Professional Documents
Culture Documents
Introduction
3
Figure 1.1 Conventional overhead air distribution system.
4
CHAPTER 1—INTRODUCTION
5
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
nal units, either used alone or in combination with one another; (2)
zero-pressure plenum with air delivered into the conditioned space
through local fan-powered (active) supply outlets in combination
with the central air handler; and (3) in some cases, ducted air
supply through the plenum to terminal devices and supply outlets.
The use of pressurized underfloor plenums appears to be the
focus of current practice, although zero-pressure plenums pose no
risk of uncontrolled air leakage to the conditioned space, adjacent
zones, or the outside.
• Within the plenum, air flows freely in direct contact with the
thermally massive slab and floor panels and enters the
workspace through diffusers at floor level or as part of the
furniture or partitions. Because the air is supplied directly into
the occupied zone, floor supply outlet temperatures should be
maintained no lower than in the range of 61-65°F (16-18°C) to
avoid uncomfortably cool conditions for the nearby occupants. For
TAC supply outlets located closer to the occupant (e.g., furniture-
or partition-based diffusers) where the occupant is exposed to
diffuser velocity cooling, even warmer supply temperatures may
be advisable.
• UFAD systems are generally configured to have a relatively larger
number of smaller supply outlets, many in closer proximity to the
building occupants, as opposed to the larger diffusers and spacing
used in conventional overhead systems. Outlets that are located
within workstations or otherwise near occupants at their work
locations are typically adjustable or thermostatically controlled,
providing an opportunity for adjacent individuals to at least have
some amount of control over their perceived local thermal
environment. Fan-driven TAC diffusers can more directly
influence local thermal comfort by using increased air movement
to provide occupant cooling.
• Air is returned from the room at ceiling level, or at the maximum
allowable height above the occupied zone. This produces an
overall floor-to-ceiling airflow pattern that takes advantage of the
natural buoyancy produced by heat sources in the office and more
efficiently removes heat loads and contaminants from the space,
particularly for cooling applications. In contrast to the well-mixed
room air conditions of the conventional overhead system, during
cooling conditions, UFAD system operation can be optimized to
promote some amount of stratification in the space, with elevated
temperatures and higher levels of pollutants above head height
where their effect on occupants is reduced.
7
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
1.3 BACKGROUND
8
The most important features, amenities, and services to the
responding tenants are related to the comfort and quality of
9
CHAPTER 1—INTRODUCTION
indoor air, the acoustics, and the quality of the building man-
agement’s service.
10
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
12
CHAPTER 1—INTRODUCTION
1.4 BENEFITS
What are the potential advantages that UFAD systems have over
traditional overhead air distribution systems? Well-engineered
systems can provide the following.
15
CHAPTER 1—INTRODUCTION
17
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
19
CHAPTER 1—INTRODUCTION
underfloor plenum, floor diffusers along with all power, voice, and
data outlets can be placed almost anywhere on the raised floor grid.
In-house maintenance personnel can carry out these reconfigurations
at signifi- cantly reduced expense using simple tools and modular
hardware. Firms that are more likely to install underfloor systems are
also, for the very same reasons, more likely to churn at a higher rate.
For further dis- cussion, see Chapter 10.
21
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
2002a, 2002b; Lin and Linden 2002; Yamanaka et al. 2002]. For fur-
ther discussion, see Chapter 2.
1.5.3.2 Underfloor air supply plenum. An important differ-
ence between conventional and UFAD system design is the heat
exchange between the concrete slab, raised floor panels, and the sup-
ply air as it flows through the underfloor plenum. If the slab has
absorbed heat, particularly from warm return air flowing along the
underside of the slab, then supply temperature will increase with dis-
tance from the plenum inlet. Energy and operating cost savings,
including peak shaving, can be achieved by using the concrete slab
in a thermal storage strategy, but further research is still needed to
opti- mize and quantify this effect. For further discussion, see
Chapter 4.
1.5.3.3 Whole-building performance. There currently does
not exist a whole-building energy simulation program capable of
accurately modeling UFAD systems, a subject discussed by Addison
and Nall (2001). This is one of the top technology needs identified
by system designers. Additionally, whole-building performance data
are needed from completed UFAD projects in the form of energy
use, indoor environmental quality, occupant satisfaction, comfort,
health, and performance, and first and life-cycle (operating) costs to
quantify the relative benefits of the technology.
24
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
26
CHAPTER 1—INTRODUCTION
28
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
1.6 APPLICATIONS
UFAD systems are well suited for all office buildings, especially
those with open office plans in which adjustable diffusers can allow
occupants to individually control their local workstation
environments. In high-tech offices and other businesses with
extensive use of infor- mation technologies and typically high
churn rates (e.g., dot-com offices, call centers, trading floors), the
flexibility provided by service delivery systems, including cable
management, is a great benefit. Because of the significant savings
in life-cycle costs for UFAD sys- tems, owner-occupied buildings
are strong candidates for application. Other buildings suitable for
UFAD systems include schools, television studios, and light
manufacturing installations that don’t involve spill- age of liquids.
Any building that already is using a raised floor system for cable
distribution or other purposes should consider a UFAD system. An
exception would be clean room applications that are designed to
return air at floor level. There are other areas in buildings where
raised floors and underfloor air distribution are generally not
appropriate. These areas include those in which spillage has the
potential to occur, such as in laboratories, cafeterias, and shop areas.
Bathrooms have often been considered as an area where raised floor
systems should be avoided, but there are cases where they have
been used successfully. Although requiring a membrane on top of
the floor to protect against leaks, plumbing costs can be reduced by
simplifying the piping installation.
In high ceiling spaces UFAD systems provide good energy-
savings opportunities in cooling applications by promoting thermal
stratifica- tion. Comfort and improved indoor air quality are
maintained in the occupied zone near the floor, while allowing
increased temperatures and pollutant concentrations to occur at
higher elevations in the space. Auditoriums, theaters, libraries,
museums, and converted warehouses all make good UFAD
applications. In contrast, these types of buildings can present
problems for conventional overhead air distribution design.
Buildings using UFAD systems located in dry, mild climates will
achieve the best energy savings. These are primarily associated with
increased economizer operation and increased chiller COP due to the
higher supply air temperatures used in these systems. These climates
are also more suitable for the implementation of thermal storage con-
trol strategies using the concrete floor slabs of the building. Many of
these energy benefits are not available in more humid climates.
29
CHAPTER 1—INTRODUCTION
30
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
31