FCAG-BVEB Databook EEDEN19
FCAG-BVEB Databook EEDEN19
Technical Data
FCAG-B
> FCAG35BVEB
> FCAG50BVEB
> FCAG60BVEB
> FCAG71BVEB
> FCAG100BVEB
> FCAG125BVEB
> FCAG140BVEB
• Indoor Unit • FCAG-B
TABLE OF CONTENTS
FCAG-B
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Safety device settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional Drawings with Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensional Drawings with Fresh Air Intake . . . . . . . . . . . . . . . . . . . . . . . . 10
6 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1 Features
Infrastructure Presence & Home leave Fan only Auto-cleaning Draught Auto cooling- Whisper quiet Ceiling soiling
cooling floor sensor operation filter prevention heating prevention
changeover
Individual flap Vertical auto Fan speed Dry programme Air filter Weekly timer Infrared remote Wired remote Centralised
control swing steps control control control
Online Auto-restart Self diagnosis Drain pump kit Twin/triple/ Multi model
controller via double twin application
app application
2 Specifications
2 Specifications
2-1 Technical Specifications FCAG35B FCAG50B FCAG60B FCAG71B FCAG100B FCAG125B FCAG140B
Piping connections Sound absorbing insulation Foamed polyurethane
Liquid Type/OD mm Flare connection/6,35 Flare connection/9,52
Gas Type/OD mm Flare Flare connection/12.70 Flare connection/15.90
connection/
9.52
2 Drain VP25 (O.D. 32 / I.D. 25)
Heat insulation Foamed polystyrene / Foamed polyethylene
Safety devices Item 01/02 PC board fuse/Fan motor overcurrent protector -/Fan motor overcurrent protector
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Drain hose; Quantity : 1;
Standard Accessories : Clamp for drain hose; Quantity : 1;
Standard Accessories : Washer for hanger bracket; Quantity : 8;
Standard Accessories : Screws; Quantity : 4;
Standard Accessories : Installation guide; Quantity : 1;
Standard Accessories : Insulation for fitting; Quantity : 2;
Standard Accessories : Sealing pads; Quantity : 1;
Standard Accessories : Wire clamp material; Quantity : 7;
Standard Accessories : Clamps; Quantity : 1;
2-2 Electrical Specifications FCAG35B FCAG50B FCAG60B FCAG71B FCAG100B FCAG125B FCAG140B
Power supply Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Notes
The sound power level is an absolute value indicating the power which a sound source generates.
The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the
BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt.
BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black
louvers.
&'Ͳ 3
^ĂĨĞƚLJĚĞǀŝĐĞƐ &,'ϳϭͲϭϰϬ,s
WĨƵƐĞ ͲͲͲ
&ĂŶŵŽƚŽƌŽǀĞƌĐƵƌƌĞŶƚƉƌŽƚĞĐƚŝŽŶ EŽŵŝŶĂů ϭ͕ϰϵ
&ĂŶŵŽƚŽƌƚŚĞƌŵĂůƉƌŽƚĞĐƚŽƌ DĂdžŝŵƵŵ ͲͲͲ
ƌĂŝŶƉƵŵƉĨƵƐĞ ͲͲͲ
ϰϭϮϭϲϵϬ
4 Options
4-1 Options
&'Ͳ ǀĂŝůĂďŝůŝƚLJ
&,'ϳϭͲ
ϭϰϬ,s
ϭϰϬs
ϭϮϱs
&'ϯϱͲ
&y&YϮϬͲ
KƉƚŝŽŶŬŝƚ WƌŽĚƵĐƚŶĂŵĞ
Zϭϱϯϳ丁͕Zϭϱϯϳ丂͕
tŝƌĞĚƌĞŵŽƚĞĐŽŶƚƌŽů ض ض
Zϭϱϯϳ七丄͕Zϭ,ϱϭ;ϵͿtͬ<ͬ^ϳ
5 Dimensional drawings
5-1 Dimensional Drawings
&'Ͳ
Notes
3
Location of nameplate
The unit nameplate is located on the control box cover.
The decoration panel nameplate is located on the piping-side panel frame, under the corner cover.
When installing optional accessories, refer to their respective documentation.
Make sure the distance between the ceiling and the cassette does not exceed ·35·mm.
