 1G6 1G7 1G8 1G9 23LB50 23LA62 23B21 230Y/13.8 Δ KV
23LA10 23T43 23T33 23T23 23T4 23T41 230-57 230-56 23B62 23M62
34.5/0.605 kV 230-1B 109/109MVA 52-ST
2.8 MVA 23B13 23A12 T4 M M 2.002 km 1T1 1T2 1T3 23B22
23LA50
CS CEDRO 3LA11
34-180
3LA21 34.5/230 kV T1
50/50 MVA 23LA20 29.16 km
ACAR 750
230-29
16.41 km
ACAR 1200
23LB50 T4
23NT4
T3
23NT3
T2
23NT2
230/22.2 kV
90/120 MVA
2.002 km S/E ANTÓN IV 230Y/13.8 Δ KVT1
23LB40
19.01 KM ACSR 636 42/7
S/E 24 DE DICIEMBRE 23B11 T3 1G3
220 m 230Y/34.5Y/13.8 Δ KV 230Y/34.5Y/13.8ΔKV 230Y/34.5Y/13.8Δ KV B A T2 230Y/13.8 KVΔ T3 23B52 23M52 23A52 230-2B M 13.8Y/0.48 Δ KV 13.8Y/0.48 Δ KV
23T1 230-2A
G1-G4 3T1 23B22 23A22 S/E GUASQUITAS 120/150/36MVA 120/150/36MVA 120/150/36MVA 63MVA 23T1 23T2 64MVA 23T3
23LA40 89-G3 G3 1000/1000KVA 1000/1000KVA

230-19
10.67 KM ACSR 636 42/7 60.53 KM ACSR 636 42/7 23LA11

0.5 km
9.9 MW 23T11 23T21 23T31 23B12 86MW
3T4 3T3 3T2 23LB20 23LA20
B A 230-26 CT PANAM B A 23LA12 230Y/13.8Δ KV
109/109MVA
34.5/0.605 kV
BARRA C 3BC1 BARRA B 3AB1 BARRA A 25.1 km 23LB30
2.8 MVA S/E ESPERANZA S/E FORTUNA 23B52 23M52 23A51 SE TOABRÉ ACAR 1200 24/13 23LA10
23B42 23M42 23A42
23B22 23M22 23A22
230Y/13.8 ΔKV
CS CAOBA 3AB3 3AB1 23LB10 23LA10 230-16 3C4 3C3 3C2 3C1 230-11
A 23B32 23M32 100/100 MVA
230-20A M M 230-18 23LB40 23LA40 84.81 km ACAR 1200 24/13 230-49B 230-49A 23LA30 3T2 23M12
8.5 KM 88.93 KM 16.41 km 23B12 23A12
G1-G3 8.5 kM 23LB30 23LA30 23T35A S/E LL. SÁNCHEZ 23LB20 23LB30 S/E CHORRERA M M
ACAR 750 18/19 ACAR 1200 24/13 C4 C3 C2 C1 23B32 23M32 23A32
9.9 MW B A
23B42 23M42 23A42
230-17 75MVAR 75MVAR 75MVAR 75MVAR
S/E LL. 23T35 ACAR 1200 24/13 ACAR 1200 24/13 T2 T1 FUERA DE USO

230-25A
142 km
23B22 23M22 23A22 23LA20
CH
23LB30 M 23LA30 84.81 km ACAR 1200 24/13
13.8/6.4 kV 9.42MW 9.42MW 0.97MW 230/34.5 kV S/E PANAMÁ 230Y/34.5 Δ /13.8Y KV 230Y/13.8Y KV
CH RP490
6.6/34.5 kV
23B12 23M12 23A12
13.8Δ/230Y kV T1
FORTUNA B A
230-22
23B32 23M32 23A32
S/E EL VALLE
7 MVA
CH LAS CRUCES G1 G2 G3 SÁNCHEZ B A
23B22 23M22 23A22 30/40/50 MVA 50/50 MVA
ANTIGUA S/E
VISTA HERMOSA
23LA20
T3 T1 T2 T3 A AUTOTRAFO
8.5 MVA 23LB20 100MVA 23B32 23M32 23A32 6 km 23LA20
2X7.0MW T1 3T11 230/13.8 kV 1T3 34.5/11 KV 230Y/115YKV 23B12 23M12 1T2 1T1
M ACAR 750 G3 3T1 3T2 3T3 3A72 3C1 T5 350/350MVA 1AB
23B22 23M22 23A22 G1 32/32/64MVA 230-11 AUTOTRAFO 3000A 3000A
3T1 100MW 1G1 23T1 23LA10 23M22 23A22 5 MW 3LA12 23T5
G1 3LA12 T1 1G1 28.1MW S/E LAS CRUCES D C C1 230Y/115Y/13.8Δ KV
6.6/34.5 kV 34-73 230-31 230-32 13.8Δ/230Y kV T2 G1 8MVAR 23B62 23A62 175/175/30 MVA DIC-1C2 DIC-1C1
T2 3T21 9 km 100MVA 23B12 23M12 23A12 23T1 28.1MW M 34-93 11T5A
230-1C
8.5 MVA 0.6 kM 0.6 kM M 230-3A
750 KCM 750 KCM G2 23LB20
ACAR 100MW 1G2 23T2 23LA20 CH 3LA12 40.48 KM ACAR 750 18/19 23LA20 13.09 KM ACSS/AW3 605 23T3
G2 3T2 ACAR /0.65 kV 1C12
T3 1C11
13.8Δ/230Y kV T3 PRUDENCIA 34.5 23B22 23M22 23A22
CH LA CUCHILLA 127/127MVA 100MVA 23B22 23M22 23B22 115 KV 34.5 KV 230-4A 230-2C C2 C1
127/127MVA S/E GUALACA S/E ZAMBRANO 13.8/6.4 kV 23D93 23M92 23C92 11T3 T. AUX.
6.6/34.5 kV 3LB12 13.8Δ/ 230Y kV 13.8Δ/230 Y kV G3 230-41 40.48 KM ACAR 750 18/19 23LB10 23LA10 13.09 KM ACSS/AW3 605 5.4 MVAR
23T3 15/15/30MVA 20/20/40MVA 1G2 5.4 MVAR
5.25 MVA
2X4.135MW T1 3T11 T1 T2 100MW1G3
23B42 23M42 23T1C
T1 1G1
G1 23T1C
T1 1G1
G1
G2
28.1MW
7 MVA
T2 S/E VELADERO 11T1 3T1 TRANSF. DE
GABINETE
SERVICIOS
94 KM 1024 KCM ACAR CE TOABRÉ
S/E CHORRERA 230-47
23B12 23M12 23A12
AUTOTRAFO
230Y/115Y/13.8Δ KV
G1 3T1 34-179 3LB93 3LB91 2X12.65MW 2X18.8MW 1T2 T1 AUXILIARES 175/175/30 MVA
3LA12 R1 1G2 G4 23M82 23C82 66 MW 38.07 KM ACAR 1200 24/13 23LB30
34-135 709 m 1G1 R2 23T1 G2 23T1 G2 230-42 B A
6.6/34.5 kV M 23LA20 1G2 B G1-G20
T2 3T21 2.5 km 3LB92 1G2 5 MW A 3T11 94 KM 1024 KCM ACAR 23T2
5.25 MVA G1 G2 CH 23B32 23M32 23A32
CH 230/115/34.5 KV 23T1 1T2
106.4 MW 106.4 MW LORENA CS
G2 3T2 GUALACA 150/50/100 MVA 23M72 23C72
1T4A 1T4B PRUDENCIA 230-51 23LA80 AUTOTRAFO T2 11T2 T12
T1

