You are on page 1of 9

230.

1 ARTICLE 230 — SERVICES

Table 225.61 Clearances over Buildings and Other Structures


General Part I
Overhead Service Conductors Part II
Horizontal Vertical Underground Service Conductors Part III
Clearance from Conductors Service-Entrance Conductors Part IV
or Live Parts from: m ft m ft Service Equipment—General Part V
service point Service Equipment—Disconnecting Means Part VI
Building walls, projections, 2.3 7.5 — — Service Equipment—Overcurrent Protection Part VII
and windows Services Exceeding 1000 Volts, Nominal Part VIII
Balconies, catwalks, and 2.3 7.5 4.1 13.5
Serving Utility
similar areas accessible to
people Underground
Overhead
Over or under roofs or —
building —
exterior3.8 12.5 Last pole Street main
projections not readily
accessible to people Part II Overhead Underground Part III
Over roofs accessible to — — 4.1 13.5 service conductors service conductors
vehicles but not trucks 230.24 Clearances Depth of burial 230.32
Over roofs accessible to — — 5.6 18.5 and protection
trucks
Other structures 2.3 7.5 — — Service head Terminal box,
meter, or other
enclosure

ARTICLE 230
Service-entrance Part IV
Services conductors

Service equipment—general Part V


230.1 Scope. This article covers service conductors and equip‐
ment for control and protection of services and their installa‐ Grounding and bonding Article 250
tion requirements. Service equipment—
disconnecting means Part VI
Informational Note: See Figure 230.1.
Service equipment—
overcurrent protection Part VII
Part I. General
230.2 Number of Services. A building or other structure Branch circuits Articles 210, 225
served shall be supplied by only one service unless permitted in Feeders Articles 215, 225
230.2(A) through (D). For the purpose of 230.40, Exception
No. 2 only, underground sets of conductors, 1/0 AWG and
larger, running to the same location and connected together at FIGURE 230.1 Services.
their supply end but not connected together at their load end
shall be considered to be supplying one service.
(2) Where the load requirements of a single-phase installa‐
(A) Special Conditions. Additional services shall be permitted tion are greater than the serving agency normally
to supply the following: supplies through one service
(1) Fire pumps (3) By special permission
(2) Emergency systems
(3) Legally required standby systems (D) Different Characteristics. Additional services shall be
(4) Optional standby systems permitted for different voltages, frequencies, or phases, or for
(5) Parallel power production systems different uses, such as for different rate schedules.
(6) Systems designed for connection to multiple sources of (E) Identification. Where a building or structure is supplied
supply for the purpose of enhanced reliability by more than one service, or any combination of branch
(B) Special Occupancies. By special permission, additional circuits, feeders, and services, a permanent plaque or directory
services shall be permitted for either of the following: shall be installed at each service disconnect location denoting
all other services, feeders, and branch circuits supplying that
(1) Multiple-occupancy buildings where there is no available building or structure and the area served by each. See 225.37.
space for service equipment accessible to all occupants
(2) A single building or other structure sufficiently large to 230.3 One Building or Other Structure Not to Be Supplied
make two or more services necessary Through Another. Service conductors supplying a building or
other structure shall not pass through the interior of another
(C) Capacity Requirements. Additional services shall be building or other structure.
permitted under any of the following:
230.6 Conductors Considered Outside the Building. Conduc‐
(1) Where the capacity requirements are in excess of tors shall be considered outside of a building or other structure
2000 amperes at a supply voltage of 1000 volts or less under any of the following conditions:

70 –84 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 230 — SERVICES 230.24

