Professional Documents
Culture Documents
Iocl CBW FD 1007 Boundary Wall
Iocl CBW FD 1007 Boundary Wall
April - 2022
1|Page
Copyright
©Meinhardt
This document is subject to copyright. Use or
copying of this document in whole or part without
the written permission of Meinhardt constitutes an
infringement of copyright.
Disclaimer
Information in this document is current at the time
of writing. While all professional care has been
undertaken in preparing the document, Meinhardt
accepts no liability for loss or damages incurred as a
result of reliance placed upon its content.
The mention of any company, product or process in
this report does not constitute or imply
endorsement by Meinhardt.
Revision History
REVISION PREPARED BY REVIEWED BY APPROVED BY DESCRIPTION DATE
R0 Ganapathi P Kashyap V. Nittala Philips Issued for Approval 29-Apr-2020
Avadhanam Kiwi
R1 Ganapathi P Kashyap V. Nittala Philips Updated comments 07-June-2020
Avadhanam Kiwi
R2 Ganapathi P Kashyap V. Nittala Philips Updated comments 02-July-2020
Avadhanam Kiwi
R3 Ganapathi P Kashyap V. Nittala Philips Issued for tender 15-June-2021
Avadhanam Kiwi
R4 Ganapathi P Kashyap V. Vasudevan Issued for tender 29-April-2022
Avadhanam Murugan
Document Acceptance
ACTION NAME SIGNED DATE
IOCL Subhendu chowdhury / Arvind
Ravi / Awaneesh kumar
2|Page
TABLE OF CONTENTS
STANDARDIZATION OF BOUNDARY WALL
3|Page
DESIGN STANDARDIZATION DOCUMENT
Standardization Design
Area
Standardization Principles & Functional
Control
Key Words: Boundary wall
DISCLAIMER:
The requirements and guidelines set out in this document shall not apply or be implemented
to the extent that they do not meet the requirements of applicable laws and regulations. In all
cases, all applicable legal and regulatory requirements must be met when conducting
activities associated with this document.
1. Details specified in this document are to be read in conjunction with the applicable
legal and regulatory requirements.
2. The document indicates, the Mandatory and Preferred design standards for IOCL to
choose accordingly and those have been identified with prefix (M) / (P) respectively.
3. Mandatory are minimum standards which IOCL must follow without any deviation
unless otherwise approved in writing by Meinhardt.
4|Page
1.GENERAL
Boundary wall facility for all the newly developed archetypes of retail outlets has been
standardized as follows.
a) Conventional Brick work Boundary wall
b) Conventional Solid Block Boundary wall
c) Precast Boundary wall
d) Chainlink Fencing
Type a, b & c boundary wall to be painted with colour Pantone cool grey 1C (RAL 9002).
Prior to the construction of boundary wall, the site condition, level differences between
adjacent land Average natural Ground level and proposed Finished driveway levels of retail
outlets shall be assessed by contractor themselves and the differences in levels shall be
constructed with size stone masonry/ RCC retaining wall to retain the soil as shown in
drawings.
Following retaining wall system has been standardized and shall be adopted in general for all
type of boundary wall to retain soil between the levels of Average natural ground level of
surrounding plot and Finished driveway levels.
a) Retaining Wall with Size Stone Masonry-Upto level differences of 1m. (As per detailed
drawing attached with this document).
b) Retaining Wall with Size Stone Masonry(Type-2)-For level differences between 1m to 2m.
(As per detailed drawing attached with this document).
c) Retaining Wall with Reinforced Concrete(RCC)-For level differences between 2m to 3m.
(As per detailed drawing attached with this document).
For level differences above 3m suitable site specific retaining wall system shall be adopted.
For construction of Retaining wall with size stone masonry, material specifications such as
mortar to be used and stones to be used for rubble masonry and construction procedures
shall be as per General Specifications of Civil works- IOCL-GSC-TS-1037 clause 4.3 & 4.11.
And construction shall be done as per detailed drawing with staggered PVC weep holes of
75mm diameter at 2.5m centre to centre horizontal and 1.5m verticle. Weep Holes are
provided in these structures to relieve hydrostatic pressure or water pressure on the walls.
