EE355 OEM Dew Point Transmitter


down to -60 °C Td
The compact EE355 Dew Point Transmitter with a measuring
range down to -60 °C Td is ideal for applications in compressed
air systems, plastic dryers and industrial drying processes. An
integrated auto-calibration procedure permits a measurement
accuracy of <2 °C Td.

The measured values for dew point, frost point or ppm volume
concentration are available on an analog 4-20 mA and a digital
Modbus RTU output. Integration into the measurement task is

stainless steel housing.

With an optional Modbus to USB converter and the free EE-

set the Modbus parameters, and change the scaling of the


analog output.
EE355

Technical Data
Measuring values
Dew point (Td)
Measurement range -60...60 °C Td (-76...140 °F Td)
Accuracy 1) 80
Dew point temperature (°C)

60

40

20

0
-40 -30 -20 -10 0 10 20 30 40 50 60
-20

-40
Accuracy: ≤ ±2°C Td
-60
Medium temperature (°C)

Response time t90 < 5 min -20 °C Td ( -4 °F Td) → -60 °C Td ( -76 °F Td)
< 15 sec -60 °C Td ( -76 °F Td) → -20 °C Td ( -4 °F Td)
Volume concentration (ppm) 80

60
Measurement range 20...200,000 ppm
40
Accuracy at 20 °C (68 °F) and 1013mbar 5 ppm + 9 % from measured value
20
Output 0
Analog output (scalable) 4 - 20
-20
-40 mA
-30 (3-wire
-20 -10 technology)
0 10 20 30 40 50 RL
60 < 500 Ohm
Maximum adjustable scaling -100...80 °C Td (-148...176 °F Td)
-40
Resolution of analog output 2 µA
-60
Digital interface MODBUS
-80
RTU (max. 32 units in one bus)
Temperature dependence ±5ppm of the measuring span / °C (Deviating from 20 °C)
General
Supply voltage 18...28 V DC
Current consumption at 24V DC <20 mA + load current /
with autocalibration: 100 mA + load current
Pressure range of use 0...80 bar
Housing / protection class Stainless steel AISI 316L / IP65
Electrical connection 2) M12x1 5-pin plug
Sensor protection Stainless steel sintered filter
Temperature / humidity operating range -40...70 °C (-40...158 °F) / 0...100 % RH
Storage temperature range -40...60 °C (-40...140 °F)
Electromagnetic compatibility EN61326-1 EN61326-2-3 Industrial environment
FCC Part 15 ICES-003 ClassB
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in
accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) Field-attachable mating connector is included in the scope of supply.

100 v1.3 / Modification rights reserved EE355


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Dimensions in mm (inch) Connection Diagram


140 (5.5)

ISO Plug
92 ( 3.6) 4 3
5
34.5 (1.36) 1...V+
2...Analog output 4-20mA
1 2 3...GND
(0.5)

(1.2)
Ø12

Ø30
4...RS485 A (=D+)
AD27
5...RS485 B (=D-)
G1/2“
77 (3)

89 (3.5)

NPT

1/2“NPT AD22

74 (2.9)

Sampling Cell with Quick Connector


The sampling cell is specially developed for use in compressed air lines and has a quick-connector 1

Pressure range: 0...10 bar (0...145 psi).


2

1 = G 1/2“ ISO
2 = Bleed screw
3
3 = Quick connector

Ordering Information
EE355-T63G
G1/2" thread A
Pressure-tight screw connection
1/2“ NPT thread C
Software configuration
Physical parameter Dew point temperature Td [°C/°F] TD
for analog output Frost point temperature Tf [°C/°F] output for Td < 0 TF
volume fraction of water vapor Wv [ppm] WV
Scaling of analog output see chart Scaling Range (e.g. TD002 for -40...60 °C Td) xxx
metric [°C] M
Measured value unit
non metric [°F] N

Scaling Range
Dew point TD or Frost point TF (in °C or °F) volume fraction of water vapor WV
002 -40...60 063 -80...20 083 -40...140 001 0...100 004 0...10000
003 -10...50 064 -60...60 141 -100...20 002 0...500 011 0...100000
010 -20...120 065 -60...20 003 0...1000

