MiCOM P122

Phase and Earth Overcurrent Protection

MiCOM P122 is the advance phase and earth overcurrent and overload relay.
Numerous protection functions allied with large monitoring capacities give
optimised efficiency and maximum control.

More compatible
Applications
• MODBUS, Courier,
IEC 60870-5-103 or DNP3.0
• Industrial electrical networks
communication protocols
• Drawout case with CT short • Utilities
circuits
• HV and MV substations
• Dual rated 1 and 5A CT inputs
• MV and LV transformers
Inputs and outputs
• 3 phase current inputs
• 1 earth current input Protection and control
• Dual rated 1 and 5A CT inputs
• 3 programmable logic inputs • 3 independent phase and
• 7 programmable logic outputs earth overcurrent thresholds
(50/51/50N/51N)
More protection Measurement
• 3 independent phase and earth • True rms phase and earth currents • 11 families of curves (IDMT)
overcurrent thresholds • Peak and rolling demands (5 x IEC, 5 x IEEE/ANSI,
• 11 families of curves (IEC, 1 RI)
• Thermal state
IEEE/ANSI, Electromechanical) • Thermal overload (49)
• 75 event record 1ms time tag
• Thermal overload (true rms)
• Fault recording, last 5 faults • Minimum current (37)
• Broken conductor detection
• Disturbance recording, 5 records
• Circuit breaker failure detection • 2 setting groups
• Permanent self test
• Cold load pick-up • Broken conductor detection
User interface
• Logic selectivity
• 8 LEDs including 4 • Circuit breaker failure
• Output relay latching programmables detection (50BF)
More information • 32 character alphanumeric
• Cold load pick-up
• True rms measurement display
(up to 10th harmonic) • RS232 front communication • Logic selectivity
• Event, fault and disturbance • RS485 rear connection • Output relay latching (86)
recording
• Fully programmable
More convenient • MODBUS, Courier,
• 2 setting groups IEC 60870-5-103 or DNP3.0
• Front RS232 for Setting Software communication protocols
• Rear RS485 for Local Area • Drawout case
Network

T&D
Protection & Control
Technical specifications Communication
• Type: RS485 2 wires, half duplex,
Busbar isolated
• Data rate:
from 300 to 38 400 bauds
• Protocol: MODBUS RTU, Courier,

010130 CPS Printed in England


52 TRIP Logic IEC 60870-5-103 or DNP3.0
inputs
49 37
WD
Housing
Phase CTs 3 51 50 • Case: MiCOM 20 TE, rack or flush
Logic mounting, rear connections, full
51N 50N
outputs drawout with automatic CT shorting
Earth CT 86 50BF • Size: 4U (152mm) H x 103 mm
RS 485 Remote control W x 230 mm D
Communication
RS 232
Communication Setting software • Protection: IEC 60529; IP 52,
IK 07

Our policy is one of continuous development and the right is reserved to supply equipment which may vary from that described.
• Weight: 2.1Kg
Current inputs • Dropout time: DMT: 50ms to 60s • Connectors: MIDOS 2 x 28 points
5 x IDMT curves (double faston + M4 screw per
Phase current
Undercurrent connection)
• Range: 1 and 5A
• 2 to 100% In
• Burden: < 0.3VA (5A) HMI
• Instantaneous time: half cycle
• Overload withstand: • Display: 2 x 16 alphanumeric
1 second 100 In Thermal overload
characters, back-lit
2 seconds 40 In • Thresholds: 2 (θ>,θ>>)
• LEDs: 8 including 4 programmables
continuous 4 In • Ranges:
from 0.1 to 3.2 In • Keyboard: 7 button tactile keypad
Earth current • Front RS232 for Setting Software,
• Range: 1 and 5A from 50 to 200% x θ
• Time delay: 1 to 200mn • Languages: French, English, Dutch,
• Burden: < 0.01VA at 0.1Ion (5A) German, Spanish, Portuguese,
• Overload withstand: Cold load pick-up Italian, American, Russian, Polish
1 second 100 Ion • Ranges: from 20 to 500% setting
2 seconds 40 Ion • Time delay: 0 to 3600s Environment
continuous 4 Ion • Temperature: IEC 60255-6
Auxiliary supply
operating: –25°C to +55°C
Settings • Ranges: 24 to 250V dc storage: –25°C to +70°C
Phase time overcurrent 100 to 250V ac;
• Humidity: IEC 60068-2-3
• Thresholds: 3 (I>, I>>, I>>>) 50/60Hz
• Dielectric withstand: IEC 60255-5
• Ranges: 0.1 to 40 In • Burden:
< 2W + 0.25W per logic output • Impulse voltage: IEC 60255-5
• I> IDMT curves: • Fast transient: IEC 61000-4-4;
< 5VA with ac voltage supply
IEC 60255-3: STI, SI, VI, EI, LTI, ANSI C37.90.1
+0.5VA per logic output
IEEE/ANSI : MI, VI, EI, CO2, CO8 • High frequency disturbance:
Electromechanical : RI • Variations: 0.8 to 1.2 Uaux
• DC supply interruption: 50ms IEC 61000-4-1 class 3
• Instantaneous time (I>, I>>, I>>>): • RFI: IEC 61000-4-3;
< 30ms Logic inputs ANSI C37.90.2
• Time delay (tI>, tI>>, tI>>>): • 3 isolated programmable inputs • Electrostatic discharge:
0 to 150s IEC 61000-4-2
• Range: 24 to 250V dc
• Drop-out time: DMT; 50ms to 60s • Auxiliary supply: IEC 60255-11,
• Burden: 0.25W per input
5 x IDMT curves VDEW; ripple: 12%,
Logic outputs
©2001 ALSTOM

Earth time overcurrent supply interruption: 50ms


• Thresholds: 3 (Io>, Io>>, Io>>>) • 2 changeover programmable • Vibration: IEC 60255-21-1 class 2
• Ranges: 0.002 to 40 Ion outputs • Shock & bumps:
• Io> IDMT curves: • 4 N/O programmable outputs IEC 60255-21-1 class 1
IEC 60255-3: STI, SI, VI, EI, LTI • 1 watchdog output • Seismic: IEC 60255-21-3 class 1
Publication: L1 1502B

IEEE/ANSI: MI, VI, EI, CO2, CO8 • Current: make and carry for 3s;
Electromechanical: RI 30A Standards
• Instantaneous time (Io>, Io>>, carry continuously 5A CE conformity to IEC 60947-1
Io>>>): < 30ms • Break: (EMC and LV directives)
• Time delay (tIo>, tIo>>, tIo>>>): at 135V dc (L/R = 30ms); 0.3A;
0 to 150s at 220V ac (50/60Hz);
cos ϕ = 0.6; 5A

T&D Protection & Control, 60 Route de Sartrouville, 78230 Le Pecq, France. Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 www.tde.alstom.com