Abstract
The objective of this work was to determine the accuracy and limitations of a new version of
Fire Dynamics Simulator (FDS), developed by McGrattan et al., on axi-symmetric fire
plumes. The current version uses LES for turbulence, a mixture-fraction-based infinitely fast
chemistry model for combustion, and a constant radiative loss fraction. These sub-models
have been tested for unconfined fires of different sizes, based on a dimensionless heat release
rate QD in the range of 0.1 to 10.0, which covers most natural fire scenarios. No adjustment of
constants or algorithms in the model FDS2.0 have been made. An examination of plume
theory is made first to find the benchmark correlations. This shows a generalization for a
collection of correlations based on theory, and which might be ‘‘the best’’. Using the
characteristic length as the scaling factor, it is found that the optimum resolution of a pool fire
simulation is around 0.05. With this resolution, the flame height prediction is found to fit well
with flame height correlations. Some other parameters such as temperature and mixture
fraction are found to be close to the empirical estimations at flame tips. The Froude number,
which describes the relative strength of momentum and buoyancy, falls within the
measurement range of many researchers. The simulation also reveals that the temperature
near the burner is over-predicted, while the centerline temperature and velocity in the non-
combusting region is predicted well.
r 2003 Elsevier Science Ltd. All rights reserved.
Keywords: Fire plume dynamics; Flame height; Entrainment; Large eddy simulation
0379-7112/03/$ - see front matter r 2003 Elsevier Science Ltd. All rights reserved.
doi:10.1016/S0379-7112(02)00082-6
468 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
Nomenclature
1. Introduction
2. Methodology
Here we briefly summarize the new models adopted in the code, which is supplied
by McGrattan et al. [30].
The new combustion model used here is based on mixture-fraction based infinitely
fast chemistry kinetics. The general form of the combustion reaction is
X
vO ½O þ vF ½F- vP ½P: ð1Þ
P
where the mass burning rate is based on the oxygen consumption rate given as
dYO dYO
m ’ 000
O ¼ r rD rZ r rDrZ: ð7Þ
dZ dZ
The ability to predict the rZ over the cell is a reason for Eq. (4b).
Specifically for our fire simulation, by default in the code, we can have the
following diagram showing the relationship between species (Fig. 1) for fires of a
typical fuel, propane. Here DhO ¼ 13:1 MW/kg is used for propane.
The net radiant energy gained by a grid cell is the difference between that which is
absorbed and that which is emitted. The source term is defined as
(
ksT 4 =p; Outside;
kIb ¼ ð10Þ
wr q’ 000 =4p; Inside:
Here q’ 000 is the chemical heat release rate per unit volume and wr is the local
fraction of the energy emitted as thermal radiation. The radiant heat flux vector qr is
defined as
Z
qr ðxÞ ¼ sIðx; sÞ dO: ð11Þ
Through the simulations, we use the default parameters for radiation calculation,
since we have no better experimental result on radiation prediction in flames.
There has been some work done with FDS on isolated fire plumes [28]. Our
purpose is to examine the code for a wide range of fire plumes. The former needs a
specific fire experiment while the latter needs general experimental correlations for
comparison. In the following, plume theory will be used to extend existing
correlations to a more complete and accurate representation of data. While some
specific correlations are considered, it should not be inferred that others not
considered are inferior.
The appropriate scaling parameters for most of the features of fire plumes have
not been universally established by all investigators. However, the scaling laws for
the size of the diffusion flames have been developed by a number of authors, and
some consensus has been reached that a dimensionless fire power [32]
Q’
QD ¼ pffiffiffiffiffiffiffi ð12Þ
rN cp TN gDD2
’ 5=2 can be used
or a dimensional parameter that is proportional to QD ; such as Q=D
as a scaling parameter. Flame-length data discussed by Zukoski [16] and Hasemi [6]
indicate that scaling laws for the visible flame length, and possibly for other
parameters of interest including the entrainment rate, have a different functional
form for several ranges of QD ; and must be considered separately for each regime.
It is also pointed out by Heskestad [33] that QD does not appear to be a sufficient
scaling parameter for the flaming region. Flame height measurements data support a
new scaling parameter N:
Q’ 2 cp TN 3 ’ 2
cp T N
N¼ ¼ ðQ D Þ : ð13Þ
grN ðDhc =sa Þ3 D5 Dhc =sa
In practice, the distinction from QD is important mainly when atmospheric
conditions differ significantly from standard. So here we still rely on QD as the
scaling parameter.
