CLIENT ~%¢ HELIX la ENERGY [PROJECT | S3KV Capacitor Panel Report no. - 33KV VCB/1VY031721001877 Page 1 of 2 ‘Name of the Equipment 33 KV VCB ‘Equipment location CAP BANK-1 Date of Testing 03/12/21 + Nameplate Details: Make ABB SILNO 1VY031721001877 INSULATION LEVEL 70 KV/170 KV pk RATED 36 KV MOTOR SUPPLY 230 V AC VOLTAGE — VOLTAGE RATED 1250 A CONTROL SUPPLY 110 V DC CURRENT VOLTAGE FREQUENCY | 50 Hz ‘YEAR OF 2021 MANUFACTURING * Insulation Resistance measurement: Ambient Temperature: 24°C Condition Reference Applied Voltage | Measured IR Value Dc ‘Open R-R’ 5 KVDC 16.5 GQ esa 12.1 GQ B-B 19.3 GQ Close R- Earth, SKVDC 2.07 GQ 2.27 GO 2.60 GO. 23.0 GO 24.1G9 31.8 GQ Subtleweigh Blectric (india) Private Limited ‘SPS Steel Rolling Mills SIGNATURE DATE CLIENT ‘SPS STEEL ROLLING MILLS LIMITED we) HELIX | al ENERGY [PROJECT [55k Capacitor Panel Report no. - 33KV VCB/1VY031721001877 Page 2 of 2 + Coil Winding Resistance test: Reference ‘Measured Value Closing Coil 7.8 MQ Trip Coil-1 83.2 Trip Coil-2 86.0 Motor 105.19 + Timer Test (Using Timer Test Kit): Reference Measured Time(ms.) Ro Ye Be Close Time 67 68 67 Trip Time-1 32 32 32 Trip Time-2 30 31 31 Close-Open 34 33 35 Time * CRM Test: Current Injected Measured Contact Resistance(Q) Ro Yo Be 100 A 26.5 27.7 26.6 * Check List: Reference Remarks External Condition OK Electrical & Manual Operation OK Counter Operation OK Subiewelgh Blectrc india) SPS Steel Rolling Mills Private Limited Limited ‘SIGNATURE DATE Page |2 HELIX (CLIENT SPS STEEL ROLLING MILLS LIMITED @2@) ENERoY | rRoveCT | sata Capactor Panel Report no. - 33KV VCB/1V¥031721001876 Page 1 of 2 Name of the Equipment) | 33 KV VCB Equipment location CAP BANK-2 Date of Testing (03/12/21 + Nameplate Details: Make ABB ‘SLNO 1V¥031721001876 __ [INSULATIONLEVEL | 70 KV/170 KV pk RATED 36 KV MOTOR SUPPLY 230 VAC VOLTAGE VOLTAGE, RATED 1250A CONTROL SUPPLY 110 VDC CURRENT. VOLTAGE, FREQUENCY | 50 Hz YEAR OF 2021 MANUFACTURING * Insulation Resistance measurement: Ambient Temperature: 24°C Condition Reference Applied Voltage | Measured IR Value Dc Open R-R’ 5 KVDC 41.4 GQ. Y-¥" 39.3 GO, B-B 58.6 GQ Clos R- Earth SKVDC 9.13 GO. Y = Earth, 15.1 GQ B- Earth 9.87 GO. R-Y >1 TQ Y-B 53.1 GO B-R 42.2 GO Subileweigh Electric (indiay ‘SPS Steal Rolling Mills Private Limited Limited Page |a ‘CLIENT SPS STEEL ROLI ee HELIX fal ENERGY [PROJECT | 33kV Capacitor Panel Report no. - 33KV VCB/1VY031721001876 Page 2 of 2 * Coil Winding Resistance test: Reference Measured Value Closing Coil 13 KQ Trip Coil-1 85.80 Trip Coil-2 85.30 Motor 102.62 + Timer Test (Using Timer Test Kit): Reference | Measured Time(ms.) Re yo Bo Close Time 64 65 64 Trip Time-1 31 33 31 Trip Time-2 29 29 29 Close-Open 36 36 36 Time + _CRM Test: Current Injected Measured Contact Resistance(i®) Rb Yo Be 100 A 27.2 26.1 29.2 + Check List: Reference Remarks External Condition OK Electrical & Manual Operation | OK Counter Operation OK ‘Subteweigh Electric (mdia) | SPS Steel Rolling Wiis Private Limited Limited SIGNATURE DATE Page |2 CLIENT | SPS STEEL ROLLING MILLS LIMITED ) HELIX ENERGY | PROJECT | SSKV Capacitor Pancl Report no. ~ REV615/1VYV91451319 Page 1 of 2 Name of the Equipment | Protection Relay Equipment