AERMEC Electronic GR3 controller NRA_NRC_NBW_NLW_NRL After Sales Service Manual Edition December 2012 ELECTRONIC SYSTEM FUNCTIONS, NRE UNITS CONFIGURATIONS Configuration of the command card on the basis the of machine model ‘The system has been developed to be able to manage the models, itis sherefore necessary to configure the card on the bass ofthe machine mode! iis to be installed on. The Imicoprocessor then wil be able o find the ight software to run, accorting to the card DP switch Setings, and tothe accessories that might have been install, The meanings of the thee dip switches are given inthe following figures. Through these it is possible to select the machine model and the type of functioning. ‘The contol card gets the DIP switch configuration at power-on time, therefore the DIP switches have tobe configured withthe Card powered of. Total recovery Pumpdown 1 Fan group Centritugal Heat pump Freecooing Bicondenser Condensing unit Normal ‘Monocondenser Normal ‘Only cooling Axial 2 Fan group mal Normal ipswich 120 ‘Small times 1/10 WaterWater 2.3.4 Compressors Autotest Normal 6 Compressors Ar to Water (WEL) Normal times. Dipswten swe, IFL NOT Primary P{ NOT Primary TV} NOT Primary |AP2.NOT Primary [Tv2 NOT Primary V2 Primary (lays ON at NR2001) ‘AP2 Primary TV1 Primary ‘AP Primary FL Primary Dip-swtch sw. 21 ‘Setting of power compressors values refers to the NRE units Wodelomacchina | Power | Power | Power | Power [Power | Pawar cpr | cera_| cere | ‘cp2 | crea | cous NRL 20 50%} 0% | 0% | s0% Jo” | O% sHi20 suizo_| NRL 300 ‘8% | OR [OR [4am | ORO suet 120 NRL 330 ‘0k | 0% | —O% | _s0% | 0% | om suet sH161 NRL 350 0% | OR [oR 80% | oR [Oh si 168 su ie4 ~ RL 300 26% | 28% | o% [4am | 0% | OH stig | st120 sH188 NRL 50 “3% | 26% | 0% | a0 | OR | Om sue | si120 SH 166 NRL OO 2% | 21% | Ok | 20h | 2m | Om sie |_shiz0 ste | sHi20 NRL 650 25% | 25%. | 0% | 25% [25% | — Om sHie1_|_stT61 sieie_|_sii6: NRL 700 25% | 25% | 0% | 25% | 25% | Oh cites | sHiee sites | siie4 NRL TSO 21% | 21% | OR | 29% —}_23% | om siies | shee shoo | 240 NRL 800 25% | 25% | 0% | 25% [25% | OR siz | st240 sii2<0 | stato NRL 900 Z| 22%] 0% | 26% | 28% | Om stoo | sao st#a00_|_sH300 NRL 000 25% —|_25% [OR —|_28% | 25% “| Oh sit300_|_si'300 sis00_|_sH'300 _| RL 250 25%] 25% | 0% | 25% [25% | Oh si3s0 | si's60 si3s0_|_sH380 NRL 400 2%) 23% | OR | te | ts 78 stiago | stae0 st#300_| st¥300 | sts00 NRL 500 1% | 17% | ie | 1% | 1%] 168 sHsco_| st'3o0 | stsco | sro | stiso0 | st00 NRL 1650 i) 1% | 1% | fom | tem J 10 sti300_| st'300_| stsoo_| stsg0 | stsso | stss0 NRL 1000 ae | im | ie | 7m | a7m | 16 sHgo | si3e0 | stséo | sts60 | st1360 | stts60 (Please rete to paragraph PARAMETER ESTABLISHMENT of units ‘Compressors spate part code utlize on NRL units mm Software Configuration Parameters “The software thats programmed onthe card GRS inclues is configuration parameter, which corspond {oa standerd vereion othe car In elaton tthe aiforet versions and accassores avaiable forthe covet behavior of the sofware shoud enya al configuration parameters ofthe sofware are care. “This procedure sil has to Bo tsing the cr atthe end of he ine and inthe case of cars epaced n parts In order to expedte tis operation, the process invatves ging fo check and change any ose parameters ‘ht are diferent than the sondard version precharged. ‘To perform tis configuration you must 1) Consider each group of modified [Group [Models cfmactine ar — Wade fo choosing he new Parametorsto madly vale to set, 2) Check ifthe units ino te desertion 2) Change the parameters deserbe int tis column CConiguraton rues Fae [1/213 |418]6 [7 —[s Je oa Fae Ts fe os ‘Codo/NRL Size | Camp. |Exp- /Modei|Heat | Version| Coils| Fans Power /Accimulaton| vave| ~~ | Recovery supply Dip switches sotings on the GR board ‘SW1 default all OFF — or UNIT TYPE on eI T Tala eovey x Alluts NRL wth otal fecoveey T a ‘ainays OFF “fan group x ‘models rom 275 0 700 [At moos fom 780 10 1250 igh eticiency (no version & ‘and z ways OFF 7 5 eat pumps NRL. te € Fisecooing NRL F and x fo ‘always OFF te Moiccondensing NRL x 139 ‘5W2 default all OFF OP ‘URITTE ON, 7 Faaltine aways OFF = 2 ‘Always OFF 2 "aes wih & compressors ul size 7250) x “ utotet Alay OF '8W™3 default all OFF OP UNITE Tow. 1 FL neipsmary aways OFF 2 ~ ‘Al modes x 3 ‘ile x 4 ‘Almeodels x 5 ‘Almodels x 140 ‘Ui model where necessary the modieatons| New vale Sang oaiicaion pararaios ‘Aimed wi the fexcention of er ois (Saou (Comer compressors evametre fo change) NRL DS NRL 320 NRL 350 RRC NRL SOT NRL SSO 14 crap Une Posed where necessary the rmosiiatons ow value sets Nasir paramore | (Power compressors | parameter fo change) NRLTEO PowerCPt Zi PowerGPia 24 PowercPi8 -0 PowerP2 29 PowerCP2n 29 PowerCP2e 0 RRUBST NRL 700 NRL 800 NRL 1000, NRL 1250 PowercP! 25 PowercPIAa 25 PowercPia 0 PoweccP2 25 PowerCP2n 25 PowercP2 0 RRCBOT PowerGP1 22 PoweecPIAa 22 PowerPia “0 PoweeP2 28 PoweP2n 28 PoweecP26_-0 NRL TSO INR 1800 PowecP! 7 | PoweecPIA 17 PowePIs 18 PowercP2 17 PowecP2a 17 | PowercP26 16 RRL TAT PowecPi 25 PowercPIA 23 PowercPi8 0 PowercP2 18 PowercPan 12 PowercP26. 18 RRLTES PawecPT 5 PowercPiAa 15 PowerePi8 18 PowercP2. 19 PowercP2n 18 PonercP2e 18 142 ‘Group [Units model wheres | Now value stings] Moaiicanion parameters = Versions RT Famps 7 or.0308.07,P1P3 N= Pumps ON Pump AG ON versions Ne Pimps 2 22.04.06 08,72,P4 Pumps ON | NRC ow temparatre” A RG Evap. OFF versions [SetaGC1 100 SeiFresao 60, DT RRC sence versions | From NRL#O0 T= NRL Config 28 bar 1800 ini bar Dept n 38 bar ETC aacoatng Fa in Use R20 OUT versione [P| RRC heat pump RRL aa POO versions ith ony one ep PDO one compressor eeu (omen factory psw 150800) roup [Unis madel wees [Now vate soings | Wacatonpronetes necessary he ‘oats ‘S| NRL Cversans | Wi compress rotation | PowrtP =D | fondensngunts Chere wn? PowercPtA “0 | itu ereprar site |cargresars PowercP8 0 | ‘rchanger New PowerP2 80 | Bs PowercP2A "0 300 PowersP2e 0 20 350 _| Wan compress TaRGT | PowerOPT 35 hier wah 3 PowerSPiA 38 cerrescors| PowercPiB 0 Ne Pouca” 93 S00 PowercP2n 0 550 PomercP28 9 (Group — | Units model wheres [New valve eetings —— Moaiicanton paramos necessary the medications [NRA asa HRC With eorpressors rian | PowerCPT 25 [Cversions condensing |Chirs wits Powerceia 25 cate compressors PowercPis 0 witout evapeater pate | NRL PowercP2. 25 exchanger 600 PowercPan 25 650 PowercP2e 0 700 750 200 900 0 1250, Win compressors raion | PowerGPT 20 Chis wth PowercPiA 20 compressors PowercPIB 0 int 1400 powercP2. 20 PowercP2A 20 PowerCP26 20 “th compressor aan | PowerCP) 15 1 ‘Chie th | PowercPtA 18 | compressors PowerCPIB 15 Nt '800 Ponerce2 15 NRL 1680, PowercP2n 18 NRL 1800, Powerce2e 18 tout compressors | PowerCPY 100 tation Powerceia 0 Chiles with 2 PowercP1® 0 compressors PowercP2. 100 NRL PowercP2n "0 275 PowercP2e 0 300 320 350 (Group ~ [Unks madal wheres [New value stings] Moaeaniion parameters necessary he rmostiatone ST NRA ana NRC Vito compressos | PoweiCP7 100 Crversions condensing |reation PowercPiA 100 (Gone Chillers wn 3 PowercPi 0 witout evaporator pate | compressors PowerGP2_ 100 ‘changer NR PowercP2A 0 500 PowercP28 0 580, Whoo compressors [PowerGP? 100 retabon PomerCPIA 100 Chiles wth PowercP1® 0 compressors PowerCP2 100 NR PowercP2n 100, B00 Powerce25 0 50 ro 750 00 300 ‘000 1250 ‘hour compress | PowerGPi 100 rotation PowerCPIA 100 hilo win ¢ PowecPi6 0 compressors PowercP2 100 NRU 1400" PowercP2n 100 PowercP26 100 ito compressor | PowerCPi 100 rotator PomercP1A 100, Chiles wth 6 PonerGP1B 100, compressors PonercP2. 100 NRA 1500, PonerCP2A 100 NRL 1650 PonercP28 100 NRL 1800 NRC a BAG Evap 1205 [Unis model where is [Naw vas selings | Meciicanton pararatas necessary the mosieabons RC NRCEOT ‘Sep Feed Ffeecooing veslons NRL 800 (Get tacary meni) NRL 1000 NRL 1250 NRL 1400 NRL 1500 NRL 1680 NRL 1800 NaC om size 28010 3650 vih | A AP AUS bar Hp preseosia42ba" | (set factory mend) [NRL ony cooing ar BP OHO bar ‘xcept version Y and X (setTecory mena) NRL ar Pins Ze bar Hiheat pump versions (set fectory mend) Tae ORE {set faciory mend) 17

You might also like