INF ROCKWELL RVR-1 Single Phase 32-Step Voltage Regulator 6.35KV-14.4KV-33KV RVR-1 Installation Manual ! Dest S Introduction y Wye High voltages. Will cause death, serious injury and property damage. Do not contact energized conductors, De-energize and ground high voltage conductors before working on A WARNING oF near them. Heavy weight. Can result in death, serious injury or propertydamage. Obtain the services of a qualified rigger prior to hoisting the recloser switch Unit to assure adequate safety margins inthe hoisting equipment and procedures to avoid damage Signal word The signal words "danger," "warning" and "caution" used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. Warning - Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury. Caution - Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. Caution (without safety alert symbol) -indicates a potentially hazardous situation that, if not avoided, may result in property damage. Field service operation and warranty issues: Rockwell can provide competent, well trained field service representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Rockwell equipment, processes and systems. Rockwell service Tel: +86 (577) 2786-9969 Or check the website information: http:!/www.rockwell-transformer.com 1.Summary As the developing of the computer technology, transducer technology and network communication, and advance of power system network working requirements, primary equipment of single function turn out the ineanvenient when in the using of the network, According to the whole power system, developing intelligent integration switch base on terminal it is necessary. Based on this idea, Our company developed a RVR-1 Series intelligent integration outdoor Single Phase 32- Step Voltage Regulator Rockwell RVR-1 are all comply with relevant standards. IEEECS7.15-2009 lec 60076 IEC 60068-2-4 IEC 60214-1, IEEE Std c57.91™ IEEE Std C57.98™ IEEE Std C57.131™ IEEE Std C57.12.31™ IEC 60076 China Standard 2. Using condition Ambient temperature:-25°C~+40°C, Day temperature difference :25°C Altitude: <1000m area; Wind speed no exceeds 35m/s; No normally intensity vibration No intensity erosion gas, medium place (for example acid, alkali, smother eg.) Pollution class: IV class; 3.Reminding before using The RVR-1 continues to be completely factory adjusted and sealed. Accessories such as a MOV-type extemal series arresters and Bypass Switches. Equipment Included with each RVR-1 Set —Q)— RVR Provided and visible MOV-type external series Provided and visible Bypass Switches. Provided and visible ‘SEL2431 Controller Provided and visible 4.Acceptance , Transport, Lifting and Storage 4.4 Pictorial marking for handling Under normal circumstances, the RVR-1 is packed in a wooden box during transport. Bypass Switches. is packaged separately as a product accessory. Packaging markings are printed on both sides of the packing box. Packaging markings include the information of packing box number, gross weight, etc. In addition, the outside of the packing box is also printed with pictorial marking. When lifting the product, please follow the markings on the outside of the box, as it shown in pictures below: i Y U ‘Tuts SIDE UP FRAGILE Do Nor STACK [KEEPDRY KEEPAWAY FROM HEAT DONOTROLL 4.2 Accompanying documents The following documents are packed in the packing box along with the product: Installation Manual Factory Inspection Report Project Drawings Packing List SEL2431 controller field reference guide 4.3Packaging and Transport (see the figures) ‘The RVR-1 should be transported under correct packaging. The following should be noted during transport: Make sure that the packing box is not placed in wet or flooded areas. Do not overlay and stack the voltage regulator. 