According to Hasemi et al. [6], natural fires always fall into the range of QD ¼ 0:1
to QD ¼ 10:0: Fig. 2 summarizes the correlation between fuel size and QD for typical
natural fires in unconfined environments. This demonstrates that the range of QD for
most building combustible objects with the size of 0.1–2 m is approximately 0.3–3.0,
474 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
whereas measurements of the plume properties have been made mostly for a wider
range of QD : In order to investigate the significance of the flame geometry on the
plume properties, Hasemi et al. [6] measured the centerline and the radial
distribution of temperature and upward velocity on porous round burners with
propane as the fuel for 0.4oQD o4.0. Here our computed simulation range is
0.1oQD o10.0, which covers the range of QD for most common fires. In order to
develop the appropriate theoretical basis for the general dimensionless correlations,
we will examine specific fire plume features.
Or,
w2
Fr ¼ ¼ 2: ð17bÞ
ðT TN Þ=TN gz
This gives the inviscid steady value along the centerline a buoyant plume. In a
review of real fire plume data, Beyler [12] summarized many experimental results and
found the plume centerline Froude number ranged from about 1.16 to 2.0 for a wide
range of data with an average of about 1.5 in the non-combusting and flame
intermittent region. Quintiere and Grove [17] have shown that Fr ¼ 1:570:1 for
both line and axi-symmetric fire plumes along the centerline in their entire domain,
combusting and non-combusting regions. Heskestad [33] uses an alternative
parameter defined as z ¼ ð9:1Þ0:3 Fr1=2 in the non-combusting plume region. This
value is found to be 2.2 [33], 2.7 [4], 2.4 [10] corresponding to a range of Fr from 1.29
to 1.94.
It appears that a multitude of data from fire plumes suggest a fairly constant time-
averaged Fr along the centerline. Since it ties the velocity directly to the temperature
change, it is a valuable feature and useful tool in fire induced flow research. The
approximate constancy of Fr also suggests a small and uniform departure of real
fires from inviscid flow.
Dimensional analysis of the governing equations can show that the centerline
plume temperature satisfies
T TN
¼ f ðXr ; z=z ; D=z Þ; ð18Þ
TN
where
!2=5
Q’
z ¼ pffiffiffi ¼ ðQ’ D Þ2=5 D ð19Þ
r N cp T N g
is a characteristic plume length scale, and D is the effective diameter of the fuel
source (the diameter of the circle with an equivalent area). Theoretical analysis [16]
can show the general power-law form of this relationship in the combusting and the
non-combusting regions of the plume. The coefficients in these relationships must be
set from experimental data.
In the non-combusting plume region, Heskestad [14] developed a relationship in
terms of a virtual origin z0, offset below the base of the fire, to account for the
dependence on D:
i.e. for z > zf ;
T TN z z
5=3
0
¼ CT ð1 Xr Þ2=3 ; ð20Þ
TN z
476 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
where
z0 D
¼ 1:02 þ 1:37 ð21Þ
z z
gives the virtual origin. Heskestad [14] obtained CT ¼ 9:1 for the domain of pool
fires, 0:04pQD p2:0; QD ¼ ðz =DÞ: Quintiere and Grove [17] found CT ¼ 10:6
based on far field data of Yokoi [2], and this variation suggests the current level of
uncertainty in CT :
From the constancy of Fr, the centerline dimensionless velocity can be consistently
written as
w z z
1=3
0
W ¼ pffiffiffiffiffiffiffi ¼ CV ð1 wr Þ1=3 ; ð22Þ
gz z
where CV is 3.4 according to Heskestad [14], or 4.17 from Quintiere and Grove [17].
For the combusting region, it is assumed that the entrainment rate of air into the
plume controls the burning rate. With the similar turbulent mixing effects, the fire
consumes the same fraction of stoichiometric air. The entrained air is about 10 times
of the stoichiometric air [17]. A theoretical analysis based on these assumption leads
to a constant centerline temperature in the fire region. Accordingly,
T TN Dhc =sa
¼ CT;f ð1 Xr Þ ; ð23Þ
TN cp TN
where CT,f is a constant dependent on a fit to data. After checking Table 1 for
selected centerline flame temperatures, chosen for accuracy and fuel range, an
estimate of CT,f=0.50 is a good choice. For the propane fuel in our simulation, the
temperature is estimated as 10411C in the flaming region.
This result should serve as an approximate benchmark in the combusting region to
assess the accuracy of both predictive and experimental results. The radiation
fraction is a significant factor, and it probably represents the most complex
phenomena. The value of Xr is difficult to measure and will vary, depending on fuel
type and fire diameter. A fundamental predictive model for Xr would require more
detailed data and be capable of resolving distributions for flame properties.