Inside edge of weep holes are covered with galvanized strainers.
5|Page
Galvanized Strainers: Galvanized Strainers of size 200mmX200mm as shown in drawing with
mesh size of 20mmX20mm with 2mm dia strainer shall be provided at Inside edge of weep
holes to protect soil particles from washing away with water. Coasre grained pebbles shall
be arranged at the locations of Galvanised strainers as shown in drawings which acts as
filter media for soil particles and allows water to flow through weep holes.
Rate Recommendation: Supply,delivery and fixing GI Strainer mesh (200mm x 200mm) as
per drawing and specifications for Retaining Wall. This work includes delivery, unloading,
checking, segregating, storing and placing in position including lead and lift and other
incidental charges to complete the work as instructed is -Rs.810 per Square metre.
For construction of Retaining wall with RCC, material specifications such as Concrete and
reinforcement and construction procedures shall be as per General Specifications of Civil
works- IOCL-GSC-TS-1037 clause 4.3 & 4.4.
And construction shall be done as per detailed drawing with size of retaining walls and
reinforcements as indicated in drawing. Staggered PVC weep holes of 75mm diameter at
1.5m centre to centre horizontal and 1.5m verticle shall be provided as indicated in
drawing.
Dowel bars shall be provided from RCC retaining walls for constructing 200mmx200mm RCC
Column stiffeners at typical 3metres centre to centre for conventional boundary walls.
Pockets shall be provided in Retaining walls (Both in Size stone/rubble masonry and RCC
retaining walls) for placing Chainlink Fencing Posts or Precast Columns and for Construction
of Yardlight Pedestals as indicated in detailed drawings.
6|Page
I.SECTION-1-CONVENTIONAL BRICK WORK/ SOLID BLOCK BOUNDARY WALL
230mm thick Brickwork/ 200mm thick Solid Concrete blockwork is proposed for Conventional
Boundary wall system with 360x360mm brickwork stiffeners/ 400mmx400mm blockwork
stiffeners at typical 3m centre to centre throughout the length of Boundary wall and incase of
brickwork/ Block work constructed over RCC retaining walls due to site specific requirement
of level differences between 2 to 3m, then 230mmx230mm RCC columns will be provided in
case of brickwork boundary wall & 200mmx200mm RCC columns will be provided in case of
blockwork boundary wall at typical 3m c/c above retaining wall with reinforcement bars
lapped with retaining wall. At every typical 30m intervals of Boundary wall Blockwork
construction, 25mm gap shall be provide as expansion joints. This gap shall be kept open
above ground level and below ground level, the gap shall be filled with mortar of 1:5.
The manufacturing, physical requirements and other features to be as per IS 2185 (Part 1):
Concrete Masonry Units. Technical Specifications of Brickwork, Blockwork and mortar shall
be as per- General Specifications of Civil works- IOCL-GSC-TS-1037 clause 4.3, 4.8, 4.9 & 4.12.
7|Page
2.GENERAL INSTRUCTION
a) Clearing the site by removing all obstacles for construction of Precast Boundary Wall.
b) Manufacturing of precast boundary wall blocks in contractor’s plant as per requirement
in technical specification.
c) Supplying of precast boundary walls at site, including handling at both ends.
d) Construction of precast boundary wall at site on size stone masonary as per design
drawing and requirement of technical specification.
e) Submission of Test Certificates through reputed Govt. / IOCL Approved Test house (Duly
recognized) and submission of test results as per requirements in technical specifications.
f) The contractor shall guarantee that all material and components designed, fabricated,
supplied and laid by him shall be free from any type of defect due to faulty materials.
3.MATERIALS
Cement: Grade of cement shall be of 33 OPC, 43 grade OPC and other PPC shall comply with
as per IS standard.
Fine and coarse Aggregate: Fine and Coarse aggregates shall comply with the requirements
of IS 383. The nominal maximum size of coarse aggregates shall be used in production of
precast panels shall be 12 mm. Fine aggregates used shall have the below mentioned
gradations.
Both river/quarry sand (M-Sand) meeting the requirements can be used as per approved IS
standards.