(1) Where installed under not less than 50 mm (2 in.) of 230.23 Size and Rating.
concrete beneath a building or other structure
(2) Where installed within a building or other structure in a (A) General. Conductors shall have sufficient ampacity to
raceway that is encased in concrete or brick not less than carry the current for the load as calculated in accordance with
50 mm (2 in.) thick Article 220 and shall have adequate mechanical strength.
(3) Where installed in any vault that meets the construction (B) Minimum Size. The conductors shall not be smaller than
requirements of Article 450, Part III 8 AWG copper or 6 AWG aluminum or copper-clad aluminum.
(4) Where installed in conduit and under not less than
450 mm (18 in.) of earth beneath a building or other Exception: Conductors supplying only limited loads of a single branch
structure circuit — such as small polyphase power, controlled water heaters, and
(5) Where installed within rigid metal conduit (Type RMC) similar loads — shall not be smaller than 12 AWG hard-drawn copper
or intermediate metal conduit (Type IMC) used to or equivalent.
accommodate the clearance requirements in 230.24 and (C) Grounded Conductors. The grounded conductor shall
routed directly through an eave but not a wall of a build‐ not be less than the minimum size as required by 250.24(C).
ing
230.24 Clearances. Overhead service conductors shall not be
230.7 Other Conductors in Raceway or Cable. Conductors readily accessible and shall comply with 230.24(A) through (E)
other than service conductors shall not be installed in the same for services not over 1000 volts, nominal.
service raceway or service cable in which the service conductors
are installed. (A) Above Roofs. Conductors shall have a vertical clearance
of not less than 2.5 m (8 ft) above the roof surface. The vertical
Exception No. 1: Grounding electrode conductors or supply side bond‐ clearance above the roof level shall be maintained for a
ing jumpers or conductors shall be permitted within service raceways. distance of not less than 900 mm (3 ft) in all directions from
Exception No. 2: Load management control conductors having overcur‐ the edge of the roof.
rent protection shall be permitted within service raceways. Exception No. 1: The area above a roof surface subject to pedestrian or
230.8 Raceway Seal. Where a service raceway enters a build‐ vehicular traffic shall have a vertical clearance from the roof surface in
ing or structure from an underground distribution system, it accordance with the clearance requirements of 230.24(B).
shall be sealed in accordance with 300.5(G). Spare or unused Exception No. 2: Where the voltage between conductors does not exceed
raceways shall also be sealed. Sealants shall be identified for use 300 and the roof has a slope of 100 mm in 300 mm (4 in. in 12 in.) or
with the cable insulation, shield, or other components. greater, a reduction in clearance to 900 mm (3 ft) shall be permitted.
230.9 Clearances on Buildings. Service conductors and final Exception No. 3: Where the voltage between conductors does not exceed
spans shall comply with 230.9(A), (B), and (C). 300, a reduction in clearance above only the overhanging portion of the
(A) Clearances. Service conductors installed as open conduc‐ roof to not less than 450 mm (18 in.) shall be permitted if (1) not more
tors or multiconductor cable without an overall outer jacket than 1.8 m (6 ft) of overhead service conductors, 1.2 m (4 ft) horizon‐
shall have a clearance of not less than 900 mm (3 ft) from tally, pass above the roof overhang, and (2) they are terminated at a
windows that are designed to be opened, doors, porches, balco‐ through-the-roof raceway or approved support.
nies, ladders, stairs, fire escapes, or similar locations. Informational Note: See 230.28 for mast supports.
Exception: Conductors run above the top level of a window shall be Exception No. 4: The requirement for maintaining the vertical clear‐
permitted to be less than the 900 mm (3 ft) requirement. ance 900 mm (3 ft) from the edge of the roof shall not apply to the final
(B) Vertical Clearance. The vertical clearance of final spans conductor span where the service drop or overhead service conductors
above, or within 900 mm (3 ft) measured horizontally of plat‐ are attached to the side of a building.
forms, projections, or surfaces that will permit personal contact Exception No. 5: Where the voltage between conductors does not exceed
shall be maintained in accordance with 230.24(B). 300 and the roof area is guarded or isolated, a reduction in clearance
(C) Building Openings. Overhead service conductors shall to 900 mm (3 ft) shall be permitted.
not be installed beneath openings through which materials (B) Vertical Clearance for Overhead Service Conductors.
may be moved, such as openings in farm and commercial Overhead service conductors, where not in excess of 600 volts,
buildings, and shall not be installed where they obstruct nominal, shall have the following minimum clearance from
entrance to these building openings. final grade:
230.10 Vegetation as Support. Vegetation such as trees shall (1) 3.0 m (10 ft) — at the electrical service entrance to build‐
not be used for support of overhead service conductors or serv‐ ings, also at the lowest point of the drip loop of the build‐
ice equipment. ing electrical entrance, and above areas or sidewalks
accessible only to pedestrians, measured from final grade
or other accessible surface only for overhead service
Part II. Overhead Service Conductors conductors supported on and cabled together with a
grounded bare messenger where the voltage does not
230.22 Insulation or Covering. Individual conductors shall be
exceed 150 volts to ground
insulated or covered.
(2) 3.7 m (12 ft) — over residential property and driveways,
Exception: The grounded conductor of a multiconductor cable shall be and those commercial areas not subject to truck traffic
permitted to be bare. where the voltage does not exceed 300 volts to ground

2017 Edition NATIONAL ELECTRICAL CODE 70 –85


230.24 ARTICLE 230 — SERVICES

(3) 4.5 m (15 ft) — for those areas listed in the 3.7 m (12 ft) (1) Bare copper used in a raceway
classification where the voltage exceeds 300 volts to (2) Bare copper for direct burial where bare copper is approved for the
ground soil conditions
(4) 5.5 m (18 ft) — over public streets, alleys, roads, parking (3) Bare copper for direct burial without regard to soil conditions
areas subject to truck traffic, driveways on other than resi‐ where part of a cable assembly identified for underground use
dential property, and other land such as cultivated, graz‐ (4) Aluminum or copper-clad aluminum without individual insula‐
ing, forest, and orchard tion or covering where part of a cable assembly identified for
(5) 7.5 m (241∕2) over tracks of railroads underground use in a raceway or for direct burial
(C) Clearance from Building Openings. See 230.9. (B) Wiring Methods. Underground service conductors shall
be installed in accordance with the applicable requirements of
(D) Clearance from Swimming Pools. See 680.9. this Code covering the type of wiring method used and shall be
(E) Clearance from Communication Wires and Cables. Clear‐ limited to the following methods:
ance from communication wires and cables shall be in accord‐ (1) Type RMC conduit
ance with 830.44(A)(4). (2) Type IMC conduit
230.26 Point of Attachment. The point of attachment of the (3) Type NUCC conduit
overhead service conductors to a building or other structure (4) Type HDPE conduit
shall provide the minimum clearances as specified in 230.9 and (5) Type PVC conduit
230.24. In no case shall this point of attachment be less than (6) Type RTRC conduit
3.0 m (10 ft) above finished grade. (7) Type IGS cable
(8) Type USE conductors or cables
230.27 Means of Attachment. Multiconductor cables used for (9) Type MV or Type MC cable identified for direct burial
overhead service conductors shall be attached to buildings or applications
other structures by fittings identified for use with service (10) Type MI cable, where suitably protected against physical
conductors. Open conductors shall be attached to fittings iden‐ damage and corrosive conditions
tified for use with service conductors or to noncombustible,
nonabsorbent insulators securely attached to the building or 230.31 Size and Rating.
other structure. (A) General. Underground service conductors shall have
230.28 Service Masts as Supports. Only power service-drop or sufficient ampacity to carry the current for the load as calcula‐
overhead service conductors shall be permitted to be attached ted in accordance with Article 220 and shall have adequate
to a service mast. Service masts used for the support of service- mechanical strength.
drop or overhead service conductors shall be installed in (B) Minimum Size. The conductors shall not be smaller than
accordance with 230.28(A) and (B). 8 AWG copper or 6 AWG aluminum or copper-clad aluminum.
(A) Strength. The service mast shall be of adequate strength Exception: Conductors supplying only limited loads of a single branch
or be supported by braces or guys to withstand safely the strain circuit — such as small polyphase power, controlled water heaters, and
imposed by the service-drop or overhead service conductors. similar loads — shall not be smaller than 12 AWG copper or 10 AWG
Hubs intended for use with a conduit that serves as a service aluminum or copper-clad aluminum.
mast shall be identified for use with service-entrance equip‐
ment. (C) Grounded Conductors. The grounded conductor shall
not be less than the minimum size required by 250.24(C).
(B) Attachment. Service-drop or overhead service conductors
shall not be attached to a service mast between a weatherhead 230.32 Protection Against Damage. Underground service
or the end of the conduit and a coupling, where the coupling conductors shall be protected against damage in accordance
is located above the last point of securement to the building or with 300.5. Service conductors entering a building or other
other structure or is located above the building or other struc‐ structure shall be installed in accordance with 230.6 or protec‐
ture. ted by a raceway wiring method identified in 230.43.

