Professional Documents
Culture Documents
Guo-Qiang Li ZHANG JIANG, 2017
Guo-Qiang Li ZHANG JIANG, 2017
A R T I C L E I N F O A BS T RAC T
Keywords: This paper presents experimental investigations on the thermal and mechanical behavior of composite floors
Fire resistance subjected to ISO standard fire. Four 5.2 m×3.7 m composite slabs are tested with different combinations of the
Experimental investigation presence of one unprotected secondary beam, direction of ribs, and location of the reinforcement. The
Composite floor experimental results show that the highest temperature in the reinforcements occurs during the cooling phase
Unprotected secondary beam
(30–50 °C increment after 10-min cooling). The temperature at the unexposed side of the slabs is below 100 °C
Direction of rib
up to 100-min heating, compared to the predicted fire resistance close to 90 mins from EC4. For the slabs
Location of reinforcement
EC4 without secondary beams, the cracks first occur around the boundaries of the slab, while for the slabs supported
by one unprotected secondary beam, concrete cracks first occur on the top of the slab above the beam due to the
negative bending moment, and later on develop around boundaries. Debonding is observed between the steel
deck and concrete slab. The secondary beam significantly impacts the deformation shape of tested slabs.
Although a large deflection, 1/20 of the span length, is reached in the tests, the composite slabs can still provide
sufficient load-bearing capacity due to membrane action. The occurrence of tensile membrane action is
confirmed by the measured tensile stress in the reinforcement and compressive stress in the concrete. A
comparison between measured and predicted fire resistance of the slabs indicates that EC4 calculations might
be used for the composite slabs beyond the specified geometry limit, and the prediction is conservative.
⁎
Corresponding author.
E-mail address: jiangjian_0131@163.com (J. Jiang).
http://dx.doi.org/10.1016/j.firesaf.2017.02.009
Received 20 August 2015; Received in revised form 21 February 2017; Accepted 26 February 2017
0379-7112/ © 2017 Elsevier Ltd. All rights reserved.
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Table 1
Summary of previous experiments on composite floor systems.
References Slab Slab size (m) Type of decking Secondary beam Test load Fire Maximum deflection
(kN/m2) (mm)
TNO tests Simply supported 3.2×0.9 Prins PSV 73 NA 5.8 ISO 834 290
[15] Continuous 3.2×0.9 150
2
Cardington tests BS Corner 9.5×6.5 PMF CF70 Unprotected 5.4 Wood ribs 40 kg/m 428
[11,18] BRE Corner 9×6 269
Test 7 11×7 6.0 1000
BRANZ Two-way 4.3×3.3 Hibond NA 5.5 ISO 834 253
[21]
Purdue Tests Two-way 4.6×4 Vulcraft 1.5VLR Unprotected and 9 ASTM E119 with 250
[26] protected cooling
Manchester tests One-way rotational 6.45×1.2 PMF CF60 NA 3.85–11.7 Parametric fire 33–103
[13] restrained
FRACOF Two-way 8.7×6.7 COFRAPLUS 60 Unprotected 5.1 ISO834 460
[29]
COSSFIRE Two-way 9×6.7 COFRAPLUS 60 Unprotected 3.9 ISO834 550
[28]
CTU test Two-way 4.5×3 TR40/160 NA 1.8 ISO834 300
[5]
64
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Table 2
Details of the tested slabs.
Specimen No. Arrangement of Concrete cover of reinforcement Direction of ribs Secondary beam Test load (kN/ Load Test duration
reinforcement (mm) m2) ratioa (min)
a
Load ratio: the ratio of applied load to the design load resistance
in fire. It was proven that the thickness of the steel deck had a
significant influence on the fire resistance of the composite slab.
However, the strength of the concrete and the mesh size only played
a minor role. Based on the NIST investigation on the WTC7 collapse,
McAllister [23] proposed that the floor beam length and connection
type impact the structural response of the floor system more signifi-
cantly than the girder studs and girder framing.