Accessories
M12x1 5pin connection cable socket/flying leads 1.5m HA010819 sampling cell with quick connector HA050102
M12x1 5pin connection cable socket/flying leads 5m HA010820 basic sampling cell HA050103
M12x1 5pin connection cable socket/flying leads 10m HA010821 stainless steel sintered filter HA010103
Modbus - USB converter for EE35x HA011013

Order example
EE355-T63GA/TD065M
Pressure-tight screw connection: G1/2” thread
Output: Dew point Td
Output scaling: 4-20 mA = -60...20 °C Td
Measured value unit: metric [°C]

EE355 v1.3 / Modification rights reserved 101


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

EE354 Miniature Dew Point Transmitter


up to -20 °C Td (-4 °F Td)
The EE354 was developed for monitoring dew point up to -20 °C Td
(-4 °F Td). The high measurement accuracy of ±1 °C Td (±1.8 °F Td)
in the typical working range of a refrigeration dryer makes the EE354
the ideal solution for OEM manufacturers.
Integration into the measurement task is considerably simplified
thanks to its highly compact design and exceptional robust stainless
steel housing. The measurement values are issued on an analog
4-20 mA and a digital Modbus RTU output. Furthermore, excellent
long-term stability and temperature compensation across the entire
measurement range are important features of the EE354.
Using the free EE-PCS configuration software and the Modbus USB
converter (available as an accessory), the scaling of the analog
output can be modified. This also permits one and two-point
adjustments by the user. EE354

Typical Applications Features


Compressed air monitoring Measurement range -20...50 °C Td (-4...122 °F Td)
Refrigeration dryer Accuracy ±1 °C (±1.8 °F) for refrigerant dryers
Output 4...20 mA
MODBUS RTU digital interface
Pressure-tight up to 80 bar (1160 psi)
Technical Data
Measured Values
Dew point (Td)
Sensor HC1000
Measurement range -20...50 °C Td (-4...122 °F Td)
Accuracy at 20 °C1)
50
40
Dew point [°C Td]

30
20

10 ±1 °C ±2 °C
±1.8 °F ±3.6 °F
0
-10
±3 °C / ±5.4 °F
-20
-10 0 10 20 30 40 50 60
Gas temperature [°C]
Response time t90 at 20°C < 30 sec.
Output
Analog output (scalable) 4 - 20 mA (3-wire technology) RL < 500 Ohm
Maximum adjustable scaling -40...80 °C Td (-40...176 °F Td)
Digital interface MODBUS RTU
Temperature dependence ±0.005 % of the measuring span / °C
General
Supply voltage 10*)...28 V DC *)
10V+0.02*RL
Power consumption at 24V DC <40 mA
Pressure range of use 0...80 bar (0...1160 psi)
Housing / protection rating Stainless steel 1.4404 / IP65
2)
Electrical connection M12x1 5-pin plug
Sensor protection Stainless steel sinter filter
Temperature / humidity operating range -40...60 °C (-40...140 °F) / 0...100 % rh
Storage temperature range -40...60 °C (-40...140 °F)
Electromagnetic compatibility in accordance with EN61326-1 EN61326-2-3
Industrial environment
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2 x standard deviation).
The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) Flange receptacle for self assembly included in scope of supply.

102 v1.4 / Modification rights reserved EE354


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Dimensions in mm (inch) Connection Diagram


140 (5.5)

ISO Plug
92 ( 3.6) 4 3
5
34.5 (1.36) 1...V+
2...Analog output 4-20mA
1 2 3...GND
(0.5)

(1.2)
Ø12

Ø30
4...RS485 A (=D+)
AD27
5...RS485 B (=D-)
G1/2“
77 (3)

89 (3.5)

NPT

1/2“NPT AD22

74 (2.9)

Modbus Map
The measured values are 32Bit float values. The factory-set slave ID is 243 as integer 16Bit value. This ID can be
customised in the register 0x00 (value range 1 - 247 permitted). For Modbus setting please see Application Note
AN0103. The factory setting of the transmission rate is: baud rate 9600, parity even, and stop bit 1.
FLOAT: INTEGER:
Register Protocol Parameter Register Protocol Parameter
address address name address address name
30032 0x1F dew point Td 60001 0x00 Slave-ID
30042 0x29 frost point Tf 60002 0x01 RS485 setting