230.29 Supports over Buildings. Service conductors passing 230.33 Spliced Conductors. Service conductors shall be
over a roof shall be securely supported by substantial struc‐ permitted to be spliced or tapped in accordance with 110.14,
tures. For a grounded system, where the substantial structure is 300.5(E), 300.13, and 300.15.
metal, it shall be bonded by means of a bonding jumper and
listed connector to the grounded overhead service conductor.
Where practicable, such supports shall be independent of the Part IV. Service-Entrance Conductors
building. 230.40 Number of Service-Entrance Conductor Sets. Each
service drop, set of overhead service conductors, set of under‐
ground service conductors, or service lateral shall supply only
Part III. Underground Service Conductors one set of service-entrance conductors.
230.30 Installation. Exception No. 1: A building with more than one occupancy shall be
(A) Insulation. Underground service conductors shall be insu‐ permitted to have one set of service-entrance conductors for each service,
lated for the applied voltage. as defined in 230.2, run to each occupancy or group of occupancies. If
the number of service disconnect locations for any given classification of
Exception: A grounded conductor shall be permitted to be uninsulated service does not exceed six, the requirements of 230.2(E) shall apply at
as follows: each location. If the number of service disconnect locations exceeds six

70 –86 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 230 — SERVICES 230.44

for any given supply classification, all service disconnect locations for Exception No. 2: The sum of the noncontinuous load and the continu‐
all supply characteristics, together with any branch circuit or feeder ous load if the service-entrance conductors terminate in an overcurrent
supply sources, if applicable, shall be clearly described using suitable device where both the overcurrent device and its assembly are listed for
graphics or text, or both, on one or more plaques located in an operation at 100 percent of their rating shall be permitted.
approved, readily accessible location(s) on the building or structure
served and as near as practicable to the point(s) of attachment or (2) The minimum service-entrance conductor size shall have
entry(ies) for each service drop or service lateral, and for each set of an ampacity not less than the maximum load to be served
overhead or underground service conductors. after the application of any adjustment or correction
factors.
Exception No. 2: Where two to six service disconnecting means in sepa‐
rate enclosures are grouped at one location and supply separate loads (B) Specific Installations. In addition to the requirements of
from one service drop, set of overhead service conductors, set of under‐ 230.42(A), the minimum ampacity for ungrounded conductors
ground service conductors, or service lateral, one set of service-entrance for specific installations shall not be less than the rating of the
conductors shall be permitted to supply each or several such service service disconnecting means specified in 230.79(A) through
equipment enclosures. (D).