In order to study the influence of the boundary conditions, slab
layout, reinforcement location, and the unprotected secondary beams
on the development of tensile membrane action, four composite slabs
were tested in the furnace of State Key Laboratory for Disaster
Reduction in Civil Engineering in Tongji University. Unprotected
secondary beams were placed at the mid-span of two out of the four
slabs. The concrete cover of the reinforcement at the top of the slabs
were 21 mm and 30 mm respectively, to investigate to what extent the
Fig. 3. Test setup of S-1 and S-2 (unit: mm).
location of the reinforcement affects load-bearing capacity of composite
slabs. In the tests, the steel decks were welded to the protected primary
beams by shear studs. The primary beams were sitting on the furnace
wall, and were considered as solid beams in fire. The direction of deck
ribs was designed along the longer span in two slabs with the
unprotected secondary beam, and along the shorter span in the other
two. The temperature in the reinforcement and on the top and bottom
of the slab, the strain in the reinforcement and concrete, the deflection
of slabs were measured and discussed. The test results were also
compared to the EC4 calculations [9].
2. Test setup
65
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
vertically at each lower flange of the steel deck, as shown in Fig. 6. The
cross sections of hot-rolled I-type primary and secondary beams are
shown in Fig. 7. Grade 10.9 M16 high strength friction bolts were used
for beam-to-beam connection as shown in Figs. 8 and 9. The end of the
reinforcement penetrated the concrete and was extended for 150 mm
to simulate the boundary condition observed in Cardington fire tests
[18]: concrete crushing and reinforcement rupture above the primary
beams due to negative bending moment (Fig. 10).
66
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
between TB2 and the triangular plate, a steel hemisphere was welded to
the bottom of TB2 at each end. These steel hemispheres were put onto
the smaller circular holes/slots located at the center of the triangular
plates. The triangular loading plate was then supported at its vertices
on the slab. Three hemispheres were welded at the vertices to allow
rotations. A 150 mm by 150 mm by 10 mm steel plate was inserted
between the hemisphere (on the triangular loading plate) and the
concrete slab at each loading point to avoid the stress concentration.
The deformation and stress distribution in the triangular loading plate
was examined using Solid 92 element in the finite element software
ANSYS, as shown in Fig. 13. The figure shows that in most of the area
of the plate the stress level was lower than 50% of the strength at
yielding. The maximum deformation was less than 3 mm, which
Fig. 10. Extension of the reinforcement along the sides of the slab.
satisfied the test requirement. A total of two sets of the described
loading systems were used in the tests (one for half of the slab). The
Table 3
performance of the proposed loading systems at large deflections is
Material properties of concrete and reinforcement.
shown in Fig. 14. It was found that the loading points remained in the
Test No. Concrete Reinforcement initial position at the end of the tests.
strength (MPa)
Yield Ultimate fy/fu Ultimate
strength fy strength fu strain (%) 2.4. Instrumentation
(MPa) (MPa)
A total of 9 large-stroke LVDTs, 13 thermocouples, 26 steel strain
S−1 26.1 579.1 632.1 0.92 33.3
S−2 21.0 531.9 604.9 0.88 36.0 gauges, and 20 concrete strain gauges were installed in each specimen.
S−3 22.37 557.0 661.3 0.84 31.3 The LVDTs were located at the center, quarter span, and the sides of
S−4 22.87 the slab (on the top surface) to monitor the displacement profile
(shown in Fig. 15). The thermocouples were attached to the bottom
flange of the steel deck, to the top surface of the slab, and to the
piece of steel tube was welded to each end of TB1 to form a point
reinforcement embedded in the concrete to record the temperature at
contact. Two steel rods were welded on TB2 beside the contact point to
the exposed and unexposed surface of the slab, and in the reinforce-
prevent the unexpected lateral sliding of TB1. To allow the rotation
ment mesh as shown in Fig. 16. The steel strain gauges were installed
67
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Fig. 13. Stresses and displacements in the triangular loading plate (unit: MPa).
68
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Fig. 20. Comparison of the temperature at the bottom surface of the slabs.
Fig. 21. Comparison of the temperature on the top surface of the slabs.
Fig. 19. Comparison of ISO fire and the average furnace temperature. The test protocol is as follows:
Phase I: loading at ambient temperature. The slabs were loaded in
gauges is 10–60 °C. Accordingly, all the data on the temperature out of 10 even steps, until the designed testing load (in Table 2) was applied.
this range were ignored. The locations of the steel and concrete strain Phase II: heating process. ISO 834 standard fire was adopted. The
gauges are shown in Figs. 17 and 18, respectively. fire durations for the four slabs were 75 min, 90 min, 90 min, and
100 min, respectively.
69
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Table 4
Comparison of the temperature in the steel deck and reinforcement during heating and cooling phases.