Table 1
Maximum accurately measured centerline flame temperatures
1260 Nat. Gas 2.91 0.3 17.9 0.15 Smith et al. [34] 0.50
1100 Nat. Gas 2.91 0.3 70.1 0.25 Smith et al. [34] 0.48
930 Heptane 2.96 1.74 7713 0.43 Kung et al. [10] 0.52
990 Methanol 3.07 1.74 973 0.18 Kung et al. [10] 0.59
T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492 477
Numerous correlations exist for flame height, and some are summarized in the
SFPE Handbook [13]. Usually, flame height correlations are produced under a
specific situation and offer independent results from each other. Among them,
Heskestad’s [8] expression is easy to use and Zukoski’s [26] expression is based on
consistent data.
Heskestad gives
2=5
zf QD
¼ 15:6 1:02; ð24Þ
D ðDhc =sa Þ=cp TN
which is commonly presented as
zf 2=5
¼ 3:88QD 1:02 for Dhc =sa ¼ 2:975 kJ=g: ð25Þ
D
Based on the three data regimes characterized by QD ; Zukoski developed
zf
¼ 40Q2
D for 0:03pQD o0:15; ð26aÞ
D
zf 2=3
¼ 3:3QD for 0:15pQD o1:0; ð26bÞ
D
zf 2=5
¼ 3:3QD for 1:0oQD o40:0: ð26cÞ
D
Both correlations (Eqs. (24) and (26)) ignore the effect of flame radiation. Hamins
et al. [11] attempted to include this effect with an empirical inclusion of Xr : They
obtained
2=5
zf Q’ ð1 Xr Þ2=5
¼ 18:5 D 3=5 1:06: ð27Þ
D ðDhc =sa Þ=cp TN
This expression does not contain the correct dependence for Xr according to the
theory of Quintiere and Grove [17]. They theoretically derived the effect of radiation
and found an implicit expression for flame height.
z
1=2
f zf
2 QD
1 þ 0:357 ¼ 169:5 3=2 : ð28Þ
D D ðDhc =sa Þ=cp TN ð1 Xr Þ1=2
5=2
For zf =D > 0:1; the LHS can be approximated as 0:775 þ 0:463ðzf =DÞ ; giving
2=5
zf QD
E16:8 3=5 1:67: ð29Þ
D ðDhc =sa Þ=cp TN ð1 Xr Þ1=5
This has the form of Eqs. (24) and (26). It would appear that radiation does not have
a strong effect on flame height. However, it has the opposite trend in Hamins’ result.
Qualitatively, as Xr increases, the flame temperature, velocity and entrainment rate
should decrease, and therefore the flame height should increase as more air is
available for combustion.
478 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
For zf =Do0:1 the LHS of Eq. (29) can be approximated as ðzf =DÞ1=2 therefore
zf Q2
E2:873 104 D
3 ð30Þ
D ðDhc =sÞcp TN ð1 Xr Þ
or using Dhc =sa ¼ 2:975 kJ=g
zf 2:75 2
E Q ð31Þ
D 1 Xr D
with the same form as Zukoski (Eq. (26c)), but now including Xr :
The range of flame height data is about 0:05pQD p100: All of these formulas give
good accuracy above QD ¼ 1:0: There is a larger disagreement among the formulas
and a larger scatter of the data below QD ¼ 1:0: We shall use Eqs. (24), (26) and (29)
as good representations of flame height (shown in Fig. 3). In practice, we usually
take the following parameters: Dhc =sa ¼ 2:975 kJ=g; cp ¼ 1:0 kJ=kg K; TN ¼
298 K:
There is an important constant in relating the entrainment rate and flame height
prediction. It is an empirical number, which has different values among different
researchers due to different test methods or analyzing theories applied. This number,
n, is the ratio of entrained air up to the flame tip with the stoichiometric air needed.
Some early research work on fire plume was performed by Yokoi [2]. Roughly 12
times stoichiometric air at flame tip was deduced by McCaffrey and Cox [35] from
his temperature and velocity profiles.
In order to fit his combustion plume model to a large quantity of flame height
data, Steward [36] found that only 400% excess air was entrained up to the flame tip,
i.e., the flame has entrained about 5 times the stoichiometric requirements.
Using k2e2g model, Tamanini [18] produced 9 times stoichiometric at flame tip.
This value was thought to be low, due to the deficiencies in the treatment of large
scale eddies near the point of transition to turbulence.
Zukoski’s [5] hood collection technique produced an equivalence ratio of
0.067710% measured value at flame tip, which yields about 15 times stoichiometric.