4.4 Lifting RVR-1 is fitted with lifing lugs, also can be moved on pallets with a forklift truck. The RVR-1 are very heavy so please handle with care! 4.5 Receipt & Storage prior to installation The RVR-1 with complete packing should always be stored indoor to protect from direct sunlight& rain/snow. Voltage regulator can be stored up to 3 months from date of shipment from the factory. For longer storage, the packing needs to be removed and the breaker be kept under controlled environmental conditions. We define storage in controlled conditions as a place with: Leak proof roof, Solid, flat ground, Relative humidity less than 50%, Temperature 20°C (# 10° C). 4.6Acceptance and storage voltage regulator For the delivery and acceptance of each batch of products, the following should be checked: 4.6.1 Quantity of products and accessories, specifications (check orders and shipping documents) 46.2If there is any shipping damage or loss 4.6.3Any abnormal situation should be immediately notified to: ROCKWELL, freight forwarder and insurance company. If the RVR-1 cannot be installed immediately, original packing materials need to be used. Restore it to the original packaging and place hygroscopic agent in the packing box. At least one standard bag of hygroscopic agent should be placed for every packing box. If there is no original packaging, nor can it be installed immediately, the device should be covered with weatherproof plastic sheeting and placed in a dry.and clean environment to avoid corrosive and freezing damage Spare parts in the original packaging should be stored indoors where’s dry and clean. 5.RVR-1 type 32-Step Voltage regulator installation on ground 5.1 Outline schematic diagram of single phase regulator 1. MOV-type external series arresters. 2.Terminals block 3.High-creep porcelain bushings 4.Pressure relief device 5. Lifting lugs 6. Radiator group 7.The tap position indicator 8. Oil level gauge 9 Nameplate 10. SEL2431 controller 11. Control box 12. Ground stud 13. Oil drain valve with sampling device 5.2 Typical connections for single phase regulators Figures 5.11 to 5.4 describe the four basic connections for monophasic and triphasic systems, where regulation is performed by monophasic regulators. By BASS SwTCH POWER SUPPLY SWITCH Figure 5.1 Single-phase voltege regulators connection monophasic line aye iron | SUPPLY SuETCH Cec wate ‘By BASS SwrTCH POWER SUPPLY s\nTCH POWER LINE swaToH Figure 5.2 OPEN DELTA ‘Two single-phase regulators connected to a triphasic line in open delta providing the system with 10% of the regulation range on the three phases. ee. = |g Lovo sires go BY BASS SWITCH 2 owe 1 AG ea 5 scone 5H phase Loa sures e909 S Byoxss sviTCH ath ste &o Lowe swircr| gona Figure 5.3 CLOSED DELTA Three single-phase regulators connected to a triphasic line in closed delta providing the system with 15% of the regulation range. ey a ee BY BASS SWITCH oats Figure 5.4 STAR CONNECTION Three single-phase regulators connected in star a triphasic line with grounded neutral providing the system with 10% of the regulation range. 5.3 Installation diagram for three single phase regulators connected in triphasic. A A 8 8 © c phase phase phase phase phase phase Incoming outgoing incoming outgoing incoming outgoing BY BASS SWITCH Outdoor floor Bare copper wire 11920 Galvanized round bar 2500°020 Galvanszed round bar ‘Grounding system Three single-phase regulators connected to a triphasic line in closed delta providing the system with 15% of the regulation range. 2; ‘utdoar Toor. 1220 Galvanized round bar] Left view of Grounding system A A 8 8 © c phase" phase phase phase =—=phase. phase ineoming ouigong — incoming olégang incoming ouly0ing He i _ (de yay oi BY BASS SWITCH 25007220 Galvanized round bar Grounding system Three single regulators connected in star a triphasic I providing the system with 10% of the regulation range. Left view of Grounding system ‘Outdoor floor Bare copper wire e with grounded neutral 8 SEL2431 controller 6.1 Figure 6.1 shows the front panel of the SEL-2431 Voltage Regulator Control. Use default messages, (oF program up to 32 custom display points Type A USB Port Front-panel status LEDs provide simple indication of control and system status. Ethernet Activity Lights (if equipped) ©0900 O© Figure 6.1 Front Panel Feature 2x 20 character LCD display