ACAR 750 18/19


23LB80 225/225

ACAR 750 18/19


23LA14 230-23 23LA120 111.38 km ACAR 1200 24/13 23LD60 23LC60 230Y/115Y/13.8 Δ KV
9.8/13MVA 23LA14 230-24 23T1 MVA
23LA20 175/175/30 MVA
23LA12 8 km 23B82 23M82 23A82 AUTOTRAFO
S/E PANAMÁ II
37.72 km
T4 13.8Δ/34.5 Y kV
S/E EL TEJAR CH 37.72 km ACAR 750 23LA12 7 km 23B123 23M122 23A122
S/E SAN BARTOLO 230-50 11T1 1T1 SERVICIOS

230-7
A ACAR 750 23D62 23M62 23C62 230-48 230Y/115Y/13.8 KV AUXILIARES
230-8
CHANGUINOLA I 3T4 230-52 156.19 KM 23LB70 23LA70 175/175/30 MVA T1 225/225
FÁBRICA 23LA110 111.38 km ACAR 1200 24/13 ACAR 1200 24/13 38.07 KM ACAR 1200 24/13 23LB40 23M42
23LD50 23LC50 MVA
3T3
9.8/13MVA
B A 23B72 23M72 23A72 11T1
T11 11LA20 115-32 S/E TOCUMEN II
PREPARO
EXTRACCIÓN
T3 6.9Δ/34.5 Y kV 23B113 23M112 23A112
23T1 230-14A 23D52 23M52 23C52
B
S/E EL HIGO A 23LB50 M
AUTOTRAFO
23A52
AUTOTRAFO B.No.4 B.No.3 B.No.2 B.No.1 B.No.6 B.No.5 SERVICIOS
AUXILIARES
11B12 11M12 M 3.7 KM 636 ACSR
TOCUMEN II
115-61
3.8 KM
3LB32 23LB100 68.20 km ACAR 1200 24/13 23LD40 23LC40 23B52 20MVAR 20MVAR 20MVAR 20MVAR 20MVAR 20MVAR 115-60
CALDERA 34-154 230-3B 23M52 230Y/115Y/13.8 Δ KV 230Y/115Y/13.8 Δ KV 3.8 KM
0G3 23B32 23M32 23A31
460 V 13 km 60.81 KM 23LB40 23LA40 350/350/75 MVA 175/175/0.5 MVA 11C4 11C3 11B22 11M22 11A22
CALDERA
1T1
T1
3T1
G3 9.77MW
S/E MATA DE NANCE 23B102
23LB90
23M102
23LA90
230-14B
42.89 km ACAR 1200 24/13
23LB20 23LA20 230-15A
68.20 km ACAR 1200 24/13
23D42
23LD30
23M42 23C42 3LB30
23M32
3LA30
ACAR 750 18/19
23B42 23M42 23A42
C
11T3
23T3 23T2
11C2 11C1 11C6 11C5 11LA30
M
115-33
3.7 KM 636 ACSR 11LC 11CD2
690 V 23LC30 23B32 23A32 T3 1T3 T2 11LA 11AB2 11LB 11BC2 11LD
M 230-4B 1T2 11B32 11M32 11A32
30 MW B A 23B22 23M22 23A22 CS1 1T12 11NT2 11LA40
CENTRAL 23B92 23M92 23A92 23D32 23M32 23C32 3LB20 3LA20 60.81 KM 1T13 115-28
S/E PORVENIR 230-6C 230-15B 23LA10 30MVAR 23CS1 23C2 11NT3 M
CADASA G1 1G1 23LB40 85.60 km ACCC 714 CS4 ACAR 750 18/19 C2 T13 7.5KM 636 ACSR
B 23LB80 23LA80 42.89 km ACAR 1200 24/13 23LB10 RS1 23CRS1 23CRS2 23CS4 30MVAR 23B32 23M32 30 MVAR 11AF2 11DE2
EDECHI 3T2B 23T2 23B22 23M22 23A22 23LB30 T12 11T2 250KVA 11B42 11M42 11A42
1.8 MW 3LA22 3T2A 20MVAR 23RS1 23LA20 11LA50
34-52 23B12 23M12 23A12 230Y/115Y
250KVA 115-29
G2 DG2 DT2 1T2 34.5/4.16 kV 3LA21 3T2 23B82 23M82 23A82 23D22 23M22 23C22 M 7.5KM 636 ACSR 11GH2 11FG2 11EF2
230-5B 100/100 MVA T3 HACIA
T2 2X5.55MW
G1
13/13 MVA
3L52 3L72
NA T2
230Y/34.5Y kV
S/E BOQUERÓN 3 23LA40 85.60 km ACCC 714 23LB70 23LA70
230-5A
110.65 km ACAR 750 18/19 23AC2
11T3
23T3 23CRS3 CS2
23CS2 30MVAR
23M12 23A12
23B22 23M22 23A22 C3
30 MVAR
23C3 23C1 C1
30 MVAR HACIA
ALIMENTACION
CND
20MVARX3
C4
11B52 11M52 11A52 20MVARX3
115Y/13.8YKV 11T1 115Y/34.5/ 11T3 115Y/13.8YKV 11T2 115Y/34.5YKV 11T4
CH M 23LA10 ALIMENTACION C1 50/50 MVA 13.8YKV
OG1 83.33/83.33 MVA B A 23D12 23M12 23C12 23T1 11C4 11C1 T1 T3 42/42 MVA T2 30/30 MVA T4
CONCEPCIÓN G2 3T1 34-72 23B72 23M72 23A72 23C1
CND
C5 C2 50/50/50
3LR12 23B23 23M32 23B42 23M42 23A42 230-6B C1 23BD2 23AC2 RS2 23M12
OG2 23T1 30MVAR 23B12 23A12 11C5 11C2 MVA
T1 3AB12 M 23LB60 23LA60 8.66 km ACAR 750 18/19 23RS2 20MVAR 11B62 11M62 11A62
2.5 MVA 23A31 23LB30 B 23LB10 23LA10 A
CT SPARKLE
C6
11C3
C3 34-147
1.47 KM
S/E PANAMÁ 11C6
34-72