Based on point measurement techniques coupled to an integral model of the fluid
dynamics behavior, McCaffrey and Cox [35] got the number to be about 20 times the
stoichiometric requirement:
m ’
’ e;f ¼ 0:007QE20ðs ’ f Þ:
am ð32Þ
Beyler [37] measured the entrainment rate using the hood technique. He got
m’ e;f =Q’ ¼ 0:045 kg=k=kW ð33Þ
representing about 13 times the stoichiometric air requirement of the flame.
Based on Zukoski’s data on entrainment at flame tip, Heskestad [38] assumed self-
preserving density deficiency profiles instead of the assumption of self-preserving
excess temperature profiles used by Cetegen et al. [40] It is found that 12 times the
mass stoichiometric air is required at the flame tip.
m’ e;f ¼ 0:0054Q’ c ¼ 0:0038ðsa m
’ f ÞðDhc =sa ÞE12ðsa m
’ f Þ: ð34Þ
Using an apparatus similar to Ricou and Spalding [39], Delichatsios and Orloff
[41] found that the air entrainment is about 10 times the stoichiometric requirements
at the flame height of turbulent buoyant fires. This number had been used directly to
derive the flame height correlations from the entrainment correlations [9].
Examining a lot of data using an integral model approach, Quintiere and Grove
[17] derived the entrainment and the flame height separately, and by comparison of
coefficients, found n=9.6 for both axi-symmetric and linear plumes.
Hence, the range of n is found to be 1075.
4. Simulation results
Generally in fire research, a circular burner is used more widely than a square burner
which is used in McCaffrey’s experiments. Measurements by Hasemi et al. [6] for
square and round gas burners show little effect of the burner shape when for the square
burners, D is taken as the diameter of a circular burner of equal area. Subsequent
measurements of Hasemi and Nishita [42] have indicated tendencies to slightly higher
flame-height ratio than circular burner data for small fires. Investigation by Orloff
[43,44] revealed that the height of a peripheral rim or lip above the surface of a circular
pool fire affects the burning rate and flame shape, but has little effect on the flame
height (except through QD ). Other geometric effects on flames have attracted attention.
Without further comment, these include interactions with ceilings, interaction with
walls and corners, and interaction/merging of proximate flames.
480 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
Here for the numerical plume simulation, we are dealing with an unconfined, free
burning, square burner surface, no rim or lip, pool fire with propane as typical fuel,
and with fire sizes ranging from QD ¼ 0:1 to 10.0. (For our 0.3 0.3 m square
burner, the fire size ranges from 7.37 to 737 kW). Unless stated, all simulations are
based on constant radiative loss fraction (Xr ¼ 0:35). The mass flow rate of the
propane was specified and supplied with uniform velocity. The platform for the
simulation is the Pentium IV, 2.0 GHz, 1GB RAM, and Windows 2000. All cases are
run for 10 s of simulation with last 4 s for steady state averaging.
As Zukoski [16] pointed out, when QD o0:10; the combustion region is divided
into many flamelets that lean toward the axis of the source and that have flame
lengths much smaller than the diameter of the source. For values above 1.0, the
flames are more than three diameters high and have a columnar form. In the middle
regime the short flamelets merge as QD increases and form a single short flame near
QD ¼ 0:1: Here the simulations produced similar results as shown in Fig. 4.
The reason that we could not show results for QD o0:2 fires here is that for very
low fire intensity, the Z ¼ Zst contour will be very close to the burner, even for a very
well resolved grid size. As the cells get larger, the mixture faction value at the burner
surface is too small to reach its stoichiometric value. Sometimes, for low enough QD ;
the Z ¼ Zeff will be located inside the burner, which is invisible in SMOKEVIEW
[45], the visualization tool for FDS. We still can see the flame structure if a smaller
mixture fraction value is used, but this has less physical meaning.
There are some different definitions of flame height. The averaged luminous flame
height is generally defined as the height at which the flame is observed at or above
that height 50% of the time [48]. Hasemi’s flame height was defined as the limit
above which flame tips have never been observed by eye [6]. Visual observation tends
to yield slightly over-estimates of the 50% flame heights [16]. Video image analysis
seems to provide the best estimates though averaging a number of 1-s exposure
photographs. Cox and Chitty found the flame lengths from 3 s time exposure by
photographs of fires [7].
For our simulation, there are many parameters available that can serve as
indicators of flame height, such as temperature, fuel concentration, mixture-
fraction, or energy release, etc. Here we couldn’t use 50% intermittency, as the
frequency of fire pulsation is still not accurately resolved. Instead, we choose a
more fundamental one, local energy release rate Q’ 000 ; as the parameter for flame
height. For calculating the flame height, first we average the recorded slice file
for Q’ 000 : Generally, we choose to average the frames of 4 s steady fire simulation.