T (°C) Time (min) Tmax (°C) Time (min) T (°C) Time (min) Tmax (°C) Time (min)
3. Test results
The targeted ISO 834 standard fire heating curve and the average
furnace temperatures for all tests are compared in Fig. 19. The
recorded furnace temperatures agree well with the ISO fire during
the heating phase. A cooling phase followed the heating phase under
the air circulation of the furnace, and the furnace temperature reduced
to 200 °C after 105 min cooling for S-1, and 300 °C after 80–90 min
cooling for S-2 to S-4.
The temperature at the bottom of the steel deck and on the top
surface of the four slabs are shown in Figs. 20 and 21, respectively. It is
observed that the temperature at the bottom of the slabs (above the
steel deck) is about 100 °C lower than the furnace temperature due to
the isolation of the steel deck. The temperature on the unexposed top
surface is less than 100 °C for all slabs due to the isolation of the
Fig. 23. Comparison of the temperature in the reinforcement at the center of the slabs. composite slabs and the evaporation of the remaining free water in the
concrete. The difference in the temperature at the unexposed surface
Phase III: cooling process. The furnace was cooled via natural air (Fig. 21) is due to the presence of the secondary beam. For S-1 and S-2,
circulation, until the residual deformation of the slab was stabilized. cracks first developed at the center of the slab due to the negative
Data acquisition remained operative during the entire cooling phase. bending moment above the secondary beam, while for S-3 and S-4,
Phase IV: unloading. The slabs were unloaded in 5 even steps. cracks first developed at the boundaries of the slab. The occurrence of
70
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
the sand pockets and the free water filling the voids are all factors
which may affect the temperature of the reinforcement.
Table 4 compares the maximum temperature in the steel deck and
in the reinforcement during the heating and cooling phases of the fire.
It was observed that the temperatures in the reinforcement reached
their maximum values during the cooling phase. The delay on the
occurrence of the highest temperature is more significant for the
reinforcement than the concrete. The temperatures in the reinforce-
ment continue to rise in the cooling phase for a period of 10 mins for S-
2, S-3, S-4 and 25 mins for S-1, and the increment is about 40 °C. This
indicates that there might be a potential failure after the peak
temperature has been reached at the end of the heating phase even if
the slab survives the heating phase of the fire. The post-peak of the
Fig. 26. Cracks on the side of S-1.
temperature in the reinforcement during the cooling phase should be
properly considered when determining the fire resistance of slabs
through membrane action.
Fig. 23 compares the temperature in the reinforcement at the center
of the slab. The temperatures measured in S-1 and S-2 are lower than
those in S-3 and S-4 due to the presence of the secondary beam. The
shielding effect of the secondary beams may lead to a temperature
reduction of 50–100 °C in the reinforcement.
The crack patterns past the tests are shown in Fig. 24. The crack
pattern of S-3 and S-4 is very similar to that of S-1 and S-2, except that
S-1 and S-2 have cracks aligned with the short sides above the
Fig. 27. Cracks at the corner of S-1. secondary beam due to the negative bending moment at the beginning
of the test. In all slabs, the elliptical cracks were developed at the
the crack tremendously encourages the local heat transfer, and boundary of the slab, which indicates the formation of the tensile
increases the temperature on the top surface at the center. membrane action. The concrete rings comprised between the quasi-
Fig. 22 shows the comparison of average temperatures in the elliptical cracks and the concrete outside the cracked elliptical zone
reinforcement of S-1 to S-4. It was found that the reinforcement formed the "compressive ring" which allows the membrane action to be
temperature of S-1 was lower than that of the other slabs. This was developed. Highly-visible cracks were found along the long and short
mainly due to the shorter heating period (75 mins) of S1, compared to sides of the slabs (as shown in Fig. 25). Cracks are also formed on the
about 100 mins for the other slabs. A big temperature gap was side due to the bending and pull-out trend of the steel bars (shown in
observed between S-1 and other slabs after 75-min heating. The lower Fig. 26). However, no significant bond-slip were observed between the
temperature in S1 was also due to the smaller furnace temperature steel bars and the concrete. After the test, cracks were observed at some
(about 20 °C~70 °C lower) as shown in Fig. 19. In addition, the corners (Fig. 27). The debonding between the steel deck and the
reinforcement in S1 had a larger distance to the fire-exposed surface concrete slab is shown in Fig. 28, which may have significant influence
of the slab (a distance of 21 mm to the top surface of the slab) and thus on the heat transfer through the depth of the slab. No collapse was
a lower temperature in it, compared to a distance of 30 mm for the found in the tests, which indicates that the load-bearing capacity of the
other three tested slabs. Besides, the grading of the coarse aggregate, slabs at high temperatures benefits from membrane action.