4.GRADE DESIGNATION
The quality of panels produced will depend upon various parameters like the capacity of
compaction and vibration of machine, grade of cement used, water content, quality of
aggregates used, their gradation and mix design adopted, additives used, handling
8|Page
equipment employed, curing methods adopted, level of supervision, workmanship and
quality control achieved.
Recommended Grade of Concrete used Shall be M25.
5.MANUFACTURING PROCESS
The entire process of manufacturing of Boundary wall columns, wall Panels shall be done at
Contractor’s manufacturing Yard in quality controlled manner. The quality of Precast
elements, materials shall be as per Specifications and sizes shall be as shown in the detailed
drawing.
5.1Submission of Test Certificates
The contractor may be required to provide the following at his own expense.
b) Cube compressive strength Test for hardened Concrete blocks of concrete used for
Precast Boundary elements of grade M25.
5.2Warranty certificates
6.CONSTRUCTION PROCESS
6.1Construction of Size Stone Masonary
Prior to construction of boundary wall, the site condition, level differences between
adjacent land Average natural Ground level and proposed Finished driveway levels of retail
outlets shall be assessed by contractor themselves and the differences in levels shall be
constructed with size stone masonry to retain the soil and pockets shall be provided in the
SSM for Placing foundaions for Precast concrete columns.
6.2Construction of Precast Columns and Panels
Precast Columns shall be constructed along with their foundations as shown in the drawing.
Precast Wall panels shall be inserted between the Column posts with suitable arrangements
9|Page
as shown in detailed drawing. Any gaps in the groove between Precast Columns and Precast
panels shall be filled with cement mortor at site.
7.DESIGN, COLOUR & FINISH
Precast Boundary wall shall have plane wall panels. However decorative pre designed wall
panels are also available in the market. Design, colour and finish shall be as per IOCL
Branding.
III.SECTION-3-CHAINLINK FENCING
Chain Link :
The chain link shall be of approved manufacture and of correct size, gauge etc. as shown in
drawing. It shall be of hot dip galvanized (G.I.) 2mm thick as specified of approved
manufacture and of 50mmX50mm mesh size, 2mm gauge. The wire shall be circular in
section, free from rust, scale, cuts, welds and other defects and shall be uniformly
galvanized as specified.
Fixing of the Chain Link Fencing:
The chain link of specified height of fencing shall be fixed first to 50x50x6 Angle frame at top
and bottom. The top and bottom angles shall be provided with galvanizing coat and shall be
fixed to the vertical MS SHS 100x100x3 column posts provided with galvanized coat. After
fixing the chain link to the top and bottom frame, it shall be stretched tightly and fixed
to end column posts through welding. The point at the change in level of the fencing
top/bottom, necessary links shall be adjusted suitably as per the manufacturers
specification or as directed by the Engineer-in-charge.
Spacing of MS Post:
MS Square hollow sections of approved make 100X100X3 sections are used as supporting
Posts for the Chainlink fencing. The spacing of posts shall be maximum 2.50 m centre to
centre. MS Posts of SHS 100x100x3 shall be connected with 50x50x6mm ISA at top and
bottom as shown in drawing and on which GI Chainlink Mesh will be connected.
10 | P a g e
IV.SECTION-4-YARDLIGHT FOUNDATIONS
Yard Light Foundations are Flushed with external surface of Boundary walls in all proposed
retail outlets as shown in drawing. Foundations for Yardlights are in the form of Reinforced
Concrete Pedestals of size 400mmx400mx1300mm depth with reinforcements as shown in
the drawing. Pockets shall be provided in retaining walls such as size stone masonry wall or
RCC wall to cast Yardlight pedestals which will be combined together.
Yardlight Anchor bolts shall be placed in position with suitable templates prior to concreting
of Yardlight Pedestals. 50mm GI pipe sleeves shall be placed in pedestals before concreting
as shown in drawing for entry of cable for yardlight.
Grade of concrete for Yardlight Pedestal shall be M25 and Grade of PCC shall be M15.
Technical Specifications of Concrete shall be as per- General Specifications of Civil works-
IOCL-GSC-TS-1037 clause 4.3 & 4.4.