Then the Q’ 000 value was integrated over the combustion domain upwards from the
burner surface. So we have an energy release rate as a function of height. The critical
value for flame tip was considered as 95%, 99%, or 99.9%. After a series of
simulations, we decided that 99% is a good indicator for flame height (Fig. 5.). That
is to say, our flame tip is defined as the level below which 99% of the chemical
reaction occurred.
The impact of grid size on simulation results is an important consideration for any
CFD analysis. Generally, good CFD software should have a relative constant result
in a certain grid size range. Baum et al. [29] suggested that to correctly capture the
impact of burner surface, it is necessary to have 10 10 grids over the burner
surface. Here since we are dealing with a wide range of fire intensity, this empirical
rule is not enough. The choice of grid size should reflect not only the impact of fire
dimension, but also the fire size. The characteristic length, defined by Eq. (19),
combines the impact from both burner diameter and the fire size, so it is widely used
in fire research field. Here we can define the resolution of fire plume simulation as a
dimensionless parameter,
maxðdx; dy; dzÞ
R ¼ : ð35Þ
z
To simulate the fire correctly, non-uniform grid is allowed and the aspect ratio of
grid size should not exceed 2. Here we have uniform grid size in all three dimensions
in all runs, i.e. dx ¼ dy ¼ dz: The simulation resolutions for all cases are listed in
Table 2. After a lot of simulation runs, the optimum resolution for flame height
simulation was found to be R ¼ 0:05: Above this value, the simulations tend to
under-predict the flame height. Below, then the flame height is over-predicted. It is
found [49] that the plume dynamics can only be accurately simulated if the resolution
limit is about R ¼ 0:1 or smaller. Our result is even strict. The flaming region has
the chemical reactions and wide range of turbulence scales, so a finer grid size is
needed.
A closer look at other critical parameters at the flame height (calculated using
Zukoski’s correlation) shows the following result (Fig. 6.). For fires between QD ¼
1:0 to QD ¼ 10:0; the temperature at flame height is about T=3501C, which is close
to Zukoski’s value. The critical mixture fraction Z ¼ 0:01 is also close to the result
calculated using Eq. 4(a). For small fires (QD o0:5) the reaction happens only one or
two grid cells from the burner surface, the high value at flame tip is caused mainly by
diffusion alone, where the turbulence is low and the entrainment is not enough. The
fire is more laminar-like, rather than turbulent. But the temperature prediction
follows the correlation over a wide range of fires.
As Tamanini [46] pointed out, since our combustion model is based on the concept
of mixture fraction, the temperature and the mixture fraction share the same
governing equation. When using a constant radiative loss fraction, the temperature
and the mixture fraction are linearly related, so these two lines should converge into
one line, or parallel to each other. Fig. 6 shows this trend. As mixture fraction level is
an indication of the mixing level, it is also deduced that the mixture fraction level at
Table 2
List of simulation inputs
flame tip is 0.013, which is about one sixth of its stoichiometric value. This shows
that the flame entrains about 6 times stoichiometric air to the flame tip.
Currently there are no direct data available on temperature measurement at the
flame tip. But using McCaffrey’s well-accepted temperature distribution [13] and
Heskestad’s simple flame height correlation [14], we can deduce an empirical value of
temperature at the flame tip. McCaffrey’s correlation for temperature has the form
2
zf 2n1
2gDT k
¼ : ð36Þ
TN C Q2=5
Here the flame tip should be somewhere in the intermittent region. The according
constants for intermittent region are, k ¼ 1:9; C ¼ 0:9; and n ¼ 0: The flame height
using Heskestad’s correlation, which is very simple in form:
zf ¼ 0:235Q’ 1:02D: ð37Þ
The solid line in Fig. 6 shows the temperature prediction from Eqs. (36) and (37).
Fig. 7 shows the computational results for the averaged centerline Froude number.
The Froude number, after the flow develops away from the burner surface, ranges
from 2 for a very small fire to 1.1 for a very large fire. For fire intensity QD from 0.2
to 1.0, which covers McCaffrey [4] experimental range, the Froude number lies
within the range of 1.5 to 1.8, while McCaffrey got 1.62. This value is virtually
invariant throughout the fire plume region, from the intermittent zone right down
through the continuous flames at the base of the burner.