71
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Fig. 28. Debonding between the steel deck and the concrete.
Fig. 29. Comparison of the strain of the reinforcement in the middle of the slabs.
72
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Fig. 33. Deflection at the center of the slabs. Fig. 34. Deflection at various measuring points of S-1.
deflections during the heating phase than S-2 due to higher tempera- provided by the concrete ribs on the short span reinforcement in S-3
ture of steel deck (about 50 °C higher as shown in Fig. 20) and and S-4 may also have a slight contribution. As for the membrane
premature debonding at its lower flange (Fig. 28). However, S-1 had action, the reinforcement aligned with the short sides gives a major
a smaller maximum deflection because of the shorter heating period contribution to the bearing capacity, compared with the minor role of
and lower rebar temperature at the end of the test. The effect of steel the reinforcement aligned with the long sides. This is due to the fact
deck on the deflection of slabs is limited since it was at very high that the same central deflection induces larger strains and curvatures in
temperatures and subjected to severe material degradation. the bars aligned with the short sides. The lower temperature of the
A continuous increment of displacements was observed at the reinforcement along the short span of S-3 and S-4 resulted in smaller
beginning of the cooling phase for all tests, as shown in Fig. 33, which deflections, compared to S-1 and S-2.
leads to maximum deflections of 180 mm, 190 mm, 150 mm and Fig. 34 compares the deflection at various locations on S-1. It shows
150 mm for S-1 to S-4 respectively. This is mainly due to the further the deflection at Point 2 (refer to Fig. 15) is significantly smaller than
temperature increment (30–50 °C) in the reinforcement after 10 min the other two points due to the presence of the secondary beams. It
cooling. The larger central displacement of S-1 and S-2 is caused by the again proves the significant influence of the secondary beam on the
higher applied load (Table 2). In addition, the better fire protection deflection shape of the slabs.
73
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
Table 5
Comparison of the vertical displacements of four slabs during heating and cooling.
Specimen No. Ambient displacement (mm) End of heating Maximum values Residual displacement (3-h cooling) (mm)
Table 6
Moment resistances of the tested slabs from bending and membrane action calculated by EC4.
Test No. Fire duration Temperature of Mq (kNm) Distance of neutral axis to the top MT (kN·m)
(min) reinforcement (°C) surface of slabs (mm)
Bending Membrane of Membrane of Total
decking reinforcement
74
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
for Slabs S-3 and S-4). The temperatures of the lower flange, web and duration up to 100 mins, compared to a calculated fire resistance
upper flange of the deck were assumed the same. The critical of 93 mins based on EC4. This indicates a conservative prediction
temperature of the deck was thus determined as about 600 °C from of fire resistance by EC4. For the load-bearing criterion, the tensile
the equilibrium of MT=Mq. This critical temperature was equivalent to membrane action contributed to nearly 50% of the load-bearing
a fire resistance of about 40 mins. This calculated fire resistance is capacity of the tested slabs, which led to a fire resistance over
much smaller than the practical fire duration of the tested slabs without 100 mins. Based on the EC4, the calculated fire resistance is
collapse (over 90 mins). The enhancement of the load-bearing capacity 40 mins when the membrane action is not considered.
of the tested slabs can be attributed to the tensile membrane action. (4) For slabs with the secondary beam, concrete cracks were first
The moment resistances of the tested slabs at elevated temperatures observed at mid-span above the beam due to negative bending
were determined and listed in Table 6. The moment resistance from moments. For all tests, concrete cracks developed at the boundary
bending was determined by Eq. (3) using the measured temperature of of slabs due to membrane action. Some cracks also extended to the
steel deck and reinforcement in the tests. The moment resistances from side surface of slabs. Significant debonding of the steel deck and
the membrane action of the deck and reinforcement were calculated the concrete was observed, which can influence the heat transfer
from the product of their forces and maximum deflection of the slab. and the load bearing capacity of the slab.