T1 3LT1 23LB10 23B62 23M62 23A62 23B12 23M12 23A12 1T1 1T2
23C2 1T3 METRO PMÁ 34-148
CH
G1
3T1
23B22 23M22 23A21 23LA10 230-9A 23B32 23M32 23A32 C2
30MVAR 230-6A 23B62 23M62
4X3.87 MW POWER 4X8.73 MW
B A
1.60 KM
MACANO 2X1.785 3LA12 3LA22 3LA42 24.17 km ACAR 750 18/19 23LA20 C R1
23R1 23R2
R2
107.97 KM 23LB20 23LA20 CS3
T1 230Y/115Y/34.5 Δ KV
G4 G3 G2 G1 G8 G7 G6 G5
B A
S/E TINAJITAS METRO PMÁ
MW ACAR 750 18/19 23CS3 30MVAR 50/50/50 MVA
3L64 34-64 23B12 23M12 23A12 20MVAR 23B52 23M52 23A52 20MVAR C 11LA11 1C11 1AB
T2 3LT2 23B22 23M22 23A22 M 11LA13 11T1 1T1 5.4 MVAR
G2 M RS3 EDEMET 115-9
3T2 11LA60
23LB20 C1 23C1 23RS3 20MVAR 3T13 TT1 1G4 1G3 1G2 1G1 1G8 1G7 1G6 1G5 3.0 KM 636 DSCR 11LA12 T1 TIN-1C1 S/E TOCUMEN 1C22
34-181
3LR12 2.5 MVA
30MVAR 23LB40 23R3 S/E A B 11B62 11M62 11A62 M 115-10 11AB1 115Y/13.8YKV C1 4.5 MVAR 5.4 MVAR C2
1.6 km 3T1B 3T1A 23B22 23M22 23A22 23T1 R3 230-3C 3T12 3TT1 11AB2 42/42 MVA
3C 1/0 ACSR + 1C 1/0 N
3LR11 3LR13
34.5/4.16KV 3T1 23C2
23B42 23M42 23A42 20MVAR
S/E BELLA VISTA 230Y/115Y/34.5 KV 81.93 KM
3T11
EL GIRAL II 1T1 1AB12 1AB22 1T2 11LA50 5.7 KM MCM 750 XLP
11AB3 1AB
13/13 MVA C2 100/100/100 MVA ACAR 750 18/19 11M52 11A52 11LB13 11LB11 11T2 1T2 2000A 4.5 MVAR
30MVAR 13.8 115 Y kV 13.8 115 Y kV 11B52 M
T1 3L52 T1
2X5.55MW 34-62 3LA32 230Y/34.5Y kV
23T1 230-4C 20MVA T1 T2 40 MVA 11LB12 T2 TIN-1C2
23B12 23M12 23A12
CH PERLAS
G1
OG1 3T1 83.33/83.33 MVA
B 23LB20 23LA20 T1 81.93 KM
A
11A12 11A22
11LA40
115Y/13.8YKV
S/E CERRO VIENTO
3LR12 C3 23C3 A ACAR 750 3LA11 11B42 11M42 11A42
NORTE G2 3LA21 11A11 11A21 A 42/42 MVA METRO PMÁ
OG2 23T3 30MVAR 11T1 18/19
34.5/4.16KV 3T3A 23B22 23M22 23A22 3T1A 3LA22 3LA12 11LA30 34-150
2X5.55MW
CH PERLAS
G1
OG1
13/13 MVA
T1 3L63
LAG 2 11LA10
11B32 11M32 11A32
S/E MONTE OSCURO 0.728 KM
T3 23B13 23M12 23A12 (Hacia Coronado) M 8.1 MVAR
SUR G2
CH 11LA13 11LA11 11T11 11LA 3T1
OG2 3T1 34-63 115-43 11LB20 11LA20 115-42 1T1 T1
S/E PARAÍSO III BARRO LAG 1 11AB2 11XB 1T1
(Hacia Farallón) AUTOTRAFO T1 5.4 MVAR
T1 11T3 BLANCO 2.3 km 11B22 11M22 11A22 9.0 KM 11LA12 11T12
230Y/115Y/34.5 Δ KV AUTOTRAFO M 750 XLP
G1 34-67 3LA22 AUTOTRAFO
0T1 2.00 MW 11.4 km 230Y/115Y/34.5 Δ kV
15.67MVA M
23LA10
100/100/100 MVA
3T2
230Y/115Y/34.5 Δ KV
50/50/50 MVA
S/E CEMENTO PANAMA 11LB10 11LA10 115Y/13.8Y KV
50/50 MVA 1AB 115Y/13.8Y KV
11BC1