11 | P a g e
CONVENTIONAL BOUNDARY WALL
DETAILS-
STANDARD CIVIL DRAWINGS
10000 (TYP.) 200
WEEP HOLE
PROPOSED BOUNDARY OF 230 360x360 BRICKWORK 75Ø PVC PEBBLES.
YARD LIGHT THK. WALL WITH BRICKWORK/ STIFFENER/ 400x400 SOLID PIPE
200
200 THK. WALL WITH SOLID BLOCK WORK STIFFENER
BLOCKWORK
200/ 230
3000(TYP.) 3000(TYP.)
A B TYP.DETAILS OF
GALVANIZED STRAINER WEEP HOLE GALVANIZED
SCALE-1:15 STRAINER
400
75Ø PVC
PIPE
360 400
A B FULL BRICK
TYP. DETAIL-'X'
BOUNDARY WALL PLAN
HALF BRICK SCALE-1:15
(CONVENTIONAL-1)
1
360
400
FULL SOLID
CONCRETE
FULL BRICK BLOCKS
25MM EXPANSION JOINT, BOUNDARY WALL STIFFENER
(REFER NOTE NO:6) COPING CONCRETE
5050
BOUNDARY WALL TYP. 360X360 BRICKWORK
100
TYP. 400X400 SOLID (M15 GRADE)
STIFFENER BLOCKWORK STIFFENER
SCLE 1:15 SCLE 1:15
25 25
360x360 BRICKWORK
OUTSIDE INSIDE 230 THK WALL IN BRICKWORK/
STIFFENER/ 400x400 SOLID
200 THK WALL IN SOLID TYPICAL DETAILS OF COPING ON
1200
1200
1200
BLOCK WORK STIFFENER
CONCRETE BLOCKS IN 1:5 CM 230 THK BRICKWORK/ 200 THK
IN 1:5 CM (PLASTERING ON
(PLASTERING ON BOTH SIDE) SOLID BLOCK WORK WALL
BOTH SIDE) SCALE - 1:5
POCKET FOR PCC 100 THK
PCC 100 THK
100
100
FENCING POST FIXING COPING CONCRETE
FDL FDL FDL
5050
100
(M15 GRADE)
VARIES UP TO
VARIES UP TO
VARIES UP TO
MAX. 1000MM
MAX. 1000MM
MAX. 1000MM
450 450
VARIES 500
VARIES 500
VARIES 500
450
FILTER MEDIA FILTER MEDIA FILTER MEDIA 25 25
MIN.1000
MIN.1000
IN 1:6 CEMENT MORTAR IN 1:6 CEMENT MORTAR IN 1:6 CEMENT MORTAR (PLASTERING ON BOTH SIDE)
750 750 750
TYPICAL CHAINLINK FENCE FOR BOUNDARY WALL SECTION A-A SECTION B-B (TYPICAL CROSS SECTION OF TYPICAL DETAILS OF COPING ON 360x360
SCALE 1:25 (TYPICAL CROSS SECTION OF BOUNDARY WALL) BOUNDARY WALL AT STIFFENER ) BRICKWORK STIFFENER/ 400x400 SOLID
SCALE 1:25 SCALE 1:25 BLOCK WORK STIFFENER
SCALE - 1:5
NOTES: 5. ALL 75Ø PVC WEEP HOLES SHALL BE PROVIDED @2500C/C HORIZONTAL 8. GRADE OF CONCRETE FOR PCC M15 (1:2:4) LEGENDS:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. AND @1500C/C VERTICAL DIRECTION STAGGERED POSITION.
2.DIMENSIONS ARE NOT TO BE SCALED. 6. AT EVERY 30 METER 25MM GAP SHALL BE KEPT AS EXPANSION JOINT AND FDL - FINISHED DRIVEWAY LEVEL
3. ANY DISCREPANCY BETWEEN THIS DRAWING AND OTHER DRAWINGS MUST BE THIS GAP SHALL BE FILLED WITH CEMENT MORTAR IN 1:5 BELOW GROUND NGL -NATURAL GROUND LEVEL
BROUGHT TO THE NOTICE OF DESIGN TEAM. AND ABOVE GROUND LEVEL THE GAP SHALL BE KEPT OPEN.