Ordering Information
EE354-T63G
G1/2" thread A
Pressure-tight screw connection
1/2" NPT thread C
Software configuration
Physical parameters Dew point temperature Td [°C/°F] TD
Analog output Frost point temperature Tf [°C/°F] at dew point <0°C, the frost point is issued TF
Td/Tf output scaling xxx (acc. to table
(in °C or °F) scaling ranges)
metric [°C] M
Measured value unit
non metric [°F] N

Scaling Range
TD or TF
002 -40...60 007 0...60 024 -20...80 048 -20...50 090 32...120
003 -10...50 008 -30...70 025 -20...60 060 -20...40 091 32...140
004 0...50 022 -40...80 047 -20...150 083 -40...140

Accessories
M12x1 5pin mating plug suitable for customer-specific assembly HA010708 sampling cell with quick connector HA050102
M12x1 5pin connection cable socket/flying leads 1.5m HA010819 basic sampling cell HA050103
M12x1 5pin connection cable socket/flying leads 5m HA010820 stainless steel sinter filter HA010103
M12x1 5pin connection cable socket/flying leads 10m HA010821 Modbus - USB converter for EE35x HA011013

Order example
EE354-T63GA/TD060M
Pressure-tight screw connection: G1/2" thread
Output: Dew point Td
Scaling of output: 4-20 mA = -20...40 °C Td
Measured value unit: metric [°C]

EE354 v1.4 / Modification rights reserved 103


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

EE35 Industrial Transmitter for


Dew Point Measurement
Exact dew point monitoring is increasingly playing a more impor-
tant role in many industrial applications, such as drying process-
es, air pressure pipelines, etc. For these purposes the multifunc-
tional EE35 Series offers the ideal features.

The EE35 Series is based on a functional, user-friendly housing


concept and on the proven polymer humidity sensors of the HC
Series.
A specially developed autocalibration process enables measure-
ments in a measurement range of -60...60°C Td (-76...140°F Td), with
a Td measurement accuracy of ±2°C (±3.6°F).
Two freely configurable and scalable analogue
outputs are available for the two measurement values (Td, T).
An optional hygrostat output, which can be set by means of a potentiometer, provides an alarm signal in
a simple way when a threshold of the permitted dew point is exceeded.
An optional display for the measurement values and the associated MIN/MAX values allows a quick overview
of the current situation.

Autocalibration
Dew points in the range of -60...-20°C (-76...-4°F) at room temperatures correspond to relative humidity values
of 0.08...5.37% RH. The measurement of such low humidity values is not possible with conventional
capacitive measurement methods. For the EE35 Series, a special autocalibration process is used to compen-
sate for the usual drift effects and thus to achieve high accuracy measurements also at -60°C Td (-76°F Td).

Installation
In addition to the direct mounting of the dew point probe, a ball valve installation enables the mounting and
removal of the probe without having to interrupt the running process.

Alarm Output
An optional alarm module with one relay output is available for control and alarm purposes. The setting
of the Td threshold can be easily done with the potentiometer on the printed circuit board.

Integrated power supply


A power supply, integrated in the back module of the housing, can be ordered
optionally (100...240V AC, 50/60Hz; ordering code V01). The power supply V01 is
available for both polycarbonate and metal housing and comes standard with two
plugs for supply and outputs to allow an easy connection.

Typical Applications Features


industrial processes measuring range -60...60°C Td (-76...140°F Td)
monitoring of air pressure pipelines accuracy of measurement ±2°C Td (±3.6°F Td)
warehouses traceable calibration
drying processes alarm output for dew point
paper industries autocalibration
chemical industries
86 V2.7 / Modification rights reserved EE35
T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Housing Dimensions (mm) Installation Example

Housing: ball valve installation


(pressure-tight up to
polycarbonate housing metal housing 20bar/290psi)
135 (5.3”) 66.5 (2.6”) 135 (5.3”) 66.5 (2.6”)
(3.5”)

(3.5”)
90

90 163 (6.4”)

For use in harsh industrial environ- 1/2” ISO or 1/2” NPT


ments the EE35 series is available in a
robust metal housing.