Exception No. 3: A one-family dwelling unit and its accessory struc‐ (C) Grounded Conductors. The grounded conductor shall
tures shall be permitted to have one set of service-entrance conductors not be smaller than the minimum size as required by
run to each from a single service drop, set of overhead service conduc‐ 250.24(C).
tors, set of underground service conductors, or service lateral. 230.43 Wiring Methods for 1000 Volts, Nominal, or Less.
Exception No. 4: Two-family dwellings, multifamily dwellings, and Service-entrance conductors shall be installed in accordance
multiple occupancy buildings shall be permitted to have one set of with the applicable requirements of this Code covering the type
service-entrance conductors installed to supply the circuits covered in of wiring method used and shall be limited to the following
210.25. methods:
(1) Open wiring on insulators
Exception No. 5: One set of service-entrance conductors connected to the (2) Type IGS cable
supply side of the normal service disconnecting means shall be permitted (3) Rigid metal conduit (RMC)
to supply each or several systems covered by 230.82(5) or 230.82(6). (4) Intermediate metal conduit (IMC)
230.41 Insulation of Service-Entrance Conductors. Service- (5) Electrical metallic tubing (EMT)
entrance conductors entering or on the exterior of buildings (6) Electrical nonmetallic tubing
or other structures shall be insulated. (7) Service-entrance cables
(8) Wireways
Exception: A grounded conductor shall be permitted to be uninsulated (9) Busways
as follows: (10) Auxiliary gutters
(1) Bare copper used in a raceway or part of a service cable assembly (11) Rigid polyvinyl chloride conduit (PVC)
(2) Bare copper for direct burial where bare copper is approved for the (12) Cablebus
soil conditions (13) Type MC cable
(3) Bare copper for direct burial without regard to soil conditions (14) Mineral-insulated, metal-sheathed cable, Type MI
where part of a cable assembly identified for underground use (15) Flexible metal conduit (FMC) not over 1.8 m (6 ft) long
(4) Aluminum or copper-clad aluminum without individual insula‐ or liquidtight flexible metal conduit (LFMC) not over
tion or covering where part of a cable assembly or identified for 1.8 m (6 ft) long between a raceway, or between a race‐
underground use in a raceway, or for direct burial way and service equipment, with a supply-side bonding
(5) Bare conductors used in an auxiliary gutter jumper routed with the flexible metal conduit (FMC) or
the liquidtight flexible metal conduit (LFMC) according
230.42 Minimum Size and Rating. to the provisions of 250.102(A), (B), (C), and (E)
(A) General. Service-entrance conductors shall have an (16) Liquidtight flexible nonmetallic conduit (LFNC)
ampacity of not less than the maximum load to be served. (17) High density polyethylene conduit (HDPE)
Conductors shall be sized to carry not less than the largest of (18) Nonmetallic underground conduit with conductors
230.42(A)(1) or (A)(2). Loads shall be determined in accord‐ (NUCC)
ance with Part III, IV, or V of Article 220, as applicable. Ampac‐ (19) Reinforced thermosetting resin conduit (RTRC)
ity shall be determined from 310.15. The maximum allowable 230.44 Cable Trays. Cable tray systems shall be permitted to
current of busways shall be that value for which the busway has support service-entrance conductors. Cable trays used to
been listed or labeled. support service-entrance conductors shall contain only service-
(1) Where the service-entrance conductors supply continu‐ entrance conductors and shall be limited to the following
ous loads or any combination of noncontinuous and methods:
continuous loads, the minimum service-entrance conduc‐ (1) Type SE cable
tor size shall have an allowable ampacity not less than the (2) Type MC cable
sum of the noncontinuous loads plus 125 percent of (3) Type MI cable
continuous loads. (4) Type IGS cable
Exception No. 1: Grounded conductors that are not connected to an (5) Single conductors 1/0 and larger that are listed for use in
overcurrent device shall be permitted to be sized at 100 percent of the cable tray
sum of the continuous and noncontinuous load. Such cable trays shall be identified with permanently affixed
labels with the wording “Service-Entrance Conductors.” The

2017 Edition NATIONAL ELECTRICAL CODE 70 –87


230.46 ARTICLE 230 — SERVICES

labels shall be located so as to be visible after installation with a (B) Other Cables. Cables that are not approved for mounting
spacing not to exceed 3 m (10 ft) so that the service-entrance in contact with a building or other structure shall be mounted
conductors are able to be readily traced through the entire on insulating supports installed at intervals not exceeding
length of the cable tray. 4.5 m (15 ft) and in a manner that maintains a clearance of not
less than 50 mm (2 in.) from the surface over which they pass.
Exception: Conductors, other than service-entrance conductors, shall be
permitted to be installed in a cable tray with service-entrance conduc‐ (C) Individual Open Conductors. Individual open conductors
tors, provided a solid fixed barrier of a material compatible with the shall be installed in accordance with Table 230.51(C). Where
cable tray is installed to separate the service-entrance conductors from exposed to the weather, the conductors shall be mounted on
other conductors installed in the cable tray. insulators or on insulating supports attached to racks, brackets,
or other approved means. Where not exposed to the weather,
230.46 Spliced Conductors. Service-entrance conductors shall the conductors shall be mounted on glass or porcelain knobs.
be permitted to be spliced or tapped in accordance with
110.14, 300.5(E), 300.13, and 300.15. 230.52 Individual Conductors Entering Buildings or Other
Structures. Where individual open conductors enter a build‐
230.50 Protection Against Physical Damage. ing or other structure, they shall enter through roof bushings
(A) Underground Service-Entrance Conductors. Under‐ or through the wall in an upward slant through individual,
ground service-entrance conductors shall be protected against noncombustible, nonabsorbent insulating tubes. Drip loops
physical damage in accordance with 300.5. shall be formed on the conductors before they enter the tubes.

(B) All Other Service-Entrance Conductors. All other service- 230.53 Raceways to Drain. Where exposed to the weather,
entrance conductors, other than underground service entrance raceways enclosing service-entrance conductors shall be listed
conductors, shall be protected against physical damage as or approved for use in wet locations and arranged to drain.
specified in 230.50(B)(1) or (B)(2). Where embedded in masonry, raceways shall be arranged to
drain.
(1) Service-Entrance Cables. Service-entrance cables, where
subject to physical damage, shall be protected by any of the 230.54 Overhead Service Locations.
following: (A) Service Head. Service raceways shall be equipped with a
(1) Rigid metal conduit (RMC) service head at the point of connection to service-drop or over‐
(2) Intermediate metal conduit (IMC) head service conductors. The service head shall be listed for
(3) Schedule 80 PVC conduit use in wet locations.
(4) Electrical metallic tubing (EMT)
(5) Reinforced thermosetting resin conduit (RTRC) (B) Service-Entrance Cables Equipped with Service Head or
(6) Other approved means Gooseneck. Service-entrance cables shall be equipped with a
service head. The service head shall be listed for use in wet
(2) Other Than Service-Entrance Cables. Individual open locations.
conductors and cables, other than service-entrance cables, shall
not be installed within 3.0 m (10 ft) of grade level or where Exception: Type SE cable shall be permitted to be formed in a gooseneck
exposed to physical damage. and taped with a self-sealing weather-resistant thermoplastic.

