2.0 CERTIFICATION/LISTINGS
NOTE
• Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
08.15 1669 Rev G Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
1
victaulic.com
4.0 DIMENSIONS
Series 722 Brass Body Ball Valve
F
B
A
Nominal
Actual Approximate
Nominal Outside A B C F (Each)
inches inches inches inches inches inches lb
DN mm mm mm mm mm kg
¼ 0.540 1.54 0.77 1.03 1.65 0.2
DN8 13.7 39 20 26 42 0.1
3/8 0.675 1.77 0.88 1.28 3.07 0.3
DN10 17.1 45 22 33 78 0.1
1/2 0.840 2.13 1.06 1.33 3.07 0.4
DN15 21.3 54 27 34 78 0.2
3/4 1.050 2.44 1.22 1.79 3.78 0.7
DN20 26.9 62 31 45 96 0.3
1 1.315 2.95 1.48 1.95 3.78 1.0
DN25 33.7 75 37 50 96 0.5
1 1/4 1.660 3.31 1.65 2.17 3.78 1.5
DN32 42.4 84 42 55 96 0.7
1 1/2 1.900 3.66 1.83 2.68 5.43 2.1
DN40 48.3 93 46 68 138 1.0
2 2.375 4.21 2.11 2.89 5.43 2.4
DN50 60.3 107 53 73 138 1.1
08.15 1669 Rev G Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
Handle Extension
5.0 PERFORMANCE
Cv/Kv Values:
Cv/Kv values for flow of water at 60ºF/16ºC are shown in the table below.
For additional details contact Victaulic.
Formulas for Cv and Kv values
∆P = Q2 Where: Where:
Cv2 Q = Flow (GPM) Q = Flow (m3/hr)
∆P = Pressure Drop (psi) ∆P = Pressure Drop (Bar)
Q = Cv x ∆P Cv = Flow Coefficient Kv = Flow Coefficient
Size Flow
Actual
Outside
Nominal Diameter
inches inches Cv
DN mm Kv
¼ 0.540 7.0
DN8 13.7 6.1
3/8 0.675 7.0
DN10 17.1 6.1
1/2 0.840 10.0
DN15 21.3 8.7
3/4 1.050 25.0
DN20 26.9 21.6
1 1.315 37.0
DN25 33.7 32.0
1 1/4 1.660 50.0
DN32 42.4 43.3
1 1/2 1.900 87.0
DN40 48.3 75.3
2 2.375 110.0
DN50 60.3 95.2
08.15 1669 Rev G Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping
products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
08.15 1669 Rev G Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 4