Model: 1/2” ISO or 1/2” NPT

bore diameter:
>13.1 (0.5”)
code “cable length” EE35-xEx
32 (1.3”) code “probe length” 15 (0.59”) Remote probe for T up to 60°C (140°F)
and pressure-tight up to 20bar (290psi)
Probe material: stainless steel
(0.51”)

(0.47”)
∅13

∅12

23 (1”)

minimum installation depth


fixed installation
(pressure-tight up to 20bar/290psi)

1/2” ISO or 1/2” NPT

64 (2.5”) resp. 164 (6.5”)

maximum installation depth

bore diameter:
>13.1 (0.5”)

Connection Versions

Standard Plug Option C03 Plug Option C06

2x M16x1.5 Lumberg
Lumberg M16x1.5
RSC 5/7
RKC 5/7

Power supply +
Analogue output
EE35 V2.7 / Modification rights reserved 87
T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Technical Data
Measuring Quantities
Dew point
Humidity sensor HC1000-400
Measuring range standard calibration: -40...60°C (-40...140°F)
(below 0°C / 32°F the transmitter outputs frostpoint) special calibration: -60...60°C (-76...140°F)
Accuracy ≤ ±2°C (≤ ± 3.6°F)
Traceable to intern. standards, 80

administrated by NIST, PTB, BEV...


60

dew point temperature (°C)


40

20

0
0 10 20 30 40 50 60
-20
uncert ainty of measurement ±2 degC
-40

-60 limit of measuring range


-80
Process temperature (°C)

Response time t90 80 sec. -20°C → -40°C (-4°F → -40°F)


10 sec. -40°C → -20°C (-40°F → -4°F)
Temperature
Sensor Pt1000 DIN A
Measuring range 0...60°C (32...140°F)
Accuracy of temperature measurement at 20°C (68°F) ±0.2°C (±0.36°F)
Sensitivity error at full scale ±0.1°C (±0.18°F)
Temperature dependence of electronics < 0.005°C/°C
Outputs 0 - 5V -1mA < I < 1mA L

Two freely selectable and scaleable analogue outputs 0 - 10V -1mA < I < 1mA L

xx...yy°C T, Td/Tf / xx...yy°C respectively 4 - 20mA R < 500 Ohm L

0 - 20mA R < 500 Ohm L

General
Supply voltage 8...35V DC
12...30V AC (optional 100...240V AC, 50/60Hz)
Current consumption - voltage output typ. 40mA, with autocalibration: 100mA
- current output typ. 80mA, with autocalibration: 140mA
Pressure range 0...20bar (0...300psi)
Housing / protection class PC or Al Si 9 Cu 3 / IP65; Nema 4
Cable gland M16 x 1.5 (option: plug) cable Ø 4.5 - 10 mm (0.18 - 0.39”)
Electrical connection screw terminals up to max. 1.5mm² (AWG 16)
Sensor protection stainless steel sintered filter
Working temperature range probe: -40...60°C (-40...140°F)
electronic: -40...60°C (-40...140°F)
with LC display: -20...50°C (-4...122°F)
with alarm module: -40...60°C (-40...140°F)
Storage temperature range -40...60°C (-40...140°F)
Electromagnetic compatibility according to EN 61326-1 EN61326-2-3 ICES-003 ClassB
Industrial Environment FCC Part15 ClassB

Technical Data for Options


Display graphical LC display (128x32 pixels), with integrated push-
buttons for selecting parameters Td or T and MIN/MAX functions
Alarm output for Td/Tf - range: -60...40°C Td (-60...40°F Td) adjustable with the potentiometer
on the printed circuit board
- 1 switch contact
- 250V AC/6A or 28V DC/6A
Connection Diagram

RxD/B-
Terminal configuration - Alarm output
8
Serielle Schnittstelle
TxD/A+ 7 serial connection
für Konfiguration / for
NC
serial connection for 11
configuration
configuration
GND Ser 6
REL 1 C 12
V
mA OUT 2 5
Analog Ausgang / NO 13
V OUT 1 4 analogue output
analogue output
mA
NC 14
GND 3

