You are on page 1of 1

ANCHOR BOLTS AS

POLE - SEE POLE SKETCH RECOMMENDED BY


CONDUIT STUBBED UP AND SPECIFICATION MANUFACTURER OF
POLE
ADJACENT TO HANDHOLE;
NUMBER AND SIZE AS
HANDHOLE - SEE POLE
REQUIRED
SKETCH AND SPECIFICATION

SET TOP OF CONCRETE CHAMFER ALL EDGES OF


FOUNDATION 100 MM CONCRETE BASE 13 MM
ABOVE GRADE
POLE AND
BASE
INSULATED COPPER GROUNDING
FINISHED GRADE CONDUCTOR ATTACHED TO
INTERNAL LUG WELDED TO
CIRCUIT CONDUCTORS
INTERIOR OF POLE. SIZE PER
AND CONDUIT TO POWER
NFPA 70. SOURCE OR NEXT POLE

ANCHOR BOLTS AS RECOMMENDED


BY MANUFACTURER OF POLE
PLAN VIEW
CIRCUIT CONDUCTORS AND 4 PCS
ANCHOR
BOLTS

COPPER EQUIPMENT CONDUIT TO POWER


GROUNDING CONDUCTOR - SOURCE OR NEXT POLE 80
0

ATTACH TO INTERNAL LUG


WELDED TO INTERIOR OF POLE.
CONDUCTOR TO BE SAME SIZE ANCHOR BOLTS AS
AND TYPE AS SUPPLY PHASE RECOMMENDED BY
CONDUCTOR. MANUFACTURER OF POLE
POLE - SEE POLE SKETCH AND
SPECIFICATION
POLE - SEE POLE SKETCH

#4 BARS VERTICAL AT 150


CONDUIT STUBBED UP AND SPECIFICATION
CONDUIT STUBBED UP ADJACENT TO HANDHOLE - SEE POLE SKETCH AND
HANDHOLE; NUMBER AND SIZE AS SPECIFICATION 3 ADJACENT TO HANDHOLE;
4
"Ø ELECTRICAL CONDUIT
REQUIRED NUMBER AND SIZE AS
REQUIRED HANDHOLE - SEE POLE
SKETCH AND SPECIFICATION

CHAMFER ALL EDGES OF CONCRETE ANCHOR BOLTS AS


RECOMMENDED BY
BASE 13 MM MANUFACTURER OF
SET TOP OF CONCRETE SET TOP OF CONCRETE CHAMFER ALL EDGES OF POLE
FOUNDATION 100 MM CONCRETE BASE 13 MM CONDUIT STUBBED UP
FOUNDATION 100 MM ABOVE
ABOVE GRADE ADJACENT TO HANDHOLE;
GRADE NUMBER AND SIZE AS
INSULATED COPPER GROUNDING REQUIRED
FINISHED GRADE CONDUCTOR ATTACHED TO
FINISHED GRADE
INTERNAL LUG WELDED TO

MM EACH FACE
INSULATED COPPER GROUNDING INTERIOR OF POLE. SIZE PER

CIRCUIT CONDUCTORS AND


CONDUCTOR ATTACHED TO INTERNAL NFPA 70. POLE AND SET TOP OF CONCRETE
BASE
LUG WELDED TO INTERIOR OF POLE. FOUNDATION 100 MM
SIZE PER NFPA 70. ANCHOR BOLTS AS RECOMMENDED ABOVE GRADE
BY MANUFACTURER OF POLE CIRCUIT CONDUCTORS
AND CONDUIT TO POWER
COPPER EQUIPMENT SOURCE OR NEXT POLE
GROUNDING CONDUCTOR - FINISHED GRADE
ATTACH TO INTERNAL LUG CIRCUIT CONDUCTORS AND
COPPER EQUIPMENT CONDUIT TO POWER
WELDED TO INTERIOR OF
POLE. CONDUCTOR TO BE GROUNDING CONDUCTOR - SOURCE OR NEXT POLE
SAME SIZE AND TYPE AS CIRCUIT CONDUCTORS AND ATTACH TO INTERNAL LUG
CONDUIT TO POWER WELDED TO INTERIOR OF POLE. ANCHOR BOLTS AS RECOMMENDED
SUPPLY PHASE ANCHOR BOLTS AS BY MANUFACTURER OF POLE
CONDUCTOR. SOURCE OR NEXT POLE CONDUCTOR TO BE SAME SIZE
AND TYPE AS SUPPLY PHASE RECOMMENDED BY
CONDUCTOR. MANUFACTURER OF POLE
ANCHOR BOLTS AS

CONDUIT TO POWER SOURCE


RECOMMENDED BY
#4 BARS VERTICAL AT 150 COPPER EQUIPMENT
MANUFACTURER OF POLE MM EACH FACE
CIRCUIT CONDUCTORS AND CIRCUIT CONDUCTORS AND GROUNDING CONDUCTOR -
CONDUIT TO POWER CONDUIT TO POWER SOURCE ATTACH TO INTERNAL LUG
#4 BARS VERTICAL AT 150 OR NEXT POLE
SOURCE OR NEXT POLE #3 BARS AT 300 MM ON WELDED TO INTERIOR OF POLE.
MM EACH FACE CENTER HORIZONTALLY CONDUCTOR TO BE SAME SIZE
AND TYPE AS SUPPLY PHASE
#3 BARS AT 300 MM ON CONCRETE PER SPECIFICATION CONDUCTOR.
CENTER HORIZONTALLY 19 MM X 3 M GROUND ROD

CONCRETE PER 19 MM X 3 M GROUND ROD CIRCUIT CONDUCTORS AND


SPECIFICATION CONDUIT TO POWER SOURCE
OR NEXT POLE

OR NEXT POLE
CONCRETE PER SPECIFICATION

#3 BARS AT 300 MM ON
CENTER HORIZONTALLY

CONCRETE PER SPECIFICATION


19 MM X 3 M GROUND ROD

ANCHOR BASE POLE FOUNDATION