PurePowerTM 1050

WARNING: Do not remove case lid. Components inside Procedure:


case can hold charges even with the battery and input
power cord disconnected. 1 Make sure unit is shut down by pressing off button.
2 Disconnect input power cord.
Batteries can present a risk of electrical shocks or burn 3 Place unit at table edge, with front panel slightly
from high short circuit current. Do not attempt to alter any overhanging table.
battery wiring or connectors. 4 Remove 2 phillips head screws holding front bezel.
5 Hinge front bezel downward.
The following precautions should be observed: 6 Remove 2 phillips screws securing battery tray.
> Remove watches, rings or other metal objects. 7 Unplug battery connector by pulling connector apart.
> Use tools with insulated handles. 8 Discharge static charges by pressing on/off button for 3
> Do not lay tools or metal parts on top of batteries.. seconds.
9 Slide out battery tray, taking care to keep battery
interconnect wires from catching on case. Be careful,
batteries are heavy.
10 Place tray on flat surface.
11 Remove 4 tray cover screws.
12 Place replacement batteries in position alongside.
13 Place new batteries in same relative position as
batteries in the tray.
14 Remove leads from spade terminals on furthest
battery. Remove battery and replace with new battery.
Re-attach leads. Continue with all batteries.
15 Reverse removal procedure to complete process.

Test the new batteries:


Plug unit in. Turn on. When display reads “normal” press
and hold the on/off button momentarily (1 sec,) to initiate
a self test. If the batteries are functioning normally the
unit will switch to battery for 10 seconds. If the display
indicates an error, check all battery wiring connections.
Call PurePower tech support if the problem persists.

Recycling Used Batteries:


Contact your local recycling center for information on the
proper disposal of the used batteries.
> Do not dispose of the batteries in a fire. Batteries
may explode.
> Do not open or mutilate batteries. This product
contains sealed lead acid batteries and must be
disposed of properly.