GND 2 REL 2 C 15
8 - 35V DC Versorgung /
supply
supply
12 - 30V AC
V+ 1 NO 16

88 V2.7 / Modification rights reserved EE35


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Ordering Guide EE35

EE35-
Hardware Configuration
Housing metal housing M
polycarbonate housign P
Type pressure tight E
Cable length 1m (3.3ft) 01
(incl. probe length) 2m (6.6ft) 02
5m (16.4ft) 05
Probe length 100mm (3.9”) 3
200mm (7.9”) 5
Pressure tight 1/2" male thread HA03
feedthrough 1/2” NPT thread HA07
Display without display
with display D05
Alarm output without relay
1)

with relay SW
Plug cable glands
1 plug for power supply and outputs C03
1 cable thread / 1 plug for RS232 C06
Probe fixed
pluggable P01
Td-Calibration standard -40...60°C (-40...140°F)
special calibration -60...60°C (-76...140°F) CA02
Supply voltage 8...35V DC / 12...30V AC
integrated power supply 100...240V AC, 50/60Hz V01
2)

Software Configuration
Physical parametres temperature T [°C/°F] output 1 B
of the outputs dew point temperature Td [°C/°F] output 2 C
frost point temperature Tf [°C/°F] D
Type of 0-5V 2
output signals 0-10V 3
0-20mA 5
4-20mA 6
T / Td / Tf Einheit °C
°F E01
Scaling of T-output -40...60 (T02) -60...20 (T65) -40...100 (T79) output T Select accorcding to
-50...50 (T27) -50...100 (T66) -40...140 (T83) ordering guide (Txx)
-80...20 (T63) -20...70 (T73) -60...120 (T97) Other T-scaling refer
-60...60 (T64) 20...140 (T77) to data sheet „„T-Scalings““
Scaling of Td/Tf-output -40...60 (T02) 0...60 (T07) -60...60 (T64) output Td resp.Tf Select accorcding to
-10...50 (T03) 0...80 (T21) 32...120 (T90) ordering guide
0...50 (T04) -40...80 (T22) 32...140 (T91) (Tdxx resp. Tfxx)
0...100 (T05) -20...80 (T24) 32...132 (T96) Other Td/Tf-scaling refer

to data sheet „„T-Scalings““

1) Combination alarm output and plugs is not possible (with cable glands only) / combination alarm output and integrated power supply is not possible
2) Integrated power supply includes 2 plugs for power supply and outputs / further plug options are not possible

Accessories
- Ball valve set 1/2” ISO (HA050101) - Interface cable for PCB („HA010304“)
- Ball valve set 1/2” NPT (HA050104) - Interface cable for plug C06 („HA010311“)
- Display + housing cover in metal („D05M“) - Bracket for installation onto mounting rails*(„HA010203“)
- Display + housing cover in polycarbonate („D05P“) - Sealing element (HA050308)
- Stainless steel sintered filter („HA010103“) *Note: Only for plastichousing, not for metalhousing

Order Example
EE35-ME025HA03D05P01/BC5-T02-Td02
Housing: metal housing Output 1: T
Type: pressure tight Output 2: Td
Cable length: 2m (6.6ft) Output signal: 0-20mA
Probe length: 200mm (7.9”) Measured value unit: metric
Pressure tight feedthrough: 1/2" male thread Scaling of T-output: -40...60°C
Display: with display Scaling of Td-output: -40...60°C
Alarm output: without relay
Plug: cable glands
Sensing probe: pluggable
Td Calibration: standard
Supply voltage: 8...35V DC / 12...30V AC

EE35 V2.7 / Modification rights reserved 89


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

EE371 Compact Dew Point Temperature


Transmitter / Switch
The exact monitoring of dew point temperature in
compressed air systems, dryers for plastic and other industrial
processes is becoming increasingly more important.
EE371 series with a measuring range -60...60°C Td
(-112...140°F Td) is the ideal solution for such applications.
The core of the transmitter is the monolithic measurement cell
type HMC01, developed by E+E Elektronik in thin-film technolo-
gy.
An autocalibration procedure which is integrated in the device
and years of experience in low humidity adjustment make an
accuracy of <2°C Td (±3.6°F Td) possible.
The compact construction in a robust aluminium housing and EE371
the numerous options allow easy mounting and many applicati-
on possibilities.