Table 6 shows that the total mid-span moment resistance MT of the (5) The occurrence of membrane actions was confirmed by the tensile
tested slabs at the end of heating was larger than the load-induced stress measured in the reinforcements and primary compressive
moment Mq. This indicates that the composite slabs had a fire stress in the concrete.
resistance of at least 90 mins without any fire protection. The mem- (6) Large deflections were found at the quarter-span of slabs with a
brane effect of the reinforcement contributed nearly 50% of the secondary beam in the mid-span. A large deflection, about span/
moment resistance. The contribution from the steel decking through 20, was reached in the test without any collapse, which indicates a
membrane action was smaller than that from the bending, and reduced sufficient load-bearing capacity of composite floor systems when
significantly as temperature increased. exposed to fire.
In addition, a composite slab can be treated as an equivalent flat (7) Compared with the test results, the prediction of EC4 on the fire
concrete slab by using effective depth heff. For slabs having the same resistance and temperature of steel deck was conservative. The
lower flange and upper flange width, which is also the case in this application of EC4 equations can be extended to other geometric
study, EC4 suggests that the heff should be determined as the sum of configuration of composite slabs.
the thickness of the upper continuous flat part and one half the height
of the rib. The heff of the tested slabs was thus calculated to be 108 mm. Acknowledgements
EC4 also specifies the minimum effective thickness requirement as a
function of the standard fire resistance. For a fire resistance of The work presented in this paper was supported by the National
120 mins, the required minimum heff is 100 mm, which is smaller Natural Science Foundation of China with grant 51120185001 and
than 108 mm. Therefore the tested slab should have a fire resistance of 51408418.
120 mins at least. This seems reasonable since the temperature at the
top surface of the tested slabs was lower than 100 °C for a fire duration References
of 100 mins.
The calculation of fire resistance of composite slabs in EC4 applies [1] C.G. Bailey, T. Lennon, D.B. Moore, The behaviour of full-scale steel framed
to the slabs with a specified range on the width of the top of the rib buildings subject to compartment fires, Struct. Eng. 77 (8) (1999) 15–21.
[2] C.G. Bailey, D.S. White, D.B. Moore, The tensile membrane action of unrestrained
(80–155 mm), width of the lower flange (32–132 mm) and width of the composite slabs simulated under fire conditions, Eng. Struct. 22 (2000)
upper flange (40–115 mm), respectively (Table D.7 in EC4). These 1583–1595.
geometric limitations are drawn from the parametric studies by Both [3] C.G. Bailey, Efficient arrangement of reinforcement for membrane behaviour of
composite floor slabs in fire conditions, J. Constr. Steel Res. 59 (2003) 931–949.
[6]. The corresponding parameters for the tested slabs are 202 mm, [4] C.G. Bailey, W.S. Toh, Behaviour of concrete floor slabs at ambient and elevated
142 mm and 142 mm, respectively, which are out of the specified range temperatures, Fire Saf. J. 42 (2007) 425–436.
in EC4. This indicates that EC4 formulas might be used for the [5] J. Bednar, F. Wald, J. Vodicka, A. Kohoutkova, Experiments on membrane action
of composite floors with steel fiber reinforced concrete slab exposed to fire, Fire Saf.
composite slabs beyond those specified in EC4, and the prediction is J. 59 (2013) 111–121.
conservative. [6] C. Both, The fire resistance of composite steel-concrete slabs (Ph.D. dissertation),
Delft University of Technology, Delft, Netherlands, 1998.
[7] BS, The behavior of multi-storey steel framed buildings in fire. Reports of British
5. Conclusions
Steel, Swinder Technology Center, 1999.
[8] A.Y. Elghazouli, B.A. Izzuddin, A.J. Richardson, Numerical modelling of the
Four full-scale tests in fire were carried out on composite floor structural fire behaviour of composite buildings, Fire Saf. J. 35 (2000) 279–297.
systems supported by one unprotected secondary beam or not. The [9] EN 1994-1-2, Eurocode 4 Design of composite steel and concrete structures: Part 1.
2: General rules, Structural fire design, European Committee for Standardisation,
thermal field, the deflections, the crack patterns and the strains in both Brussels, 2005.
the reinforcement and the concrete were investigated. The results [10] R. Fike, V. Kodur, Enhancing the fire resistance of composite floor assemblies
presented and discussed in this paper allow to draw the following through the use of steel fiber reinforced concrete, Eng. Struct. 33 (2011)
2870–2878.
conclusions: [11] S. Foster, M. Chladna´, C. Hsieh, I. Burgess, R. Plank, Thermal and structural
behaviour of a full-scale composite building subject to a severe compartment fire,
(1) The highest temperatures of reinforcement and steel deck occurred Fire Saf. J. 42 (2007) 183–199.
