You are on page 1of 4

Worldwide

www.tyco-fire.com
Contacts

Two-Piece Recessed Escutcheons


and Protective Paint Caps for
Automatic Sprinkler Recessed Installation
Each two-piece escutcheon style pro-
IMPORTANT vides for recessed sprinkler installa-
Refer to Technical Data Sheet tions having total adjustments from the
TFP2300 for warnings pertaining to flush position as follows:
regulatory and health information.
Thread Total
Always refer to Technical Data Style Size Adjustment
Sheet TFP700 for the “INSTALLER Inch NPT Inch (mm)
WARNING” that provides cautions 10 1/2 3/4 (19,1)
with respect to handling and instal- 15 1/2 5/8 (15,9)
lation of sprinkler systems and com- 20 1/2 1/2 (12,7)
ponents. Improper handling and 30 3/4 1/2 (12,7)
installation can permanently damage
a sprinkler system or its compo- 40 3/4 3/4 (19,1)
nents and cause the sprinkler to fail 50 1/2 3/8 (9,5)
to operate in a fire situation or cause 70* 3/8 3/4 (19,1)
it to operate prematurely. * Use with Series TY-B and TY-FRB 10 mm orifice sprin-
klers only, refer to technical data sheet TFP670

The Style 10, 20, 30, 40, and 50


Scan the QR code or enter the URL Recessed Escutcheons are redesigna-
in a web browser to access the most tions for Central, Gem, and Star brands
up-to-date electronic version of this as follows:
document. Data rates may apply.
Style Central Gem Star
10 3211 F700 (1/2 in.) 2085
20 3221 F705 (1/2 in.) 2084
30 4221 F705 (3/4 in.) 2086 The owner is responsible for main-
40 4211 F700 (3/4 in.) 2088 taining their fire protection system
50 307X - -
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
Note: The Style 15 and 70 Recessed questions.
Escutcheons are not redesignated from In all cases, the appropriate NFPA or
any of the brands listed. FM Global installation standard, or
Install Protective Paint Caps to help other applicable standard, must be
protect the sprinklers while finishing referenced to ensure applicability and
ceilings or walls as seen in Figures to obtain complete installation guide-
docs.jci.com/tycofire/ 8 and 9. Protective Paint Caps are lines. The general guidelines in this
two-piece-recessed-escutcheons ordered separately. The Model Z-392 data sheet are not intended to provide
is suitable for use with the Style 10, 15, complete installation criteria.
20, 30, 40, or 70 Recessed Escutch-
General eons. The Model Z-84 is suitable for
Technical
use with Style 50 Recessed Escutch-
Description eon only.
Data
The TYCO Style 10, 15, 20, 30, 40, 50, Approvals
and 70 Recessed Escutcheons are NOTICE
Approval information, as applicable, for
designed for recessed installation with The Recessed Escutcheons described the Style 10, 15, 20, 30, 40, 50, and 70
certain pendent and horizontal sidewall herein must be installed and maintained Recessed Escutcheons is detailed in
sprinklers. They are intended for use in compliance with this document, as individual pendent and horizontal side-
in areas with finished ceilings or walls, well as with the applicable standards wall sprinkler data sheets that include
and the adjustment provided by these of the NATIONAL FIRE PROTECTION details of recessed installation.
escutcheons reduces the accuracy ASSOCIATION (NFPA), in addition to
to which fixed piping to the sprinklers the standards of any authorities having Materials and Finishes
must be cut, while providing a decora- jurisdiction, such as FM Global. Failure Carbon steel chrome plated, white or
tive recessed sprinkler installation. to do so may impair the performance black coated, or brass plated. Series
of these devices. 300 stainless steel white coated or
plain unpolished. Other colors are
available on special request.

Page 1 of 4 NOVEMBER 2021 TFP770


TFP770
Page 2 of 4

1/2" NPT 1-15/16" DIA. 1/2" NPT 1-15/16" DIA.


MOUNTING (49,2 mm) 1-1/8" (49,2 mm)
MOUNTING 1"
PLATE CLOSURE (28,6 mm) CLOSURE
PLATE (25,4 mm)

FLUSH TO 2-7/8" DIA. 1/8" FLUSH TO 2-7/8" DIA. 1/8"


3/4" (19,1 mm) (73,0 mm) (3,2 mm) 5/8" (15,9 mm) (73,0 mm) (3,2 mm)
FIGURE 1 FIGURE 2
STYLE 10 RECESSED ESCUTCHEON, STYLE 15 RECESSED ESCUTCHEON
1/2 IN. NPT - 3/4 IN. ADJUSTMENT 1/2 IN. NPT - 5/8 IN. ADJUSTMENT

1/2" NPT 1-15/16" DIA. 3/4" NPT 1-15/16" DIA.