Autocalibration
Dew point temperatures in the range of -60...-20°C (-76...-4°F) at room temperature correspond to relative
humidity values of 0.08...5.37% RH. The measurement of these low humidity values is not possible with
conventional capacitive measurement methods. For the EE371 series a special autocalibration procedure is
utilized to achieve high accuracy measurements at lowest dew points too.

Outputs
Model T: The transmitter has two freely selectable and scaleable outputs for dew point, frost point or ppm
volume concentration.
Model S: The switch with two relay outputs is designed for control and alarm purposes. The status for early
warning and main alarm is indicated by LED's. Adjustment of the Td/Tf set point and hysteresis can
be achieved with the optional configuration software.

Configuration Software
The optional configuration software allows flexible and easy adjustment of the analogue resp. relay outputs
to the respective requirements.
The adjustment / calibration of the transmitters can easily be performed.

Screw Connection for Mounting - 360° positionable


The construction of this screw connection enables any
position / rotation of the mounted transmitter.
So an optimal position of the display resp. the cable
outlet is guaranteed.

Typical Applications Features


monitoring of compressed air systems measuring range -60...60°C Td (--76...140°F Td)
refrigerant type dryer accuracy of measurement ±2°C Td (±3.6°F Td)
absorption dryer two Td/Tf alarm outputs
plastics dryer autocalibration
pressure tight up to 100 bar (1450psi)

98 v1.7 / Modification rights reserved EE371


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Technical Data
Measuring Quantities
Dew point (Td)
Dew point sensor HMC01
Measuring range -60...60°C Td (-76...140°F Td)
Accuracy Traceable to intern. standards, administrated by NIST, PTB, BEV...
80

60

dew point temperature (°C)


40

20

0
-40 -30 -20 -10 0 10 20 30 40 50 60
-20

-40
Accuracy ≤ ±2°C Td (≤ ± 3.6°F)
-60
process temperature (°C)

Response time t90 80 sec. -20°C Td → -40°C Td (-4°F Td → -40°F Td)


10 sec.
80 -40°C Td → -20°C Td (-40°F Td → -4°F Td)
Volume concentration 60

Measuring range 20...200,000ppm


40

Accuracy at 20°C (68°F) and 1013mbar ±(5 ppm + 9 % from measured value)
20

Outputs 0
-40 -30 -20 -10 0 10 20 30 40 50 60

EE371-Tx two freely selectable and scaleable 0 - 1V / 0 - 5V / 0 - 10V1)


-20
-1mA < IL < 1mA
analogue outputs for Td, Tf, Wv 4 - 20mA / 0 - 20mA
-40
RL < 500 Ohm1)
EE371-Sx Alarm output 2 potential-free relays (NC)
-60

-80
30V DC 0.6A / 35V AC 0.3A (resistive)
General
Supply voltage 10...30V DC
Current consumption at 24V DC voltage output: typ. 40mA / during autocalibration: 100mA
current output: typ. 80mA / during autocalibration: 140mA
Pressure range 0...20bar (0...290psi) / 0...100bar (0...1450psi)
System requirements for software WINDOWS 2000 or later; serial interface
Serial interface for configuration RS232C
Housing / protection class Al Si 9 Cu 3 / IP65
Electrical connection 7-pole industrial plug: DIN VDE 0627 / IEC 61984
cable cross-section: 0.25 - 1 mm2
cable connection: PG 11
Sensor protection stainless steel sintered filter
Working temperature range probe: -40...70°C (-40...158°F)
electronic: -40...60°C (-40...140°F)
with LC display: -20...50°C (-4...122°F)
Storage temperature range -40...60°C (-40...140°F)
Electromagnetic compatibility according to EN 61326-1 EN61326-2-3 ICES-003 ClassB
Industrial Environment FCC Part15 ClassB
1) minimum supply voltage 15V DC

Dimensions (mm) Connection Diagram


48 (1.9”) analogue output
32 (1.3”) 1 V+
10...30V DC
6 7 1 2 GND
(2.1”)

3 GND
5 2 V
4 OUT1
(3”)
54

mA
4 3 5 OUT2 V
75

mA
6 NC
28 (1.1”) 100 (4”)
7 NC

relay output
1 V+
10...30V DC
2 GND
40 (1.6”)
24 (1”)