1.4 KM MCM 636 ACSR


B A 25/25 MVA
2500 kVA CS MACANO 3LA12 70/60/50 MVA 3T1A AUTOTRAFO 3T1 11B12 11M12 11A12

115-7
1G1
CS PANASOLAR G1 230-40 230Y/115Y/34.5 Δ KV 11LB30 115Y/13.8Y/7.97Δ KV M
1-2
11LB13 11LB11 11T21 1T2C
7.5 km

1G2 23LA10 T2 3.6 MVAR


34-66

G2 1T1
100/100/100 MVA 23T3 23T1 12/16/20 MVA 11T5 11LA70 11HA2 11BC2
3T2A G5-9 G1-4 T2 T2 1T2A
23T2 T1 AUTOTRAFO G3
1G3 23T1
3T3 T3
11LB12 11T22 11XC 89T2C
6MW 4MW 23T2 T1 11B32 11M32 T1 11B72 11M72 11A72

ACSR 636 26/7


T2 230Y/115Y/34.5 Δ KV 2.22MVA T1 230/13.8KV 23T2 A S/E ARRAIJAN 11LH 9.9 MVAR
AUTOTRAFO 100/100/100 MVA 34-8 3LA10 11LB20 11T1 3T1 115Y/13.8Y KV 2B-2C
3LA11 11T1 33 MVA

115-12
CH 3LA11 1T2B

0.81 KM
50/50 MVA 1T2B
3T1 PEDREGALITO II 3T1 CH
PEDREGALITO I
230Y/115Y/34.5 Δ KV
70/60/50 MVA
11T2 S/E A S/E VACAMONTE
477 ACSR B A M
115Y/13.8Y KV
42/42 MVA
T1 34.5/13.8 kV
16/16 MVA
T1 34.5/13.8 kV
LAS FILIPINAS 3T2A
34-1 3LB10
CAPIRA
11B22 11M22 11A22 115-37 METRO PMÁ
29/29 MVA 34.5 kV 34.5 kV S/E DIVISA 5 MVA 34-149
1G2 1G1 1G2 1G1
/ 400 V / 400 V 3B12 3M12 3A12 3LA20 34-13
11B12 11M12 B A
0.80 KM 750 XLP S/E SANTA MARIA 11GH2 11CD2 0.728 KM
3LB20 1T3 2-3
G2 G1
S/E MATA DE NANCE S/E MATA DE NANCE 230Y/115Y/34.5 Δ KV
T2
S/E CACERES

ACSS/AW3 605 24/7


G2G1 3CE2 3AE2 100/100/100 MVA 11LB10 11A82 11LC T3
S/E LLANO SANCHEZ

6.50 KM636 ACSR


2X7.2MW 11T2 11XD 1T3

6.50 KM636 ACSR


2X10MW 11LB10 B A 2561 3LB30 3B22 3M22 3A22 34-31 6.3 MVAR
CH B A 115-4A

115-38
A S/E TIJERA 3T2 11X31 1T3
29.95 km ACAR 750 18/19

115-22
BAITÚN 3LA52 N.A. 31.18 KM ACSS/AW3 605 24/7
S/E VISTA 3T12 A 11A72 11LB12 11X3 T3 11FG2 11DE2 115Y/13.8Y KV 8.1 MVAR
13.8 Δ /230 Y kV 11B12 11M12 11A12 5MVA
45/60MVA T1 S/E BAITÚN 3B12 3M12 3A12
5MVA A S/E VALBUENA
HERMOSA II 34-30A M 3A2
3LA52 3T3A 3B32 3M32 3A32
110Y/13.8Y KV
42/42 MVA
M11LF
34-15 34-10 34-120
S/E SANTA RITA 11EF2

115-3A
2X44.1 MW 11B22 11M22 11A22 M M 42/42 MVA 1-3 11LE 115-49
8.0 km

7 KM 1500 MCM
230-27 40 m PLAZA 19.9 MVA
230-9B

3R2 3LB10 3LA10 3R1 4.35 km 11A62

115-48A
SECCIONADOR
G1 477 ACSR 3T22 ITALIA A 1T1

2.2KM 636 ACSR


3B42 3A42 11X1

2.2KM 636 ACSR


B
B
23LA30
A
25 km ACAR 750 11LB20 11LA20 EL PORVENIR
20MVAR
3B22 3M22 3A22
20MVAR A S/E CHIRIQUÍ LL. S- IX 11X11 T1 3.6 MVAR 11LB13 11LA13