7. MASONRY STONE SHOULD BE DENSE STONE LIKE GRANITE, GNEISSES &
4.CHAIN LINK SHALL BE 2MM THICKNESS GI CHAIN LINK AND OF 50MM MESH SIZE.
CONSTRUCTION SHALL BE DONE AS PER IS 1597 PART-1/PART-2
1200
1200
1200
CONCRETE BLOCKS IN 1:5 CM 1:5 CM (PLASTERING ON
(PLASTERING ON BOTH SIDE) BOTH SIDE)
POCKET FOR PCC 100 THK PCC 100 THK
100
100
FENCING POST
FIXING FDL FDL FDL
500
500
500
450 450 450
1000 TO 2000MM
1000 TO 2000MM
1000 TO 2000MM
500
500
500
VARIES
VARIES
VARIES
AVG. NGL RANDOM RUBBLE AVG. NGL RANDOM RUBBLE AVG. NGL RANDOM RUBBLE
900 MASONRY IN 1:6 900 MASONRY IN 1:6 900 MASONRY IN 1:6
500
500
500
MINI.1000
MIN.1000
MIN.1000
500
500
500
5050
100
(M15 GRADE)
5050
100
(M15 GRADE)
25 25 25 25
PEBBLES.
230 THK WALL IN BRICKWORK/ 360x360 BRICKWORK STIFFENER/
200 THK WALL IN SOLID 400x400 SOLID BLOCK WORK
CONCRETE BLOCKS IN 1:5 CM STIFFENER IN 1:5 CM
GALVANIZED
200 WEEP HOLE (PLASTERING ON BOTH SIDE) (PLASTERING ON BOTH SIDE)
75Ø PVC
GALVANIZED PIPE
200
NOTES: 5. ALL 75Ø PVC WEEP HOLES SHALL BE PROVIDED @2500C/C HORIZONTAL 8. GRADE OF CONCRETE FOR PCC M15 (1:2:4) LEGENDS:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. AND @1500C/C VERTICAL DIRECTION STAGGERED POSITION.
2.DIMENSIONS ARE NOT TO BE SCALED. 6. AT EVERY 30 METER 25MM GAP SHALL BE KEPT AS EXPANSION JOINT AND FDL - FINISHED DRIVEWAY LEVEL
3. ANY DISCREPANCY BETWEEN THIS DRAWING AND OTHER DRAWINGS MUST BE THIS GAP SHALL BE FILLED WITH CEMENT MORTAR IN 1:5 BELOW GROUND NGL -NATURAL GROUND LEVEL
BROUGHT TO THE NOTICE OF DESIGN TEAM. AND ABOVE GROUND LEVEL THE GAP SHALL BE KEPT OPEN.
7. MASONRY STONE SHOULD BE DENSE STONE LIKE GRANITE, GNEISSES &
4.CHAIN LINK SHALL BE 2MM THICKNESS GI CHAIN LINK AND OF 50MM MESH SIZE.
CONSTRUCTION SHALL BE DONE AS PER IS 1597 PART-1/PART-2
(TYP.)
450
(PANEL) (PANEL)
50
450 50THK. FOUNDATION
PRECAST ELEVATION ELEVATION
(TYP.) (TYP.)
PANEL
150
(TYP.)
300
PRECAST
COLUMN
FDL
RCC FOUNDATION
50THK DECORATIVE (CAST IN SITU)
PRECAST PANEL
750
750
M25 GRADE
CONCRETE
50
50
50
P.C.C M15
(1:2:4)
75 450 75 75 450 75 75 450 75
ELEVATION
2
PRECAST
COLUMN
750
40 CLEAR COVER
ALL ROUND
10mm Ø REINFORCEMENT
50
P.C.C M15
150 75 450 75
450
8Ø REINFORCEMENT
8Ø LINKS @125C/C
(PANEL)
2100
@ 200C/C
150
450
8Ø STIRRUPS
55x50mm
@150C/C
GROOVE
40 CLEAR COVER
ALL ROUND
2100
(TYP.)
450
200 (PANEL)
500
PRECAST
COLUMN
50THK. PRECAST
450 PANEL 500
(TYP.)