MOUNTING (49,2 mm) MOUNTING (49,2 mm)
PLATE 13/16" PLATE 13/16"
CLOSURE (20,6 mm) CLOSURE (20,6 mm)

FLUSH TO 2-7/8" DIA. 1/8" FLUSH TO 2-7/8" DIA. 1/8"


1/2" (12,7 mm) (73,0 mm) (3,2 mm) 1/2" (12,7 mm) (73,0 mm) (3,2 mm)
FIGURE 3 FIGURE 4
STYLE 20 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
1/2 IN. NPT - 1/2 IN. ADJUSTMENT 3/4 IN. NPT - 1/2 IN. ADJUSTMENT

3/4" NPT 1-15/16" DIA. 1/2" NPT 1-13/16" DIA.


MOUNTING (49,2 mm) 1-1/8" SLOTTED (46,0 mm)
PLATE CLOSURE (28,6 mm) MOUNTING 13/16"
CLOSURE (20,6 mm)
PLATE

FLUSH TO 2-7/8" DIA. 1/8" FLUSH TO 2-7/8" DIA. 3/32"


3/4" (19,1 mm) (73,0 mm) (3,2 mm) 3/8" (9,5 mm) (73,0 mm) (2,4 mm)
FIGURE 5 FIGURE 6
STYLE 40 RECESSED ESCUTCHEON STYLE 50 RECESSED ESCUTCHEON
3/4 IN. NPT - 3/4 IN. ADJUSTMENT 1/2 IN. NPT - 3/8 IN. ADJUSTMENT

3/8" NPT 1-15/16" DIA.


MOUNTING (49,2 mm) 1-1/8"
PLATE CLOSURE (28,6 mm)

FLUSH TO 2-7/8" DIA. 1/8"


3/4" (19,1 mm) (73,0 mm) (3,2 mm)
FIGURE 7
STYLE 70 RECESSED ESCUTCHEON
3/8 IN. NPT - 3/4 IN. ADJUSTMENT
TFP770
Page 3 of 4

Care and
3-1/4"
(82 mm) Maintenance
Specific requirements of the NFPA
must be performed, and any impair-
ment must be immediately corrected.
Absence of an escutcheon to cover a
1-7/8" DIA.
(48 mm) FRICTION FIT clearance hole can delay the sprinkler
PAINT CAP OVER operation in a fire situation.
ESCUTCHEON The owner is responsible for the
MOUNTING PLATE inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
FIGURE 8 well as with the applicable standards
MODEL Z-392 PROTECTIVE PAINT CAP of the NFPA, such as NFPA 25, in addi-
FOR USE WITH STYLE 10, 15, 20, 30, 40, OR 70 tion to the standards of any authority
RECESSED ESCUTCHEON having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
2-1/2" Automatic sprinkler systems should be
(64 mm) inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.

1-13/16" DIA.
(46 mm) FRICTION FIT
PAINT CAP OVER
ESCUTCHEON
MOUNTING PLATE

FIGURE 9
MODEL Z-84 PROTECTIVE PAINT CAP
FOR USE WITH STYLE 50 RECESSED ESCUTCHEON

Recessed Protective
Escutcheon Paint Cap
Installation Installation
Installation information for the Style 10, With reference to Figures 8 and 9,
15, 20, 30, 40, 50, and 70 Recessed push the Protective Paint Cap over
Escutcheons is provided in individual the Mounting Plate of the Recessed
pendent and horizontal sidewall sprin- Escutcheon in lieu of the Closure.
kler data sheets, as applicable. These After the ceiling or wall finish is com-
data sheets also include details of plete, remove the Protective Paint Cap
recessed sprinkler installations. and install the Closure.
Note: The Style 10, 15, 20, 30, 40, 50, The Protective Paint Cap may be dis-
and 70 Recessed Escutcheons must carded as a plastic commodity or Low
only be used with the sprinklers for Density Polyethylene Recycling Cate-
which they have been specifically lab- gory 4, in conformance with local reg-
oratory approved by UL, C-UL, ULC, ulations. Alternatively, the Protective
or FM. Paint Cap may be reused.
Note: The sprinkler cannot operate
properly with the Protective Paint Cap
in place.
TFP770
Page 4 of 4