11.00 KM636 ACSR


13.8 Δ /230 Y kV 34-11 34-9 11LB10 11LA10 11LB12 11LA12
S/E CHORRERA

34-2

34-3
M M

22.85 KM
T2 7.7 km 5000KVA 3R1 4 km AGUAS 11LB11 11LA11

115-11
45/60MVA 23B32 23M32 23A32
A S/E DAVID 3LB20 3LA20 11.0 km 20MVAR 115Y/13.8Y KV
DE PANAMÁ 11B12 11M12 11A12 11LA12 1-2
3LE12 34-115 3LA12 34-131 11LB20 11LA20 115-35 25/25 MVA
G2 3M32 11T1
23LA20 3T3 3B32 3A32 3T1 9.8 KM 477 AAC

5 KM 1500 MCM
M 3LA22 11X2 1T2
11LB30 11B22 11M22 11A22 5.4 MVAR 115Y/13.8Y KV T1
115-54

115-48B
M 115-6
23B22 23M22 23A22 LL. S- VIII 2.68 km 11X21 T2 50/50 MVA

47.81 KM ACSR 636 kcmil 26/7


6.538 km ACAR 750

11A52 6.00 KM 336 ACSR


.050 KM 3.255 KM
3B42 3M42 3A42
630 mm2 XLPE S/E EL TORNO 11B32 11M32 11A32
115Y/13.8Y KV 1T1
ACSR 636 26/7

1200mm2 XLPE AL ACSR 636 200 mts 400 mts 50 mts HACIA S/E EL 50/50 MVA S/E LLANO BONITO
ACSR 636 26/7
230-28B

34-110 34-114 34-111 TORNO 115/13.8 kV 11B42 11A42


25.32 KM

23B12 23M12 23A11 34-122 3T3


M 2X500Cu XLPE
115-15
25.32 KM
115-16

3LA30 3T4A M M M
T3 M 115-8

115-2A
A
.450 KM 1200mm2 XLPE AL

AUTOTRAFO 11A42 11.00 KM 11LA12


3LF10 3LE10 3LF10

6.90 KM ACSR 636 26/7

6.69 KM ACSR 636 26/7


230Y/115Y/13.8 Δ kV 11A22 SERVICIOS SERVICIOS 11NA61 11NAB1 11NAB3 1200 MM, XLPE, AL
SE LLS V SE LLS VI SE LLS IV
62.5/62.5/9.375MVA 34-140 34-139 AUXILIARES N.A. 11NA41 11NA21 11NA11 B S/E LOCERIA 5.4 MVAR

47.81 KM ACSR 636 kcmil 26/7


AUXILIARES N.A. N.A. 11NA31
T4 3-50KVA 3-50KVA 34.5 kV 34.5 kV 34.5 kV
ACSR 636

13.5 KM 13.5 KM 3A32 3M32 3B32 120/208 11A61 11B63 11AB1 11AB3 11A41 N.A. N.A. N.A. N.A. 11NA1 11NB3 9.9 MVAR
120/240 34-43 / 380 V / 380 V / 380 V
1 KM

M M
CS SOL CS VISTA 11B43 11A31 11B33 11A21 11B23 11A11 11B13 11A32 11LA42 11T31
S/E IKAKO 1T3

115-1B
CS MILTON

115-2B
3LA20 3LB20 PLAZA PALERMO T3
115-44 S/E SAN CRISTOBAL 3LB12
IV 3LA12 REAL ALEGRE SOLAR 11LA62
M 11T32 2-3
11LC12 11LA12
8.87 km 11LA12 S/E PORTÓN 11AB2 N.A. MEDIDAS 11BC 110Y/13.8Y KV

115-1A
230-28A B A 34-33 3A22 3M22 3B22 3TT4 11LA42 11T32 11T22 11T12 11A22 11AB2
ACSR 636 M M
G1-16 G1-G12 G1-G16 25/33/47MVA
18.847 km ACAR 750 3LA10 3LB10
11N54 N.A. N.A. 1T2B S/E COSTA
115-47

10 MW 7.5 MW 10 MW
S/E TT4 11LA32 11T21 11T2 11T1
34-144

34-143

34-142
34-145

11A42 B 23LB 23LA A 11T22 11T12 11LA12 S/E S/E 3A12 3M12 3B12 T4
11A12 DEL ESTE
BAJO DE MINA 2 KM IKAKO IKAKO
LA PEÑA
T1 3T1 T2 3T2 3T4
11T22 T2 1T2A 2-AB
5.4 MVAR
115Y/13.8Y KV
46/46MVA
23AB2 23AD2 1200mm2 XLPE AL II III
115/34.5 KV 115/34.5Y KV 115Y/34.5 Δ KV S/E LAS MINAS #2 115/13.8YKV
11A12

T1
11A22
11A32

11A2

11A1

S/E LLANO
11A3

28/28 MVA 25/25 MVA 15/20/25 MVA 11LA22 30/40/50 MVA T2 T1


HACIA T2 115/13.8 KV A
23BC2 23LC 30MVA 4.16 Δ /115Y KV T6
11LA10 11LA20 MEDIDAS
TENSIÓN 11T11
11T12 11T22
11T21 M
11T42
11T41 M
SANCHEZ BARRA 4.16
20 MVA 11D22 115-4B 115-4L 115-4B
T1 G1 G2 M 1-89-4.16 11L42 25.41 KMACSS/AW3 605 24/7 1T2 1T1
T2 T3 G3 G4 B.L.M. #4
10MW 10MW 10MW 10MW 11AB2 1AB2
11LA11 A 115-3B 115-3L 11LA63
1T3 B 115-3B 115-39
G1 G2 2.79 KM 1-2
13.8 Δ /115 Y kV M 32.08 KMACSS/AW3 605 24/7 11LA62
2X28MW 34.5/13.8kV 11L32 S/E
0.431 km
230-36