The maximum ceiling opening is ·910·mm.
When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam,
thickness ·10·mm). When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit.
When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller.
·300· or less
㻣
See note
㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌 ·5·. 㻢
㻤
5
㻠㻞㻜
Drain 㻌side
㻰㻱㼀㻭㻵㻸㻌㻌㻭 㻰㻱㼀㻭㻵㻸㻌㻭
·2· places ·2· places
㻤㻜
㻤㻢㻜㻙㻥㻝㻜
㻤㻜
㻥㻡㻜
㻣㻤㻜
㻝㻜㻜
㻝㻜㻜
㻞㻡㻚㻠
㻞㻡㻚㻠
㻞㻝㻟
Ceiling opening
㻝㻞㻝㻚㻡
㻝㻞㻝㻚㻡
㻟㻡㻜
㻟㻡㻜
㻝㻜㻜
㻝㻜㻜
㻣㻡
㻝㻜
㻤㻜
㻤㻜
㻥㻡
㻠㻞㻜 㻭㻮 Piping side
㻌
See
㻌㻌㻌 note ·6·. )&$*%9(%
㻣㻝㻜 㻥㻡㻜 )&$*%9(%
Suspension position
)&$+*+9(% );)4%9(%
㻤㻢㻜㻙㻥㻝㻜 㻤㻠㻜
);)4%9(%
Ceiling opening See note ·3·.
Adjustable
㻡㻡 㻤㻠㻜 㻡㻡
㻟㻠㻜
㻰㻱㼀㻭㻵㻸㻌㻌㻮 㻰㻱㼀㻭㻵㻸㻌㻮
㻠 㻝 㻞 ·2· places ·2· places
㻜㻙㻢㻣㻡
㻟
Opposite side Opposite side
Required installation space
㻝㻟㻜
㻟㻡㻜
㻟㻡㻜
㻯 㻝㻞㻝㻚㻡 㻝㻞㻝㻚㻡
㻭㻭
㻝㻣㻡
㻝㻡㻜
㻝㻜
㻝㻝㻜
㻥㻡
㻡㻟
㻢㻣
·2700· or more
㻠㻜
㻥㻢㻚㻡
See note ·3·. 㻡 㻤㻝 㻝㻜㻜 㻝㻜㻜 㻤㻡
See note ·3·. OR
㻠㻌㻙㻌㻹㻤㻌㻌㻌㻌㻌㻌㻌㻌㻹㻝㻜 㻟㻟㻜
Suspension bolt
)&$*%9(% )&$*%9(%
㻭㻾㻾㻻㼃㻌㼂㻵㻱㼃㻌㻯 )&$+*+9(% );)4%9(%
);)4%9(%
㻰㻱㼀㻭㻵㻸㻌㻌㻭 㻰㻱㼀㻭㻵㻸㻌㻭
Suspension position
㻥 ·2· places
㻭 ·2· places
Opposite side
Opposite side 㻢㻣 㻥㻢㻚㻡
㻤㻢㻜㻙㻥㻝㻜
㻡㻟
㻥㻡㻜
㻣㻤㻜
㻡㻠㻚㻡㻡㻠㻚㻡 㻥㻢㻚㻡
㻞㻝㻟
Ceiling opening
㻤㻜
㻤㻜
㻞㻡㻚㻠
㻝㻜㻜
㻝㻜㻜
㻞㻡㻚㻠
㻣㻡
㻝㻞㻝㻚㻡
㻝㻞㻝㻚㻡
㻟㻡㻜
㻟㻡㻜
㻝㻜
㻝㻜㻜
㻝㻜㻜
㻠㻞㻜 㻭㻮
㻤㻜
㻤㻜
㻟㻡㻜
Required installation space
㻝㻞㻝㻚㻡
㻭㻭
㻞㻡㻡
㻡㻠㻚㻡
㻞㻟㻜
㻝㻥㻜
㻥㻡
㻥㻢㻚㻡 㻡㻠㻚㻡
㻮
㻥㻜
㻯
·2700· or more
㻟㻡 㻡 㻟㻡 㻠㻌㻙㻌㻹㻤㻌㻌㻌㻌㻌㻌
OR 㻌㻌㻌㻹㻝㻜
㻟㻟㻜
Suspension bolt
See note ·3·. See note ·3·.