200 7
50
300
300
8Ø STIRRUPS
500
@150C/C
50
75
DETAIL-A
75
WIDTH
A A
300xBOUNDARY WALL
WIDTHx400 DEPTH M25
CONCRETE
BOUNDARY WALL 50x50x6MM THK. GI GIRT (ISA BOUNDARY WALL
INSIDE 50X50X6)
ANGLE TOP FRAME SHS 100x100x3 INSIDE
PLAN CHAIN LINK FENCING EMBEDDED IN
1 DETAIL-A
CONCRETE 4
OUTSIDE INSIDE
1050
SHS 100x100x3 CHAIN LINK FENCING
CHAIN LINK TO
SPECIFICATION
DETAIL-X
5
FDL
150
300xBOUNDARY WALL
WIDTHx400 DEPTH M25
250
CONCRETE
1050
1200
SECTION B-B
3
POCKET FOR
300 FENCING POST FIXING
150
FDL
500
B RANDOM RUBBLE
MASONRY
800
SECTION A-A 600 IN 1:6 CEMENT MORTAR
ELEVATION OF CHAIN LINK FENCING
2
PCC 100 THK
GOOD QUALITY
100
NOTES: 850 MURRAM/GRAVEL 0.3M
IMPORTANT NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. 1. LEVEL DIFFERENCES BETWEEN FDL AND ADJACENT SITE NGL LEVELS SHALL BE
EACH LAYER AND WELL
2.DIMENSIONS ARE NOT TO BE SCALED. CONSTRUCTED WITH RR MASONRY OVER WHICH CHAIN LINK FENCING COMPACTED
3. ANY DISCREPANCY BETWEEN THIS DRAWING AND OTHER DRAWINGS MUST SHALL BE CONSTRUCTED(FOR RR MASONRY CONSTRUCTION REFER SHEET-1 &
BE BROUGHT TO THE NOTICE OF DESIGN TEAM. SHEET-2).
4.CHAIN LINK SHALL BE 12-GAUGE THICKNESS AND OF 50MM MESH SIZE.
TYP. CHAIN LINK FENCING
2.POCKETS SHALL BE PROVIDED IN THE RR MASONRY FOR CHAIN LINK FENCING
5. GRADE OF CONCRETE FOR RCC M25 & FOR PCC M15 SCALE - 1:50
POST.
300
A WALL
100
A
RETAINING WALL WITH TOP CHAIN LINK FENCING/ BRICKWORK/ SOLID BLOCKWORK COMPOUND WALL PLAN
1
200 200/230
COPING COPING
1200
1200
CHAIN LINK FENCE FOR DETAILS 200 THK WALL IN SOLID BRICKWORK BOUNDARY WALL/
CONCRETE BLOCKS IN 1:5 CM 200X200 RCC COLUMN STIFFENER FOR
(PLASTERING ON BOTH SIDE) SOLID BLOCKWORK BOUNDARY WALL
TOC TOC TOC
100
td
100
100
FDL td FDL td FDL
Ld
e e
H
H
a1 a1 a1
WEEP HOLE 75Ø PVC PIPE @ 1.5M WEEP HOLE 75Ø PVC PIPE @ 1.5M WEEP HOLE 75Ø PVC PIPE @ 1.5M
d C/C (STAGGERED VERTICALLY & d C/C (STAGGERED VERTICALLY & d C/C (STAGGERED VERTICALLY &
HORIZONTALLY) (TYP.) HORIZONTALLY) (TYP.) HORIZONTALLY) (TYP.)
e
a1 a1 a1
LD.
LD.
LD.
AVG. NGL AVG. NGL AVG. NGL
a a a
D2
D2
D2
CONSTRUCTION CONSTRUCTION CONSTRUCTION
JOINT JOINT JOINT
g
1000
b g g
1000
b
1000
b
LD LD LD LD
Dt
Dt
Dt
LD LD
PCC 100mm PCC 100mm PCC 100mm
THK. THK. THK.