13.8 Δ /115 Y kV 1.5/1.5 MVA 11A20


32/32 MVA CH S/E PROGRESO CH COCHEA S/E SANTIAGO 115-40 11LA53 T1 1T1B
1LA52
1LA42

1LA32
1LA22

1LA12

18.5 MVA 115-26B 115-26L CENTRO


1TT12

1C12

BAJO DE MINA 11T11 5.4 MVAR 5.4 MVAR


1S12
1T12

T1 11B22 11M22 11A22 2.79 KM 11LA52 1-AB


1G1 2X7.5MW C2 C1
1A12 1A22 23LB30 23LA30 3A42 34-69 3LA10 G1 M
11LB10
M
11LA10
11A72 BANCARIO 11T12
1T1A 5.4 MVAR
13.8Y KV/34.5Y kV T4 B A 3A41 3A43 13.95 KM
1.0 MVA S/E CALDERA M 3T1 G2 11LA22 11LA12 115Y/13.8Y KV
34-90

1G2
4.7 KM COSTA RICA 230-10 23B32 23M32 23A32 11LA21 11LA11 30/40/50 MVA
115Y/34.5 Δ KV 11B12 11M12 11A12
9.81 km M
62.5/62.5 MVA

11LA32
3T11 3T13

11LA31
34.5Y KV/0.48Y kV T5 T6 13.8YKV/0.48Y kV ACAR 750 18/19

11T31
11T21
11T11
11T12

11T22
11T3

11T32
1/1 MVA 2/2 MVA 23LA10 34.5/13.8kV CH MENDRE 2

5.00KM 477 AAC


3T12
OG3 OG4 T1 115-27

115-21
B A 22MVA 2X4.35MW 11B32 11M32 115-20B
23M12 23A12 11T1 39 km ACSR 636
G3 G4 AUTOTRAFO T1 G2
11B22 11M22 11A22 3A32 34-71 3LA10 11LA52
1.8MVA 230Y/115Y/34.5 kV 23LA20

9.0KM477AAC
650kVA 11XA G1
50/50/50 MVA 23M22 23A22 3A31 3A33 2.5 KM M 3T1
S/E LA ARENA S/E CALZADA LARGA T1 T2 T3
MCH MCH 3T2 23T2 115-19 M 11LB30 115-13

115-5
Hacia Bomba 11B12 11M12 11A12 115KV
BAJO DE MINA BAITÚN de Estacion 0.5 KM 150KVA 40.00 km 266 ACSR CEMEX CEMEX CEMEX
T2 23T1 M M
CH MENDRE 115-14 130 RAC1776 115Y/13.8Y KV
11LB10 11LA30
34.5/13.8kV
20.00 km ACSR 266 S/E CATIVA 52AUG9 115 Δ /4.38Y KV
115Y/4.38Y 37.5/50 MVA
S/E LA POTRA S/E SALSIPUEDES
11T2 AUTOTRAFO
230Y/115Y/34.5Δ kV
20/22MVA 2X9.376MW 11LA12 11LA11
13.8 Δ /115Y KV
S/E LAS MINAS #1 25/30MVA
115 Δ/13.8Y KV 10/10MVA
110Y/4.16YKV
KV 15/15MVA 11LA22
11LA12
3A22 3LA10 G2 A B T3 T2

115-20
230-37 100/100/100 MVA 34-57 75/100/125MVA T4 T1 10.5/10.5MVA 11LA22

0.1 KM
23LA10 2.192 km 3A21 3A23 2.5 KM M G1 11T22 11T12 153 127 128 152
ACSR 636 26/7

23LA10 3T1 3T1 52G8 11M11


ACSR 636 26/7

TG8 T12 11A92 148 140 139 147


33.5/33.5 MVA T1 T1 11T2A T1 115Y/34.5 Δ KV T2 T1 115Y/34.5 Δ KV 11LA12
1.70 km

33.5/33.5 MVA
6.18 km

A
115-18

115-17

34-41 25/25 MVA 50/50 MVA TURBINA DE 11A122 AUX.


6.6/230 kV 6.6/230 kV 0T1 11LA12 3T11 GAS GRAL. 120/240V 11T42 11T32 11T22 11XA
0T1 M 11T1 A S/E ASERRIO 3T1 52AUG8 145
34-41

3T2 ELECTRIC 35MW M


25KVA 115Y/13.8Y KV 115Y/13.8Y KV
115 KV M 11A112
3T12 11T2 11T1 50/50 MVA 46/46 MVA
OT3 13.8 Δ /115YKV 13.8 Δ /115YKV
S/E COCO SOLO
0G1
0G2

OT2 3B31
0G3
0G4

0G3
0G1
0G2

OT2 OT3
3LA10 3T13 3A12 9667 9668 9669 9670 3B32 39/52MVA T2 T1 39/52MVA 11A102
34-56 CT 115-41 T4
TSA1

TSA2

TSA1

T3
TSA2

A 34-56 11CA2 M 115-1C T2 T1

11.0 KM
B 3A11 3A13 447 FORRADO 1T2 1T1 2.70 KM 1200 MM, XLPE, AL
3.72 MVAR CATIVA

115-24
ACSR 636 26/7

447 FORRADO A 0.96 KM M


11LA10 11LA10 11CB2 11AB2 B CT 52AUG5 ACSR 636
400KVA 400KVA
6.6/0.48 kV
5976KVA 3B12 3M12 3A12 5976KVA S/E LOS VALLES 11T1 11T1 S/E LA ESTRELLA 9671 S/E POCRI 1G10 1G6 1G5 1G1
JOHN BROWN 13.8 Δ /115 Y KV
11A132 CM-B1 26/7 11AB1 AUX.
6.6/0.48 kV G1 G2 G3 G4 G1 G2 G3 120/240V
27.75 km