㻭㻾㻾㻻㼃㻌㼂㻵㻱㼃㻌㻯 )&$*%9(%
·1500· or more )&$+*+9(%
);)4%9(%
·200· or more
·2000· or more
㻡 Transmission wiring intake
·4000· or more
㻡㻟
㻢㻣
5 Dimensional drawings
5-1 Dimensional Drawings
&'Ͳ
Notes
Location of nameplate
The unit nameplate is located on the control box cover.
The decoration panel nameplate is located on the piping-side panel frame, under the corner cover.
When installing optional accessories, refer to their respective documentation.
Make sure the distance between the ceiling and the cassette does not exceed ·35·mm.
The maximum ceiling opening is ·910·mm.
When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ·10·mm).
When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit.
When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller.
㻣
5 ·300· or less
㻠㻞㻜
See note
㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌 ·5·. 㻢
㻤
Drain 㻌side
㻰㻱㼀㻭㻵㻸㻌㻌㻭 㻰㻱㼀㻭㻵㻸㻌㻭
·2· places ·2· places
Suspension position
Opposite side 㻢㻣 㻥㻢㻚㻡
㻥 㻡㻟
㻭 㻡㻠㻚㻡㻡㻠㻚㻡 㻥㻢㻚㻡
㻤㻢㻜㻙㻥㻝㻜
㻤㻜
㻤㻜
㻥㻡㻜
㻣㻤㻜
㻞㻡㻚㻠
㻝㻜㻜
㻝㻜㻜
㻞㻡㻚㻠
㻞㻝㻟
Ceiling opening
㻝㻞㻝㻚㻡
㻝㻞㻝㻚㻡
㻟㻡㻜
㻟㻡㻜
㻝㻜㻜
㻝㻜㻜
㻣㻡
㻤㻜
㻝㻜
㻤㻜
㻥㻡
㻠㻞㻜 㻭㻮
Piping side )&$*%9(%
㻣㻝㻜 See note ·6·. 㻥㻡㻜 )&$*%9(% );)4%9(%
Suspension position )&$+*+9(%
㻤㻢㻜㻙㻥㻝㻜 );)4%9(%
㻤㻠㻜
Adjustable
㻮 㻟
Opposite side Opposite side
㻝㻣㻞
Required installation space
㻟㻡㻜
㻟㻡㻜
㻯 㻝㻞㻝㻚㻡 㻝㻞㻝㻚㻡
㻭㻭
㻡㻞
㻞㻝㻣
㻝㻡㻞
㻝㻥㻞
㻥㻢㻚㻡 㻡㻠㻚㻡㻡㻠㻚㻡
㻥㻡
㻡㻟
㻢㻣
·2700· or more
㻥㻢㻚㻡
㻡 㻤㻝 㻝㻜㻜 㻝㻜㻜 㻤㻡
㻠㻌㻙㻌㻹㻤㻌㻌㻌㻌㻌㻌㻌㻌㻹㻝㻜
OR 㻟㻟㻜
See note ·3·. See note ·3·. Suspension bolt
)&$*%9(% )&$*%9(%
㻭㻾㻾㻻㼃㻌㼂㻵㻱㼃㻌㻯 )&$+*+9(% );)4%9(%
);)4%9(%
Item Name
Respect the distances shown on the figure. ·1500· or more 㻝 Liquid pipe connection port
Ceiling-mounted lighting ·200· or more 㻞
Gas pipe connection port
Air fan Other unit
㻟 Drain pipe connection
·1500· or more ·1500· or more 㻠 Power supply wiring intake
·200· or more
㻡 Transmission wiring intake
·1500· or more 㻢 hole Air discharge outlet
·1500· or more
·2000· or more 㻣 Flat grille assembly
·4000· or more Required installation space 㻤 Corner decoration cover
If a discharge outlet is closed up with the "sealing member" option kit, then the required
㻥 Drain hose
installation space on that (closed up) side is ·500·mm instead of ·1500·mm. 㻝㻜 Knockout hole.