Exception: Type MI and Type MC cable shall be permitted within 3.0 m (C) Service Heads and Goosenecks Above Service-Drop or
(10 ft) of grade level where not exposed to physical damage or where Overhead Service Attachment. Service heads on raceways or
protected in accordance with 300.5(D). service-entrance cables and goosenecks in service-entrance
cables shall be located above the point of attachment of the
230.51 Mounting Supports. Service-entrance cables or indi‐ service-drop or overhead service conductors to the building or
vidual open service-entrance conductors shall be supported as other structure.
specified in 230.51(A), (B), or (C).
Exception: Where it is impracticable to locate the service head or goose‐
(A) Service-Entrance Cables. Service-entrance cables shall be neck above the point of attachment, the service head or gooseneck loca‐
supported by straps or other approved means within 300 mm tion shall be permitted not farther than 600 mm (24 in.) from the point
(12 in.) of every service head, gooseneck, or connection to a of attachment.
raceway or enclosure and at intervals not exceeding 750 mm
(30 in.). (D) Secured. Service-entrance cables shall be held securely in
place.

Table 230.51(C) Supports

Minimum Clearance
Maximum Distance Between
Supports Between Conductors From Surface
Maximum
Volts m ft mm in. mm in.
1000 2.7 9 150 6 50 2
1000 4.5 15 300 12 50 2
300 1.4 41∕2 75 3 50 2
1000* 1.4* 41∕2* 65* 21∕2* 25* 1*
*Where not exposed to weather.

70 –88 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 230 — SERVICES 230.72

(E) Separately Bushed Openings. Service heads shall have (2) Bathrooms. Service disconnecting means shall not be
conductors of different potential brought out through sepa‐ installed in bathrooms.
rately bushed openings.
(3) Remote Control. Where a remote control device(s) is
Exception: For jacketed multiconductor service-entrance cable without used to actuate the service disconnecting means, the service
splice. disconnecting means shall be located in accordance with
230.70(A)(1).
(F) Drip Loops. Drip loops shall be formed on individual
conductors. To prevent the entrance of moisture, service- (B) Marking. Each service disconnect shall be permanently
entrance conductors shall be connected to the service-drop or marked to identify it as a service disconnect.
overhead service conductors either (1) below the level of the
service head or (2) below the level of the termination of the (C) Suitable for Use. Each service disconnecting means shall
service-entrance cable sheath. be suitable for the prevailing conditions. Service equipment
installed in hazardous (classified) locations shall comply with
(G) Arranged That Water Will Not Enter Service Raceway or the requirements of Articles 500 through 517.
Equipment. Service-entrance and overhead service conductors
shall be arranged so that water will not enter service raceway or 230.71 Maximum Number of Disconnects.
equipment. (A) General. The service disconnecting means for each serv‐
230.56 Service Conductor with the Higher Voltage to Ground. ice permitted by 230.2, or for each set of service-entrance
On a 4-wire, delta-connected service where the midpoint of one conductors permitted by 230.40, Exception No. 1, 3, 4, or 5,
phase winding is grounded, the service conductor having the shall consist of not more than six switches or sets of circuit
higher phase voltage to ground shall be durably and perma‐ breakers, or a combination of not more than six switches and
nently marked by an outer finish that is orange in color, or by sets of circuit breakers, mounted in a single enclosure, in a
other effective means, at each termination or junction point. group of separate enclosures, or in or on a switchboard or in
switchgear. There shall be not more than six sets of disconnects
per service grouped in any one location.
Part V. Service Equipment — General For the purpose of this section, disconnecting means instal‐
230.62 Service Equipment — Enclosed or Guarded. Ener‐ led as part of listed equipment and used solely for the following
gized parts of service equipment shall be enclosed as specified shall not be considered a service disconnecting means:
in 230.62(A) or guarded as specified in 230.62(B). (1) Power monitoring equipment
(2) Surge-protective device(s)
(A) Enclosed. Energized parts shall be enclosed so that they (3) Control circuit of the ground-fault protection system
will not be exposed to accidental contact or shall be guarded as (4) Power-operable service disconnecting means
in 230.62(B).
(B) Single-Pole Units. Two or three single-pole switches or
(B) Guarded. Energized parts that are not enclosed shall be breakers, capable of individual operation, shall be permitted
installed on a switchboard, panelboard, or control board and on multiwire circuits, one pole for each ungrounded conduc‐
guarded in accordance with 110.18 and 110.27. Where ener‐ tor, as one multipole disconnect, provided they are equipped
gized parts are guarded as provided in 110.27(A)(1) and with identified handle ties or a master handle to disconnect all
(A)(2), a means for locking or sealing doors providing access conductors of the service with no more than six operations of
to energized parts shall be provided. the hand.
230.66 Marking. Service equipment rated at 1000 volts or less Informational Note: See 408.36, Exception No. 1 and Exception
shall be marked to identify it as being suitable for use as service No. 3, for service equipment in certain panelboards, and see
equipment. All service equipment shall be listed or field 430.95 for service equipment in motor control centers.
labeled. Individual meter socket enclosures shall not be consid‐
ered service equipment but shall be listed and rated for the 230.72 Grouping of Disconnects.
voltage and ampacity of the service. (A) General. The two to six disconnects as permitted in
Exception: Meter sockets supplied by and under the exclusive control of 230.71 shall be grouped. Each disconnect shall be marked to
an electric utility shall not be required to be listed. indicate the load served.
Exception: One of the two to six service disconnecting means permitted
in 230.71, where used only for a water pump also intended to provide
Part VI. Service Equipment — Disconnecting Means fire protection, shall be permitted to be located remote from the other
230.70 General. Means shall be provided to disconnect all disconnecting means. If remotely installed in accordance with this
conductors in a building or other structure from the service- exception, a plaque shall be posted at the location of the remaining
entrance conductors. grouped disconnects denoting its location.