c f c f c f
tb LH tb LH tb LH
TYPICAL DETAILS OF CANTILEVER RETAINING WALL
TYPICAL DETAILS OF CANTILEVER RETAINING WALL TYPICAL DETAILS OF CANTILEVER RETAINING WALL
FOR COMPOUND WALL WITH SOLID BLOCKWORK FOR COMPOUND WALL WITH COLUMN STIFFENER @
EVERY 3M C/C
NOTES: 7. MINIMUM NET SAFE BEARING CAPACITY AT LEVEL OF FOOTING SHALL BE NOT LESS THAN 8T/M²
8. IF SBC OF SOIL IS LESS THEN 8T/M² , SUITABLE SITE SPECIFIC APPROVED SOIL STRENGTHENING METHODS
LEGENDS:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. SHALL BE ADOPTED TO IMPROVE SBC OF SOIL GREATER THAN OR EQUAL TO 8T/M². FDL - FINISHED DRIVEWAY LEVEL
2.DIMENSIONS ARE NOT TO BE SCALED. 9. AT EVERY 30 METER 25MM GAP SHALL BE KEPT AS EXPANSION JOINT AND THIS GAP SHALL BE FILLED WITH NGL -NATURAL GROUND LEVEL
3. GRADE OF CONCRETE FOR RCC M25 & FOR PCC M15 CEMENT MORTAR IN 1:5 BELOW GROUND AND ABOVE GROUND LEVEL THE GAP SHALL BE KEPT OPEN.
4.GRADE OF REINFORCEMENT STEEL Fe500. 10. YARDLIGHT SHALL BE PROVIDED AT EVERY 10M C/C & POCKETS SHALL BE PROVIDED IN THE RETAINING WALL
5. CHAIN LINK SHALL BE 2MM THICKNESS GI CHAIN LINK AND OF 50MM MESH SIZE. FOR YARDLIGHT PEDESTALS.
6. CLEAR COVER FOR WALL & BASE SLAB SHALL BE 50mm. 11. WEEP HOLE 75Ø PVC PIPE @1.5M C/C (STAGGERED VERTICAL & HORIZONTAL SHALL BE PROVIDED
THROUGHOUT THE LENGTH AND HEIGHT OF RETAINING WALL.
200
GALVANIZED
2.5 230 350 450 3200 STRAINER
TYP.DETAILS OF
GALVANIZED STRAINER JOINT FILLER
REINFORCEMENT SHOULD BE
SCALE-1:15
3.0 230 400 450 4500 CURTAILED
TYP. DETAIL-'X'
SCALE-1:15 TYP. EXPANSION JOINT DETAILS
SCALE-1:15
200/230
200/230
RETAINING SLAB SLAB
WALL 'H' (M) T8-STIRRUPS
a a1 b c d e f g @150C/C
12Ø TOR@250 10Ø TOR@250 12Ø TOR@250 10Ø TOR@150 10Ø TOR@150 TYP. COLUMN STIFFENER DETAIL
2.5 10Ø TOR@150C/C 8Ø TOR@150C/C 8Ø TOR@150C/C (230X230 RCC COLUMN STIFFENER FOR
C/C C/C C/C C/C C/C
BRICKWORK BOUNDARY WALL/
200X200 RCC COLUMN STIFFENER FOR
12Ø TOR@250 12Ø TOR@250 16Ø TOR@250 10Ø TOR@150C/C 8Ø TOR@125C/C 8Ø TOR@125C/C 10Ø TOR@150 10Ø TOR@150 SOLID BLOCKWORK BOUNDARY WALL)
3.0
C/C C/C C/C C/C C/C SCLE 1:5
NOTES: 7. MINIMUM NET SAFE BEARING CAPACITY AT LEVEL OF FOOTING SHALL BE NOT LESS THAN 8T/M² LEGENDS:
8. IF SBC OF SOIL IS LESS THEN 8T/M² , SUITABLE SITE SPECIFIC APPROVED SOIL STRENGTHENING METHODS
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. SHALL BE ADOPTED TO IMPROVE SBC OF SOIL GREATER THAN OR EQUAL TO 8T/M². FDL - FINISHED DRIVEWAY LEVEL
2.DIMENSIONS ARE NOT TO BE SCALED. 9. AT EVERY 30 METER 25MM GAP SHALL BE KEPT AS EXPANSION JOINT AND THIS GAP SHALL BE FILLED WITH NGL -NATURAL GROUND LEVEL
3.GRADE OF CONCRETE FOR RCC M25 & FOR PCC M15 CEMENT MORTAR IN 1:5 BELOW GROUND AND ABOVE GROUND LEVEL THE GAP SHALL BE KEPT OPEN.