[12] FRACOF, Fire resistance assessment of partially protected composite floors
during the cooling phase. The increment of the temperature in (FRACOF): Engineering background, Technical Report of European Coal and Steel
reinforcement is 30–50 °C after 10 mins of cooling. A potential Community (ECSC), 2010.
failure might occur during the cooling phase although the slabs [13] S. Guo, C.G. Bailey, Experimental behaviour of composite slabs during the heating
and cooling fire stages, Eng. Struct. 33 (2011) 563–571.
survives the heating process. [14] S. Guo, Experimental and numerical study on restrained composite slab during
(2) The location of the reinforcement had significant influence on its heating and cooling, J. Constr. Steel Res. 69 (2012) 95–105.
temperature. The shielding effect of the secondary beam led to a [15] R. Hamerlinck, L. Twilt, J. Stark, A numerical model for fire-exposed composite
steel/concrete slabs. in: Proceedings of the tenth International Specialty
temperature reduction of 50–100 °C in the reinforcement above
Conference on Cold-formed Steel Structures, USA, 115-130, 1990.
the beam. [16] Z. Huang, I.W. Burgess, R.J. Plank, Effective stiffness modelling of composite
(3) For the fire insulation criterion, the temperature on the unexposed concrete slabs in fire, Eng. Struct. 22 (9) (2000) 1133–1144.
side of all the tested slabs was less than 100 °C for a heating [17] B.A. Izzuddin, X.Y. Tao, A.Y. Elghazouli, Realistic modelling of composite and R/C
75
G.-Q. Li et al. Fire Safety Journal 89 (2017) 63–76
floor slabs under extreme loading–Part I: analytical method, J. Struct. Eng. 130 compartment under different heating regimes—part 1 (slab thermal gradients), Fire
(12) (2004) 1972–1984. Saf. J. 35 (2000) 99–116.
[18] B.R. Kirby, British steel technical European fire test program design, construction [25] A.M. Sanad, S. Lamont, A.S. Usmani, J.M. Rotter, Structural behaviour in a fire
and results, Fire, static and dynamic tests of building structures, London, 1997. compartment under different heating regimes—part 2 (slab mean temperatures),
[19] S. Lamont, A.S. Usmani, M. Gillie, Behaviour of a small composite steel frame Fire Saf. J. 35 (2000) 117–130.
structure in a “long-cool” and a “short-hot” fire, Fire Saf. J. 39 (2004) 327–357. [26] E.I. Wellman, A.H. Varma, R. Fike, V. Kodur, Experimental evaluation of thin
[20] G.Q. Li, S.X. Guo, H.S. Zhou, Modeling of membrane action in floor slabs subjected composite floor assemblies under fire loading, J. Struct. Eng. 137 (9) (2011)
to fire, Eng. Struct. 29 (6) (2007) 880–887. 1002–1016.
[21] L.C.S. Lim, A. Buchanan, P. Moss, J.M. Franssen, Numerical modelling of two-way [27] N.S. Zhang, G.Q. Li, A new method to analyze the membrane action of composite
reinforced concrete slabs in fire, Eng. Struct. 26 (2004) 1081–1091. floor slabs in fire condition, Fire Technol. 46 (2009) 3–18.
[22] L. Lim, C. Wade, Experimental fire tests of two-way concrete slabs (Fire [28] B. Zhao, M. Roosefid, A. Breunese, Connections of steel and composite structures
Engineering Research Report 02/12), University of Canterbury and BRANZ Ltd, under natural fire conditions (COSSFIRE), Technical Report of Research Found for
New Zealand, 2002. Cool & Steel (FRCS), 2011.
[23] T.P. McAllister, Sensitivity of composite floor system response at elevated [29] B. Zhao, M. Roosefid, O. Vassart, Full scale test of a steel and concrete composite
temperatures to structural features, Eng. Struct. 58 (2014) 115–128. floor exposed to ISO fire. Proceedings of 5th International Conference on
[24] A.M. Sanad, S. Lamont, A.S. Usmani, J.M. Rotter, Structural behaviour in a fire Structures in Fire, Singapore, 2008.
76