Navigation buttons provide easy access without a PC Use defaul: pushbuttons oF program your own pushbutton actions and LED indicators User-configurable label kit Pushbutton or toggle switch options for raise/lower operation 6.2 Figure 1.2 shows the front panel of the SEL-2431 Voltage Regulator Control. Communications Communications Port 1 Port 2E +— Solid die-cast aluminum casing Optional snap-in communications —— cards Self-shorting, Connectorized® CT connector ‘Simple plugin retrofit harness | — Easy-towire i/o Figure 6.2 Rear Panel Feature 6.3 Reference of Controller wiring schematic cr 1S ot + — 2] correnr pri 103 FA 108 a 104 77 £ pre VOLTAGES so +105 __Ti05 ‘Tap Changer Motor ~ Tap Changer Motor” otto} 07 114 Capacitance an ae; 113 e1—toe ag Neutral Position switch ) Netti Position six | 109 109} uz mt lan 107] _ [ue CURRENT VOLTAGES mS ie 4 we roi] [102 103|103] 105 |104' tii [bo [109 6.4 SEL2431 controller basic settings 6.4.1 Overview The SEL-2431 Voltage Regulator Control stores customer-entered settings in nonvolatile memory. Settings are divided into the following settings classes: 1. Global 2. Group n (where n = Group 1-4) 3. Logicn (where n = Group 1-4) 4, Front Panel 5. Report 6. Port p (where p =F, 1, and 2 [Ports 1’and 2 are optional communications ports}) 7. Distributed Network Protocol (DNP) Maps 1 and 2 6.4.2 View/Change Settings Using the Front Panel You can use the pushbuttons on the front panel to viewichange settings. ront-Panel Interface presents the operating details of the front panel. Enter the front-panel menu by pushing the ESC pushbutton. It wil display the following message: MAIN Meter Scroll down the menu by using the Down Arrow pushbutton until the display shows the following message: Control et/Show The cursor (underline) should be on Set/Show. Enter the Set/Show menu by pushing the Enter pushbutton. The display shows the following message SET/SHOW Jobal Scroll down the menu to underline the desired settings class: Global, Group, or Port. Select the underined settings class with the ENT pushbutton, and the device will present you with the settings as listed in the SEL- 2431 settings sheets. Use the Up Arrow, Down Arrow, Left Arrow, and Right Arrow pushbuttons to scroll through the settings and view/change them according to your needs by selecting and editing them. Affer viewing/changing the settings, press the ESC pushbutton until the following message appears: Save Changes? Yes No Select and enter the appropriate command by pushing the Enter pushbutton, Select Yes to save the settings changes and No to discard the changes. NOTE: For more information on all settings and how to modify them refer to SEL2431 controller field reference guide, 6.5 Control Power Section of the SEL-2431 Front Panel (Toggle Switch Version) roe | On 5 (Do toca . o-- bi () G C ara C Lerma | CVS wena} | tomo] The CONTROL POWER toggle switch has three positions 1 INTERNAL: This is the position for normal operation. Alll the voltages wired to the rear-panel VOLTAGES connector are switched in/connected to energize the power supply and voltage input VS1 (voltage input VS2 is energized, too, if a second voltage is available at terminal 3 of the VOLTAGES connector). 2. OFF: All the voltages wired to the rear-panel VOLTAGES connector are switched out/disconnected to de- energize the SEL-2431. 3. EXTERNAL: The EXTERNAL SOURCE terminals are switched in/ connected to energize the power supply and voltage inputs from a 120 Vac nominal external source (connected to the EXTERNAL SOURCE terminals). Note: If the voltage regulator is connected to the line, set the switch to the internal power supply. Note: More question PLS consult with Rockwell Transformer This manual is from Rockwell copyright, If any modification will not give notice. IRF Whenzhou Rockwell Transformer Co.,Ltd . Add: No 1,Fazhan Road, Wengyang Industrial Zone, Yueqing,Zhejiang,China,325604 Tel: +86-577-27869965 27869969 Fax: +86-577-27869967 ckwell@rockwill.cn Website: hitp://www.rockwell-transformer.com

You might also like