location 5.9 MVAR CR PANEL Date of Testing (03.12.2021 + Nameplate Details: Make ABB Model no REV615 Serial No__| 1V¥V91451319 Function Protection Relay Type Numerical Relay Year of 2021 2 Manufacturing ae es Aux. Supply [ 110 VDC ‘Active CT Ratio 120/ * O/C Test: [PHLPTOC1] Itest: 1.0xIn & TMS: 1.0, Curve: IEC-NI Phase Pickup fault —_ | Theoretical Time (Sec.) ‘Measured Time (Sec.) Reference Current (A) 2xfault ‘Sxfault ‘2xfault ‘Sxfault current current current current R 0.93 A 9.33 4.24 Y 0.96 A 10.029 4.28 9.68 419 B 0.904 9.86 4.26 * O/C Test: [PHLPTOC1] Itest: 1xIn & Curve: DT, Time delay: 160 msec Phase Injected Current (A) Delay Time (ms) | Measured Time (mSec.) Reference R 11 160 191 = 11 160 186 B 11 160 193 * O/C Test: [PHHPTOC1] Itest: 2xIn & Curve: DT, Time delay: 100 msec Phase Injected Current (A) Delay Time (ms) | Measured Time (mSec.) Reference R 2.0 100 130 - Y. 2.0 100 131 B_ 2.0 100 135 Hel Subileweigh Electric Wadia ‘SPS Steel Rolling Mills Private Limited Limited ‘SIGNATORE iE DATE El ir Page |a ae Rey CLIENT | SPS STEEL ROLLING MILLS LIMITED PROJECT | 33KV Capacitor Panel Report no. ~ REV615/1VYV91451319 Page 2 of 2 + E/F Test: [DEFLPDEF1] Itest: 0.1xIn & TMS: 1.0, Curve: IEC-NI Phase TMS ‘Actual Time (Sec.) ‘Measured Time (Sec.) Reference ‘2xfault Sxfault ‘2xfault Sxfault current current current current N 1.0 10.029 4.28 9.432 4.084 © E/F Test: [DEFHPDEF1] Itest: 0.1xIn & Curve: DT; Time delay: 100 msec Phase Pick up current (A) Delay Time (ms) | Measured Time (mSec.) Reference N 0.096 100 131 * Check List: Reference Remarks Inspect for any physical damage or defects. | Ok Relay LED Ok SPS Steel Rolling Mills Limited, ‘SIGNATURE DATE CLIENT [SPS STEEL ROLLING MILLS LIMITED ee HELIX. la ENERGY =| PROJECT | 33KV Capacitor Panel Report no. - REV615/1VYV91451316 Page 1 of 2 Equipment location 2.9MVAR Panel Date of Testing 03.12.2021 + Nameplate Details: Make ABB Model no REV615, Serial No_| 1VYV91451316 Function Protection Relay Type Numerical Relay Year of 2021 Manufacturing Aux. Supply: | 110 VDC ‘Active CT Ratio 60/1 A + O/C Test: (PHHPTOC1} Itest: 1.0xIn & TMS: 1.0, Curve: IEC-NI Phase TMS ‘Theoretical Time (Sec.) Measured Time (See.) Reference ‘2xfault Sxfault ‘2xfault ‘Sxfault current current current current R 9.586 4.213 Y 1.0 10.029 4.28 9.488 4.219 B 9.454 4216 + O/C Test: [PHHPTOC1] Itest: 1xIn & Curve: DT, Time delay: 100 mSec. Phase Injected Current (A) | Delay Time (ms) Measured Time (mSec.) Reference R L1A 100 137 Y 11A 100 127 B LIA 100 127 * O/C Test: [PHIPTOC] Itest: 1xIn & Curve: DT, Time delay: 100 mSec. Phase Pickup Current (A) | Delay Time (ms) Measured Time (mSec.) Reference R 0.95 100 115 Y 0.96 100 116 B 0.94 100) 115 ‘Subdeweigh Electric (ndiay ‘SPS Steel Rolling Mills Private Limited Limited SIGNATURE DATE ~, | OO ENERey PROJECT | 33KV Capacitor Panel Report no. ~ REV615/1V¥V91451316 * E/F Test: |EFHPTOC] Itest: 0.1xIn & TMS: 1.0, Curve: IEC-NI Page 2 of 2 Phase TS Actual Time (Sec.) Measured Time (Sec.) Reference ‘2xfault Sxfault ‘2xfault Sxfault current current current current N 1.0 10.029 4.28 9.389 4.233 © E/F Test: [EFHPTOC] Itest: 0.1xIn & Curve: DT; Time delay: 40 msec. Phase Injected Current (A) _ | Delay Time (ms) Measured Time (Sec.) Reference N O.11A 40. 