3 NC11
(0.5”)

4 NC12
5 NC21
∅12

G1/2” ISO spanner width: 27 or 24 6 NC22


or 1/2” NPT
7 not connected

EE371 v1.7 / Modification rights reserved 99


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Basic Sampling Cell


The basic sampling cell offers the possibility to integrate the EE371 into an
existing or self-constructed sampling system. 1

Pressure range: 0...64 bar (0...928 psi)


1 = G 1/2“ ISO or 1/2“ NPT
2 = G 1/4“ ISO or 1/4“ NPT
3 = G 1/4“ ISO or 1/4“ NPT 2
3

Sampling Cell with Quick Connector


The sampling cell is specially developed for use in compressed air lines and has 1
a quick-connector suitable for standard compressed air connections.
It allows for the cell to be fitted and removed without interrupting the process.
The flow of gas can be adjusted using a bleed screw.
Pressure range: 0...10 bar (0...145 psi)
2
1 = G 1/2“ ISO
2 = Bleed screw
3 = Quick connector
3

Ordering Guide
EE371- EE371-
Hardware Configuration
transmitter T
Model
switch S
up to 20bar E E
Pressure range
up to 100bar (1450psi) I I
Pressure tight G1/2" male thread HA03 HA03
feedthrough 1/2” NPT thread HA07 HA07
without display
Display
with display D08 D08
Software Configuration
Physical parameters dew point temperature Td [°C/°F] (C) output/relay 1 select accoriding to Ordering Guide(C,D,P)
of the outputs/relays frost point temperature Tf [°C/°F] (D) output/relay 2 select according to Ordering Guide(C,D,P)
volume concentration Wv [ppm] (P)
0-1V 1
0-5V 2
Type of
0-10V 3
output signals
0-20mA 5
4-20mA 6
Measured value units metric/SI
for T / Td / Tf non metric /US E01 E01
Scaling of Td/Tf-ouput -40...60 (Td/Tf02) -60...20 (Td/Tf65) Other Td/Tf-scaling refer select according to
(in °C or °F) -10...50 (Td/Tf03) to data sheet „Scaling of the outputs“ Ordering Guide (Tdxx / Tfxx)
0...100ppm (X01)
ppm range Wv
0...500ppm (X02) other measurment range: _______ select according to
0...1000ppm (X03) Ordering Guide
standard for configuration CC R1: -40 °C (-40°F) R2: -35°C (-31°F)
Setting of alarm H1: 2 °C (35.6°F) H2: 2°C (35.6°F)
output other set points relay 1: _______ relay 2: ______ SP
hysteresis 1: ___ hysteresis 2: __

Order Example
EE371-TEHA07D08/CD2-Td/Tf03
Model: transmitter Output 1: Td
Pressure range: up to 20bar (290psi) Output 2: Tf
Pressure tight feedthrough: 1/2” NPT thread Output signal: 0-5V
Display: with display Measured value unit: metric
Scaling of output: -10...50°C

100 v1.7 / Modification rights reserved EE371


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Scope of Supply
- EE371 Transmitter according to Ordering Guide
- Operation Manual
- Inspection certificate according to DIN EN10204 - 3.1

Accessories
- Sampling cell with quick connector (HA050102)
- Basic sampling cell ISO (HA050103)
- Basic sampling cell NPT (HA050105)
- Display (D08)
- Stainless steel sintered filter (HA010103)
- Product configuration adapter see data sheet EE-PCA
- Product configuration software EE-PCS (free download: www.epluse.com/configurator)

EE371 v1.7 / Modification rights reserved 101


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

EE46 Condensation Monitor


EE46 condensation monitors are used to monitor the
formation of condensation on chilled ceilings or to prevent
condensation at critical spots of heating-, ventilation- and air
conditioning systems. It is also used as a dew point monitor
for systems operating near the dewpoint.
Because of the temperature coupling between the condensa-
tion monitor and the environment, the relative humidity is a
measure for the dew point. The condensation monitor
measures the relative humidity near the dew point using its
high-quality capacitive sensor. At reaching the switching point
of 90% RH the output will provide an early warning signal for
the initiation of control steps (increasing the initial water EE46
temperature, reducing the cooling capacity, switching on the
heating, etc...). An additional status light indicates the
condensation danger.
Thanks to the special protection coating, sensor and electronics are highly insensitive to dust and dirt.
EE46 condensation monitors can be mounted on walls, ducts and pipes up to 2“.