ϮϭϮϭϳϬϯ
5 Dimensional drawings
5-2 Dimensional Drawings with Accessories
&'Ͳ 3
Installation methods
Remote control dimensions
Decoration panel Designer decoration panel
Transmitter
Receiver Receiver
ON/OFF
Drain side 5
Drain side
DOWN
UP
FAN
㻝㻡㻣
Decoration panel
Decoration Piping side
panel
Piping side
㻢㻞 㻝㻣㻚㻡
ϯϭϮϭϳϱϬ
&'Ͳ
Installation methods
Decoration panel
Piping side
ϯϭϮϭϳϱϱ
• Split - Sky Air • FCAG-B 9
• Indoor Unit • FCAG-B
5 Dimensional drawings
5-3 Dimensional Drawings with Fresh Air Intake
㻠㻞㻣
㻟㻞㻤
㻟㻞㻤
㻠㻞㻣
See note ·3·.
Drain side
㻠㻠㻤 Duct View ·A·
Service access panel 㻔㻝㻜㻜㻜㻕
㻡㻜㻤 Right side ·450 x 450 mm· or more
㻝㻠㻤
See note ·1·. Air flow rate [m³/min]
㻭㻭
㻞㻣㻡
㻝㻢㻡
㻝㻠㻤
A Inlet
㻭㻮
㻟㻝㻣
㻞㻜㻣
Notes
1. When installing a fresh air intake kit, provide a service access panel. Suction chamber
2. Field construction 㻠㻡㻡
Designer decoration panel
3. This corner discharge outlet needs to be closed. Ceiling opening
4. When installing a duct fan, use a wiring adapter to link the duct fan to the fan of the indoor unit.
5. The intake air flow rate is recommended to be 20% of the air flow rate at high fan speed.
If the intake air flow rate is too large, the operating sound may increase, and the detection of the indoor unit suction temperature may be affected.
6. This indicates the distance between the T-joint inlet and the indoor unit inlet when the T-tube is connected.
ϯϭϮϭϳϰϭ
6 Centre of gravity
6-1 Centre of Gravity
&'Ͳ 3
㻤㻠㻜
㻰
6
㻤㻠㻜
㻯
㻮
㻭
Model A B C D
)&$*㹼%9(% 204 70 400 405
)&$*㹼%9(% 246 100 400 405
)&$+*㹼+9(% 288 135 400 405
);)4㹼%9(% 204 70 395 400
);)4㹼%9(% 246 100 395 400
);)4%9(% 288 135 395 400
ϰϭϮϭϲϱϵ
• Split - Sky Air • FCAG-B 11
• Indoor Unit • FCAG-B
7 Piping diagrams
7-1 Piping Diagrams
&'Ͳ Model A B
FCAG35BVEB 6.35 9.52
FCAG50BVEB 12.7
7 FCAG60BVEB
FCAG71BVEB 9.52 15.9
FCAG100BVEB
FCAG125BVEB
FCAG140BVEB
FCAHG71BVEB
Refrigerant flow FCAHG100BVEB
FCAHG125BVEB
Cooling FCAHG140BVEB
Heating
Heat exchanger
M Fan
㻌㻭
㻌㻮
Gas pipe connection
port
ϰϭϮϭϰϯϯ
12 • Split - Sky Air • FCAG-B
• Indoor Unit • FCAG-B
8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase
&'Ͳ 3
WIRING DIAGRAM
Z2C R2T R3T S1L
N=1 RECEIVER / DISPLAY UNIT (OPTIONAL)
t° t° A5P X1A X1A H1P X1M
GRN
H2P BS1 T2
BLK
BLK
BLK
BLK
BLK
BLK
SS1 H3P INPUT FROM OUTSIDE
X2A T1
K2R H4P
1 X2M X27A NE V1R F2 CENTRAL REMOTE
X88A X15A H5P
2 + SS2
H6P F1 CONTROLLER (NOTE 4
1 BLK
3 F1U (NOTE 10) Z1F P2 P2
- DS1 A6P
OUTDOOR 2 WHT X24A R1T
8
(NOTE 3) EMG 1 NORM(NOTE 8) P1 P1
