System Power Requirements

Notifier NFS2-640 Fire Alarm Control Panel

Protected Premises: Date:


Address:
City: State: Zip:

Prepared By: Phone:


Address: Email:
City: State: Zip:

AC Branch Current Requirements 2.50 AMPS @ 220/240 VAC


Current required by source to power the fire
alarm system.

Primary Standby Load 0.49 Amps


Current load on the primary power supply during
non-alarm conditions.

Primary Alarm Load 0.88 Amps


Current load on the primary power supply during
alarm conditions.

Secondary Load Requirements 27.63 Amp Hours


Total Secondary Load from the calculation table below.

Current Draw Time (hours) Total (AH)


Secondary Standby Load Required Standby Time
x
0.470 A 48 hours 22.56
Secondary Alarm Load Required Alarm Time
x
0.923 A 0.500 hours 0.46
Total Secondary Load 23.02
Derating factor x 1.2
Secondary Load Requirements (Amp Hours) 27.63 AH

Battery Selection 18 Amp Hours


Select batteries from the list below.
18 AH BAT-12180 Battery (12 volt)
Two Four (two 12VDC sets in parallel)
TRUE
Battery Distribution Chart
Shows amp-hour distribution of your selections

Cannot Load Chart. The selected batteries do not have enough amp-
hour capacity to satisfy the needs of the current system. Select a
larger battery from the Battery Selection drop down list or reduce the
load on the system.

Comments
1. Batteries will fit in the FACP cabinet.
2. Selected battery size does not meet secondary load requirements.
3. The selected batteries (18AH) are within the charger range of this power supply (18-200AH).

Spare Battery Capacity -9.63 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 27.07 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 0.55 Secondary Alarm Load (AH) * Derating Factor

Page 4 of 5
Device Current Draw
NFS2-640 Fire Alarm Control Panel
Quantity x [device current draw] = total current draw per device (in amps
Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm
CPU2-640 1 x [0.25000] = 0.25000 x [0.25000] = 0.25000 x [0.25000] = 0.25000
CPS-24 1 x [0.00000] = 0.00000 x [0.00000] = 0.00000 x [0.04000] = 0.04000
# of NACs in use 1 x [0.03500] = 0.03500 x [0.03500] = 0.03500 x [0.03500] = 0.03500
LEM-320 (SLC2) 1 x [0.10000] = 0.10000 x [0.10000] = 0.10000 x [0.10000] = 0.10000
LCD2-80 1 x [0.10500] = 0.10500 x [0.09800] = 0.09800 x [0.04500] = 0.04500
SLC Loop Device Activation Current 2 x [0.00000] = 0.00000 x [0.20000] = 0.40000 x [0.00000] = 0.00000

Total (Amperes): 0.4900 A 0.8830 A 0.4700 A

Part Number Qty Secondary Alarm


Total Primary Alarm Load - C2 1 x [0.88300] = 0.88300
CPS-24 1 x [0.04000] = 0.04000

Total (Amperes): 0.9230 A