For low QD fires, the reaction zone is very small, the flow is less turbulent and
perhaps inviscid and, i.e., Froude number is close to 2.0. For fires of large QD ; the
flame is more jet-like. The computed results are in the range of experimental results,
i.e. Fr ¼ 1:570:1; and show a systymmatic effect of QD which appears related to
viscous effects.
484 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
McCaffrey [4] did a series of classical experiments in 1979. He used natural gas at
varied controlled rates on a 0.3 m square burner. His experimental data is used
widely to test combustion models. Here we directly compare the simulation result
with his experiments. His QD is 0.3 for this fire.
From Fig. 8, it is apparent that the vertical temperature distribution is fairly good,
while the flame is slightly thinner than the real measurement. A caution should be
made here that the temperature in McCaffrey’s experiment is acquired without
correction of thermocouple data. So the numerical simulation is still low for this fire
size (approx. QD ¼ 0:3). The centerline temperature distribution shows this trend
(Figs. 9 and 10).
Deep in flames, the mean temperature reaches approximately 9001C. Values of
mean temp as high as 10001C has been observed by Gregory et al. [47] in large
9 18 m2 pool fires. Also Smith and Cox [34] recorded a peak mean temperature of
12601C for 17.9 kW natural gas flame. The simulated temperature fits well in the
plume region, while over-predicted in the flaming region. The velocity from
McCaffrey’s experiment contracted together into one curve, our simulation fits well
with the measurement data.
Fig. 11 shows the temperature distribution along the centerline for a range of fire
size. It shows that the simulated temperature distribution follows the correlation well
in plume region. But the temperature rise in the combusting region is still a little
high, and the temperature drops earlier than expected in the plume region. For the
T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492 485
temperature near the burner surface, the unexpected low values for large fires and the
high values for small fires come from the main assumption that the combustion is
assumed to be infinitely fast reaction, so most reaction happens close to a flame
sheet. The location of the flame sheet determines the flame structure and all other
global parameters.
486 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
Fig. 11. Centerline temperature distribution with Heskestad’s correlation, Eqs. (20), (21) and (23).
We do not have good temperature data in the flame over a wide range of QD : The
correlation of Eq. (23) is approximate. Here from Table 2 and Fig. 5, it can be shown
that there are more grid cells over the burner diameter for QD ¼ 0:5; while the same
number of grid cells is over the flame height. It is not clear why the simulation gives
such a unusual effect in the combustion region, but good results in the far-plume
region. It is due in part to a high fuel (cool) flow rate for high QD which lowers the
flame temperature near the burner.
As pointed out by Delichatsios [9], the entrainment number n, the entrained air to
stoichiometric air required ratio at the flame tip, is important in determining the
flame height. Due to the complexity of entrainment measurements and its variations
T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492 487
For QD > 0:5 fires, the entrainment behavior is consistent with the flame height
prediction, and n varies from 8 to 14. This result is also consistent with Tamanini’s
numerical result of n ¼ 9; based on the k2e2g model, Delichatsios and Orloff [41].
Fig. 14. Non-uniform grids and comparison with different grid size.
T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492 489
Table 3
Simulation result of grid-dependent cases
No. Grid number Domain size (m) Grid size (cm) Computed Total Maximum Estimated
combustion radiative temp. (1C) Zf,eff/Zf
rate (kW) fraction
temperature decreases then increases over the range of 4501C as the grid size
decreases.
Another important point in explaining the result is the time-average effect.
Though the fire reached the approximate steady state in 2–4 s, it is fluctuating over
time, and the centerline temperature can be 750 K different depending on how time
averaging is done.
6. Conclusion
To check the applicability of FDS in simulating fire plumes, correlations for fire
plumes are reviewed for model validation purposes. Eqs. (20), (21) and (23) are
chosen to predict the temperature distribution, and (26) for flame height prediction.
Benchmark correlations are used to validate the numerical model predictions over a
490 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
wide range of fire size, QD : It is found that good results can be produced for flame
height, with a simulation grid size approximately one twentieth of the fire
characteristic length. With this simulation resolution, the flame height prediction
is found to follow the trend of most correlations, except for QD o0:5 where
experimental data are scattered.
For the flame tip, the usual definition is not applicable, as the fluctuation of flame
is unvalidated. Here a definition based on energy release is chosen and shows good
result with correlations.
At the flame tip, the temperature is around 3501C, close to predictions based on
correlations. The mixture fraction level at flame tip is around 0.012, indicating 6
times stoichiometric air occurs there.
For a single fire, the distribution of temperature is good with McCaffrey’s
experiments. Here for QD ¼ 0:3; both temperature and velocity follow well with
measurements.
From the height of 0.5z* above the burner to the flame tip, the centerline Froude
number varies with QD and is approximately constant over the steady flame length.