G10 - HASTA - G6 G5 - HASTA - G1 100/100 MVA


54/54 MVA
115-25

CH SALSIPUEDES 3X9.3MW 3LB10 54/54MVA 12.5 KM 11LA11 35MW TG5 25KVA


CH LA POTRA 3X9.3MW2.1MW 115Y/13.8 Δ kV
T1 T1
115Y/13.8 Δ kV
11T1 1T1
5X8.7MW 5X8.7MW 11A62
60/5A 9672 52G6 1T31
3TT1 TT1 60/5A 11T21 11T11 35MW TG6 T7
115-23 11LD 1T4 1T3B
3M22 3A22 EDECHI 34-51 34-56 11T22 11T12 11AB2 1T2 1T1
11XA 115Y/34.5 Δ KV 52AUG6 0.5 KM BARRA 13.8 KV 1T3A
4.16Y/115 Δ kV M 9640 9658 115Y/34.5 Δ KV T2 T1 11A52
3LA20 25/25 MVA 25/25 MVA 11AB3 11AB2
24/24 MVA 2X27.38MW 2X23.60MW 500XLPE AL 11BC2 11CD2 11DE1
3T2 3T1 115-20 11A42 11LC 11XC 3-4 2-3
52-8 3T2A CH LOS VALLES CH LA ESTRELLA 11DE2 11T22 11T12
S/E PROGRESO
34-42

3LA13 3TT2 3TT1 0.15 km M


T3 T2 T1
11XA 11T2 11XB IDAAN 11DE3
A S/E CHARCO AZUL 3T30 T1 M 115Y/13.8Y KV 115Y/13.8Y KV 115Y/13.8Y KV
T2 115-36 50/50 MVA 50/50 MVA
3B12 3M12 3A12 3T32 11A32 46/46 MVA
3LA12 34.5/13.8 KV 3-833 KVA 3-833 KVA 11LA12 11LB12 21C4 21C3B 21C2
A S/E PTO. ARMUELLES
T1 12/12MVA 3LB11 3LA11
M 1T3 1T21 1T1
115Y/13.8Y KV 115Y/13.8Y KV
S/E PROGRESO V S/E MONTE ESPERANZA 14011 ONAN/ONAF
B A 115-56A 11LG10 15/20/25MVA 15/20/25MVA 1T2B 1T2A 4.5 MVAR 5.4 MVAR 8.7 MVAR
ECOSOLAR II 1401 1T12 0.60 km 11A22 BARRA 13.8 KV
0.66/0.66/34.5 kV A 0.005 km
1 Terna 336 Linnet ACSS
14103 14102 S/E
14013 S/E 1PT1 1T21 34.5/13.8 KV T3 M 115-30
636 ACSR
89T11 A-12 89T12
S/E SAN FRANCISCO
5.1 MVA L-401 T2 5 MVA 115-52
GG1
A 1411 1421 1410 1441 B
1431
INDUSTRIAL AGUA CLARA 1G1 1G2 0A12 0A10
9.10 KM
2-3 1-2
OGG1 T1 141 T1 T2 142 143 M
T3 T4 144 6.3 MVAR
2.5 MW 4AB21 4AB23 4BC11 4XC 115-31 9.9 MVAR 8.1 MVAR
4XB L-401 11LF 636 ACSR 9.10 KM 11AB2
3T1 3T11 1T1 11-401 2401 5.4 MVAR 11LE 11EF2 11FG2 11GH2 11LH
4XA
GG2
2.5 MW OGG2 3LA11 43.8 Δ/4.16Y KV 1T3 9-30
4LA12 4LB12 11-402 2402 HACIA SISTEMA ACP
PT C1 C2 11T7A 115/13.8KV 11T14 115/13.8KV 11T15
S/E MARAÑON
0.66/0.66/34.5 kV T1 T2 T3 SERVICIOS

5.1 MVA 0.04 km


12/12MVA
14021 AUXILIARES 34-36 34-40 11DE2 S/E FRANCE11BC2
FIELD 11HA2 115-26
0.1 KM
3.6 MVAR 3.6 MVAR MVA
T14
MVA
T15
1 Terna 336 Linnet ACSS