4.GRADE OF REINFORCEMENT STEEL Fe500. 10. YARDLIGHT SHALL BE PROVIDED AT EVERY 10M C/C & POCKETS SHALL BE PROVIDED IN THE RETAINING WALL
5.CHAIN LINK SHALL BE 2MM THICKNESS GI CHAIN LINK AND OF 50MM MESH SIZE. FOR YARDLIGHT PEDESTALS.
6.CLEAR COVER FOR WALL & BASE SLAB SHALL BE 50mm. 11. WEEP HOLE 75Ø PVC PIPE @1.5M C/C (STAGGERED VERTICAL & HORIZONTAL SHALL BE PROVIDED
THROUGHOUT THE LENGTH AND HEIGHT OF RETAINING WALL.
FDL
150
FDL
150
PEDESTAL
400x400
1300
CABLE ENTRY
400
8 NOS-T10
200
24Ø HOLES,
T8 @ 200C/C 4NOS FOR
400
M20 BOLTS
200
BASE PLATE
200x200x12MM
THK.
5000/ 6000
75
°
TOP CLOSED
470
25°
STIFFNER PLATE
300
500
3 Nos. NUT/BOLT
12
150
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. 6. GRADE OF CONCRETE FOR PCC M15 & FOR RCC M25
2. DIMENSIONS ARE NOT TO BE SCALED.
LEGENDS:
3. ANY DISCREPANCY BETWEEN THIS DRAWING AND OTHER DRAWINGS MUST BE BROUGHT TO THE NOTICE OF
DESIGN TEAM. FDL - FINISHED DRIVEWAY LEVEL
4. THE POLE SHALL BE MANUFACTURED FROM G.I ERW PIPE. NGL -NATURAL GROUND LEVEL
5. OUTSIDE PORTION OF THE POLE ALONG WITH BASE PLATE IS PAINTED WITH GREY PAINT.
REMAINING EXTERIOR PORTION IS PAINTED WITH RED OXIDE PRIMER.
BOUNDARY
BOUNDARY
YARD LIGHT POLE
BLOCK WORK
400
℄ OF
(REFER SITE LAYOUT)
℄ OF
INSIDE OUTSIDE FDL
OUTSIDE
150
INSIDE
PEDESTAL
PROPOSED/EXISTING 400x400 FDL
80
150
PROPOSED/EXISTING
BOUNDARY WALL
BOUNDARY WALL
55 80120 Ø50MM GI PIPE T8 @ 200 C/C
PEDESTAL 400x400 SLEEVE FOR
CABLE ENTRY PEDESTAL
1300
BASE PLATE 8 NOS-T10
220x220x12MM THK. LIGHT POLE RCC PEDESTAL
GRADE M25 POCKETS
50MM THK. (APPLICABLE FOR
== PCC GRADE M15 EXISTING BOUNDARY
==
BOUNDARY WALL)
BOUNDARY PROPOSED/EXISTING
WALL WIDTH
WALL WIDTH BOUNDARY WALL
PROPOSED/EXISTING
BOUNDARY WALL
PLAN
LIGHT POLE FOUNDATION DETAILS SECTION A-A SECTION B-B
1 PLAN OF LIGHT POLE @1.2M 3 4
2
SHS 100X100X3
400 EMBEDDED IN GIRT (ISA 50X50X6)
CONCRETE OUTSIDE
300 CHAIN LINK FENCING
8 NOS-T10 400
200
75
24Ø HOLES,
155
T8 @ 200C/C 4NOS FOR
265
400
WIDTH
M20 BOLTS
110
200
BASE PLATE
200x200x12MM
LIGHT POLE
THK.
℄ OF
5000/ 6000
5000/ 6000
75
°
TOP CLOSED
470
25°
STIFFNER PLATE
300
500
FFL/FDL
3 Nos. NUT/BOLT
12
150
Boundary wall with blockwork with Size stone Masonry Retaining wall base BOQ for 1m Length
Boundary wall with brickwork with RCC Retaining wall base (RW) BOQ for 1m Length