The values range from 2.0 to 1.1 for QD from 0.1 to 10. As QD is decreasing, the fire
shows more inviscid flow behavior.
For 0:5oQD o5; the centerline temperature in the plume region follows
Heskestad’s correlation, while the temperature in the fire is a little over-predicted.
Good prediction of flame structure is based on the entrainment behavior. Here the
simulated fires entrain about 1072 times of its stoichiometric air at the height of
flame tip for QD > 1; consistent with experimental results. For very small fires, the
flow is more laminar-like and the entrainment is also low. It follows that the fire
entrains nearly linearly with height up to its flame tip.
Some simulation on grid effects shows that the FDS code shows a good ability to
work in a certain grid range. Our criterion of R ¼ 0:05 requires a large number of
cells for large fire simulation. FDS has a parameter to adjust the energy distribution
in the fire to counteract the grid effects. FDS code has shown promising capability to
simulate fire plume dynamics Differences between the FDS computation and
experimental correlations need to be resolved, but this calls for more complete and
better data first.
Acknowledgements
The authors wish to acknowledge the important technical discussion with Drs.
Howard Baum and Kevin McGrattan, and the partial support from NIST under
Grant No. 60NANB9D0071 supervised by Dr. T. Ohlemiller.
References
[1] Morton BR, Taylor GI, Turner JS. Turbulent gravitational convection from maintained and
instantaneous sources. Proc Roy Soc 1997;234A:1–23.
T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492 491
[2] Yokoi S. Study on the prevention of fire-spread caused by hot upward current. BRI Report, June,
1960.
[3] Thomas PH, Baldwin R, Heselden AJM. Buoyant diffusion flames: some measurements of air
entrainment, heat transfer, and flame merging. 10th Symposium on Combustion, Cambridge, UK,
1965, pp. 983–996.
[4] McCaffrey B. Purely buoyant diffusion flames—some experimental results. NBSIR 79-1910, National
Bureau of Standards, Washington, 1979.
[5] Zukoski EE, Kubota T, Cetegen BM. Entrainment in fire plumes. Fire Safety J 1980/81;3:107–21.
[6] Hasemi Y, Tokunaga T. Flame geometry effects on the buoyant plumes from turbulent diffusion
flames. Fire Sci Technol 1984;4:15–26.
[7] Cox G, Chitty R. Some source dependent effects of unbounded fires. Combust Flame 1985;60:219–32.
[8] Heskestad G. Luminous heights of turbulent diffusion flames. Fire Safety J 1983;5:103–8.
[9] Delichatsios MA. Air entrainment into buoyant jet flames and pool fires. Combust Flame
1987;70:33–46.
[10] Kung H, Stavrianidis P. Buoyant plumes of large-scale pool fires. 19th Symposium on Combustion,
1982.
[11] Hamins A, Konishi K, Borthwick P, Kashiwagi T. Global properties of gaseous pool fires. 26th
Symposium on Combustion, Napoli, Italy, 1996. p. 1429–36.
[12] Beyler CL. Fire plumes and ceiling jets. Fire Safety J 1986;11:53–75.
[13] McCaffrey B. Flame height. SFPE Handbook, 2nd ed., National Fire Protection Association, 1995.
[14] Heskestad G. Fire plumes. SFPE handbook, 2nd ed., National Fire Protection Association, 1995.
[15] Delichatsios MA. Air entrainment into buoyant jet flames and pool fires. SFPE handbook, 2nd ed.,
National Fire Protection Association, 1995.
[16] Zukoski EE. Properties of fire plumes. In: Cox G, editor, Combustion fundamentals of fire. San
Diego: Academic Press, 1995. p. 34.
[17] Quintiere JG, Grove BS. A unified analysis for fire plumes. 27th Symposium on Combustion,
Boulder, CO, USA, 1998. p. 2757–66.
[18] Tamanini F. Reaction rates, air entrainment and radiation in turbulent fire plumes. Combust Flame
1977;30:85–101.
[19] You HJ, Faeth GM. Turbulent combustion: buoyant axi-symmetric turbulent diffusion flames in still
air. Combust Flame 1982;44:261.
[20] Crauford NL, Liew SK, Moss JB. Experimental and numerical simulation of a buoyant fire. Combust
Flame 1985;61:55.
[21] Adiga KC, Ramaker DE, Tatem PA, Williams FW. Modeling pool-like gas flames of propane. Fire
Safety J 1989;14:241–50.
[22] Hossain MS, Rodi M. A turbulence model for buoyant flows and its application to vertical buoyant
jets. In: Rodi W, editor. Turbulent jets & flames. New York: Pergamon Press, 1982. p. 121–78.