(A) Location. The service disconnecting means shall be instal‐ (B) Additional Service Disconnecting Means. The one or
led in accordance with 230.70(A)(1), (A)(2), and (A)(3). more additional service disconnecting means for fire pumps,
emergency systems, legally required standby, or optional
(1) Readily Accessible Location. The service disconnecting standby services permitted by 230.2 shall be installed remote
means shall be installed at a readily accessible location either from the one to six service disconnecting means for normal
outside of a building or structure or inside nearest the point of service to minimize the possibility of simultaneous interruption
entrance of the service conductors. of supply.

2017 Edition NATIONAL ELECTRICAL CODE 70 –89


230.72 ARTICLE 230 — SERVICES

(C) Access to Occupants. In a multiple-occupancy building, 230.81 Connection to Terminals. The service conductors shall
each occupant shall have access to the occupant’s service be connected to the service disconnecting means by pressure
disconnecting means. connectors, clamps, or other approved means. Connections
that depend on solder shall not be used.
Exception: In a multiple-occupancy building where electric service and
electrical maintenance are provided by the building management and 230.82 Equipment Connected to the Supply Side of Service
where these are under continuous building management supervision, Disconnect. Only the following equipment shall be permitted
the service disconnecting means supplying more than one occupancy to be connected to the supply side of the service disconnecting
shall be permitted to be accessible to authorized management personnel means:
only. (1) Cable limiters or other current-limiting devices.
230.74 Simultaneous Opening of Poles. Each service discon‐ (2) Meters and meter sockets nominally rated not in excess of
nect shall simultaneously disconnect all ungrounded service 1000 volts, if all metal housings and service enclosures are
conductors that it controls from the premises wiring system. grounded in accordance with Part VII and bonded in
accordance with Part V of Article 250.
230.75 Disconnection of Grounded Conductor. Where the (3) Meter disconnect switches nominally rated not in excess
service disconnecting means does not disconnect the grounded of 1000 V that have a short-circuit current rating equal to
conductor from the premises wiring, other means shall be or greater than the available short-circuit current, if all
provided for this purpose in the service equipment. A terminal metal housings and service enclosures are grounded in
or bus to which all grounded conductors can be attached by accordance with Part VII and bonded in accordance with
means of pressure connectors shall be permitted for this Part V of Article 250. A meter disconnect switch shall be
purpose. In a multisection switchboard or switchgear, discon‐ capable of interrupting the load served. A meter discon‐
nects for the grounded conductor shall be permitted to be in nect shall be legibly field marked on its exterior in a
any section of the switchboard or switchgear, if the switchboard manner suitable for the environment as follows:
or switchgear section is marked to indicate a grounded conduc‐ METER DISCONNECT
tor disconnect is located within. NOT SERVICE EQUIPMENT
230.76 Manually or Power Operable. The service disconnect‐ (4) Instrument transformers (current and voltage), impe‐
ing means for ungrounded service conductors shall consist of dance shunts, load management devices, surge arresters,
one of the following: and Type 1 surge-protective devices.
(5) Taps used only to supply load management devices,
(1) A manually operable switch or circuit breaker equipped circuits for standby power systems, fire pump equipment,
with a handle or other suitable operating means and fire and sprinkler alarms, if provided with service
(2) A power-operated switch or circuit breaker, provided the equipment and installed in accordance with require‐
switch or circuit breaker can be opened by hand in the ments for service-entrance conductors.
event of a power supply failure (6) Solar photovoltaic systems, fuel cell systems, wind electric
230.77 Indicating. The service disconnecting means shall systems, energy storage systems, or interconnected elec‐
plainly indicate whether it is in the open (off) or closed (on) tric power production sources.
position. (7) Control circuits for power-operable service disconnecting
means, if suitable overcurrent protection and disconnect‐
230.79 Rating of Service Disconnecting Means. The service ing means are provided.
disconnecting means shall have a rating not less than the calcu‐ (8) Ground-fault protection systems or Type 2 surge-
lated load to be carried, determined in accordance with protective devices, where installed as part of listed equip‐
Part III, IV, or V of Article 220, as applicable. In no case shall ment, if suitable overcurrent protection and
the rating be lower than specified in 230.79(A), (B), (C), or disconnecting means are provided.
(D). (9) Connections used only to supply listed communications
equipment under the exclusive control of the serving
(A) One-Circuit Installations. For installations to supply only electric utility, if suitable overcurrent protection and
limited loads of a single branch circuit, the service disconnect‐ disconnecting means are provided. For installations of
ing means shall have a rating of not less than 15 amperes. equipment by the serving electric utility, a disconnecting
(B) Two-Circuit Installations. For installations consisting of means is not required if the supply is installed as part of a
not more than two 2-wire branch circuits, the service discon‐ meter socket, such that access can only be gained with the
necting means shall have a rating of not less than 30 amperes. meter removed.