64 * E/F Test: [DEFHPDEF] Itest: 0.2xIn & Curve: DT; Time delay: 100 msec. Phase Injected Current (A) Delay Time (ms) ‘Measured Time (Sec.) Reference N 0.22.8 100 126 Check List: Reference Remarks Inspect for any physical damage or Ok defects. Relay LED Ok | ‘Subtleweigh Bleciric (india) ‘SPS Steel Rolling Mills Private Limited Limited. ‘SIGNATURE DATE HELIX CLIENT % PROJECT ENERGY ‘33KV Capacitor Panel Report no. - 33 KV RVT/AKRVT/202107124 Page 1 of 2 Name of the Equipment | 33 KV RVT Equipment location 2.9MVAR CR PANEL Date of Testing (03/12/2021 + Nameplate Details: Make AKANKSHA POWER & INFRASTRUCTURE PVT. LTD. CORE I 2 STLNO oe AKRVT/202107124 RATIO | PRIMARY 33000 V 33000 V ‘SECONDARY 110V 190V CLASS, 05 3P BURDEN(VA) 50 50, FUNCTION, Metering Protection ‘YEAR OF MANUFACTURING 2021-22 Insulation Resistance measurement: Ambient Temperature: 24 °C Reference Applied Voltage Measured IR Value pe Primary ~ Earth 5000 V 20.1 Ga Primary ~ | CORE-T 17.6GQ Secondary | CORE-2 cad 12.7 G0 Secondary | CORE-1 TO an =Earth | EARTH Pa ‘CORE-2T0 an EARTH + Winding Resistance Test: Ambient Temperatui c CORE Measured Value ab be ca T 0.62.0 0.610 0678 2 (da-dn} 0.799 Subileweigh Biesire Tmdiay | SPS Steel Roling Mls Lived Private Limited, STGHATORE DATE Page Ia CLIENT ~%¢ HELIX Ja ENERGY [PROJECT | 33KV Capacitor Panel Report no. - 38 KV RVT/AKRVT/202107124 Page 2 of 2 + Polarity Test: CORE Rs. 1 OK OK + Ratio Test: 2 Measured Voltage (V) & 2 Pri -Volt Sec - Volt eS Beer = a ¢ 412 | 416 | 414 | 1.389 1.385] 1.385] 0.804 | 0.798 | 0.796 8 ° = a 3 412 | 416 | 414 0.017 3 * Check List: Reference Remarks External Condition OK Subileweigh Electric (dia) | SPS Steel Rolling Wille Limited Private Limited SIGNATURE DATE Page |2 CLIENT | SPS STEEL ROLLING MILLS LIMITED HELIX we ja’ ENERGY [PROJECT | 33KV Capacitor Panel Report no. - 33 KV NCT/AI/24901 Page 1 of 2 Name of the Equipment) | 33 KV NCT Equipment location ‘5.9MVAT CR Panel (NCT) Date of Testing (03/12/2021 + Nameplate Details: Make ‘AGARWAL INDUSTRIES, CORE 1 2 SLNO : A1/24901 RATIO. | PRIMARY 2A 2A SECONDARY IA TA ‘CLASS SP. 1.0 BURDEN(VA) 15 15 FUNCTION Protection Metering (Spare) YEAR OF MANUFACTURING 2021 + Insulation Resistance measurement: Ambient Temperature: 24 °C Reference ‘Applied Measured IR Value Voltage ata ON Primary - Earth 5000 V 2.73 GA Primary~ | CORE-1 >100 Ga Secondary [ CORE-2 ZN >100 GO Secondary | CORE-I TO =Earth | EARTH — aoe CORE-2T0 saa EARTH * Winding Resistance Test: Ambient Temperature: 24 °C CORE Measured Value ‘DN 1 1.28 9 2 2.62 2 Fel Subileweigh Bleciric (ndia) | SPS Steel Rolling Mills Limited Private Limited SIGNATURE DATE ey, HELIX CLIENT SPS STEEL ROLLING MILLS LIMITED @2@) ENERGY [PROTECT — [sai Capacitor Panel Report no. - 33 KV NCT/AI/24901 Page 2 of 2 + Polarity Test: CORE 1 2 + Ratio Test 2 tise oN 3 & 8 3 ‘Sec - Amps ec Anne s1-82 is 1 0.51 oe a 2 1.01 ae 1 0.50 a a a 2 1.00 + Cheek List: Reference Remarks External Condition OK ‘CT Secondary Connection Check ‘OK | Primary Injection Check in Relay and Meter _| OK ‘Sublleweigh lectic (ndia) | SPS Steel Roling Mills United Private Limited SIGNATURE DATE Page |2

You might also like