t°
H05VV-U4G2.5 3 RED TC RC C105 2 BLK
BLK
(NOTE 7) + ON OFF BLK WIRED REMOTE
BLK
BLK CONTROLLER
X33A(NOTE 8) BLK
PS HAP (NOTE 6)
CONTROL BOX LAYOUT PE X50A X36A
X70A R1 X39A X30A MSW M4S
X36A R1T A2P (YELLOW) X35A
X16A (NOTE 8)
(WHITE) (WHITE) (WHITE) X1 + - A1P
X33A COMPRESSOR KCR
X30A (WHITE) X81A X39A X2A V2R X35A X70A
(WHITE) (WHITE) (BLACK) OPERATION X2
X16A (NOTE 8)(NOTE 8) X25A X81A(NOTE 8) MSW M3S
FAN X3 X901A
KFR
OPERATION
WHT
WHT
RED
BLU
X4
BLK
BLK
BLK
BLK
BLK
Z1C
TERMINAL FOR F1U N=4 MSW M2S
X1M
WHT
RED
BLK
OPERATION DISPLAY
A1P X1A F2U KHuR WHT
R1T
M1P MS
A3P A4P
YC t° MSW M1S
X2M Y2 M1F MS CN1 S1RH
X24A X88A X25A X15A A7P 3~ SENSOR KIT (OPTIONAL)
X23A X50A (BLUE) (WHITE) X901A %H2O
(BLACK) (BLUE) ADAPTOR FOR WIRING (OPTIONAL NOTE 9)
(BLUE) (WHITE) (WHITE) A2P INDOOR
ϯϭϭϲϴϭϮ
9 Sound data
9-1 Sound Pressure Spectrum
&'ϯϱ
ŽŽůŝŶŐŵŽĚĞ ,ĞĂƚŝŶŐŵŽĚĞ
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
70 NR75 70 70 NR75 70
65 NR70 65 NR70
9 60
55
NR65
NR60
60 60
55
NR65
NR60
60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
,ŝŐŚ ŽŽůŝŶŐ dŽƚĂůĚ ,ĞĂƚŝŶŐ dŽƚĂůĚ
DĞĚŝƵŵ
>Žǁ
Ě ϯϭ͕Ϭ Ϯϵ͕Ϭ Ϯϳ͕Ϭ Ě ϯϭ͕Ϭ Ϯϵ͕Ϭ Ϯϳ͕Ϭ
>ŽĐĂƚŝŽŶŽĨŵŝĐƌŽƉŚŽŶĞ
EŽƚĞƐ
ϭ KƉĞƌĂƚŝŶŐĐŽŶĚŝƚŝŽŶƐ͗ƉŽǁĞƌƐŽƵƌĐĞϮϮϬͲϮϰϬsͬϮϮϬsϱϬͬϲϬ,nj͖:/^ƐƚĂŶĚĂƌĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ
ϯϭϮϭϲϲϬ
&'ϱϬ ŽŽůŝŶŐŵŽĚĞ ,ĞĂƚŝŶŐŵŽĚĞ
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
70 70 70 70
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
NR75 NR75
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ
ϯϭϮϭϲϲϭ
9 Sound data
9-1 Sound Pressure Spectrum
80 NR85 80 80 NR85 80
75 NR80 75 NR80
70 NR75 70 70 NR75 70
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
65 NR70 65 NR70
60
55
NR65
NR60
60 60
55
NR65
NR60
60
9
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ
ϯϭϮϭϲϲϮ
&'ϳϭ ŽŽůŝŶŐŵŽĚĞ ,ĞĂƚŝŶŐŵŽĚĞ
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
70 70 70 70
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
NR75 NR75
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ ϯϭϮϭϲϲϯ
9 Sound data
9-1 Sound Pressure Spectrum
80 NR85 80 80 NR85 80
75 75
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
NR80 NR80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
70 NR75 70 70 NR75 70
65 NR70 65 NR70
9 60
55
NR65 60 60 NR65 60
NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ ϯϭϮϭϲϲϰ
&'ϭϮϱ ŽŽůŝŶŐŵŽĚĞ ,ĞĂƚŝŶŐŵŽĚĞ
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
70 70 70 70
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
