NOTIFICATION
NOTIFICATION NO. 45
Amendment No. 2/IRC:22-2015/Rebruary, 2021 (Effective from 1" May, 2021)
IR
To
-2015 “Standard Specifications and Code of Practice for Road Bridges Section VI
Composite Construction” (Limit State Design) (Third Revision)
SL] Clause No, For Read
No.| Page No.
1] Clause No. [If the flexural tensile stress in concrete thus [If the flexural tensile stress in concrete
603.1, calculated exceeds the tensile strength of concrete, | thus calculated exceeds the tensile
(Pg.n0. 11) | fyou.a8given in Table 6,5 of IRC:112-2011 strength of concrete, f., 0f fy 8 given in
Second para Table 6.5 of IRC12
2 | Clause No. 611.2 Field testing of Stud shear
6112, connectors
(Pg. no. 67) The following field tests shall be
(New clause
conducted on every steel concrete
composite bridge before pouring of|
conerete:
Visual inspection:
1. Weld to a stud shear connector should
form a complete collar around the
shank, be free from eracks and other
defects like twist, bends etc. And
excessive splashes of weld material.
2, Weld to a stud shear connector should
havea'steel blue appearane
‘Tests to check the fixing of shear studs:
1. Ring test: the fixing of studs after being
‘welded in position shall be tested to the
satisfaction of the engineer in change
by striking the side of the head of the
stud witha 2 kg hammer. Aringing tone
after striking indicates good fus
whereas a dull tone indicates a lack of
fusion, All studs need to be checked by
aring test.
2. Bend test: any stud selected by the
engineer in charge shall be capable of
being bent by striking the side of the
ad of the stud with a 6 kg hammer
until its head is displaced laterally a
distance of approximately 25% of the
height of the stud from its original
position. The weld should then be
checked for signs of cracking or lack of
fusion. Stud should not be bent back as
this is likely to damage the weld. The
testingrate shouldbe | in 50,