(C) One-Family Dwellings. For a one-family dwelling, the serv‐


ice disconnecting means shall have a rating of not less than Part VII. Service Equipment — Overcurrent Protection
100 amperes, 3-wire.
230.90 Where Required. Each ungrounded service conductor
(D) All Others. For all other installations, the service discon‐ shall have overload protection.
necting means shall have a rating of not less than 60 amperes.
(A) Ungrounded Conductor. Such protection shall be provi‐
230.80 Combined Rating of Disconnects. Where the service ded by an overcurrent device in series with each ungrounded
disconnecting means consists of more than one switch or service conductor that has a rating or setting not higher than
circuit breaker, as permitted by 230.71, the combined ratings of the allowable ampacity of the conductor. A set of fuses shall be
all the switches or circuit breakers used shall not be less than considered all the fuses required to protect all the ungrounded
the rating required by 230.79. conductors of a circuit. Single-pole circuit breakers, grouped in

70 –90 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 230 — SERVICES 230.95

accordance with 230.71(B), shall be considered as one protec‐ Exception No. 6: Where service equipment is power operable, the control
tive device. circuit shall be permitted to be connected ahead of the service equipment
if suitable overcurrent protection and disconnecting means are provi‐
Exception No. 1: For motor-starting currents, ratings that comply with ded.
430.52, 430.62, and 430.63 shall be permitted.
230.95 Ground-Fault Protection of Equipment. Ground-fault
Exception No. 2: Fuses and circuit breakers with a rating or setting that protection of equipment shall be provided for solidly grounded
complies with 240.4(B) or (C) and 240.6 shall be permitted. wye electric services of more than 150 volts to ground but not
Exception No. 3: Two to six circuit breakers or sets of fuses shall be exceeding 1000 volts phase-to-phase for each service discon‐
permitted as the overcurrent device to provide the overload protection. nect rated 1000 amperes or more. The grounded conductor
The sum of the ratings of the circuit breakers or fuses shall be permitted for the solidly grounded wye system shall be connected directly
to exceed the ampacity of the service conductors, provided the calculated to ground through a grounding electrode system, as specified
load does not exceed the ampacity of the service conductors. in 250.50, without inserting any resistor or impedance device.
Exception No. 4: Overload protection for fire pump supply conductors The rating of the service disconnect shall be considered to
shall comply with 695.4(B)(2)(a). be the rating of the largest fuse that can be installed or the
highest continuous current trip setting for which the actual
Exception No. 5: Overload protection for 120/240-volt, 3-wire, single- overcurrent device installed in a circuit breaker is rated or can
phase dwelling services shall be permitted in accordance with the be adjusted.
requirements of 310.15(B)(7).
Exception: The ground-fault protection provisions of this section shall
(B) Not in Grounded Conductor. No overcurrent device shall not apply to a service disconnect for a continuous industrial process
be inserted in a grounded service conductor except a circuit where a nonorderly shutdown will introduce additional or increased
breaker that simultaneously opens all conductors of the circuit. hazards.
230.91 Location. The service overcurrent device shall be an (A) Setting. The ground-fault protection system shall operate
integral part of the service disconnecting means or shall be to cause the service disconnect to open all ungrounded
located immediately adjacent thereto. Where fuses are used as conductors of the faulted circuit. The maximum setting of the
the service overcurrent device, the disconnecting means shall ground-fault protection shall be 1200 amperes, and the maxi‐
be located ahead of the supply side of the fuses. mum time delay shall be one second for ground-fault currents
230.92 Locked Service Overcurrent Devices. Where the serv‐ equal to or greater than 3000 amperes.
ice overcurrent devices are locked or sealed or are not readily (B) Fuses. If a switch and fuse combination is used, the fuses
accessible to the occupant, branch-circuit or feeder overcur‐ employed shall be capable of interrupting any current higher
rent devices shall be installed on the load side, shall be moun‐ than the interrupting capacity of the switch during a time that
ted in a readily accessible location, and shall be of lower the ground-fault protective system will not cause the switch to
ampere rating than the service overcurrent device. open.
230.93 Protection of Specific Circuits. Where necessary to (C) Performance Testing. The ground-fault protection system
prevent tampering, an automatic overcurrent device that shall be performance tested when first installed on site. This
protects service conductors supplying only a specific load, such testing shall be conducted by a qualified person(s) using a test
as a water heater, shall be permitted to be locked or sealed process of primary current injection, in accordance with
where located so as to be accessible. instructions that shall be provided with the equipment. A writ‐
230.94 Relative Location of Overcurrent Device and Other ten record of this testing shall be made and shall be available to
Service Equipment. The overcurrent device shall protect all the authority having jurisdiction.
circuits and devices. Informational Note No. 1: Ground-fault protection that func‐
tions to open the service disconnect affords no protection from
Exception No. 1: The service switch shall be permitted on the supply faults on the line side of the protective element. It serves only to
side. limit damage to conductors and equipment on the load side in
the event of an arcing ground fault on the load side of the
Exception No. 2: High-impedance shunt circuits, surge arresters, protective element.
Type 1 surge-protective devices, surge-protective capacitors, and instru‐
ment transformers (current and voltage) shall be permitted to be connec‐ Informational Note No. 2: This added protective equipment at
ted and installed on the supply side of the service disconnecting means the service equipment may make it necessary to review the over‐
as permitted by 230.82. all wiring system for proper selective overcurrent protection
coordination. Additional installations of ground-fault protective
Exception No. 3: Circuits for load management devices shall be permit‐ equipment may be needed on feeders and branch circuits where
ted to be connected on the supply side of the service overcurrent device maximum continuity of electric service is necessary.
where separately provided with overcurrent protection. Informational Note No. 3: Where ground-fault protection is
Exception No. 4: Circuits used only for the operation of fire alarm, other provided for the service disconnect and interconnection is made
with another supply system by a transfer device, means or devi‐
protective signaling systems, or the supply to fire pump equipment shall ces may be needed to ensure proper ground-fault sensing by the
be permitted to be connected on the supply side of the service overcurrent ground-fault protection equipment.
device where separately provided with overcurrent protection.
Informational Note No. 4: See 517.17(A) for information on
Exception No. 5: Meters nominally rated not in excess of 600 volts shall where an additional step of ground-fault protection is required
be permitted, provided all metal housings and service enclosures are for hospitals and other buildings with critical areas or life
grounded. support equipment.