NR75 NR75
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ ϯϭϮϭϲϲϱ
9 Sound data
9-1 Sound Pressure Spectrum
80 NR85 80 80 NR85 80
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
^ŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞůĚ
75 NR80 75 NR80
70 NR75 70 70 NR75 70
65 NR70 65 NR70
60
55
NR65
NR60
60 60
55
NR65
NR60
60
9
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25
20 20 20
NR0 NR25
15 NR0
NR5 NR10 NR15
NR20 15
NR5 NR10 NR15 NR20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj KĐƚĂǀĞďĂŶĚĐĞŶƚƌĞĨƌĞƋƵĞŶĐLJ,nj
>ĞŐĞŶĚ
ĚсͲǁĞŝŐŚƚĞĚƐŽƵŶĚƉƌĞƐƐƵƌĞůĞǀĞů;ƐĐĂůĞĂĐĐŽƌĚŝŶŐƚŽ/Ϳ͘
^ĐĂůĞ &ĂŶƐƉĞĞĚ
,ŝŐŚ ŽŽůŝŶŐ dŽƚĂůĚ ,ĞĂƚŝŶŐ dŽƚĂůĚ
DĞĚŝƵŵ
>Žǁ
Ě ϰϭ͕Ϭ ϯϱ͕Ϭ Ϯϵ͕Ϭ Ě ϰϭ͕Ϭ ϯϱ͕Ϭ Ϯϵ͕Ϭ
>ŽĐĂƚŝŽŶŽĨŵŝĐƌŽƉŚŽŶĞ
EŽƚĞƐ
ϭ KƉĞƌĂƚŝŶŐĐŽŶĚŝƚŝŽŶƐ͗ƉŽǁĞƌƐŽƵƌĐĞϮϮϬͲϮϰϬsͬϮϮϬsϱϬͬϲϬ,nj͖:/^ƐƚĂŶĚĂƌĚ
Ϯ ĂĐŬŐƌŽƵŶĚŶŽŝƐĞĂůƌĞĂĚLJƚĂŬĞŶŝŶƚŽĂĐĐŽƵŶƚ͘
ϯ KƉĞƌĂƚŝŶŐŶŽŝƐĞǀĂƌŝĞƐĚĞƉĞŶĚŝŶŐŽŶŽƉĞƌĂƚŝŽŶĂŶĚĂŵďŝĞŶƚĐŽŶĚŝƚŝŽŶƐ͘
ϰ dŚĞŽƉĞƌĂƚŝŽŶŶŽŝƐĞŵĞĂƐƵƌŝŶŐŵĞƚŚŽĚŝƐŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚ:/^ϵϲϭϮ͘
ϱ DĞĂƐƵƌŝŶŐůŽĐĂƚŝŽŶ͗ĂŶĞĐŚŽŝĐĐŚĂŵďĞƌ
ϯϭϮϭϲϲϲ
&'ϯϱ
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
ϯϭϮϭϲϭϴ
&'ϱϬ
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
ϯϭϮϭϲϭϵ
&'ϲϬ 3
Air velocity distribution (cooling) Air velocity distribution (heating)
Air flow direction: horizontal Air flow direction: vertical
Air discharge: all-round Air discharge: all-round
10
2.7 m 2.7 m
1.5-1.7 m/s
1.3-1.5 m/s 1.5-1.7 m/s
1.1-1.3 m/s 2m 2m
1.3-1.5 m/s
0.9-1.1 m/s
1.1-1.3 m/s
0.7-0.9 m/s 0.9-1.1 m/s
0.5-0.7 m/s 1m 0.7-0.9 m/s 1m
0.3-0.5 m/s 0.5-0.7 m/s
0.3-0.5 m/s
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
ϯϭϮϭϲϮϬ
&'ϳϭ
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
ϯϭϮϭϲϮϭ
&'ϭϬϬ
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
ϯϭϮϭϲϮϮ
&'ϭϮϱͲϭϰϬ
ϯϭϮϭϲϮϯ
20 • Split - Sky Air • FCAG-B
Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
Daikin Europe N.V. participates in the Eurovent Certified
Performance programme for Liquid Chilling Packages
and Hydronic Heat Pumps, Fan Coil Units and Variable
Refrigerant Flow systems. Check ongoing validity of cer-
tificate: www.eurovent-certification.com
EEDEN19 03/19
The present leaflet is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fit-
ness for particular purpose of its content and the products and services presented therein. Specifica-
tions are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or inter-
pretation of this leaflet. All content is copyrighted by Daikin Europe N.V.