[23] Nam S, Bill RG. Numerical simulation of thermal plumes. J Fire Safety, 1993;21:231–56.
[24] Sinai YL, Owens MP. Validation of CFD modeling of unconfined pool fires with crosswind: flame
geometry. Fire Safety J 1995;24:1–34.
[25] Miles S, Kumar S, Cox G. The balcony spill plume—Some CFD simulations. Fire Safety Science—
Proceedings of Fifth International Symposium, Tsukuba, Japan, 1997. p. 237–47.
[26] Madrzykowski D. The future of fire investigation, Fire Chief, October, 2000
[27] Rehm RG, Baum HR. The Equations of motion for thermally driven, buoyant flows. NBS J Res
1978;83:297.
[28] McGrattan KB, Baum HR, Rehm RG, Hamins A, Forney GP. Fire dynamics simulator—user’s
guide. NISTIR 6784, National Institute of Standards and Technology, Gaithersburg, MD, 2001.
[29] Baum HR, McGrattan KB, Rehm RG. Three dimensional simulations of fire plume. Fire Safety
Science—Proceedings of the Fifth International Symposium, Tsukuba, Japan, p. 511–22.
[30] McGrattan KB, Forney GP, Floyd J. Fire dynamics simulator—technical reference guide, Version 2.
NISTIR 6783, National Institute of Standards and Technology, Gaithersburg, MD, 2001.
[31] Huggett C. Estimation of the rate of heat release by means of oxygen consumption measurements.
Fire Mater 1980;4:61–5.
492 T.G. Ma, J.G. Quintiere / Fire Safety Journal 38 (2003) 467–492
[32] Zukoski EE. Mass flux in fire plumes. Fire Safety Science—Proceedings of the Fourth International
Symposium, Gaithersburg, MD, USA, 1995. p. 137–47.
[33] Heskestad G. On Q* and the dynamics of diffusion flames, NISTIR 6030, June 1997.
[34] Smith DA, Cox G. Major chemical species in buoyant turbulent diffusion flames. Combust Flame
1992;91:226–38.
[35] McCaffrey B, Cox G. Entrainment and heat flux of buoyant diffusion flames. Report NBSIR
82-2473, National Bureau of Standards, 1982.
[36] Steward FR. Prediction of the height of turbulent diffusion buoyant flame. Combust Sci Technol
1970;2:203.
[37] Beyler CL. Development and burning of a layer of products of incomplete combustion generated by a
buoyant diffusion flame. PhD thesis, Harvard University, 1983.
[38] Heskestad G. Fire plume air entrainment according to two competing assumptions. 21st Symposium
on Combustion, Munich, Germany, 1986. p. 111–20.
[39] Ricou FP, Spalding BP. Measurements of entrainment by axi-symmetric jets. J Fluid Mech
1961;11:21–32.
[40] Cetegen BM, Zukoski EE, Kubota T. Entrainment in the near and far field of fire plumes. Combust
Sci Technol 1984;39:305–31.
[41] Delichatsios MA, Orloff L. Entrainment measurements in turbulent buoyant jet flames and
implications for modeling. 20th Symposium on Combustion, Ann Arbor, MI, USA, 1984. p. 267–375.
[42] Hasemi Y, Nishita M. Fuel Shape on the deterministic properties of turbulent diffusion flames.
Fire Safety Science—Proceedings of the Second International Symposium, Tsukaba, Japan, 1988.
p. 275–84.
[43] Orloff L. Simplified radiation modeling of pool fires. 18th Symposium on Combustion, Waterloo,
Canada, 1981. p. 549–61.
[44] Orloff L, de Ris J. Froude Modeling of Pool Fires. 19th Symposium on Combustion, Haifa, Israel,
1982. p. 885–95.
[45] Forney GP, McGrattan KB. User’s guide for smokeview 2.0—a tool for visualizing fire dynamics
simulation data. NISTIR 6761, National Institute of Standards and Technology, Gaithersburg, MD,
USA, 2001.
[46] Tamanini F. Private Communication, June 2001.
[47] Gregory JJ, Keltner NR, Mata Jr. R. Thermal measurements in large pool fires. J Heat Transfer
1989;111:446–54.
[48] Zukoski EE, Cetegen BM, Kubota T. Visible structure of buoyant diffusion flames. 20th Symposium
(International) on Combustion, Ann Arbor, MI, USA, 1984. p. 361–66.
[49] Baum HR. Private Communications, Building Fire Research Laboratory, National Institute of
Standards and Technology, May 2000.