2017 Edition NATIONAL ELECTRICAL CODE 70 –91


230.200 ARTICLE 230 — SERVICES

Part VIII. Services Exceeding 1000 Volts, Nominal (B) Type. Each service disconnect shall simultaneously
disconnect all ungrounded service conductors that it controls
230.200 General. Service conductors and equipment used on and shall have a fault-closing rating that is not less than the
circuits exceeding 1000 volts, nominal, shall comply with all the maximum short-circuit current available at its supply terminals.
applicable provisions of the preceding sections of this article
and with the following sections that supplement or modify the Where fused switches or separately mounted fuses are instal‐
preceding sections. In no case shall the provisions of Part VIII led, the fuse characteristics shall be permitted to contribute to
apply to equipment on the supply side of the service point. the fault-closing rating of the disconnecting means.
Informational Note: For clearances of conductors of over (C) Remote Control. For multibuilding, industrial installa‐
1000 volts, nominal, see ANSI/IEEE C2-2012, National Electrical tions under single management, the service disconnecting
Safety Code. means shall be permitted to be located at a separate building
230.202 Service-Entrance Conductors. Service-entrance or structure. In such cases, the service disconnecting means
conductors to buildings or enclosures shall be installed to shall be permitted to be electrically operated by a readily acces‐
conform to 230.202(A) and (B). sible, remote-control device.

(A) Conductor Size. Service-entrance conductors shall not be 230.206 Overcurrent Devices as Disconnecting Means. Where
smaller than 6 AWG unless in multiconductor cable. Multicon‐ the circuit breaker or alternative for it, as specified in 230.208
ductor cable shall not be smaller than 8 AWG. for service overcurrent devices, meets the requirements speci‐
fied in 230.205, it shall constitute the service disconnecting
(B) Wiring Methods. Service-entrance conductors shall be means.
installed by one of the wiring methods covered in 300.37 and
300.50. 230.208 Protection Requirements. A short-circuit protective
device shall be provided on the load side of, or as an integral
230.204 Isolating Switches. part of, the service disconnect, and shall protect all ungroun‐
ded conductors that it supplies. The protective device shall be
(A) Where Required. Where oil switches or air, oil, vacuum,
capable of detecting and interrupting all values of current, in
or sulfur hexafluoride circuit breakers constitute the service
excess of its trip setting or melting point, that can occur at its
disconnecting means, an isolating switch with visible break
location. A fuse rated in continuous amperes not to exceed
contacts shall be installed on the supply side of the disconnect‐
three times the ampacity of the conductor, or a circuit breaker
ing means and all associated service equipment.
with a trip setting of not more than six times the ampacity of
Exception: An isolating switch shall not be required where the circuit the conductors, shall be considered as providing the required
breaker or switch is mounted on removable truck panels or switchgear short-circuit protection.
units where both of the following conditions apply: Informational Note: See Table 310.60(C)(67) through Table
(1) Cannot be opened unless the circuit is disconnected 310.60(C)(86) for ampacities of conductors rated 2001 volts and
(2) Where all energized parts are automatically disconnected when above.
the circuit breaker or switch is removed from the normal operating Overcurrent devices shall conform to 230.208(A) and (B).
position
(A) Equipment Type. Equipment used to protect service-
(B) Fuses as Isolating Switch. Where fuses are of the type that entrance conductors shall meet the requirements of Arti‐
can be operated as a disconnecting switch, a set of such fuses cle 490, Part II.
shall be permitted as the isolating switch.
(B) Enclosed Overcurrent Devices. The restriction to
(C) Accessible to Qualified Persons Only. The isolating switch 80 percent of the rating for an enclosed overcurrent device for
shall be accessible to qualified persons only. continuous loads shall not apply to overcurrent devices instal‐
(D) Connection to Ground. Isolating switches shall be provi‐ led in systems operating at over 1000 volts.
ded with a means for readily connecting the load side conduc‐ 230.209 Surge Arresters. Surge arresters installed in accord‐
tors to a grounding electrode system, equipment ground ance with the requirements of Article 280 shall be permitted on
busbar, or grounded steel structure when disconnected from each ungrounded overhead service conductor.
the source of supply.
Informational Note: Surge arresters may be referred to as light‐
A means for grounding the load side conductors to a ning arresters in older documents.
grounding electrode system, equipment grounding busbar, or
grounded structural steel shall not be required for any dupli‐ 230.210 Service Equipment — General Provisions. Service
cate isolating switch installed and maintained by the electric equipment, including instrument transformers, shall conform
supply company. to Article 490, Part I.

230.205 Disconnecting Means. 230.211 Switchgear. Switchgear shall consist of a substantial


metal structure and a sheet metal enclosure. Where installed
(A) Location. The service disconnecting means shall be loca‐ over a combustible floor, suitable protection thereto shall be
ted in accordance with 230.70. provided.
For either overhead or underground primary distribution 230.212 Over 35,000 Volts. Where the voltage exceeds
systems on private property, the service disconnect shall be 35,000 volts between conductors that enter a building, they
permitted to be located in a location that is not readily accessi‐ shall terminate in a switchgear compartment or a vault
ble, if the disconnecting means can be operated by mechanical conforming to the requirements of 450.41 through 450.48.
linkage from a readily accessible point, or electronically in
accordance with 230.205(C), where applicable.

70 –92 NATIONAL ELECTRICAL CODE 2017 Edition

You might also like