43.8 Δ/13.8Y/4.16Y KV 11CD2 11AB2


2.30 KM

GG3 3LA12 44 Δ /13.8Y KV 1402 G1 G2


OGG3 T2 20/20/20 MVA 20/20/20MVA
14023 1C5 S/E CHILIBRE
15-21

3-333 KVA 1T14 11T7C


15-26
15-25
15-24
15-23

2.5 MW 2X4.929MW 1T15


15-22

15-20

11T5 11T3 11T2 11T1 1AB


0.2 km

CH LOS ALGARROBOS
34-166

3T2 3T12 OT2 OBT3 BARRA 13.8 KV 115-7.97Y/13.8Y KV


GG4 OAT3 T5 T3 T2 50/50 MVA 1G11 1G9 1G10 1G12
T1
2.5 MW OGG4
BT1 BT2 S/E COLON 1 15-1C5
11A82
T7A T7B T7C
75MVA
9AB
44-1 1614 1615 44-1
4LA10
3000A 115Y/13.8YKV
42/42 MVA
11T9
11T8
S/E CATIVA II 115/44KV
47MVA
115/44KV
50MVA
G11 G9 G10 G12 115/44KV
CT MIRAFLORES
S/E PROGRESO IV 1500 MCM-AL-EPR CU 0.33 KM CU 1500 MCM-AL-EPR 4DA12 4CD13
1T5 115Y/13.8YKV
30/40/50 MVA
115Y/43.8YKV
42/42 MVA T4 1XT1 S/E LAS MINAS 44
VIGADUCTO SUBTERRANEO 2.15 km 1.00 km RESPALDO
ECOSOLAR I 4AB12 115Y/13.8 Δ KV 3.0 MVAR 3.0 MVAR 7417A 7417C
0.66/0.66/34.5 kV A 1616 1618 4LB23 4LB21 4LA11 4LA13 4CD11 4T31 28/28MVA M M
43.8Y/13.8 Δ /115Y KV
56/56/56 MVA 11LA12 11LA22 S/E MIRAFLORES
44-3 1617 44-3 44-2 T9 3-500 KVA T8
5.1 MVA 1.2KM 1.0KM 7410
GG1 4LB22 4LA12 1500 MCM-AL-EPR 4LB10 4BC12 4T32 4T31 1T2C 1T2B 1T1 2.63MVA 2.63MVA
2.5 MW OGG1 T1 3.63 km 3000A 3000A 3000A 11T1 11T2 11T3 115/13.8Δ KV
75/75 MVA
4L1-1 3-500 KVA
3T1 3T11 52AB 52T8 T1 T2 T3
GG2 52T9 CT
2.5 MW OGG2 3LA11 3LB11
0.66/0.66/34.5 kV 34-166 HACIA HACIA HACIA 1G1 1G2 1G3 TERMOCOLÓN
4L1-2 4L1-7 G1 G2 G3
BARRA 1C BARRA 1B BARRA 1A
5.1 MVA 0.04 km 4.97 km 3X50MW
GG3 3LA12 1 Terna 336 Linnet ACSS 4AB2 4XB2
2.5 MW OGG3 T2
4XA2
3T2 3T12
GG4
2.5 MW OGG4

32 21 10 ENE-2021
REPÚBLICA DE PANAMÁ EMPRESA DE
OCT-2020 TRANSMISIÓN ELECTRICA, S.A.
LEYENDA
TRANSFORMADOR DE TRES 20 9
SIMBOLOGIA: CUCHILLA MANUAL
DEVANADOS AUTORREGULADO GRUPO GENERADOR CONJUNTO STATCOM
31
INTERRUPTOR DE AIRE NOTA: PENDIENTES POR VERIFICACIÓN EN CAMPO
30 19 8 JUL-2020 GERENCIA DE DISEÑO
TRANSFORMADOR DE TRES GENERADOR
CUCHILLA MOTORIZADA VOLTAJE 230 KV (MAGENTA)
INTERRUPTOR DE AIRE 13.8 kV DEVANADOS 29 18 7 NOV-2018
SUBTERRÁNEO
NOTA: PENDIENTES POR VERIFICACIÓN EN CAMPO VOLTAJE 115 KV (CELESTE)
REGULADOR DE VOLTAJE VOLTAJE 44 KV (AZUL) 28 17 6 AGO-2018
INTERRUPTOR DE HEXAFLORURO (SF6) TORRES
TRANSFORMADOR DE POTENCIA HOJA : 01 DE: 02
CUCHILLA DE ATERRIZAJE VOLTAJE 34.5 KV (AMARILLO) CENTRO NACIONAL DE DESPACHO
27 16 5 JUL-2018
INTERRUPTOR DE VACÍO REGULADOR DE VOLTAJE VOLTAJE 22.2 KV (VERDE OLIVA)

TRANSFORMADOR DE TIERRA
VOLTAJE 13.8 KV (CHOCOLATE) 26 15 4 ENE-2018 DIAGRAMA UNIFILAR
INTERRUPTOR DE ACEITE CUCHILLA MOTORIZADA DE DEL SISTEMA INTERCONECTADO NACIONAL
VOLTAJE 12.0 KV (ROSADO)
ATERRIZAJE REACTOR 25 14 SEP-2022 3 SEP-2017
REPRESENTADO POR VOLTAJE UNIF-GD-2022-09-001V-A
NOTAS GENERALES: VOLTAJE 6.9 KV (VERDE)
INTERRUPTOR DE CIRCUITO LAS DISTANCIAS (Km) DE LAS LÍNEAS ESTÁN VOLTAJE 6.6 KV (VERDE LIMA)
FUSIBLE DADAS POR LA LONGITUD DEL 24 13 DIC-2021 2 OCT-2016 DIBUJADO REVISADO VISTO BUENO
AUTOTRANSFORMADOR M MEDIDORES DEL MERCADO (SMC) CONDUCTOR. VOLTAJE 4.16 KV (NARANJA)
INTERRUPTOR EXTRAÍBLE (AIRE, AIRE 13.8, SF6, NOTA: PARA TRANSFORMADORES DE POTENCIA, T4 (230-55 Y 230-54) ESTÁ UBICADA VOLTAJE 2.4 KV, O MENOR (MORADO) JUL-2021 ESCALA:
VACÍO) TRANSFORMADORES DE TIERRA Y AUTOTRANSFORMADORES LA FÍSICAMENTE EN LT SANTA RITA - PANAMÁ. 23 12 1 JUL-2016
CAPACIDAD DE LOS TRANSFORMADORES ES POR EMBOBINADO
Y EN BASE A SU MÁXIMO ENFRIAMIENTO. O. ORTEGA D. JIMÉNEZ S/E
22 11 FEB-2021 0 DIC-2015 R. RICORD M. JAÉN L. HALPHEN
APROBADO POR:
REV. FECHA REV. FECHA REV. FECHA
CARLOS BARRETTO