Typical Applications Features


chilled ceilings early detection of condensation danger
heating-, ventilation- and compact design
air conditioning systems fast response time
switching cabinets dust protection
simple and easy mounting
status indication
Technical Data
Humidity sensor HC105
Working range 10...100% RH
Switching point at 20°C (68°F) 90±3% RH
Switching hysteresis Hysteresis
5% RH

85±3% RH 90±3% RH

Response time at change of t90 < 3 min.


pipe/wall temperature
Response time at change of t90 < 25 sec.
relative humidity
Electrical output potentialfree relay with changeover contact
Switching capacity max. 24V AC/DC, 1A
Supply voltage 24V AC/DC ±20%
Current consumption at 24V DC < 3mA
Relay status indication LED, red
Electrical connection 5-pole push-in terminal, max. 1.5 mm2 (AWG 16)
Dust protection by special coating (permeable for water vapour)
Housing protection class IP40
Housing material Polycarbonate, UL94-V2 approved
Electromagnetic compatibility EN 61326-1 EN 61326-2-3
industrial environment
Temperature range working temperature range 0...50°C (32...122°F)
storage temperature range -20...70°C (-4...158°F)
Weight approx. 60g

48 v1.2 / Modification rights reserved EE46


T: (+34) 968 162 005
www.sensovant.com
comercial@sensovant.com

Dimensions (mm) Installation


1 mm = 0.03937” / 1” = 25.4 mm

Pipe mounting
max. Ø 50mm (2“)

“)
(2
m
m
50

ax
m
Wall mounting
22
33.5
Ø4.5
63.5
23

43
53

Connection Diagram Status Indication

V+
power supply
24V AC/DC ±20%
GND

NC

COM

NO

LED continuous red: Operating < 90% RH


LED blinking red: Condensation danger

Ordering Guide
Condensation Monitor EE46 (EE46)

EE46 v1.2 / Modification rights reserved 49


EE10-04 Dew Point
Room Transmitter
EE10 dew point room transmitters are the ideal solution for
indoor applications such as HVAC Systems in residential and
commercial buildings.
The very stylish, functional housing allows for service purposes
easy installation and fast exchange of the sensing unit.
The high quality E+E humidity sensor and state-of-the-art
microprocessor controlled electronics guarantee the best
accuracy and long term performance.

EE10-04

Typical Applications Features


building management for residential and office areas excellent price / performance ratio
air conditioning easy installation
switching cabinets modern design
climate control in hotels and museums long term stability
display
traceable calibration
Technical Data

Measuring Quantities
Dew Point
Working range 0...80 Td °F
Accuracy at 68 °F (20°C); 48 Td°F (9 Td°C); ±1.26 Td°F (0.7 Td°C)
U =24V DC and 50 %RH
V
traceable to intern. standards, administrated by NIST, PTB, BEV...
Temperature dependence at 73,4°F (23°C) typical 0.33 Td°F (0.18 Td°C)
Temperature (active output)
Accuracy at 68°F (20°C) and U =24VDC
V
±0.72°F (±0.4°C)
Outputs
4 - 20mA (two wires) R < (U - 10) / 0.02 < 500 Ohm
L v

Output 1: dew point Td 4...20mA = 0...80°F (-17.78...26.67°C)


Output 2: temperature T 4...20mA = 32...120°F (0...48.89°C)
General Data
Voltage supply (U ) V

for 4 - 20 mA 28V DC > U > 10 + 0.02 x RL (RL < 500 Ohm)


V

Electrical connection screw terminals max. 1.5 mm2 (AWG 16)


Display dew point / temperature alternating
CE compatibility according EN 61000-6-1 FCC Part15 ClassB
EN 61000-6-3 ICES-003 ClassB
Temperature ranges working temperature range: 23...131°F (-5...55°C)
storage temperature range: -13...140°F (-25...60°C)

1 v1.0 EE10-04
preliminary
Connection Diagram

Dimensions (mm)

Housing color: Cover: RAL 9003 (signal white)


Back: RAL 7035 (light grey)

WxHxD= 3.3“ x 5.4“ x 1“

EE10-04 2