Limited Style 40
3/4 in. NPT (20 mm), 3/4 in. (19,1 mm)
Style 40
3/4 in. NPT (20 mm), 3/4 in. (19,1 mm)
Warranty total adjustment
Brass Plated ���������������������������������� 56-700-2-010
total adjustment
Signal White (RAL9003) ����������������56-700-4-010
For warranty terms and conditions, visit Pure White (RAL9010)* ������������������56-700-3-010 Plain Unpolished ���������������������������� 56-700-1-010
Signal White (RAL9003) ����������������56-700-4-010 Grey Aluminum (RAL9007) ������������ 56-700-7-010
www.tyco-fire.com. Jet Black (RAL9005) ����������������������56-700-6-010
Chrome Plated . . . . . . . . . . . . . . . 56-700-9-010 Style 50
Ordering Style 50
1/2 in. NPT (15 mm), 3/8 in. (9,5 mm)
total adjustment
Procedure 1/2 in. NPT (15 mm), 3/8 in. (9,5 mm)
total adjustment Signal White (RAL9003) ���������������� 56-711-0-010
Plain Unpolished ����������������������������� 56-711-1-010
Contact your local distributor for avail- Brass Plated . . . . . . . . . . . . . . . . . . 56-711-2-010
ability. When placing an order, indicate Pure White (RAL9010)* ������������������ 56-711-3-010 Style 70
the full product name and Part Number Signal White (RAL9003) ���������������� 56-711-4-010 For use with TY-B and TY-FRB 10 mm
(P/N).
Chrome Plated . . . . . . . . . . . . . . . 56-711-9-010 orifice sprinklers only, refer to data
Style 70 sheet TFP670
Protective Paint Cap For use with TY-B and TY-FRB 10 mm 3/8 in. NPT (10 mm), 3/4 in. (9,1 mm)
Specify: Model (specify) Protective orifice sprinklers only. Refer to data total adjustment
Paint Cap, P/N (specify): sheet TFP670
Model Z-84 . . . . . . . . . . . . . . . . . . . 56-711-1-084 ANZ only:
Model Z-392 . . . . . . . . . . . . . . . . . 92-000-0-412 3/8 in. NPT (10 mm), 3/4 in. (9,1 mm) Plain Unpolished �������������������������������ECPL2PS10
total adjustment
Recessed Escutcheon EMEA only:
Specify: Style (specify) Recessed ANZ only:
Plain Unpolished ����������������������������ESCSTDSS10
Escutcheon, (specify Carbon Steel Signal White (RAL9003) ������������������ECPL2PW10
or Stainless Steel), (specify) finish, Chrome Plated �������������������������������� ECPL2PC10
P/N (specify): Brass . . . . . . . . . . . . . . . . . . . . . . . . . ECPL2PB10
Jet Black (RAL9005) �����������������������ECPL2PBL10
Carbon Steel EMEA only:
Style 10 Pure White (RAL9010)* ������������������ESCSTDRA10
1/2 in. NPT (15 mm), 3/4 in. (19,1 mm) Signal White (RAL9003) �������������� ESCSTDWH10
total adjustment Chrome Plated . . . . . . . . . . . . . . . ESCSTDCH10
Brass . . . . . . . . . . . . . . . . . . . . . . . ESCSTDBR10
Brass Plated . . . . . . . . . . . . . . . . . 56-701-2-010 Jet Black (RAL9005) ���������������������� ESCSTDJB10
Pure White (RAL9010)* ������������������ 56-701-3-010
Signal White (RAL9003) ���������������� 56-701-4-010 * Eastern Hemisphere sales only
Jet Black (RAL9005) ���������������������� 56-701-6-010 Stainless Steel
Chrome Plated . . . . . . . . . . . . . . . 56-701-9-010
Style 10
Style 15 1/2 in. NPT (15 mm), 3/4 in. (19,1 mm)
1/2 in. NPT (15 mm), 5/8 in. (15,9 mm) total adjustment
total adjustment
Signal White (RAL9003) ���������������� 56-701-0-010
Brass Plated . . . . . . . . . . . . . . . . . 56-715-2-010 Plain Unpolished �����������������������������56-701-1-010
Pure White (RAL9010)* ������������������ 56-715-3-010 Grey Aluminum (RAL9007) �������������56-701-7-010
Signal White (RAL9003) ���������������� 56-715-4-010
Jet Black (RAL9005) ���������������������� 56-715-6-010 Style 15
Chrome plated . . . . . . . . . . . . . . . 56-715-9-010 1/2 in. NPT (15 mm), 5/8 in. (15,9 mm)
total adjustment
Style 20
1/2 in. NPT (15 mm), 1/2 in. (12,7 mm) Signal White (RAL9003) ���������������� 56-715-0-010
total adjustment Style 20
Brass Plated . . . . . . . . . . . . . . . . . 56-705-2-010 1/2 in. NPT (15 mm), 1/2 in. (12,7 mm)
Pure White (RAL9010)* ������������������56-705-3-010 total adjustment
Signal White (RAL9003) ����������������56-705-4-010
Jet Black (RAL9005) ����������������������56-705-6-010 Signal White (RAL9003) ����������������56-705-0-010
Chrome Plated . . . . . . . . . . . . . . . 56-705-9-010 Plain Unpolished ��������������������������� 56-705-1-010

Style 30 Style 30
3/4 in. NPT (20 mm), 1/2 in. (12,7 mm) 3/4 in. NPT (20 mm), 1/2 in. (12,7 mm)
total adjustment total adjustment
Brass Plated . . . . . . . . . . . . . . . . . 56-705-2-011 Signal White (RAL9003) ���������������� 56-705-0-011
Pure White (RAL9010)* ������������������ 56-705-3-011 Plain Unpolished �����������������������������56-705-1-011
Signal White (RAL9003) ���������������� 56-705-4-011
Jet Black (RAL9005) ���������������������� 56-705-6-011
Chrome Plated . . . . . . . . . . . . . . . 56-705-9-011

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association

You might also like