ISLAND 11:57:49
MFT REMARK
REASON
RH LOSE PROTECTION GOVERNING VALVE PASSING
PUSH BUTTON LDO PRESSURE NOT AVAILAVBLE
EH OIL PRESSURE NOT SUSTAIN 11:58:24 FAST CLOSE DUE TO VACCUM
FDF-TRIP LOW, UNDER VOLTAGE 6.6 KV FAILURE (11:58:31)
RH LOSE PROTECTION HPBP OUTLET TEMP HIGH, FAST CLOSE
1 MILL RB, 1 EM STOP, 1 NO LUBE OIL LL DUE TO EMRGENCY POWER
LOSE ALL FUEL LOSS
MECH RELAY-1,1 MILL RB, 1 EM STOP, 1 NO LOADING PR FAIL DUE TO
LOSE ALL FUEL EMRGENCY POWER LOSS
FDF-TRIP MECH RELAY-1, UNDER VOLTAGE 6.6 KV FAILURE (11:58:31)
OPC ACTED SEVERAL TIMES, EH OIL PR NOT SUSTAIN, VCM BRKR OPEN
RH LOSE PROTECTION BY OPERATOR MANUALLY THINKING BLACK OUT
9/10/2021 11:57:51 AM U1SOE:SOE053203.CIN
9/10/2021 11:57:51 AM U1SOE:SOE052113.CIN
9/10/2021 11:57:51 AM U1SOE:SOE052213.CIN
Unit 1 9/10/2021 11:57:51 AM U1SOE:SOE052212.CIN
9/10/2021 11:57:51 AM U1SOE:SOE052301.CIN
9/10/2021 11:57:51 AM U1SOE:SOE052112.CIN
9/10/2021 11:57:51 AM U1SOE:SOE052310.CIN
OPC OPERATED ON
GENERATOR TRANS 1 220kV BRK 1DL OP LOUT ON
GENERATOR TRANS 1 220kV BRK 1DL OP LOUT OFF
GENERATOR TRANS 1 220kV BRK 1DL OP LOUT ON
GT PROT A B PANEL FREQ PRO TRIP
UNIT SHUT OFF STATE ALARM INDICATION ON
GENERATOR PROTECTION ACT SHUT OFF ALARM ON
ALL SHUT OFF ALARM OUTPUT OFF
GT PROT C PANEL AUX TRANS WNDG TEMP HIGH ON
HP MSV A CLOSED OFF
IP RSV B CLOSED OFF
IP RSV B CLOSED ON
IP RSV B CLOSED OFF
APH A MAIN MOTOR BREAKER TRIP ON
NO.1 CW BOOSTER PUMP BREAKER TRIP ON
NO.1 CW BOOSTER PUMP BREAKER TRIP OFF
IP RSV B CLOSED ON
NO.1 CW BOOSTER PUMP BREAKER TRIP ON
NO.1 CW BOOSTER PUMP BREAKER TRIP OFF
NO.1 CW BOOSTER PUMP BREAKER TRIP ON
NO.1 CW BOOSTER PUMP BREAKER TRIP OFF
IP RSV B CLOSED OFF
NO.1 CW BOOSTER PUMP BREAKER TRIP ON
IP RSV B CLOSED ON
IP RSV B CLOSED OFF
NO.2 CW BOOSTER PUMP BREAKER TRIP ON
NO.2 GEN COOLING PUMP BREAKER TRIP ON
APH B MAIN MOTOR BREAKER TRIP ON
APH B GUIDE BEARING OIL PUMP BREAKER TRIP ON
NO.2 HEATER DRAIN PUMP BREAKER TRIP ON
NO.2 VACUUM PUMP BREAKER TRIP ON
GT PROT C PANEL EXCIT TRANS WNDG TEMP HIGH OFF
NO.2 GEN COOLING PUMP BREAKER TRIP OFF
APH B GUIDE BEARING OIL PUMP BREAKER TRIP OFF
NO.1 CW BOOSTER PUMP BREAKER TRIP OFF
NO.1 VACUUM PUMP BREAKER TRIP OFF
APH B AUX MOTOR BREAKER TRIP OFF
NO.4 PULVERIZER BREAKER TRIP ON
APH A AUX MOTOR BREAKER TRIP OFF
LP BYPASS > 5 % OFF
LP BYPASS > 5 % ON
GT PROT A B PANEL FREQ PRO TRIP
OPC OPERATED OFF
EH OIL PRESSURE
NOT SUSTAIN
11:58:24 FAST Parallel Operation (11:58:05 to 11:58:31- 26sec) of
EH OIL PR. CLOSE DUE TO
11:58:28 GVR2, GVL2, HPLP Bypass and IVRs lead to fall in EH Oil
LOW VACCUM LOW,
pressure in the system
UNDER VOLTAGE
6.6 KV FAILURE
(11:58:31)
Increasing Trend
Increasing Trend
0.4
11:58:22 12.25 10.55 0.4
11:58:23
11:58:24
11:58:25
11:58:26 12.25 10.55 0.4
11:58:27 46 56 22.4 17.04 3.5
11:58:28 26 39 25
Reducing
Reducing
11:58:29 13.2 11.08 70
11:58:30 13 9 94
11:58:31 -5.6 0.3 103
11:58:42
11:58:43
11:58:47
11:58:53
12:01:45
Current
LPBP Vacuum EH Oil Pr EH MP EH SB
-85.95
-85.95
-85.95
-85.95
-85.95
-85.95
-85.95
-86.02
-86.02
-86.02
-86.02
-86.31
-0.9
4.44
23.93 13.68
72 -87.5
97 27 0
97 11.71 30.52 26
97 12.71 30.52 26
97 -78.93 12.71 30.52 26
97
75.6
75.6
18.51
in reducing trend
0.3
0.3
6.8
41
96
96
96.5 -84.06 9.61
-77.92
1.41(min)
2.06
7.48
13.15
Turbine Trip Reason Remarks Probable Cause
11:58:03 GT PROT A B PANEL FREQ PRO TRIP
Turbine Trip Reason Remarks Probable Cause
11:58:05 GT PROTECTION A B PANEL FREQUENCY PROTECTION TRIP
Turbine Trip Reason Remarks Probable Cause
11:58:09 GEN-FAULT B PANEL FREQUENCY PROTECTION TRIP
Turbine Trip Reason Remarks
12:02:00 EH OIL PR. LOW
Probable Cause